HomeMy WebLinkAboutX2019-0058 - Miscr i Ob J Provide a connection detail for guardrail to withstand a 200 Ib force at top of the railing acting in any direction, and min 50 Ib for intermediate guard components. The loads are not required to be cumulative. �.1. Specify U -factors and Solar Heat Gain Coefficient (SHGC) values for all fenestrations on window and door schedules. Add note to schedules, "Fenestrations must have tem orary and permanent T u . IP" labels." U-�r�c'aR- = E>--3 2- tA4A. I S Gj(L =0.2.AV I -AA* /0 12. Add note to the plans indicating that all lighting shall be high efficacy per section 150.0 (k) y3: In kitchen specify the local exhaust system vented to outdoors shall have a minimum exhaust rate of 100 cfm. BEES 150(0), Exc. 5 to 150.2(a) & ASHRAE Std. 62.2. 14. In baths specify the local exhaust system vented to outdoors shall have a minimum exhaust rate of 50 cfm. Humidistat controlled and Energy STAR rated. Forms\patio covers 9-16-04 CITY OF NEWPORT RC20 tq . cosy 32 j MOYI-lery �1l'Q , BEACH COMMUNITY DEVELOPMENT DEPARTMENT BUILDING DIVISION 100 Civic Center Drive I P.O. Box 1768 1 Newport Beach, CA 92658-8915 www.newportbeachca.gov 1 (949) 644-3200 Project Description: Project Address: PLAN REVIEW COMMENTS 321 MONTERO Plan Check No.: Permit App. Date: 1/4/19 Valuation: $80,000 Plan Reviewer: MELISSA KUBISCHTA, SE Phone: 949-644-3278 The project plans were reviewed for compliance with the following codes and standards: v2016 CRC; 2016 CBC; 2016 CPC; 2016 CEC; 2016 CMC; 2016 California Energy Code; 2016 California Green Building Standards Code (CG); & Chapter 15 of the Newport Beach Municipal Code (NEMC). 1. Obtain plan review approval from the following: a. Building Division b. Planning Division 2. Final drawings which will be approved for permit issuance, shall be signed by the respective design professional (electronic signature is acceptable). 3 - Provide drawings not on the City Standard Plan detailing the entire scope of work. 4: Provide fully dimensioned plot plan to scale. Show lot dimensions, street, alley, easements, all projections, and location of all structures. Include the following on all plan sheets in the title block: a. Site address b. Plan preparer's name, address and telephone number, ,6�- On the cover sheet provide the following information: a. Provide property owner's name, address and telephone number. b. Complete project description. ,,c: Code analysis including Construction Type, Occupanc Category, if the building is sprinklered. V 5 7/' Incorporate the latest version of the RESIDENTIAL CONSTRUCTION MINIMUM REQUIREMENTS specification into plans. Update plans to comply with the minimum requirements. Form available online at: http //www newportbeachca gov/Modules/ShowDocument aspx?documentid=11141 8 Incorporate the latest version of the CAL GREEN RESIDENTIAL MINIMUM REQUIREMENTS specification into plans. Update plans to comply with the mandatory requirements. Form available online at: http //www newportbeachca oov/Modules/ShowDocument aspx?documentid=11142 9. Guards (guardrails) shall meet the following: a. provide guards where the open side is more than 30 inches measured vertically to the floor (h or grade below at any point within 36 inches horizontally to the edge of the open side. R312.1.1 b. Guard height shall be a minimum of 42 inches. R312.2 C. Openings between intermediate balusters shall preclude the passage of a 4 inch diameter sphere. R312.3 d. The triangular openings formed by the riser, tread and bottom rail shall preclude the passage of a 6 inch diameter sphere. R312.1.3 Exception 1. e. Openings between intermediate balusters on the open side of stairs shall preclude the passage of a 4-3/8 inches diameter sphere. 312.1.3 Exception 2.