Loading...
HomeMy WebLinkAboutX2021-2275 - Calcs4159r Rd, Ste 200 SOD �aVJ� Temecula CA, 92590 Bayview coolin Tower Replacement PROJECT: 100 Bay g 001-022-21 JOB NO: CALCULATED BY: TJP 16 08/24/2021 SHEET NO. 1 OF DATE: ------- Structural Structural Calculations for: 100 Bayview Closed Circuit Cooler Replacement 100 Bayview Circle, Newport Beach, CA 92660 Prepared for: EMCOR Service Mesa Energy Systems 2 Cromwell Irvine, CA 92618 BUILDING DIVISION Project # 001-022-21 AUG 2 6 2021 August 24, 2021 V.Y.T. �FpFESS/ L Exp(12/31/21 ST STR�TUPP� \TF c" DATED SIGNED: 08.24.21 41593 WiPIRM ncVlester Rd, Ste 200 Temecula CA, 92590 PROJECT: 100 Bayview Cooling Tower Replacement JOB NO: 001-022-21 CALCULATED BY: TJP DATE: 08/24/2021 Sheetindex Sectio 1. Scope of Work and Project Information SHEET NO. = OF 16 Page Number 2. Design Parameters and ATC Hazards Ma p 3 3. ........... . Cooling Tower Seismic Fp Force6 -8 , Bolted Connection, and Frame Design ,.,,,.,., 4. Cooling Tower Frame and Spring Isolator Anchorage Design 5. Existing Composite Roof Framing Checks 9-11 6. Appendix 12-15 ............................... 16 PROJECT: 100 Bayview Cooling Tower Replacement JOB No: 001-022-21 41593 Winchester Rd, Ste 200 Temecula CA, 92590 CALCULATED BY: TJP DATE: 08/24/2021 SHEET NO. 3 OF 16 Scope Of Work The structural scope of work includes the design of a new steel frame supporting a replacement cooling tower on spring isolators and their attachment to existing concrete piers located on composite steel roof framing. Project Information Project Name: 100 Bayview Closed Circuit Cooler Replacement Project Address: 100 Bayview Circle, Newport Beach, CA 92660 Latitude/Longitude: 33.6560550N, 117.867818°W Project Manager: Jared Ferini e-mail: jared@equipproinc.com Applicable Building Code: 2019 California Building Code (CBC) PROJECT: 100 Bayview Cooling Tower Replacement 1r�MkV14M11q=1 JOB NO: 001-022-21 41593 Winchester Rd, Ste 200 Temecula CA, 92590 CALCULATED BY: TJP DATE: 08/24/2021 SHEET NO. 4 OF 16 Design Parameters Seismic Design Parameters: Site Class: Short Period Spectral Acceleration, Ss: Long Period Spectral Acceleration, S,: Short Period Site Coefficient, Fa: Design, Short Period Spectral Acc, Sns: Component Importance Factor, Ip: Over -strength Factor, Do: Component Amplification Factor, ap: Component Response Factor, Rp: Wind Design Parameters: Ultimate Design Wind Speed, Vult: Wind Exposure Category: Pressure Coefficient, (GCr): D - Default 1.299g 0.463g 1.2 1.039g 1.0 2.0 2.5 (spring isolators) 2.0 (spring isolators) 95 mph C 1.9 'Equipment is enclosed within full height walls, wind loading on the equipment has been ignored. Equipment Weights: BAC Closed Circuit Cooling Tower CT -3 (Model# FXV -0812A -12D -K): 13,785 lbs Existing Cooling Tower: 14,200 lbs P PROJECT: 100 Bayview Cooling Tower Replacement a� " J �" JOB NO: 001-022-21 41593 Winchester Rd, Ste 200 Temecula CA, 92590 CALCULATED BY: Tip DATE: 08/24/2021 SHEET NO. 6 OF 16 ATC Hazards Report 3/25/2021 ATC Hazards by Location OTCHazards by Location Search Information Address: 100 Bayview Cir, Newport Beach, CA 92660, �Slp� USA 56 ft 15 Coordinates: 33.65605499999999,-117.8678177 Farmers insurance James Mciver Elevation: 56 ft Timestamp: 2021-03-25T23:30:22.164Z Iii Sjereoscuoe Coffee .S�.. Hazard Type: Seismic '+krrsx,: • Ddivary Google Map data 02021 Google Reference ASCE7-16 Document: Risk Category: II Site Class: D -default Basic Parameters Name Value Description SS 1.299 MCER ground motion (period=0.2s) S1 0.463 MCER ground motion (period=11.0s) SMS 1.558 Site -modified spectral acceleration value SMI ' null Site -modified spectral acceleration value SDS 1.039 Numeric seismic design value at 0.2s SA SDI ` null Numeric seismic design value at 1.Os SA " See Section 11.4.8 ,. 41593 Winchester Rd, Ste 200 Temecula CA, 92590 PROJECT: 100 Bayview Cooling Tower Replacement JOB NO: 001-022-21 CALCULATED BY: Tip DATE: 08/24/2021 SHEET NO. 6 OF 16 Cooling Tower To Frame Seismic Flo Force And Bolted Connection Check Fp= Fp max = Fp min = Governing Fp= 0.4o,,.S,vill. fry �I+F� 113.311 Equation F 111 a.o9lwp �y / 1 E�662 F„ is not required to be taken as greater than 133-2 F„ = 1.6.S,ad„I1J, (1.3.3-3) o.z18wp and Fr, shall not he taken as less than Resisting Moment (Mr) = 52491 lb -ft Fl, =03.Sur7.1D„ (133-3) SDe=1.0399 Design 5%Damped, Spectral Response Acceleration at short periods Ip= 1.00 Component Importance Factor that varies from r.o to r.5 ap= 1.50 Component amplification factor that varies from i.00to 2.5 Rp= 1.00 Component esponse modification factor value z/h=1.o0 height in structure of point of attachment divided by average roof height of structure Or,= 2.00 Overstrength factor Fp= Fp max = Fp min = Governing Fp= `', BAC Closed CircuitCoolin TowerCT-3,(Model#':FXV-68saA=22DK).:,-`> ,- ASD Equation Weight=a3800 lbs Governing Fp=1.559wp (LRFD)(Per Previous Calc) a.o9lwp 13,3-1 E�662 1.164 wp 133-2 in Moment Arm, Fp 54 in o.z18wp 133-3 Resisting Moment (Mr) = 52491 lb -ft 1.0g1 wp (E,*d/1)- -188916-ft `', BAC Closed CircuitCoolin TowerCT-3,(Model#':FXV-68saA=22DK).:,-`> ,- `Loading Weight=a3800 lbs Governing Fp=1.559wp (LRFD)(Per Previous Calc) E,,=().2*SDs*DL)= 2868lbs (LRFD) SDs= 1.039 (Per Previous Calc) Non -Omega Level F = 21 07lbs (LRFD) Determine Max Tension Force Per Bolt: 1tof Bolts in Tension=2 d=loo in Moment Arm, Fp 54 in Non -Omega Level Overturning Moment(Mo)= 96783 lb -ft Resisting Moment (Mr) = 52491 lb -ft (E,*d/1)- -188916-ft (total) = 39602 Ili UPLIFT Tension Der Bolt= 3448lbs Determine Max Shear Forte. Per Bok Number of bolts in Shear= 4 Non -Omega Level V/bolt= s377lbs tension capacity for (1) 7/8” diameter A307 bolt, ern = 20.3 kip > 3.45 kip shear capacity for (1) 7/8" diameter A307 bolt, ern = 12.2 kip > 5.38 kip bolted connection is sufficient to resist the proposed seismic loads PROJECT: 100 Bayview Cooling Tower Replacement JOB NO: y ,. 001-022-21 -EZZ IJFi 'n n , .. 41593 Winchester Rd, Ste 200TJP CALCULATED BY: Temecula CA, 92590 7 OF 16 08/24/2021 SHEET No. DATE: Cooling Tower Frame Member Design CODE REFERENCES Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16 Load Combination Set: ASCE 7-16 Material Properties Fy : Steel Yield : 50.0 ksi Analysis Method Load Resistance Factor Design E: Modulus: 29,000.0 ksi Beam Bracing : Beam is Fully Braced against lateral -torsional buckling Bending Axis : Major Axis Bending _ -- _. _ - - _.._ _ _ E(3.50) _ D 0.750 'i - Wez24 WSx24 : W8x24 SPan = 1 .670 ft � SSpan = 8.670 ft pan = x.870 ft - - - - _ - - Service leads entered. Load Factors will be applied for calculations. lied Loads Beam self weight calculated and added to loading Load for Span Number 1 Uft niform Wilt, Extent = 0.250 --» 1.670 ft, Tributary Width = 1.0 Load: D = 0.750 Point Load : E = 3.50 k @ 0.330 ft Load for Span Number 2 Uniform Load : D = 0.750 k/ft, Tributary Width = 1.0 ft Load for Span Number 3 nt = 0.0 --» 1.420 ft, Tributary Width = 1.0 ft Uniform Load : D = 0.750 k/ft, Exte Point Load : E = 3.50 k @ 1.340 ft DESIGN SUMMARY Maximum Bending Stress Ratio = Section used for this span Mu: Applied Mn * Phi: Allowable Load Combination Location of maximum on span Span # where maximum occurs Maximum Deflection Max Downward Transient Deflection Max Upward Transient Deflection Max Downward Total Deflection Max Upward Total Deflection Note: 65% of tower weight applied as a line load used as per the approved submittal - 1 Maximus Stress 0.160: used for thistio ctionar span W8x24 13.817k -ft Vu :Applied 86.625 k -ft Vn *Phi :Allowable +1.408D -E Load Combination Location of maximum on span 4.3,35ft Span # where maximum occurs Span # 2 0.027 in Ratio= 1,471 >=360 span: 3 : E Only * -1.0 -0.027 in Ratio= 11471 >=360 Span: 3: E Only 0.059 in Ratio = 1776 >=180 Span: 3: +D -0.70E -0.040 in Ratio = 1005 >=180 Span: 3 : +D -0.70E deflection does not exceed 1/2" as per the approved submittal 0.087: 9 W8x24 5.056 k 58.286 k +1.408D+E 1.670 ft Span # 1 r ar� „� :■ PROJECT: 100 Bayview Cooling Tower Replacement 41593 Winchester Rd, Ste 200 JOB NO: 001-022-21 Temecula CA, 92590 CALCULATED BY: Tip DATE: 08/24/2021 ---�-- SHEET NO. $ OF 18 Cooling Tower Frame And Spring isolator Welded Connections Design For Cooling Tower Frame To Spring Isolator: longitudinally loaded weld (1/4" fillet, 4" length, each side of beam, ignore 1" at the start and end of welds): tRn = 1.392(D)(1) = 1.392(4)(6 in) = 33.41 kips (conservative) > 5.4 kip transversely loaded weld: �Rn = 1.5(1.392)(D)(1) = 1.5(33.41 kip) = 50.12 kips > 3.5 kip For Spring Isolator To Base Plate (1/4" fillet, 4" length, each side of beam, ignore 1" at the start and end of welds): longitudinally loaded weld: �Rn = 1.392(D)(1) = 1.392(4)(6 in) = 33.41 kips > 5.4 kip transversely loaded weld: ORn = 1.5(1.392)(D)(1) = 1.5(33.41 kip) = 50.12 kips > 3.5 kip C�flUIP .: 11r .� 41593 Winchester Rd, Ste 200 Temecula CA, 92590 PROJECT: 100 Bayview Cooling Tower Replacement JOB NO: 001-022-21 CALCULATED BY: TJP DATE: 08/24/2021 SHEET NO. 9 OF 16 Cooling Tower Frame and Spring Isolator Anchorage To Existing Concrete Piers R, � n 1„ r„ is not required to Iv_ taken as greater than F„= 1.6s"'10p. (13.3-2) and F„ shall not be taken as less than Fp= Fp max= Fp min = Governing Fp= LFRD F„=0.3S„J„4V„ (11.3-3) SDs=1.0399 Designs%Damped, Spectral Response Acceleration at short periods Ip= 1.00 Component Importance Factor that varies from iato¢.5 ap= 2.50 Component amplification factor that varies from 1.00 to 1.5 Rp= 2.00 Component response modification factor value 2/h=1.00 height in structure of point of attachment divided by average roof height of structure no= 2.00 Overstrength factor Fp= Fp max= Fp min = Governing Fp= LFRD ASD Equation 1559 w'P 1.091wp 13.3-1 1.662 wp 1.164 VVP 133'2 0.312 wp 0.218 wp 133-3 1559 w'P 2.091wp Determine Max Tension Force Per Anchor ” BAC Closed Circuit Cool! Tower CT -3 with frame and isolators Loading Weight =25300 lbs Governing Fe=1.559 Wp (LRFD)(Per Previous Calc) E„=(0.2*S,,.DL)=3179lbs (LRFD) SDs; =1.039 (Per Previous Calc) Non -Omega Level Omega Level (Do) F = 238 lbs (LRFD) F,,j F,,Do= E690 lbs (LRFD) Determine Max Tension Force Per Anchor g of Anchors In Tension 2 d=96in Moment Arm, Fp=71in Non -Omega Level Omega level (Dol) Overturning Moment (M.) = 141083 lb -ft Overturning Moment (Mp) no = 28216616 -ft Resisting Moment (M,) = 55o8o Ib -ft Resisting Moment (M,) = 5508016 -ft (E,*dh)= -1271716-ft (E, -d)1)= -12717 Ib -ft (total)=42363lb-ft UPLIFT (total)=4236316-ft UPLIFT Tension per Anchor= 61701bs Tper Anchor wt no 144 6816s Determine Max Shear Force Per 4w, or Number of Anchors in Shear= 4 Non -Omega Level Omega Level (DO) VlAnchor= 5961lbs VlAnchorw no= 11922 Ibs design post installed anchorage for omega tension load steel side plates resist seismic shear loads ir 41593 Winchester Rd, Ste 200 Temecula CA, 92590 PROJECT: 100 Bayview Cooling Tower Replacement JOB NO: 001-022-21 CALCULATED BY: Tip DATE: 08/24/2021 SHEET NO. 10 OF 16 Cooling Tower Frame and Spring Isolator Anchorage To Existing Concrete Piers 1 Input data Anchor type and diameter: Item number: Effective embedment depth: Material: Evaluation Service Report: Issued I Valid: Proof: Stand-off installation: Anchor plate Profile: Base material: Installation: Reinforcement: Seismic loads (cat. C, D. E, or F) Kwik Bolt TZ2 - SS 304 3/4 (3 3/4) 2210287 KB-TZ2 3/4x6 1/4 SS304 he,,, = 3.750 In., h... = 4.500 In. AISI 304 ESR -4266 3/1/2021 112/11/20211 Design Method ACI 318-14 / Mach en = 0.000 in. (no stand-off); t = 0.500 in. I, x Ir x t = 16.000 in. x 16.000 in. x 0.500 in.; (Recommended plate thickness: not calculated) no profile cracked concrete, 3000, f�= 3,000 psi; h = 15.000 in, hammer drilled hole, Installation condition: Dry tension: condition B, shear: condition B; no supplemental splitting reinforcement present edge reinforcement: > No. 4 bar Tension load: yes (17.2.3.4.3 (d)) Shear load: yes (17.2.3.5.3 (c)) R - The anchor calculation is based on a rigid anchor plate assumption. i X UIPE 41593 Winchester Rd, Ste 200 Temecula CA, 92590 PROJECT: 100 Bayview Cooling Tower Replacement JOB NO: 001-022-21 CALCULATED BY: TJP DATE: 08/24/2021 SHEET NO. 11 OF 16 Cooling Tower Frame and Spring Isolator Anchorage To Existing Concrete Piers 3 Tension load Load N,,, [lb] Steel Strength* 3,747 Pullout Strength* N/A Concrete Breakout Failure** 14,988 * highest loaded anchor **anchor group (anchors in tension) Capacity @ N„ [Ib] Utilization P. = N,,,/m N„ Status 18,041 21 OK N/A N/A N/A 15,501 97 OK y X A 41593 Winchester Rd, Ste 200 Temecula CA, 92590 PROJECT: 100 Bayview Cooling Tower Replacement JOB NO: 001-022-21 CALCULATED BY: Tip DATE: 08/24/2021 SHEET NO. 12 OF 16 Roof Framing Check - Existing W12x14 Composite Beam I CODE REFERENCES Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16 Load Combination Set : ASCE 7-16 Analysis Method' Allowable Stress Design Beam Bracing : Beam is Fully Braced against lateral -torsional buckling t Load CombinatiorASCE 7-16 Fy : Steel Yield: 36.0 ksi E: Modulus: 29,000.0 ksi Composite Beam Section Data Total Slab Thickness 6.250 in Effective Width 7,Oft Metal Deck ... Verco, PLW3 Formlok Ribs: Perpendicular D(4. -a) Concrete f Concrete Density Rib Height Rib Spacing W 12x14 K^4 .FfT0... Beam is UNSHORED for Concrete Placement 3.0 ksi Stud Diameter 3/4" in 145.0 pcf On : Stud Capacity 11.0 k 3.0 in Top Width 7.50 in 12.0 in Btm Width 4.50 in Service loads entered. Load Factors will be applied for calculations. Beam + Slab self weight calculated and added to loads Load for Span Number Uniform Load : D = 0.05625 ksf, Tributary Width = 7.0 ft, Post Composite Only Point Load : D = 4.805 k @ 2.50 ft, Post Composite Only Point Load : D = 4.805 k @ 10.0 ft, Post Composite Only Uniform Load : D = 0.020, Lr = 0.020 ksf, Tributary Width = 7.0 ft, Post Composite Only DESIGN SUMMARY MAX Bending Ratio = 0.729 :1 MAX Shear Ratio = 0.390 : 1 Steel section W12x14 Vu : Applied 13.367 k Composite Vn/Omega : Allow 34.272 k Location of maximum 0,0 ft % Composite Action 44 % Load Combination Mu: Applied 45.653 k -ft +D+Lr Mn / Omega: Allow 62.623 k -ft Location of maximum 7.830 ft Load Combination +D+Lr Pre -Composite Mu: Applied 10.927 k -ft Mn " Phi: Allowable 31.257 k -ft From Stud )ort 0 to 8.02 ft use 6 studs, ft to Support 1 use 6 studs. nnmzm�� 0.018 in Max Upward 0.000 in FINAL Composite 9790 Max Downward 0.336 in Max Upward 0.000 in Deft Ratio 517 +D+Lr Transient Composite Max Downward 0.018 in Max Upward 0.000 in Defl Ratio 9790 Lr Only NonComposite Max Downward 0.163 in Max Upward 0.000 in Defl Ratio 1069 PreCompDL+PreCompLL 41593 Winchester Rd, Ste 200 Temecula CA, 92590 PROJECT: 100 Bayview Cooling Tower Replacement JOB NO: 001-022-21 CALCULATED BY: TJP DATE: 08/24/2021 SHEET NO. 13 OF 16 Roof Framing Check - Existing W12x14 Composite Beam Load Comb 8 Design Length Max Stress Ratios Bending Summary Shear Summary Span # M V Mu -Applied 4nTr / Omega V. Vn /Omega Pre Composite:. D + Const L 0.350 0.088 10.93 31.26 3.01 34.27 Span L = 14.5 ft 1 Final Composite: D Only 0.671 0.360 42.00 62.62 12.35 34.27 Span L = 14.5 ft 1 Final Composite : +D+Lr 45.65 62.62 13.37 34.27 Span L = 14.5 It 1 0.729 0.390 Final Composite: +D+0.750Lr 44.74 62.62 13.11 34.27 Span L = 14.5 It 1 0.714 0.383 Final Composite: +0.60D 25.20 62.62 741 34 27 Span L = 14.5 ft 1 0.402 0.216 Maximum Deflections for Load Combinations - Unfactored Loads Location DEFLECTIONS (in) Added Post Ixx -Used Load Combination in Span (ft) FINAL Pre -Composite onComposite Remove Composite inA4 Precomposite Downward 7.347 0.000 0.1627 8 0 8.6 88.00 Precomposite NonComposite Removed Upward 0.000 Downward 7.347 0.000 0.000 0.1627 0.00 0.00 NonCompasite Removed Upward 0.000 0.000 0.156 0.1627 0.163 273.05 Final Composite : D Only Downward 7.347 273.05 Final Composite : D Only Upward 0.000 7.347 0.000 0.174 0.1627 0.163 273.05 Final Composite : +D+Lr Downward 273.05 Final Composite: +D+Lr Upward 0.000 7.347 0.000 0.169 0.1627 0.163 273.05 Final Composite : +D+0.750Lr Downward 273.05 Final Composite: +D+0.750Lr Upward 0.000 7.347 0.000 0.094 0.0976 0.098 273.05 Final Composite : +0,60D Downward 273.05 Final Composite: +0.60D Upward 0.000 0.000 0.018 273.05 Final Composite : Lr Only Downward 7.347 273.05 Final Composite : Lr Only Upward 0.000 0.000 Maximum Vertical Reactions - Unfactored support notation : Far left is # Load Combination Support 1 Support 2 Overall M imum 13.367 12.041 Precomposite Loads 3.014 3.014 NonComposite Removed 3.014 3.014 Final Composite: D Only 12.352 11.026 Final Composite: +D+Lr 13.367 12.041 Final Composite: +D+0.750Lr 13.113 11.788 Final Composite: +0.60D 7.411 6.616 Final Composite: Lr Only 1.015 1.015 Steel Section Properties W12x14 De th = P 11.900 in Ixx = 88.60 in"4 Iyy = 2.360 inA4 A3 Web Thick = 0.200 in S xx = 14.90 in^3 S yy _ - 1.190 !n Flange Width = 3.970 in R xx = 4.620 in R yy = 0.753 in Flange Thick = 0.225 in Zx = 17.400 in A3 Zy = 1.900 in Area = 4.160 inA2 J = 0.070 inA4 Weight = 14.000 pit Composite Section Properties Span Number Analysis %Shear Plastic N.A. Sum On #Studs per Mn -Capacity I Moment of Inertia I I-Lwr Bound Plastic N. A. Location Type Connection from Bottom Shear (k) 1/2 Span k -ft -Steel -Trans in a PNA in Flange 95.0 11.874 142.272 13 146.60 88.6 522.8 374.0 367.0 PNA in Flange 90.0 17.848 134.784 13 12 142.81 139.01 88.6 522.8 88.6 522.8 359.4 PNA in Flange 85.0 11.821 80.0 11.795 127.296 119.808 11 135.19 88.6 522.8 351.3 PNA in Flange PNA in Flange 75.0 11.769 112.320 11 131.36 88.6 522.8 342.7 333.4 PNA in Flange 70.0 11.743 104.832 10 127.51 123.66 88.6 522.8 88.6 522.8 323.5 PNA in Flange 65.0 11.717 60.0 11.690 97.344 89.856 9 9 119.78 88.6 522.8 312.9 PNA in Flange PNA in Web 55.0 11.461 82.368 8 114.06 88.6 522.8 301.4 PNA in Web 50.0 10.941 74.880 7 7 109.94 105.51 88.6 522.8 88.6 522.8 289.1 275.8 PNA in Web 45.0 10.421 40.0 9.901 67.392 59.904 6 100.75 88.6 522.8 261.5 PNA in Web 35.0 9.381 52.416 5 95.66 88.6 522.8 245.9 PNA in Web 30.0 8.861 44.928 5 90.25 88.6 522.8 229.0 PNA in Web 25.0 8.341 37.440 4 84.52 88.6 522.8 210.7 PNA in Web -^' A k{ xt 41593 Winchester Rd, Ste 200 Temecula CA, 92590 PROJECT: 100 Bayview Cooling Tower Replacement JOB NO: 001-022-21 CALCULATED BY: Tip DATE: 08/24/2021 SHEET NO, 14 OF 16 Framing Check - Existing W18x35 Composite Beam FLoadRoof CODE REFERENCES Calcper AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16 :C:om:bInationSet: ASCE 7-16 ateoperties Analysis Method Allowable Stress Design Beam Bracing : Beam is Fully Braced against lateral -torsional buckling i Load CombinatiorASCE 7-16 Fy: Steel Yield: 36.0 ksi E: Modulus: 29,000.0 ksi Composite Beam Section Data Beam is UNSHORED for Concrete Placement Total Slab Thickness 6.250 in Concrete f 3.0 ksi Stud Diameter 3/4" in Effective Width 3.50 ft Concrete Density 145.0 pcf Metal Deck., Verco, PLW3 Formlok Rib Height 3.0 Qn : Stud Capacity 11.0 k in Ribs: Perpendicular Rib Spacing 12.0 in Top Width Btm Width 7.50 in 4.50 in D(4a05) -- -�_ D 0.14 Lr 0.14 14.605) D(6 _ oto 156675 �iSL7i1r(6-67) 0. 375 II CW18 39 jooft Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam + Slab self weight calculated and added to loads Load for Span Numbed Uniform Load : D = 0.05625 ksf, Extent = 0.0 --» 15.0 ft, Tributary Width = 7.0 ft, Post Composite Only Point Load : D = 4.805 k @ 2.50 It, Post Composite Only Point Load : D = 4.805 k @ 10.0 ft, Post Composite Only Uniform Load : D = 0.020, Lr = 0.020 ksf, Extent = 0.0 -->> 15.0 ft, Tributary Width = 7.0 ft, Post Composite Only Uniform Load : D = 0.020, Lr = 0.020 ksf, Extent = 15.0 -->> 30.0 ft, Tributary Width = 3.50 ft, Post Composite Only Uniform Load : D = 0.05625 ksf, Extent = 15.0 -->> 30.0 it, Tributary Width = 3.50 ft, Post Composite Only Point Load: D = 6.680 k @ 15.0 ft, Post Composite Only DESIGN SUMMARY MAX Bending Ratio = 0.810 :1 MAX Shear Ratio = 0.305 _ :1 DEFLECTIONS 0 Steel section 1N18x35 Vu: Applied 23.329 k FINAL Composite Composite Vn/Omega : Allow 76.464 k Max Downward 0.946 in % Composite Action 42 o Location of maximum 0.0 it /o Max Upward 0.000 in Load Combination Mu : Applied PP 163.516 k -ft Dell Ratio 380 +D+Lr Mn / Omega: Allow 201.790 k -ft +D+Lr Location of maximum 15.0 ft Transient Composite Load Combination Max Downward 0.060 in +D+Lr Max Upward 0.000 in Pre -Composite Dell Ratio 6012 Mu: Applied 26.537 k -ft Lr Only Mn * Phi: Allowable 119.461 k -ft NonComposite Max Downward 0.294 in Max Upward 0.000 in Deo Ratio 1225 PreCompDL+PreCompLL Shear Stud Requirements From Support 0 to 15.00 ft use 14 studs. 41593 Winchester Rd, Ste 200 Temecula CA, 92590 PROJECT: 100 Bayview Cooling Tower Replacement JOB NO: 001-022-21 CALCULATED BY: TJP DATE: 08/24/2021 SHEET NO. 15 OF 16 Roof Framing Check - Existing W18x35 Composite Beam Shear Stud Requirements From 15.00 ft to Support 1 use 14 studs. Maximum Forces & Stresses for Load Combir Load Comb &Design Length Max Stress Ratios Bending Summary Shear Summary Span # M V Mu -Applied AnTr /Omega Va Vn / Ome a 9 Pre Composite : D + Const L 26.54 119.46 3.54 76.46 Span L = 30 ft 1 0.222 0.046 Final Composite : D Only 151.70 201.79 21.49 76.46 Span L = 30 ft 1 0.752 0.281 Final Composite: +D+Lr 0.810 0.305 163.52 201.79 23.33 76.46 Span L = 30 ft 1 Final Composite: +D+0.750Lr 160.56 201.79 22.87 76.46 Span L = 30 it 1 0.796 0.299 Final Composite : +0.60D 91.02 201.79 12.90 76.4fi Span L = 30 it 1 0.451 0.169 Maximum Deflections for Load Combinations - Unfactored Loads LocationDEFLECTIONS (in) Added Past Ixx-used in Span FINAL Pre -Composite onCom P osite Remove Composite in^4 Load Combination 510.00 20 Precomposite Downward 15.200 0.000 0.299 38 510.00 Precomposite Upward 0.000 NonComposite Removed Downward 15.200 0.000 0.000 0.2938 0.00 0.00 NonComposite Removed Upward 0.000 0.000 0.592 0.2936 0294 1,115.42 Final Composite : D Only Downward 14.800 0.000 1,115.42 Final Composite : D Only Upward 0.000 Downward 14.800 0.652 0.2936 0,294 1,115.42 Final Composite : +D+Lr Final Composite : +D+Lr Upward 0.000 0.000 0,294 1,115.42 1,115.42 Final Composite : +D+0.75nLr Downward 14.800 0.637 0.2936 1,115.42 Final Composite : +D+0.750Lr Upward 0.000 0.000 0.355 0.1762 0.176 1,115.42 Final Composite : +0.60D Downward 14.800 0.000 0.000 1,115.42 Final Composite : +0.60D Upward 0.060 1,115.42 Final Composite : Lr Only Downward 14.600 1,115.42 Final Composite : Lr Only Upward 0.000 0.000 Maximum Vertical Reactions - Unfactored Support notation : Far left is p Load Combination Support 1 Support 2 Overall MAXimum 23.329 15.197 Precomposite Loads 3.538 3.538 NonComposite Removed 3.538 3.538 Final Composite : D Only 21.492 13.884 Final Composite : +D+Lr 23.329 15.197 Final Composite: +D+0.750Lr 22.870 14.869 Final Composite: +0.60D 12.895 8.331 Final Composite: Lr Only 1.838 1.313 Steel section Properties W1 8x35 Depth = 17.700 in I pc = 510.00 in 4 I yy = 15.300 104 n Web Thick = 0.300 in 8 xx = 57.60 in -3 S yy _ _5.120 Flange Width = 6.000 in R = 7.040 in Ryy 1220 in 8.060 Flange Thick = 0.425 in ZX = 66.500 in -3 Zy _ 0.506 in -4 Area = 10.300 in"2 Weight = 35.000 plf Composite Section Properties °/ Plastic N.A. Sum On # Studs per Mn - Capacity Moment of Inertia Span Number Analysis Shear from Bottom Shear (k) 112 Span k -ft I -Steel I -Trans I-Lwr Bound Plastic N. A. Location Type Connection in ange 95.0 17.607 330.671 31 413.10 510.0 1,627.5 1,402.3 PNA in Flange 90.0 17.567 313.268 29 413.10 510.0 1,627.5 1,387.2 PNA in Flange 85.0 17.527 295.864 27 413.10 510.0 1,627.5 1,370.3 PNA in Flange 80.0 17.486 278.460 26 413.10 510.0 1,627.5 1,351.3 PNA in Flange 75.0 17.446 261.056 24 405.67 510.0 1,627.5 1,330.0 PNA in Flange 70.0 17.406 243.653 23 396.55 510.0 1,627.5 1,306.2 PNA in Flange 65.0 17.365 226.249 21 387.38 510.0 1,627.5 1,279.8 PNA in Flange 60.0 17.325 208.845 19 378.16 510.0 1,627.5 1,250.4 PNA in Flange 55.0 17.285 191.441 18 368.90 510.0 1,627.5 1,217.8 PNA in Flange 50.0 16.666 174.038 16 354.48 510.0 1,627.5 1,181.6 PNA in Web 45.0 15.860 156.634 15 343.90 510.0 1,627.5 1,141.5 PNA in Web 40.0 15.054 139.230 13 332.15 510.0 1,627.5 1,097.1 PNA in Web 144-7= 41593 Winchester Rd, Ste 200 Temecula CA, 92590 PROJECT: 100 Bayview Cooling Tower Replacement JOB NO: 001-022-21 CALCULATED BY: Tip DATE: Appendix 08/24/2021 SHEET NO. 16 OF 16 T IIIIII�oi�dlllil ENT AIR TREA CORPORATION 640 N. Puente St., Brea Ca. 92821 • (909) 869-7975 • www.airtreatment.com ENGINEERING PACKAGE Project Name: 100 Bayview — Tenant Cooling Tower Replacement Date: March 25, 2021 Contractor: EMCOR Mesa Representatives: Scott McCarthy Submittal Status: PENDING APPROVAL No equipment has been released for production Equipment Included in Submittal: Manufacturer I S ecification Number BAC Closed Circuit Coolin Tower : BALTIMORE AIRCOIL COMPANY Submittal Data Form 3-25-2021 Sold To: Air Treatment Corporation Project: 640 N Puente St Purchase Order No: SW21 116 Brea, CA 92821 Engineer: United States BAC Order # Q21002120001 Representative: AIR TREATMENT CORPORATION All Information is per Unit Quantity: 1 Model FXV -0812A -12D -K CLOSED CIRCUIT COOLING TOWER Certified Capacity: 432.00 USGPM of Water from 95.00-F to 85.00°F at 72.00°F entering air wet bulb and 6.12 PSIG fluid pressure drop. Fan Motor(s): One (1) 10 HP fan motor(s): Totally Enclosed, Air Over (TEAO), 1 Speed/1 Winding - Premium Efficiency (Inverter Duty), suitable for 460 volt, 3 phase, 60 hertz electrical service and Space Heater. Drives are based on 0 inches ESP. NOTE: Inverter Duty fan motors, furnished in accordance with NEMA Standard Mg.1 drives for fan motor control. -- Part 31, are required for applications using variable frequency Pump(s): One (1) 5 HP pump motor: 1 Speed/1 Winding - Energy Efficient, suitable for 460 volt, 3 phase, 60 hertz. Submittal Infnrrve�-7 Mechanical Specifications Submittal Drawings/Diagrams UP -Q21002120001 SS -Q21002120001 CG -Q21002120001 BA -Q21002120001 ML -Q21002120001 VL -Q21002120001 VW -Q21002120001 IA -Q21002120001 Unit Print Unit Support Center of Gravity Basin Accessories Motor Location VCOS Location VCOS Wiring Internal Access Steel Panels and Structural Members are Constructed of Galvanized Steel Standard Fan Galvanized Steel Fan Guard PVC Fill & Drift Eliminators Galvanized Steel, Full Circuit Coil Structure Designed in accordance with the IBC and ASCE/SEI 7 Integral Pumps with End Make -Up, Drain and Overflow Connections PVC Spray Branches Mechanical Float Valve Assembly Mechanical Vibration Cutout Switch Internal Walkway and Ladder THANK YOU FOR YOUR BUSINESSI Rigging and Installation Instructions, as well as Operating and Maintenance Instructions are available at www.baltimoreaJrcoil.com Corporate Headquarters: 7600 Dorsey Run Road, Jessup, Company MD 20794 Tele: (410) 799-6200 / Fax: (410) 799-6416 BALTIMORE AIRCOIL COMPANY Customer: Project: Purchase Order No: Engineer: BAC Order # Mechanical Specifications 3-25-2021 Air Treatment Corporation SW21-116 Q21002120001 All Information is per Unit Quantity: 1 Model FXV•0812A-12D-K CLOSED CIRCUIT COOLING TOWER CTI Certification: The thermal performance of this BAC unit has been certified through performance tests conducted by the Cooling Technology Institute in accordance with their standard STD -201 RS. Your equipment may be selected for factory -testing to verify CTI certified performance. Such certification by an independent third party assures engineers and users that the published thermal capacities accurately reflect the actual unit performance. CTI certification eliminates the additional costs of on-site, individual unit testing, oversizing the equipment or operating cost penalties from deficient equipment. Materials of Construction: All structural steel components are constructed from G-235 (Z700 metric) hot -dip galvanized steel. The edges of the hot -dip galvanized steel components are given a protective coat of zinc -rich compound. The basin includes a depressed section with drain/clean-out connection and the areas under the fill sections are sloped toward the depressed section for easy cleaning. The casing is constructed entirelyfrom heavy gauge, G-235 (Z700 metric) hot -dip galvanized steel panels. Hinged access doors are provided on each side wall of the tower for access to the eliminators and the fan plenum section for all cells. The doors are made of a steel frame matching the unit construction. The air inlet louvers are constructed of PVC honeycomb shape louver which also act as an air inlet screen and block sunlight to the basin and the front of the fill. Fan Type: The unit is provided with the standard fan to maximize the capacity. The fan is driven by the BALTIDRIVE Power Train. This drive system consists of cast aluminum sheaves located on minimum shaft centerline distances. A premium efficient fan motor provides maximum performance and is backed by BAC's comprehensive 5 -year motor and fan drive warranty. Fan Guard(s): A heavy gauge, G-235 (Z700 metric) hot -dip galvanized steel wire fan guard is provided over each fan cylinder. Fill: The BACross® Fill and integral drift eliminators are formed from self -extinguishing (per ASTM D-568) polyvinyl chloride (PVC), having a flame spread rating of 5 per ASTM Standard E84 -77a, and are impervious to rot, decay, and fungus or biological attack. The fill is elevated above the cold water basin floor to facilitate cleaning. This fill is suitable for a maximum entering water temperature of 130°F (54.44°C). The eliminators are designed to effectively strip entrained moisture from the leaving airstream with a minimum of air resistance. Coil Type The coil is suitable for cooling fluids compatible with carbon steel in a closed system. The coil(s) will be constructed with continuous 1.05" O.D. all prime surface steel tubes continuously formed and bent in a serpentine shape, encased in steel framework. The entire assembly is hot -dip galvanized after fabrication. Coil will be designed for free liquid drainage. Coil has a maximum allowable working pressure of 300 psig (2170 kPa) and is tested at 375 psig (2585 kPa) air pressure under water. The system should have a vent placed at the highest point in the installation to facilitate filling and drainage (provided and installed by others). Equipment Structure: The structure of this product has been designed and analyzed in accordance with the wind and seismic load requirements of the 2006 IBC, 2009 IBC, 2012 IBC, 2015 IBC, ASCE/SEI 7-05, and ASCE/SEI 7-10. Seismic qualification is based on analysis. For more information and specific wind and seismic load capacity ratings, please see the Certificate of Wind and Seismic Load Capacity. Corporate Headquarters: 7600 Dorsey Run Road, Jessup, MD 20794 — Tele: (410) 799-6200 / Fax: (410) 799-6416 Spray Water Pump Assembly: Each cold water basin has an integral pump with large area, lift out, steel strainer screens including perforated openings sized smaller than the water distribution nozzle orifices. Strainers include anti-vortexing baffles to prevent air entrainment. A close -coupled, bronze -fitted pump with a mechanical seal is mounted on the basin. The pump motors are premium efficiency, totally enclosed, fan cooled (TEFL). A water bleed line with a metering valve to control the bleed rate is installed between the pump discharge and the overflow connection. Electrical requirements match the fan motor. Spray Distribution System: Spray header with schedule 40 PVC branches. Removable branches and 360° spray pattern plastic spray nozzles are held in place with snap -in rubber grommets. Basin Water Level Control: The unit is supplied with a make-up valve with unsinkable polystyrene filled plastic float arranged for easy adjustment. The corrosion resistant make-up valve is suitable for water supply pressures between 15 psig (103 kPa) and 50 psig (345 kPa). Vibration Cutout Switch: Fan system is provided with an appropriate number of vibration cutout switches to limit collateral damage to the unit in the event of a catastrophic fan failure. The vibration switch(es) is mechanically tripped with a frequency range of 0 to 3,600 RPM and trip point of 0.2 to 2.0 g's. No input power is required. Switch rating is 10 amperes at a maximum 480 VAC, and 1/4 ampere at 250 Vdc. Internal Access Option: The unit has access doors on both ends, an internal walkway, and an internal aluminum ladderwith galvanized steel supports to facilitate access to the mechanical equipment. All components meet pertinent OSHA standards. Corporate Headquarters: 7600 Dorsey Run Road, Jessup, MD 20794 — Tele: (410) 799-6200 / Fax: (410) 799-6416 Baltimore Aircoll Company Closed Circuit Product Selection Report 0 Version: 7.8.2 NA Product data correct as of: January 27, 2021 Project Name: Selection Name: Project State/Province: California Project Country: United States Date: March 25, 2021 Model Information Product Line: Model: Number of Units: Wet Coil Type: Coil Finning: Fan Type: Fan Motor: Total Standard Fan Power: Total Pump Motor Power: Intake Option: Internal or Const. Option: Discharge Option: FXV FXV -0812A -12D -K 1 Standard Coil None Standard Fan (1) 10.00 = 10.00 HP/Unit Full Speed, 10.00 BHP/Unit (1) 5.00 = 5.00 HP/Unit None None None Design Conditions 10,555 lbs Fluid: Water Flow Rate: 432.00 USGPM Entering Fluid Temp.: 95.00 OF Leaving Fluid Temp.: 85.00 OF Wet Bulb Temp.: 72.00 OF Heat Rejection: 2,159,136 BTUH Fluid Pressure Drop: 6.12 psi Reserve Capability at 10.00 HP: 4.22% Thermal performance at design conditions and total standard fan motor power is certified by the Cooling Technology Institute (CTI). Engineering Data per Unit Unit Length:12' 00.00" + 01'06.00" (Pump) = 13'06.00" (Total) Unit Width: 08'05.25" Unit Height: 12'06.25" Approximate Shipping Weight: 8,026 lbs Heaviest Section: 5,058 lbs Approximate Operating Weight: 13,785 lbs Approximate Remote Sump Operating Weight: 10,555 lbs Air Flow: 53,850 CFM Spray Water Flow: 719 USGPM Coil Volume: 88 U.S. gallons Coil Connections: (2) 4" Coil Inlet and Outlet, Based on 432.00 USGPM Flow per Unit Remote Sump Connections: (1) 10" Heater kW Data (Optional) 0°F (-17.8°C) Ambient Heaters: (1) 8 kW -20°F (-28.9°C) Ambient Heaters: (1) 12 kW Minimum Distance Required: From Solid Wall: 5 ft. From 50% Open Wall: 4 ft. Energy Rating: 31.27 per ASHRAE 90.1, ASHRAE 189 and CA Title 24. Note: These unit weights and dimensions account for the selected fan type for the standard cataloged drive configuration, but they do not account for other options/accessories. Please contact your local BAC sales representative for weights and dimensions of units with other options/accessories. Page 113 Baltimore Alrcoll Company Closed Circuit Product Selection Report 0 Version: 7,8,2 NA Product data correct as of: January 27, 2021 Project Name: 92 Selection Name: 90L F Range Project State/Province: California Rangew86 Project Country: United States Range� Date: March 25, 2021 Point.E Model Information Product Line: FXV Design Conditions Model: Number Units: FXV -0812A -12D -K Fluid: Flow Rate: Water 432.00 USGPM of Wet Coil Type: 1 Standard Coil Entering Fluid Temp.: 95.00 OF Coil Finning: None Leaving Fluid Temp.: 85.00 OF Fan Type: Standard Fan Wet Bulb Temp.: 72.00 OF Fan Motor: (1) 10.00= 10.00 HP/Unit :.:..... Total Standard Fan Power: Full Speed, 10.00 BHP/Unit Heat Rejection: 2,159,136 BTUH Total Pump Motor Power: (1) 5.00 = 5.00 HP/Unit Fluid Pressure Drop: 6.12 Intake Option: None psi Internal or Const. Option: None 54 58 56 60 62 84 66 88 70 72 74 76 78 Discharge Option: None Wet Bulb Temperature (°F) Design Condition Ca) Standard Total Fan Rotor Pointer per Thermal performance at design conditions and total standard fan unit it (10 0. U HPl motor power is certified by the Cooling Technology Institute (CTI). These performance curves are based on constant fan power. Predicted Performance Fan Motor Alternative = Full Speed, 10.00 BHP now Rare = 4:12.00 USGPM (100.00% of Design) Page 213 92 90L F Range u B8F Rangew86 Range� Point.E 80 76 74..-. ........ .........C72- :.:..... ....�... 68 ......, . ......... ... r.a: 66 52 54 58 56 60 62 84 66 88 70 72 74 76 78 Wet Bulb Temperature (°F) These performance curves are based on constant fan power. Page 213 Baltimore Alrcoil Company Closed Circuit Product Selection Report 0 Version: 7.8.2 NA Product data correct as of: January 27, 2021 Project Name: Selection Name: Project State/Province: Project Country: Date: Model Information Product Line: FXV Model: FXV -0812A -12D -K Number of Units: 1 Wet Coil Type: Standard Coil Coil Finning: None Intake Option: None Internal or Const. Option: None Discharge Option: None California United States March 25, 2021 Fan Type: Standard Fan Fan Motor: (1) 10.00 = 10.00 HP/Unit Total Standard Fan Power: Full Speed, 10.00 BHP/Unit Total Pump Motor Power: (1) 5.00 = 5.00 HP/Unit Octave band and A -weighted sound pressure levels (Lp) are expressed in decibels (dB) reference 0.0002 microbar. Sound power levels (Lw) are expressed in decibels (dB) reference one picowatt. Octave band 1 has a center frequency of 63 Hertz. Back Lp Sound Pressure (da) Octave Distance Band 5 ft. 50 ft. 1 74 69 2 80 67 3 76 68 4 71 64 5 67 60 6 54 51 7 46 43 8 40 35 A-wgtd 73 65 Connection End Lp Sound Pressure (da) Octave Distance Band 5 ft. 50 ft. 1 78 72 2 77 68 3 74 67 4 71 62 5 70 60 6 60 49 7 54 43 89 8 36 A-wgtd 74 64 Sound Power dB Sound Pressure (da) Octave Center Frequency Band Band (Hertz) Lw 1 63 100 2 125 101 3 250 100 4 500 98 5 1000 95 6 2009 89 7 4000 86 8 8000 85 A-wgtd 100 Note: The use of frequency inverters (variable frequency drives) can increase sound levels. Extra Notes: Sound data provided by CTI ATC -128 sound test code revision 2019 Page 313 Top Lp Sound Pressure (da) Octave Distance Band 5 ft. 50 ft. 1 79 65 2 84 69 3 83 68 4 82 66 5 79 63 6 72 57 7 67 55 8 62 53 A -w gtd 83 68 End Lp Sound Pressure (d S) Octave Distance Band 5 ft. 50 ft. 1 78 70 2 79 68 3 76 67 4 70 62 5 64 57 6 54 48 7 49 42 8 44 35 A -td wg 72 64 Air Inlet Lp Sound Pressure (dB) Octave Distance Band 5 ft 50 ft. 1 77 73 2 79 68 3 78 66 4 75 63 5 71 57 6 64 51 7 61 48 8 56 41 A-wgtd 77 64 m �I� X �+ �Ra�~El o nn' QCR c.y ?B �.�q4 N O I. 6'-4 gS CD 40 f 1 non �n e: 11 a 3 W O CD O I..a u' � a, O S �.'4 a ��g g CDp ' *a O �6,' '� = V.w w g O mow^ 5T s (D ro c 0 j? Rrs � �3&�'� 92 m ° o fib' V Sv 7'-4 1/4' 3'-6 1/2' w n g C Q 6 � � w R N W .• y a o� e� O- D r n �� � 0m �� N e 3 Q CD 'o a 8 a �T z 4 c I s � 0 m 3 Y? C a N a Go —L > Co z x N r ro c N m O z w O O ._�. 00 chi � o � uo' �I� m � o Z �b wv»�Nso N�oo,v �tasw 3`4�o �$3wwnQ �o c? ry>•w� o-Q,Q vs�...o .'o. ww Z\n.w.. yc O W L7N N N w �_ �3 ��a m�ai��.o..�-�`'`c Q'wy C nR no 6 P�SJ ^O'g`J N� P9�T�• t p N 5'E N IV m$'w non 4,co'mny QN3w `° w$a.cw.�a 35 o $ 2 a 6 , w e w O y. B OT K o N w ' W _ n �.v = 3 o A D {' St O _ O Amo 03 w_ n„ e4� c o m FACE B ELEVATION B'-5 3/4 8'-3 1/2' Y YIN AML. A F2MIN FACE A )p all IF -a r II 9 Q r,o Om 1 0 y II I T.a z n II II D 9 << Iw n a m u D m m � i II II COD = CO2 o A FACE B N n =z "Z R N m 7 O A ca c C i 9 O FACE B ELEVATION s e Z Ory N 00nn W " O \V •ii O i Ca 40 S O N Wco CD Z � 0 A Co -0 EF Of pO• G 3W 3 (n = 8 C N CD O CD N N n � ol 0 N Cn -a � CD O CD D • b O m— F O m C 3 s n CQ n o O I�il 3 a aco En f � N 0 z cm W 0 N C 0 -L r3 m a G A es c O R y � o m V! 00 :�Ed <m m N. o o� �o �o 0 0 m � z Cif o N C'" ro CD imm G/ O .9m CDN 4h Q I® 3 om X 0 O z --- o I I I I I I � I I I o zo l I < <p' I I C) z(i I I I mc)q-iF--i cn m I l I I I I T L_ J o I I I I I I I I I I I I pm A I I I m S N I T I I I c z L-1---I-J I I I I I I I I I I I I � 0 I I p IA I cnW < m C-) I v = I I I I I I m A I I I I I I I I I I m m r "O m ox*� -i m m M x om a m m _ \ §»/KA ;m � CAD � ho � ¥ x sA Q - mM % § §E RK > ! $ \ \ > co 0 . . . . . ■ POW r 0-1 Q § a./ � �(§OR(/§ (•IRSƒ# 4 j\ . - �\/(/({ je§2 . _;�■ «y1°*® \ c§§ cm 7 (mklr§ z COL ` I+r� � 222§ 2 $ �� �� 79)))§ k)§§ , $§Amm« f9 f2 CA■ §Sf �!\ � F9;§ ! ■ $§§j §� \; (\ RNA mox F„"d,� z3o O yR atiys_i y�ol: amfo� Sm m 0 O z o ti y- o 03 -I = ASS o_ po N$ W A n �� mCz a 9 AtZ; `x Zz m 3 yo.5 z zo> yoz i 3 S -o oo5oz S Cil omc �m g �m am aoo3 3 z ny y � Hy a boy -ng z= S r g myw- AD.--Ni'o-z a z$ O �m zea- �m zn� OF CD "� 'ya zo 9zo yv,ai9 El T $o any �`ao Ay m fq'f j j G y 3 c 3 z 90 F m t -a �" g F o 3 fA CD O o$� n e N N oz ti `o'''a9c'Ey 3'y',"-',.iai ti -= n ii agm� s'o" az$ mS C2 N 9�w N y�ZSM IEq yo :k ~8 n o= =zy", boa mma �y C2 p aom�moA o"n`zza m.1- z y �mli z " oz Cl p ��a n m - �, `�` H mm C'� - ��� a?r. cy�`� ,0 p E; 6 m �o��mzoc m ayai ^' -F � nFim ap om a 8 g S �4 F9 G y0 3ymO fn o4][S'a - -m0 HI o=m m r S �3n� iin= ow oSy cT Z vac i c c- cin zy m m O v- y o Fym Hz� a i yo S mn z9z y 3L z m \<mc F-- <y'm° oca E�qm m c y .`5y ayc o o H ma DS 'yo -�c�i aA $ v oi'a izK n N �y o 90 �m� MaI ono m m �o-za zm Sr"m ^a'�m 3�` =90 xy o mo x- �xzv = mz S m MV oo So mm ooa on �m _ -m m;3z o * 3op ?gym 3 «N n c a9 oo pn a ra omA r y ti m zK zaoo z ' :• �s C -mei �"-i .S-, �"' is coy Jaz y a 9m C n o0 39 cZs p �= rm C�ZZI yi _ y Z3 M A y C C 2 m y 3 3 A Z a A O A O C 3 M Hmz y 9 a Zy snc_n 3 m Z 3 A 0 m O D A 0 m o Aim. p 0 2 =M M OO N A O R - O O m3 yZz mCT Z= 3K AA 0 CJ A n X C p= -ai p V V ` 0 0 p (A Z a a Z 2 Z -m-I m m Z_ c m z m m o m 1 y a m v {�Y H� mA o� > z c O 0 Z G] mcm Z L7 coL+i S y A wiC S W zz GD A 74 i x C m y y O Nm a �y pA N y a n cm O oo z i lii fC o 3 m a 2 z m N o M GZi m > m y m m z O � z m co m 'a � ^—i �+a! .7 W Q ii rQ'3E � N 4 n 9 $ f`il �aRm mcm 40 N i O m 5o S G1 O o N N �+ w � 10 C O g D' y O �' > o � CD 0' 9C C C m zs Cro _ as � oCD"' 0mCLCD 3m mo a z a co o Ln N D � 0 Z N CD N z w IC N m O z W O eai a A co e gN E S. G '< < < m � y o = � o o o