HomeMy WebLinkAboutX2019-0253 - Misc (2)CITY OF NEWPORT BEACH
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
I certify that this Certificate of Acceptance document is accurate and complete.
Documentation Author gutltly Tooley Company Name
Name
Address 41553 Evening Shade Place City
Zip Code 92562 Phone
CEA/ATT Certification Author Signature
Identification (if
applicable)
QCT �t
Date of Signature: 05/21/2019
D)ITTr3
X2019.025 3
Arise Electrical 1131 ryeu.porJ Cen�ar
timbale
(951)496-9566
RESPONSIBLE PERSON'S DECLARATION STATEMENT
1 certify the following under penalty of perjury, under the laws of the State of California:
1. I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this
Certificate of Acceptance.
2. I am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction
or installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the
declarations in this statement (responsible acceptance person).
3. The Information provided on this Certificate of Acceptance substantiates that the construction or installation identified on this Certificate of Acceptance
complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable
acceptance requirements and procedures specified in Reference Nonresidential Appendix NAI.
4. I have confirmed that the Certiflcate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and
is posted or made available with the building permits) issued for the bgildinq.
5. I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permits) issued for the
building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is
required to be included with the documentation the builder provides to the building owner at occupancy.
Responsible Acceptance Buddy Tooley Company Name prise Electrical
Person Name
Address:
City
41553 Evening Shade Place
Murrieta
Zip Code
Phone
92562
(951)496-9566
CSLB License
Position with Company
(Title)
Owner
Responsible Acceptance
Person Signature
"��...urraaraav
05/21/2019
This is page 2 of 2
General Information
Building Type:
W Nonresidential r High -Rise Res (Common Area)
r Hotel/Motel (Common Area)
Phase of Construction:
F New Construction r Addition r Alteration
F Unconditioned
Scope of Responsibility
Enter the date of approval by enforcement agency of the Certificate of Compliance that provides the specifications for the energy
efficiency measures for the scope of responsibility for this Installation Certificate.
Date: 4/1/2019 12:00:00 AM
Document Title or Description
ES
Applicable Sheets or Pages, Tables, Schedules, etc.
Notes
Date Approved
4/1/2019
12:00:00
By
the Enforcement Agency
AM
ES
T24
4/1/2019
12:00:00
AM
E3
Lighting
4/1/2019
12:00:00
AM
E4
T24
4/1/2019
12:00:00
AM
E2
Power
4/1/2019
12:00:00
AM
This is page 1 of 2
1131 ►vL XR01R - 0,253
INDOOR LIGHTING lft,PDrI Cen? er
NRCI_LTI02_E
Havaianas_
Orange
General Information
Building Type:
P Nonresidential r High -Rise Res (Common Area)
r Hotel/Motel (Common Area)
Phase of Construction:
Iw New Construction r Addition r Alteration
F Unconditioned
Scope of Responsibility
Enter the date of approval by enforcement agency of the Certificate of Compliance that provides the specifications for the energy
efficiency measures for the scope of responsibility for this Installation Certificate.
Date: 4/1/2019 12:00:00 AM
§130.4(b) Before an Energy Management Control System (EMCS), or Lighting Control System can be recognized for compliance with
the lighting control requirements in Part 6 of Title 24, the person who is eligible under Division 3 of the Business and Professions Code
to accept responsibility for the construction or installation of features, materials, components, or manufactured devices shall sign and
submit this Installation Certificate.
If any of the requirements in this Installation Certificate fail the Energy Management Control System or Lighting Control System
installation requirements, these options for controlling lighting shall not be recognized for compliance with the Building Energy
Efficiency Standards.
Check all that apply
PART 1 What type of Lighting Control System has been installed?
r A. Energy Management Control System (EMCS) - Is a computerized control system designed to regulate the energy
consumption of a building by controlling the operation of energy consuming systems, such as the heating,
ventilation and air conditioning (HVAC), lighting, and water heating systems, and is capable of monitoring
environmental and system loads, and adjusting HVAC operations in order to optimize energy usage and respond to
demand response signals.
F The Energy Management Control System has been installed to function as a lighting control required by Part
6 and functionally meets all applicable requirements for each application for which it is installed, in
accordance with Sections 110.9, 130.0 through 130.5, 140.6 through 150.0, and 150.2; and complies with
Reference Nonresidential Appendix NA7.7.2.
r The EMCS has been separately tested for each respective lighting control system for which it is installed to
function as.
r B. Lighting Control System - Requires two or more components to be installed in the building to provide all of the
functionality required to snake up a fully functional and compliant lighting control.
This is page I of 5
ccntc,
This is page 2 of 5
-r?he installed Lighting Control System complies with the requirements checked below; and all components of
'
the system Considered together as installed meet all applicable requirements for the application for which
. Itheyare installed as required in Sections 130.0 through 130.5, Sections 140.6 through 140.8, Section 141.0,
and Section 150.0(k).
PART 2 Lighting Control Functional requirements: Check all that apply when verifying
the installation of an EMCS or Lighting Control System.
F A. All lighting controls and equipment have been installed in accordance with the manufacturer's instructions.
r B. The manufacturer has provided instructions for calibration.
r C. If indicator lights are integral to any components, such indicator lights consumes no more than 1 watt of power
per indicator light.
r D. Components that are regulated by the Title 20 Appliance Efficiency Regulations have been certified to the
Energy Commission.
r E. The EMCS or Lighting Control System functions as one or more of the Time -Switch Lighting Controls checked
below, and complies with all of the following requirements:
F 1. Automatic Time -Switch Controls meeting all requirements for Automatic Time Switch Control devices in the
Title 20 Appliance Efficiency Regulations, including the requirements below:
a. Residential automatic time -switch controls have program backup capabilities that prevent the loss of the
device's schedule for at least 7 days, and the device's date and time for at least 72 hours if power is
interrupted.
b. Commercial automatic time -switch controls meet the following requirements:
i. Has program backup capabilities that prevent the loss of the device's schedule for at least 7 days, and the
device's date and time for at least 72 hours if power is interrupted
ii. Is capable of providing manual override to each connected load and shall resume normally scheduled
operation after manual override is initiated within 2 hours for each connected load and
iii. Incorporates an automatic holiday shutoff feature that turns off all connected loads for at least 24 hours
and then resumes normally scheduled operation.
F7 2. Astronomical Time -Switch Controls meeting all requirements for Astronomical Time -Switch Control devices
in the Title 20 Appliance Efficiency Regulations, including the requirements below:
a. Meets the requirements of an automatic time -switch control
b. Has sunrise and sunset prediction accuracy within plus -or -minus 15 minutes and timekeeping accuracy
within 5 minutes per year
c. Is capable of displaying date, current time, sunrise time, sunset time, and switching times for each step
during programming
d. Has an automatic daylight savings time adjustment; and
e. Has the ability to independently offset the on and off for each channel by at least 99 minutes before and
after sunrise or sunset.
F 3. Multi -Level Astronomical Time -Switch Controls, in addition to meeting all of the requirements for
Astronomical Time -Switch Controls, includes at least 2 separately programmable steps per zone.
r F. The EMCS or Lighting Control System functions as one or more of the Daylighting Controls listed below:
This is page 2 of 5
CERTIFICATE OF INSTALLATION NRCI-LTI-W-E
EMCS ar Lighting Cunrcel System
Project Name: Havaimms
Enforcement Agency: CITY OF NEWPORT BEACH
Permit Number: X2019-0253
Project Adciresc 1131 Newport Center Drive
City: Newport Besch
Zip Code: 92fifi0
r 1. Automatic Daylight Controls meet all requirements for Automatic Daylight Control devices in the Title 20
Appliance Efficiency Regulations, including the following:
a. Is capable of reducing the power consumption in response to measured daylight either directly or by
sending and receiving signals;
b. If the system includes a dimmer, complies with the Dimmer Control device requirements in the Title 20
Appliance Efficiency Regulations.
c. Automatically return to its most recent time delay settings within 60 minutes when put in calibration
mode;
d. Has a set point control that easily distinguishes settings to within 10 percent of full scale adjustment;
e. Has a light sensor that has a linear response within 5 percent accuracy over the range of illuminance
measured by the light sensor;
f. Has a light sensor that is physically separated from where the calibration adjustments are made, or is
capable of being calibrated in a manner that the person initiating the calibration is remote from the sensor
during calibration to avoid influencing calibration accuracy; and
g. Complies with the Title 20 requirements for photo controls if the system contains a photo control
component.
r 2. Photo Controls meet all requirements for Photo Control devices in the Title 20 Appliance Efficiency
Regulations, including the following that it does not have a mechanical device that permits disabling of the
control,
G. The EMCS or Lighting Control System functions as a Dimmer and meets all requirements for a Dimmer Control
device in the Title 20 Appliance Efficiency Regulations, including the following:
1. Is capable of reducing power consumption by a minimum of 65 percent when the dimmer is at its lowest level;
2. Includes an off position which produces a zero lumen output; and
3. Does not consume more than 1 watt per lighting dimmer switch leg when in the off position.
4. Dimmer controls that can directly control lamps provide electrical outputs to lamps for reduced flicker operation
through the dimming range so that the light output has an amplitude modulation of less than 30 percent for
frequencies less than 200 Hz without causing premature lamp failure.
5. If designed for use in three way circuits is capable of turning lights off, and to the level set by the dimmer if the
lights are off.
i✓ H. The EMCS or Lighting Control System meets the following requirements:
1. Is capable of automatically turning off controlled lights in the area no more than 30 minutes after the area has
been vacated;
2. Allows all lights to be manually turned off regardless of the status of occupancy; and
3. Has a visible status signal that indicates that the device is operating properly, or that it has failed or
malfunctioned. The visible status signal may have an override switch that turns off the signal.
4. All occupant sensing devices that utilize ultrasonic radiation for detection of occupants meet the Ultrasound
Maximum Decibel Values in the Title 20 Appliance Efficiency Regulations
S. All occupant sensing devices that utilize microwave radiation for detection of occupants meet the radiation
requirements in the Title 20 Appliance Efficiency Regulations
6. Occupant sensing devices incorporating dimming comply with the requirements for dimmer controls in the Title 20
Appliance Efficiency Regulations
7. The EMCS or Lighting Control System functions as one or more of the Occupant Sensing Controls Checked Below:
P a. Occupant Sensors meeting all applicable requirements for Occupant Sensor Control devices in the Title 20
Appliance Efficiency Regulations
r b. Motion Sensors meeting all applicable requirements for Motion Sensor Controls devices in the Title 20
Appliance Efficiency Regulations, including that motion sensors are rated for outdoor use.
F c. Vacancy Sensors meeting all applicable requirements for Vacancy Sensor Controls devices in the Title 20
Appliance Efficiency Regulations, including the following:
i. Does not turn on lighting automatically and does not incorporate DIP switches, or other manual means, for
conversion between manual and automatic functionality;
ii. Has a grace period of no more than 30 seconds and no less than 15 seconds to turn on lighting
automatically after the sensor has timed out; and
iii. Does not have an override switch that disables the sensor.
This is page 3 of 5
r d. Partial -ON Sensors meeting all applicable requirements for partial on sensing devices in the Title 20
Appliance Efficiency Regulations, including the following:
i. Has two poles each with automatic -off functionality;
ii. Has one pole that is manual -on and does not incorporate DIP switches, or other manual means, for
conversion between manual and automatic functionality; and
in. Has one pole that is automatic -on and is not be capable of conversion by the user to manual -on
functionality.
r e. Partial -OFF Sensors meet all applicable requirements for partial off sensing devices in the Title 20
Appliance Efficiency Regulations, including the following:
i. Has two poles;
ii. Has one pole that is manual -on and manual off; and
iii. Has one pole that is automatic -on and automatic -off and is not capable of conversion by the user to
manual -on only functionality.
P I. Occupant Sensing Control systems consist of a combination of single or multi-level Occupant, Motion, or
Vacancy Sensor Controls, and all components installed to comply with manual -on requirements are not
capable of conversion by the user from manual -on to automatic -on functionality.
PART 3 Requirements for which the control is being installed to complied with:
Identify all requirements in the Standards for which the FMCS or Lighting Control System is installed to function as and complies
with:
Check all that are applicable.
F
A. Section 130.1(a) Area Controls.
W
B. Section 130.1(6) Multi -Level Lighting Controls
W
C. Section 130.1 (c) Shut -OFF Controls
r
D. Section 130.1 (d) Automatic Daylighting Controls.
r
E. Section 130.1 (e) Demand Responsive Controls.
I-
F. Section 130.5 (d) Circuit Controls for 120 -Volt Receptacles.
F
G. To qualify for the PAF for a Partial -ON Occupant Sensing Control in TABLE 140.6-A
r
H. To qualify for the PAF for an occupant sensing control controlling the general lighting in large open plan office
areas above workstations, in accordance with TABLE 140.6-A
r
I. To qualify for the PAF for a Manual Dimming System PAF or a Multiscene Programmable Dimming System PAF in
TABLE 140.6-A
F
J. To qualify for the PAF for a Demand Responsive Control in TABLE 140.6-A
F
K. To qualify for the PAF for Combined Manual Dimming plus Partial -ON Occupant Sensing Control in TABLE 140.6-A
This is page 4 of 5
OF
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
I certify that this Certificate of Acceptance document is accurate and complete.
Documentation Author Company Name
Name Buddy Tooley
Anse Electrical
Address City
41553 Evening Shade Place
Murrieta
Zip Code Phone
92562
(951)496-9566
CEA/ATT Certification
Identification (if
applicable)
Author Signature
Date of Signature: 05/21/2019
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under Penalty Of perjury, under the laws of the State of California:
1. 1 am the From Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this
Certificate of Acceptance.
2. 1 am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design,
construction or installation of features, materials, components, or manufactured devices for the scope of warl< identified on this Certificate of Acceptance and
attest to the declarations m this statement (responsible acceptance person).
3. The information provided on this Certificate of Acceptance substantiates that the construction or installation identified on this Certificate of Acceptance
complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable
acceptance requirements and procedures specified In Reference Nonresidential Appendix NA].
4. 1 have confirmed that the Certificate(s) of installation for the construction or installation identified on this Certificate of Acceptance has been completed and
is posted or made available with the building permit(s) issued for the building.
5. I will ensure that a completed, signed copy of this Certificate of Acceptance shall be pasted, it made available with the building perm it(s) issued for the
building, and made available to the enforcement agency for all applicable inspections. 1 understand that a signed copy of this Certificate of Acceptance is
required to be included with the documentation the builder provides to the budding owner at occupancy.
Responsible Acceptance Company Name
Person Name Buddy Tooley Arise Electrical
Address: City
41553 Evening Shade Place Murrieta
Zip Cade 92562 Phone (951)496-9566
CSLB License Position with Company
(Title) Owner
Responsible Acceptance Person Signature
X
Date of Signature: 05/21/2019
This is page 5 of 5
x2019- 0953
Enforcement Agency Use: Checked by/Date ►►g► New por4 Center Dr
LIGHTING CONTROL ACCEPTANCE DOCUMENT
Automatic Shut-off Controls: Automatic Time Switch Control and Occupant Sensor
Intent: Lights are turned off or set to a lower level when not needed per Section 110.9(a) & 130.1(c).
A. Construction Inspection
Fill out Section A to cover spaces 1 through 3 that are functionally tested under Section B.
Instruments needed to perform tests include, but are not limited to: hand-held amperage meter, power meter, or light meter
1: Automatic Time Switch Controls Construction Inspection—confirm for all listed in Section B
a. All automatic time switch controls are programmed for (check ail):
P Weekdays r Weekend r Holidays
b. Document for the owner automatic time switch programming (check all):
P Weekday settings r Weekend settings r Holidays settings r Set-up settings
P7 Preference program setting r Verify the correct time and date is properly set in the time switch
F Verify the battery is installed and energized r Override time limit is no more than 2 hours
r Occupant Sensors and Automatic Time Switch Controls have been certified to the Energy Commission in accordance with
the applicable provision in Section 110.9 of the Standards, and model numbers for all such controls are listed on the Commission
database as Certified Appliance and Control Devices
2. Occupancy Sensor Construction Inspection—confirm for all listed in Section B
r Occupancy sensors are not located within 4 feet of any HVAC diffuser
Ultrasonic occupancy sensors do not emit audible sound 5 feet from source
This is page 1 of 15
B. Functional Testing of Lighting Controls
For every spacein�the building, conduct functional tests 1 through 5 below if applicable. If there are several geometrically similar spaces
that use the same lighting controls, test only one space and list in the cells below which "untested spaces" are represented by that
tested space. EXCEPTION: For buildings with up to seven (7) occupancy sensors, all occupancy sensors shall be tested. (NA7.6.2.3)
Representative Spaces Selected
Tested space/room name: Restroom
Space Type (office, corridor, etc) Restroom
Untested areas/rooms
Confirm compliance for ail control system types (1-5) present in each space:
1. Automatic Time Switch Controls
Step 1: Simulate occupied condition
a. All lights can be turned on and off by their respective area control switch r
b. Verify the switch only operates lighting in the ceiling -height partitioned area in
which the switch is located. r
Step 2: Simulate unoccupied condition
a. All lighting, including emergency and egress lighting, turns off. Exempt lighting may r
remain on per Section 130.1(c)1 and 130.1(a)1.
b. Manual override switch controls only the lights in the selected ceiling height
partitioned space where the override switch is located and the lights remain on no
longer than 2 hours (unless serving public areas and override switch is captive key
type) r
Step 3:
System returned to initial operating conditions r
2. Occupancy Sensors
Step 1: Simulate an unoccupied condition
a. Lights controlled by occupancy sensors turn off within a maximum of 20 minutes
from start of an unoccupied condition per Standard Section 110.9(b)
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. r
Step 2: Simulate an occupied condition
a. Status indicator or annunciator operates correctly
b. Lights controlled by occupancy sensors turn on immediately upon an occupied
condition OR sensor indicates space is 'occupied' and lights may be turned on
manually r
This is page 2 of 15
Step 3:
System returned to initial operating conditions r
3. Partial Off Occupancy Sensor
Step 1: Simulate an unoccupied condition
a. Lights go to partial off state within a maximum of 20 minutes from start of an
unoccupied condition per Standard Section 110.9(a) r
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. For library book stacks or
warehouse aisle, activity beyond the stack or aisle shall not activate the lighting in -
the aisle or stack. r
c. In the partial off state, lighting shall consume no more than SO% of installed lighting
power, or:
No more than 60% of installed lighting power for metal halide or high pressure
sodium lighting in warehouses.
No more than 60% of installed lighting power for corridors and stairwells in which
the installed lighting power is 80% or less of the value allowed under the Area
Category Method.
Light level may be used as a proxy for lighting power when measurements are taken F
Step 2: Simulate an occupied condition
The occupant sensing controls shall turn lights fully ON in each separately controlled
areas, Immediately upon an occupied condition r
4. Partial On Occupancy Sensors
Step 1. -Simulate an occupied condition. Verify partial on operation.
a. Immediately upon an occupied condition, the first stage activates between 50 to
700/c of the lighting automatically. r
b. After the first stage occurs, manual switches allow an occupant to activate the
alternate set of lights, activate 100% of the lighting power, and manually
deactivate all of the lights. r
Step 2. Simulate an unoccupied condition
a. Both stages (automatic on and manual on) lights turn off within a maximum of 20
minutes from start of an unoccupied condition per Standard Section 110.9(a) r
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. r
This is page 3 of 15
5. Additional test for Occupancy Sensors Serving Small Zones in Office Spaces Larger than
250 fti, to Qualify for a Power Adjustment Factor (PAF)
Step 0: First, complete Functional Test 2 (above) for each controlled zone.
Step 1: Verify area served and compare actual PAF with claimed PAF. Refer to Functional Test 2.
a. Area served by controlled lighting ft2
b. Enter PAF corresponding to controlled area from line (a) above (<125 ft2 for
PAF=0.4, 126-250 ft2 for PAF=0.3, 251-500 ft2 for PAF=0.2).
c. Enter PAF claimed for occupant sensor control in this space from the Certificate of
Compliance.
d. The PAF corresponding to the controlled area (line b), is greater than or equal to
the PAF claimed in the compliance documentation (line c). r
e. Sensors shall not trigger in response to movement in adjacent walkways or
workspaces r
f. All steps are conducted in Functional Test 2 'Occupancy Sensor (On Off Control)'
and all answers are Yes. r
This is page 4 of 15
(CERTIFICATE OF ACCEPTANCE IINRCA-LTI-02-A
r1YYY
0111 SMafEil
C. Testing Results
1. Automatic Time Switch Conti -cis (ail answers must be Yes). r
2. Occupancy Sensor (On Off Control) (ail answers must be Yes). r
3. Partial Off Occupancy Sensor (all answers must be Yes). For warehouses, library
book stacks, corridors, stairwells in nonresidential buildings must also be
accompanied by passing Test 1 or Test 2. r
4. Partial On Occupant Sensor for PAF (all answers must be Yes). r
5. Occupant Sensor serving small zones for PAF (all answers must be Yes). Also must
pass Test 2, r
Representative Spaces Selected
Tested space/room name: Sales
Space Type (office, corridor, etc) Sales
Untested areas/rooms
Confirm compliance for all control system types (1-5) present in each space:
1. Automatic Time Switch Controls
Step 1: Simulate occupied condition
a. All lights can be turned on and off by their respective area control switch r
b. Verify the switch only operates lighting in the ceiling -height partitioned area in
which the switch is located. F
Step 2: Simulate unoccupied condition
a. All lighting, including emergency and egress lighting, turns off. Exempt lighting may.
remain on per Section 130.1(c)1 and 130.1(a)1. r
b. Manual override switch controls only the lights in the selected ceiling height
partitioned space where the override switch is located and the lights remain on no
longer than 2 hours (unless serving public areas and override switch is captive key
type). r
Step 3:
System returned to initial operating conditions r
2. Occupancy Sensors
Step 1: Simulate an unoccupied condition
a. Lights controlled by occupancy sensors turn off within a maximum of 20 minutes
This is page 5 of 15
OF ACCEPTANCE
from start of an unoccupied condition per Standard Section 110.9(b)
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. r
Step 2: Simulate an occupied condition
a. Status indicator or annunciator operates correctly r
b. Lights controlled by occupancy sensors turn on immediately upon an occupied
condition OR sensor indicates space is 'occupied' and lights may be turned on
manually r
Step 3:
System returned to initial operating conditions r
3. Partial Off Occupancy Sensor
Step 1: Simulate an unoccupied condition
a. Lights go to partial off state within a maximum of 20 minutes from start of an
unoccupied condition per Standard Section 110.9(a) r
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. For library book stacks or
warehouse aisle, activity beyond the stack or aisle shall not activate the lighting in
the aisle or stack. r
c. In the partial off state, lighting shall consume no more than 50% of installed lighting
power, or:
No more than 60% of installed lighting power for metal halide or high pressure
sodium lighting in warehouses.
No more than 60% of installed lighting power for corridors and stairwells in which
the installed lighting power is 80% or less of the value allowed under the Area
Category Method.
Light level may be used as a proxy for lighting power when measurements are taken r
Step 2: Simulate an occupied condition
The occupant sensing controls shall turn lights fully ON in each separately controlled
areas, Immediately upon an occupied condition r
4. Partial On Occupancy Sensors
Step 1. -Simulate an occupied condition. Verify partial on operation.
a. Immediately upon an occupied condition, the first stage activates between 50 to
70% of the lighting automatically. r
b. After the first stage occurs, manual switches allow an occupant to activate the
alternate set of lights, activate 100% of the lighting power, and manually
deactivate all of the lights. r
Step 2. Simulate an unoccupied condition
This is page 6 of 15
a. Both stages (automatic on and manual on) lights turn off within a maximum of 20
minutes from start of an unoccupied condition per Standard Section 110.9(a)
F
b. The occupant sensor does not trigger a false 'on' from movement in an area r
adjacent to the controlled space or from HVAC operation.
This is page 7 of 15
5. Additional test for Occupancy Sensors Serving Small Zones in Office Spaces Larger than
250 ft , to Qualify for a Power Adjustment Factor (PAF)
Step 0: First, complete Functional Test 2 (above) for each controlled zone.
Step 3: Verify area served and compare actual PAF with claimed PAF. Refer to Functional Test 2.
a. Area served by controlled lighting ft2
b. Enter PAF corresponding to controlled area from line (a) above (125 ft2 for
PAF=0.4, 126-250 ft2 for PAF=0.3, 251-500 ft2 for PAF=0.2).
c. Enter PAF claimed for occupant sensor control in this space from the Certificate of
Compliance.
d. The PAF corresponding to the controlled area (line b), is greater than or equal to
the PAF claimed in the compliance documentation (line c). r—
e.
e. Sensors shall not trigger in response to movement in adjacent walkways or
workspaces r
f. All steps are conducted in Functional Test 2'Occupancy Sensor (On Off Control)'
and all answers are Yes. r
This is page 8 of 15
92660
C. Testing Results
1. Automatic Time Switch Controls (all answers must be Yes).
2. Occupancy Sensor (On Off Control) (all answers must be Yes). r
3. Partial Off Occupancy Sensor (all answers must be Yes). For warehouses, library
book stacks, corridors, stairwells in nonresidential buildings must also be
accompanied by passing Test i or Test 2. r
4. Partial On Occupant Sensor for PAF (all answers must be Yes). r
S. Occupant Sensor serving small zones for PAF (all answers must be Yes). Also must
pass Test 2. r
Representative Spaces Selected
Tested space/room name: Storage
Space Type (office, corridor, etc) Storage
Untested areas/rooms
Confirm compliance for all control system types (1-5) present in each space:
I. Automatic Time Switch Controls
Step 1: Simulate occupied condition
a. All lights can be turned on and off by their respective area control switch r
b. Verify the switch only operates lighting in the ceiling -height partitioned area in
which the switch is located.
W
Step 2: Simulate unoccupied condition
a. All lighting, including emergency and egress lighting, turns off. Exempt lighting may
remain on per Section 130.1(c)1 and 130.1(a)1. r
b. Manual override switch controls only the lights in the selected ceiling height
partitioned space where the override switch is located and the lights remain on no
longer than 2 hours (unless serving public areas and override switch is captive key
type) r
Step 3:
System returned to initial operating conditions IF
2. Occupancy Sensors
Step 1: Simulate an unoccupied condition
a. Lights controlled by occupancy sensors turn off within a maximum of 20 minutes
This is page 9 of 15
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. r
Step 2: Simulate an occupied condition
a. Status indicator or annunciator operates correctly r
b. Lights controlled by occupancy sensors turn on immediately upon an occupied
condition OR sensor indicates space is 'occupied' and lights may be turned on
manually r
Step 3:
System returned to initial operating conditions r-
3.
3. Partial Off Occupancy Sensor
Step 1: Simulate an unoccupied condition
a. Lights go to partial off state within a maximum of 20 minutes from start of an
unoccupied condition per Standard Section 110.9(a) r
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. For library book stacks or
warehouse aisle, activity beyond the stack or aisle shall not activate the lighting in
the aisle or stack. r
c. In the partial off state, lighting shall consume no more than SO°/ of installed lighting
power, or:
No more than 60% of installed lighting power for metal halide or high pressure
sodium lighting in warehouses.
No more than 60% of installed lighting power for corridors and stairwells in which
the installed lighting power is 80% or less of the value allowed under the Area
Category Method.
Light level may be used as a proxy for lighting power when measurements are taken r
Step 2: Simulate an occupied condition
The occupant sensing controls shall turn lights fully ON in each separately controlled
areas, Immediately upon an occupied condition r
4. Partial On Occupancy Sensors
Step 1. -Simulate an occupied condition. Verify partial on operation.
a. Immediately upon an occupied condition, the first stage activates between 50 to
70% of the lighting automatically. r
b. After the first stage occurs, manual switches allow an occupant to activate the
alternate set of lights, activate 100% of the lighting power, and manually r
deactivate all of the lights.
Step 2. Simulate an unoccupied condition
This is page 10 of 15
a. Both stages (automatic on and manual on) lights turn off within a maximum of 20
minutes from start of an unoccupied condition per Standard Section 110.9(a) r
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. r
This is page 11 of 15
5. Additional test for Occupancy Sensors Serving Small Zones in Office Spaces Larger than
250 ft , to Qualify for a Power Adjustment Factor (PAF)
Step O: First, complete Functional Test 2 (above) for each controlled zone.
Step 1: Verify area served and compare actual PAF with claimed PAF. Refer to Functional Test 2.
a. Area served by controlled lighting ft2
b. Enter PAF corresponding to controlled area from line (a) above (<125 ft2 for
PAF=0.4, 126-250 ft2 for PAF=0.3, 251-500 ft2 for PAF=0.2).
c. Enter PAF claimed for occupant sensor control in this space from the Certificate of
Compliance.
d. The PAF corresponding to the controlled area (line b), is greater than or equal to
the PAF claimed in the compliance documentation (line c). r
e. Sensors shall not trigger in response to movement in adjacent walkways or
workspaces f
f. All steps are conducted in Functional Test 2 'Occupancy Sensor (On Off Control)'
and all answers are Yes. r
This is page 12 of 15
ACCEPTANCE
NEWPORT BEACH
C. Testing Results
92660
1. Automatic Time Switch Controls (all answers must be Yes). r
2. Occupancy Sensor (On Off Control) (ail answers must be Yes). r
3. Partial Off Occupancy Sensor (all answers must be Yes). For warehouses, library
book stacks, corridors, stairwells in nonresidential buildings must also be
accompanied by passing Test 1 or Test 2. r
4. Partial On Occupant Sensor for PAF (all answers must be Yes). r-
5.
S. Occupant Sensor serving small zones for PAF (all answers must be Yes). Also must r
pass Test 2.
D. Evaluation :
P PASS: All applicable Construction Inspection responses are complete and all applicable
Equipment Testing Requirements responses are positive.
This is page 13 of 15
NEWPORT BEACH
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
I certify that this Certificate of Acceptance documentation is accurate and complete.
Documentation Author Company Name
Name Bernardo Torres
Address 6305 Corona ave
Zip Code 90201
CEA/ATT Certification TC -A813034
Identification (if
applicable)
Date of Signature: 05/21/2019
City
Phone
Author Signature
Advance Lighting and Electric Inc
Bell
(323)338-1040
FIELD TECHNICIAN'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The Information provided on this Certificate of Acceptance is no and correct.
2. I am the person who performed the acceptance verification reported on this Certificate of Acceptance (Field Technician).
3. The construction or installation identified on this Certificate of Acceptance complies with the applicable acceptance requirements indicated in the plans and
specifications approved by the enforcement agency, and confer ms to the applicable acceptance requirements and procedures specified in Reference
Nonresidential Appendix NAT
4. I have confirmed that the Certlficate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and
signed by the responsible builder/installer and has been posted or made available with the building permit(s) issued for the building.
Field Technician Name Company Name
Bernardo Torres Advance Lighting and Electric Inc
Address: City
6305 Corona ave Bell
Zip Code 90201 Phone (323)338-1040
ATT Certification Positlen with Company Owner
Identification TC -A813034 (Title)
Field Technician Signature
—�k
Date of Signature: 05/21/2019
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. 1 am the Field Technician, of the Field Technician is acting on my behalf as my employee or my agent and i have reviewed the information provided on this
Certificate of Acceptance.
2. I am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction
or installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the
declarations in this statement (responsible acceptance person).
3. The information provided on this Certificate of Acceptance substantiates that the construction or installation identified on this Certificate of Acceptance complies
with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance
requirements and procedures specified in Reference Nonresidential Appendix NAS.
4. I have confirmed that the Certincate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and is
posted or made available with the building permits) issued for the building.
5. 1 will ensure that a completed, signed copy of this Certificate or Acceptance shall be posted, or made available with the building permit(s) issued for the
building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is
required to be included with the documentation the builder provides to the building owner at occupancy.
Responsible Acceptance Company Name
Person Name Bernardo Torres Advance Lighting and Electric Inc
Address: City
6305 Corona ave Bell
Zip Code 90201 Phone (323)338-1040
CSLB License Position with Company
(Title) Owner
Responsible Acceptance Person Signature
/-- V
Date of Signature: 05/21/2019
This is page 14 of 15
This is page 15 of 15