Series RFII — 5.6 K -factor
"Royal Flush Il" Concealed Pendent Sprinklers
Quick & Standard Response, Standard Coverage
General
Description
The TYCO Series RFII 5.6 K -factor,
"Royal Flush II" Concealed Pendent
Sprinklers Quick Response (3 -mm
bulb) and Standard Response (5 -mm
bulb), are decorative sprinklers fea-
turing a flat cover plate designed to
conceal the sprinkler. These sprinklers
are optimal for architecturally sensi-
tive areas such as hotel lobbies, office
buildings, churches, and restaurants.
Each sprinkler includes a Cover Plate/
Retainer Assembly and a Sprinkler/
Support Cup Assembly. The separa-
ble, two-piece assembly design pro-
vides the following benefits:
• Allows installation of the sprinklers
and pressure testing of the fire pro-
tection system prior to Installation of
a suspended ceiling or application of
the finish coating to a fixed ceiling.
• Permits the removal of suspended
ceiling panels for access to building
service equipment without having
to first shut down the fire protection
system and remove sprinklers.
• Provides for 1/2 in. (12,7 mm) of ver-
tical adjustment to allow a measure
of flexibility in determining the length
of fixed piping to cut for the sprinkler
drops.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the 'INSTALLER
WARNING' that provides cautions
with respect to handling and instal-
lation of spnnklersystems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page i of 4
The Series RFII Sprinklers are shipped
with a Disposable Protective Cap. The
Protective Cap is temporarily removed
during installation and replaced to help
protect the sprinkler during ceiling
installation or finish. The tip of the Pro-
tective Cap can be used to mark the
center of the ceiling hole into plaster
board or ceiling tiles by gently pushing
the ceiling product against the Pro-
tective Cap. When ceiling installa-
tion is complete, the Protective Cap is
removed and the Cover Plate/Retainer
Assembly is Installed.
As an option, the Series RFII Standard
Response (5 -mm bulb) "Royal Flush II"
Concealed Pendent Sprinklers can be
fitted with a silicone Air and Dust Seal.
See Figure 5. The Air and Dust Seal
is intended for sensitive areas where
it is desirable to prevent air and dust
from the area above the ceiling to pass
through the cover plate.
IMM
The Series RFII Concealed Pendent
Sprinklers described herein must be
installed and maintained in compliance
with this document and with the appli-
cable standards of the NATIONAL FIRE
PROTECTION ASSOCIATION (NFPA),
in addition to the standards of any
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
The owneris responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturershould be contacted with
any questions.
Sprinkler
Identification
Number (SIN)
TY3531 — 3 mm bulb
TY3551 — 5 mm bulb
AUGUST 2020
Technical
Data
Sprinkler Approvals
Approvals apply only to the service
conditions indicated in the Design Criteria
section.
• TY3531 (3 mm Bulb) is UL Listed,
C -UL Listed and NYC Approved
(MEA 353-01-E) as Quick Response.
• TY3531 (3 mm Bulb) Is VdS Approved
(Certificate No. G4090007).
• TY3531 (3 mm Bulb) is FM and
LPCB Approved (Ref. No. 094a/10) as
Standard Response.
Note: FM and LPCB do not approve
concealed sprinklers for quick
response.
• TY3551 (5 mm Bulb) is UL Listed, C -UL
Listed, FM Approved, LPCB Approved
(Ref. No. 094a/9), and NYC Approved
(MEA 353-01-E) as Standard Response.
Approvals for Air and Dust Seal
UL and C -UL Listed for use with the RFII
Standard Response Concealed Sprinkler
(TY3551)
Maximum Working Pressure
Maximum 250 psi (17,3 bar) by UL,
C -UL, and NYC
Maximum 175 psi (12,1 bar) by FM, VdS,
and LPCB
Temperature Rating
155"F (680C) Sprinkler with
139"F (59"C) Cover Plate
200°F (93"C) Sprinkler with
1650F (74°C) Cover Plate
TFP181
TFP181
Page 2 of 4
Discharge Coefficient
K= 5.6 GPM/psi1/2 (80,6 LPM/bart/2)
Adjustment
1/2 in. (12,7 mm)
Finishes
See the Ordering Procedure section.
Physical Characteristics
Frame ............................Bronze
Support Cup ......
.............Plated Steel
Guide Pins ..................
Stainless Steel
Deflector..........................Bronze
Compression Screw
.................. Brass
Bulb. . ... . .
................. Glass
Cap ......... ...........
Bronze or Copper
Sealing Assembly, .
Beryllium Nickel w/TEFLON
Cover Plate .........................Brass
BULB
Retainer. . - .
- ............. Brass
Ejection Spring ..............
Stainless Steel
Design
Criteria
The TYCO Series RFII 5.6 K -factor,
"Royal Flush II" Concealed Pendent
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable Listing
or Approval agency; for example, UL
Listing is based on NFPA 13 and VdS
Approval is based on the CEA 4001.
For more Information on LPCB and VdS
Approvals, contact Johnson Controls
at the following office:
Enschede, Netherlands
Telephone: 31-53-428-4444
Fax: 31-53-428-3377
The Series RFII Concealed Pendent
Sprinklers are only listed and approved
with the Series RFII Concealed Cover
Plates having a factory applied finish.
Do not use the Series RFII in applica-
tions where the air pressure above the
ceiling is greater than that below. Down
drafts through the Sprinkler/Support
Cup Assembly can delay sprinkler
operation in a fire situation.
Operation
When exposed to heat from a fire, the
Cover Plate, normally soldered to the
Retainer at three points, falls away to
expose the Sprinkler/Support Cup
Assembly.
The Deflector — supported by the
Guide Pins — then drops down to its
operational position.
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, activating the sprinkler and
allowing water to flow.
1/2" NPT
SEALING
ASSEMBLY
FRAME
�\
CAP
SUPPORT
CUP WITH
II
BULB
ROLL FORMED
THREADS
TT I
COMPRESSION
SCREW
GUIDE
----""'�
PINS (2)
I
DEFLECTOR
DEFLECTORi
Imo---
POSIITION)
------ _
SPRINKLER/SUPPORT CUP
ASSEMBLY
THREADINTO
I
RETAINER
SUPPORT
O
WITH THREAD
CUP UNTIL
O
DIMPLES
MOUNTING
SURFACE IS
EJECTION
FLUSH WITH
SPRING
CEILING
/
SOLDER f
TABS (3)
COVER PLATE/RETAINER
COVER
PLATE
ASSEMBLY
FIGURE t
MODEL RFII CONCEALED SPRINKLER
ASSEMBLY
Installation
The TYCO Series RFII 5.6 K -factor,
"Royal Flush II" Concealed Pendent
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb -type sprin-
kler if the bulb is cracked or there is
a loss of liquid from the bulb. With the
sprinkler held horizontally, a small air
bubble should be present. The diam-
eter of the air bubble is approximately
1/16 in. (1,6 mm) for the 155°F (68°C)
and 3/32 in. (2,4 mm) for the 200°F
(93°C) temperature ratings.
A leak -tight 1/2 in. NPT sprinkler joint
should be obtained by applying a
minimum to maximum torque of 7 to
14 Ib -ft (9,5 to 19,0 N -m). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment In the Sprinkler
by under- or over -tightening the Sprin-
kler/Support Cup Assembly. Re -adjust
the position of the sprinkler fitting to
suit.
Step 1. Install the sprinkler only in the
pendent position with the center -line
of the sprinkler perpendicular to the
mounting surface.
Step 2. Remove the Protective Cap.
Step 3. With pipe thread sealant
applied to the pipe threads, hand -
tighten the sprinkler into the sprinkler
fitting.
Step 4. Wrench -tighten the sprinkler
using only the RFII Sprinkler Wrench.
See Figure 3. Apply the RFII Sprinkler
Wrench to the Sprinkler. as shown in
Figure 3.
FACE OF CLEARANCE HOLE
SPRINKLER DIAMETER
FITTING DIMENSION C
SPRINKLER
SUPPORTCUP
ASSEMBLY
1/2" (12,7 mm)
THREADED
D ADJUSTMENT
FACE
OF CEILING,
RETAINING RING
MOUNTING
SURFACE —
L JL
3/16" to 11/16" MANUFACTURER DEFLECTOR COVER PLATE
(4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER
REFERENCE 3/32" (2,4 mm) POSITION ASSEMBLY
COVER PLATE COVER PLATE
PROFILE DEPTH DIAMETER
DIMENSION B DIMENSION A
A: 3-1/4 In. (82,6 mm) C:2-3/8 to 2-5/8 in. (60,3 to 66,7 mm)
B: 3/16 In. (4,8 mm) D: 1-3/4 to 2-1/4 in. (44,5 to 57,2 mm)
FIGURE 2
SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS
TFP181
Page 3 of 4
Step S. Replace the Protective Cap by
pushing it upwards until it bottoms out
against the Support Cup. See Figure
4. The Protective Cap helps prevent
damage to the Deflector and Arms
during ceiling installation and/or finish.
You can also use the Protective Cap to
locate the center of the clearance hole
by gently pushing the ceiling material
up against the center point of the Pro-
tective Cap.
As long as the Protective Cap remains
in place, the system is considered "Out
of Service".
Step 6. After the ceiling has been
completed with the 2-1/2 in. (63,5 mm)
diameter clearance hole and in prep-
aration for installing the Cover Plate/
Retainer Assembly, remove and discard
the Protective Cap. Verify that the
Deflector moves up and down freely.
If the Sprinkler is damaged and the
Deflector does not move up and down
freely, replace the entire Sprinkler.
Do not attempt to modify or repair a
damaged sprinkler.
Step 7. When installing an Air and Dust
Seal, see Figure 5; otherwise, proceed
to Step 8. To attach the Air and Dust
Seal, verify the angle of the outside
edge of the seal is oriented accord-
ing to Figure 5. Start the edge of the
Retainer in the grooved slot of the Air
and Dust Seal and continue around the
retainer until the entire Air and Dust
Seal is engaged.
Step 8. Screw on the Cover Plate/
Retainer Assembly until the Retainer,
shown in Figure 2, or the Air and Dust
Seal, shown in Figure 5, contacts the
ceiling. Do not continue to screw on the
Cover Plate/Retainer Assembly so that
it lifts a ceiling panel out of its normal
position. If you cannot engage the
Cover Plate/Retainer Assembly with
the Support Cup or you cannot engage
the Cover Plate/Retainer Assembly suf-
ficiently to contact the ceiling, you must
reposition the Sprinkler Fitting.
TFP181
Page 4 of 4
SUPPORT SPRINKLER FACE OF ORIENT
CUP — / CEILING SEAL
BEVEL AS
COVER '; SHOWN
PLATE '
RETAINER
ASSEMBLY
/AIR
AND DUST
LIP OF COVER SEAL
RETAINER PLATE
FIGURE 5
OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551)
Care and
Maintenance
The TYCO Series RFII 5.6 K -factor,
"Royal Flush II" Concealed Pendent
Sprinklers must be maintained and
serviced in accordance with this
section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the Cover Plate/Retainer
Assembly can delay sprinkler opera-
tion in a fire situation.
When properly installed, there is a
nominal 3/32 in. (2,4 mm) air gap
between the lip of the Cover Plate and
the ceiling, as shown in Figure 2.
This air gap is necessary for proper
operation of the sprinkler. If the ceiling
requires repainting after sprinkler
installation, ensure that the new paint
does not seal off any of the air gap.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers - before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. See the Installation
Section.
Exercise care to avoid damage to sprin-
klers before, during, and after instal-
lation. Replace sprinklers damaged
by dropping, striking, wrench twist-
ing, wrench slipping, or the like. Also,
replace any sprinkler that has a cracked
bulb or that has lost liquid from Its bulb.
See the Installation section.
If you must remove a sprinkler, do not
reinstall it or a replacement without
reinstalling the Cover Plate/Retainer
Assembly. If a Cover Plate/Retainer
Assembly becomes dislodged during
service, replace It immediately.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION such as NFPA 25, in
addition to the standards of any other
authorities having jurisdiction. Contact
the installing contractor or sprinkler
manufacturer regarding any questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualified Inspection Service in accor-
dance with local requirements and/or
national code.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name.
Sprinkler/Support Cup Assembly
Specify: Series RFII (specify SIN),
K=5.6, "Royal Flush II" Pendent Sprin-
klers (specify) temperature rating, P/N`
(specify):
155T WO'CI 20TF 193.0)
TY3531 51-792-1-155 51-792-1-200
TY3551 51-790-1-155 51-790-1-200
Use suffix "I" for ISO 7-1 connection; for example,
51-792-1-155-1
Separately Ordered Cover Plate/
Retainer Assembly:
Specify: (temperature rating from
below) Series RFII Concealed Cover
Plate with (finish), P/N (specify).
139-F (69°C)(a) 166-F (74°10)(b)
Grey White
(RAL9002).... 56-792-0-135 56-792-0-166
Brushed Brass.. 56-792-1-135 56-792-1-165
Brass.....,.... 56-792-2-135 56-792-2-165
Pure White (c)
(RAL9010).... 56-792-3-135 56-792-3-165
Signal White
(RAL9003).... 56-7924-135 56-792-4-165
Jet Black
(RAL9005).... 56-792-6-135 56-792-6-165
Brushed
Chrome........ 56-792-8-135 56-792-8-165
Chrome........ 56-792-9-135 56-792-9-165
Custom ........ 56-792-X-135 56-792-X-165
(a) For use with 155°F (68aC) sprinklers.
(b). For use with 200aF (93aC) sprinklers.
(c) Eastern Hemisphere sales only,
Sprinkler Wrench
Specify: RFII Sprinkler Wrench,
P/N 56-000-1-075
Air and Dust Seal
Specify: Air and Dust Seal,
P/N 56-908-1-001
1400 Pennbrook Parkway, Lansdale, PA 194461 Telephone +1-215-362-0700 {.
09=JeMuen eon Vola. All rabb...mad. latormwe
atlonall. re ca—M At at CPounmotr".an data and am subleot to AMnpawHbeN notice. Johnson ��♦♦/'
a...LL PP.t r.. ASSe .... and LAIPA en IpYYwdtrWam. of elbA., I..m ..,.a.:
Controls
IEFlMiI..,e96Mdved.mMa, ouPom s
Firel-ock® V27, K5.6 x.4065 licr
Models V2703, V2707, V2704, V2708 40.10
Y
V2703/V2704 V2707/V2708 V2707/V2708 V2707/V2708 V2703/V2704
Upright Pendent Recessed Pendent Pendent w/V9 Upright w/V9
1.0 PRODUCT DESCRIPTION
Models: V2703, V2704, V27O7, V27O8
Style: Pendent, Upright or Recessed Pendent
Nominal Orifice Size: 1/2713 mm
K Factor: 5.6 Imp./8.1 S.1.1
Nominal Connection Size: 1/2" NPT/20 mm BSPT/IGS Grooved
Max. Working Pressure:
• 175 psi/1200 kPa (FM)
• 250 psi/1725 kPa (UL)
Factory Hydrostatic Test: 100% @ 500 psi/3450 kPa
Min. Operating Pressure:
• 7 psi/48 kPa
• 0.35 bar/5 psi (VdS for upright only)
Temperature Rating: See chart
I For K -Factor when pressure is measured In Bar, multiply S.I. units by 10.0.
2.0 CERTIFICATION/LISTINGS
oQu FM> FL—PCB] ® vdsUMB 0786
E
Threaded and IGS connections have different approvals/listings. See tables on pages 2 and 3.
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.
System NoT. Spec Section Paragraph
El
Submitted By Date Approved Date
Victaulic.com
40.10 2544 Rev L Updated 04/2020 02020 Victaulic Company. All rights reserved. �CtBIJliC
1
victaulic.cam
2.0 CERTIFICATIOWLISTINGS (CONTINUED)
Threaded Sprinkler Approvals/Listings:
APPROVALS/LISTINGS
Model
V2703 V2707 V2707 V2704
V2708
V27082
Orifice Size (Inches)
'/2" 1/2" Vi' 1/2'
1/2"
42"
Orifice Size (mm)
13 13 13 13
13
13
Nominal K Factor Imperial
5.6 5.6 5.6 5.6
5.6
_
5.6
Nominal K Factor 5.1.2
8.1 8.1 8.1 8.1
8.1
8.1
Response
Standard Standard Standard Quick
Quick
Quick
Deflector Type
Upright Pendent Recessed Upright
Pendent
Recessed
Pendent
Pendent
Approved Temperature Ratings
F°/C°
135°F/57°C
135°F/57°C
155°F/68°C
155°F/68°C
135°F/57°C
135°F/57°C
135°F/57°C
175°F/79°C
175°F/79°C
155°F/68°C
155°F/68°C
155°F/68°C
135°F/57°C
cULus
200°F/93°C
200°F/93°C
175°F/79°C
1757/79°C
175°H79°C
155°F/68°C
286°F/141°C
286°F/141°C
200°F/93°C
200°F/93°C
200°F/93°C
175°F/79°C
360°F/182°C
360°F/182°C
286°F/141°C
286°F/141°C
286°F/141°C
200°F/93°C
500°F/260°C
500°F/260°C
135°F/57°C
135°F/57°C
155°F/68°C
155°F/68°C
135°F/57°C
135°F/57°C
135°F/57°C
135°F/57°C
FM
175°F/79°C
175°F/79°C
155°F/68°C
155°F/68°C
155°F/68°C
155°F/68°C
200°F/93°C
200°F/93°C
175°F/79°C
175°F/79°C
175°F/79°C
175°F/79°C
286°F/141°C
286°F/141°C
200°F/93°C
200°F/93°C
200°F/93°C
200°F/93°C
360°F/182°C
360°F/182°C
286°F/141°C
286°F/141°C
135°F/57°C
135°F/57°C
135°F/57°C
135°F/57°C
135°F/57°C
155°F/68°C
155°F/68°C
155°F/68°C
155°F/68°C
155°F/68°C
1357/57°C
NYC/MEA 62-99-E
175°F/79°C
175°F/79°C
175°F/79°C
175°F/79°C
175°F/79°C
155°F/68°C
200°F/93°C
200°F/93°C
200°F/93°C
200°F/93°C
200°F/93°C
175°F/79°C
286°F/141°C
286°F/141°C
286°F/141°C
286°F/141°C.
286°F/141°C
°
200°F/93C
360°F/182°C
360°F/182°C
135°F/57°C
135°F/57°C
135°F/57°C
135°F/57°C
135°F/57°C
155°F/68°C
155°F/68°C
155°F/68°C
155°F/68°C
155°F/68°C
135°F/57°C
CSFM 7690-0531:112
175°F/79°C
175°F/79°C
175°F/79°C
175°F/79°C
175°F/79°C
155°F/68°C
200°F/93°C
200°F/93°C
200°F/93°C
200°F/93°C
200°F/93°C
175°F/79°C
286°F/141°C
286°F/141°C
286°F/141°C
286°F/141°C
286°F/141°C
200°F/93°C
3607/182°C
360°F/182°C
135°F/57°C
155°F/68°C
135°F/57°C
LPCB
175°F/79°C
None
None
155°F/68°C
None
None
200°F/93°C
175°F/79°C
286°F/141°C
200°F/93°C
360°F/182°C
ZSTZ
ZSTX
K-ZSTZ
K-ZSTZ
CCC
155°F/68°C
155°F/68°C
None
155°F/68°C
155°F/68°C
None
200°F/93°C
200°F/93°C
200°F/93°C
200°F/93°C
135°F/57°C
135°F/57°C
155°F/68°C
155°F/68°C
Vd5
175°F/79°C
None
None
175°F/79°C
None
None
200°F/
C°C
200°F/93°C
286°F/14411
°
286F/141°C
360°F/182°C
135°F/57°C
155°F/68°C
135°F/57°C
175°F/79°C
155°17/68°C
CE
200°F/93°C
None
None
175°F/79°C
None
None
286°F/141°C
200°F/93°C
360°F/182°C
286°F/141°C
2 For K Factor when pressure is measured in Bar, multiply S.I. units by 10.0
2 FM Approved with 1Y adjustment escutcheon only - quick response
NOTE
.Listings and Approvals as of printing. All are approved open.
40.10 2544 Rev L Updated 04/2020 0 2020 Victaulic Company. All rights reserved.
victaulic.com
Jctaulic
victaulic.com
2.0 CERTIFICATION/LISTINGS (CONTINUED)
IGS Sprinkler Approvals/Listings
t For K -Factor when pressure Is measured In bar, mul8piy S.I. units by 10.0
NOTE
• Listings and Approvals as of printing. All are approved open.
40.10 2544 Rev L Updated 04/2020 ® 2020 Vlctaulic Company. All rights reserved.
victaulic.com
Model
APPROVALS/LISTINGS
V2703
V2707
V2704
V2708
Orifice Size (inches)
Vz'
'/i'
ile
Yx"
Orifice Size (mm)
_
13
13
13
_
13
Nominal K -Factor Imperial
5.6
5.6
5.6
5.6
Nominal K -Factor 5.1.'
8.1
8.1
8.1
8.1
Response
Standard
Standard
Quick
Quick
Deflector Type
Upright
Pendent
Upright
Pendent
Adjustment
Approved Temperature Ratings
F'/C'
135'F/57°C
135°F/57'C
155'F/68'C
155°F/68°C
135°F/57°C
135'F/57°C
175'F/79'C
175°F/79°C
155°F/68°C
155°F/68°C
cULus
200'F/93'C
200°F/93'C
175°F/79°C
175°F/79°C
286'F/141'C
286°F/141°C
200°F/93°C
200°F/93°C
360°F/182'C
360'F/182°C
286'F/141°C
286°F/141'C
500°F/260'C
500°F/260'C
135°F/57'C
135'F/57°C
135°F/57'C
135°F/57°C
155'F/68'C
155'F/68'C
155°F/68'C
155'F/68°C
FM
175°F/79°C
175°F/79°C
175°F/79°C
175°F/79°C
200°F/93°C
200°F/93°C
200°F/93°C
200°F/93'C
286'F/141'C
286°F/141°C
286°F/141°C
286°F/141'C
360'F/182'C
360°F/182°C
t For K -Factor when pressure Is measured In bar, mul8piy S.I. units by 10.0
NOTE
• Listings and Approvals as of printing. All are approved open.
40.10 2544 Rev L Updated 04/2020 ® 2020 Vlctaulic Company. All rights reserved.
victaulic.com
victaulic.com
3.0 SPECIFICATIONS — MATERIAL
Upright Deflector: Bronze
Pendent Deflector: Bronze
Bulb: Glass with glycerin solution
Bulb Nominal Diameter:
❑ Standard: 5.0 mm
❑ Quick Response: 3.0 mm
Load Screw: Bronze
Pip Cap: Bronze
Spring: Beryllium nickel
Seal: PTFE tape
Frame: Die cast brass
Lodgement Spring: Stainless steel
Installation Wrench:
❑ Open End: V27
❑ Recessed: V27-2
❑ 3/,e Hex Bit: V9 coupling
Sprinkler Finishes:
❑ Plain Brass4
❑ Chrome plated
❑ White polyester coated5
❑ Black painted5
❑ Custom painted5
❑ VC -2506
4 Plain Brass is only available for the V9 coupling.
a UL Listed for corrosion resistance.
6 UL Listed and FM Approved for corrosion resistance.
Exaggerated for clarity
40.10 2544 Rev L Updated 04/2020 ® 2020 Victaulic Company. All rights reserved.
victaulic.com
4
�ctaulllcr
victaulic.com
4.0 DIMENSIONS
6r
PAY 41
60 mm
111'4 i
37 mm
25 mm f J
Standard Pendent with/Without standard V9 coupling— V2707, V2708 Standard Upright with/without standard V9 coupling — V2703, V2704
NOTE:
• V27, K5.6 sprinklers with Style V9 coupling dimensions are the same
as threaded sprinkler dimensions.
n
24
MAXIMUM EMENSION
Ya' Adjustment Recessed - V2707, V2708 (drawing not to scale)
Nee
24mm
75mm
MAXIMUM 1 X 14510N
4'4' Adjustment Recessed—V2707, V2708 (drawing not to scale)
Standard Pendent with V9 Sprinkler Coupling—V2707, V2708 Standard Upright with V9 Sprinkler Coupling— V2703, V2704
NOTE:
• IGS options are not available for recessed applications.
40.10 2544 Rev L Updated 04/2020 0 2020 Victaulic Company. All rights reserved.
victaulic.com 5 ✓ctaulid
victaulic.com
5.0
Sprinkler is to be installed and designed as per NFPA, FM Datasheets, or any local standards.
6.0 NOTIFICATIONS
• Always read and understand Installation, care, and maintenance instructions, supplied with each box of
sprinklers, before proceeding with installation of any sprinklers.
• Always wear safety glasses and foot protection.
• Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping
products.
• Installation rules, especially those governing obstruction, must be strictly followed.
• Painting, plating, or any re -coating of sprinklers (other than that supplied by Victaulic) is not allowed.
Failure to follow these instructions could result in serious personal injury and/or property damage.
The owner is responsible for maintaining the fire protection system and devices in proper operating condition.
For minimum maintenance and inspection requirements, refer to the current National Fire Protection Association
pamphlet that describes care and maintenance of sprinkler systems. In addition, the authority having jurisdiction
may have additional maintenance, testing, and inspection requirements that must be followed.
If you need additional copies of this publication, or if you have any questions about the safe installation of this
_ product, contact Victaulic World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031 USA, Telephone:
_ 001.610-559-3300.
40.10 2544 Rev L Updated 04/2020 ® 2020 Victaulic Company. All rights reserved.
victaulic.com 6 XAotauhcr
victaulic.com
7.0 REFERENCE MATERIALS
Ratings
All glass bulbs are rated for temperatures from—650F/-540C to those shown in table below.
Sprinkler victaulic
Temperature Part
__Classification Identification
Temperature -°FPC
Glass
Bulb
Color
Nominal
Temperature
Rating
Maximum
Ambient
Temperature
Allowed
Ordinary A
135°F/570C
10fPF/38°C
Orange,
-Ordinary C
155°F/68°C
100°F/38°C
Red
Intermediate E
175°F/79°C
150°17/69C
Yellow
Intermediate F
200°F/93°C
150°F/65°C
Green
Nigh 1
286°F/141°C
225°Fa/107°C
Blue.
Extra HIgh7 K
360°F/182°C
300°F/149°C
Purple
- M
Open
No bulb
Ultra HIgh7 N
500°F/260°C
475°F/246°C
Black
7 Standard response only.
Available Wrenches:
Sprinkler Type
V27-2
Recessed
V27
Open End
Hex -Bit
V2707,V2708 Pendent
✓
✓
-
V2707, V2708 Recessed Pendent
✓
-
-
V2703, V2704 Upright
-
✓
-
V2703, V2704 Upright w/V9
-
-
✓
V2707, V2708 Pendent w/V9
✓
NOTE
e aha -Inch hex bit provided with V9 coupling shipment.
29.01: Victaulic Terms and Conditions of Sale
1-40: Victaulic FireLockl- Automatic Sprinklers
V9 Style V9 victaul c Fire Lock' IGS I nstrallation-Readyna Sprinkler Coupine Installation Instructions
User Responsibility for Product Selection and Suitability
Each user bears final responsibility for making a determination as to the suitability of
Vletaulle products for a particular and -use application, In accordance with Industry
standards and protect specifications, and the applicable building codes and related
regulators as well as Vleteulle performance, maintenance, safety, and warning
Instructions. Nothing In this or any other document, nor any verbal recommendation,
advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede,
or waive any provision of Vlctaullc Company's standard conditions of sale, Installation
gulde, or this disclaimer.
Intellectual Properly Rights
No statement contained herein concerning a possible or suggested use of any material,
product, service, or design is Intended, or should be constructed, to gram any license
under any patent or other Intellectual property right of Victaulic or any of Its subsidiaries
or affiliates covering such use or design, or as a recommendation for the use of such
mstarle, product, service, or design In the Infringement of any patent or other Intellectual
property right. The terms "Patented" or "Patent Pending" refer to design or utility parents
or parent applications for articles and/or methods of use In the United States and/or other
countries.
Note
This product shall be manufactured by Victaulic or to Victaulic specifications. All products
to be installed In accordance with current Victaulic installation/assembly Instructions.
volatile reserves the right to change product specifications, designs and standard
equipment without notice and without incurring obligations.
Installation
Reference should always be made to the Viclaulic installation handbook or Installation
Instructions of product you are Installing. Handbooks are included with each shipment
of Victaulic products, providing complete installation and assembly data, and are available
in PDF format an our website at www.victaulipcom.
Warranty
Refer to the Warranty section of the current Price List or contact Victaulic for details.
hademarks
Wafaulic and all other Victaulic marks are the trademarks or registered trademarks of
Victaulic Company, and/or Its affiliated entitles, In the U.S. and/or other countries.
40.10 2544 Rev L Updated 04/2020 0 2020 Victaulic Company. All rights reserved.
victaulic.com 7 ✓ctaulia
Hydraulic Calculations by HydraCALC
A&D FIRE SPRINKLERS INC
1601 W ORANGEWOOD AVE
C16 1069002
ORANGE,CA,92868
714-634-3923
Job Name LAD1699 - HRC CLINIC—recover
Drawing
Location
Remote Area
Contract
Data File LAD1699 - HRC CLINIC recover Area 1.WXF
Computer Programs by Hydratec Inc. Revision: 50.54.2
M
X
c
0
m
m
A
v
N
W
A
N
M
V
W
M—+
'
—+
n
O
O
O
O
O
O
O
O
O
O
O
_
N
O O
W
O
A
O
0Iz
O
CC
000
n W
�
CD cn
W N C
CD
o
aaci�
n0y
0 Cn
CM
O
N fD
C
N
01 (n
dV M V
~Olin
O
O
N
Ol
O
T
r
O
w
O
z
>o
6
0
w
0
A
O
O
3
cnvxvvv�
O N N!
NW N i a
i<nr° m co m
Kfi Oyu mu
No
3y330
om'uTm
ma@o
3�1
C c
CLpj �
�W OOA ODA
:-.
W o A o A
C A
p Cc o MZ
-V-1� O
C
-immco
>
_a o
o Nc m
O
� iso 3
�c
2.
N
2
2�
y 3 'ON
a
C�fD
C
r
N
W
0
Jx C: CD
C
@ '� D U3
C:Fn C:3
vvvv
3 m
3a J r
y
m
DDaa
0< 0) co
O
W W W W
J-d-Ci.J N
y 0
0 W 00
OF OC
CD .0+CD 7'a
�W c d0'o
om 5'i3
g M 0 <
���mCD
2xaw
C, -M .» CD W
J WW
i MM
N
0 U3 W a Ol cCL
m
E
ao y <
01 W ._'2, a. N
33vO J
Wo "o
N d N O '"` •-•
O�
0CnCD J
(/J
CD x O. W .O
G fOD S
~N
f0/ [] [WY N
a0
y N
:E�
AONO
w
S W
i W
CD a CL
»3 Er3
c W
NNNO
J CD07 W O
w
fnQ fD »O
N J
n N
c
W V W O
e
0 W W J' O J
'Cc
06
CL a J O
:E C)
J'
r,�a
O W nW =`:
WtOAO
mnM my
wCCLCD
O
400
J N
CD8
-00
N
9 N
D SU
W a
C N I a
<
O <.n3
J N 0 3
V
w
C !016N
W O
fD 0 @
W O
W
0
V W
u
O N O N
A
fNI�V NW
N
O N A O
0
MOM"
0
O M NN —
O
OfOTrN
N
O O
A
W A O
� N
W
O O
O
00
N -+
N
A
Flow Summary - NFPA
A&D FIRE SPRINKLERS INC Page 3
LAD1699 - HRC CLINIC recover Date
SUPPLYANALYSIS
Node at Static Residual Available
Source Pressure Pressure Flow Pressure Total Demand Required Pressure
BOR 57.5 56.5
Node Tag Elevation Node Type
187.0 55.375 281.06 34.744
NODE ANALYSIS
Pressure Discharge
at Node at Node Notes
1
9.5
5.6
16.14
22.5
2
12.0
20.97
3
12.0
21.16
4
12.0
21.33
5
12.0
22.26
6
12.0
22.4
7
12.0
22.49
8
12.0
22.54
9
12.0
22.57
10
12.0
22.59
11
12.0
22.61
12
12.0
22.61
13
12.0
22.61
14
12.0
22.73
15
12.0
22.73
16
12.0
22.73
17
12.0
22.75
18
12.0
22.77
19
12.0
22.8
20
12.0
23.45
21
12.0
23.54
22
12.0
23.67
23
12.0
23.91
24
12.0
24.29
25
12.0
24.78
26
12.0
25.45
TOR
0.5
31.04
BOR
0.0
34.74
100.0
27
9.5
5.6
16.14
22.5
28
12.0
20.97
29
12.0
21.16
30
9.5
5.6
16.27
22.59
31
12.0
21.14
32
12.0
22.24
33
12.0
22.26
34
12.0
22.26
35
12.0
22.28
36
9.5
5.6
16.17
22.52
37
12.0
21.0
38
12.0
21.2
39
12.0
21.35
40
9.5
5.6
16.17
22.52
Computer Programs by Hydratec Inc. Revision: 50.54.2
Flow Summary - NFPA
A&D FIRE SPRINKLERS INC Page 4
LAD1699 - HRC CLINIC recover Date
NODE ANALYSIS (cont.)
Pressure Discharge
Node Tag Elevation Node Type at Node at Node Notes
41
12.0
21.01
42
12.0
21.2
43
9.5
5.6 16.29 22.6
44
12.0
21.16
45
9.5
5.6 16.74 22.91
46
12.0
21.77
47
12.0
22.0
48
9.5
5.6 16.74 22.91
49
12.0
21.77
50
12.0
22.0
Computer Programs by Hydratec Inc. Revision: 50.54.2
Final Calculations: Hazen -Williams
A&D FIRE SPRINKLERS INC
LAD1699 - HRC CLINIC recover
Page 5
Date
Nodal Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ***"" Notes
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
1
9.5
5.60 22.50
1
E
2.0
2.500
120
16.143
to
Eql
32.0
34.000
-1.083
2
12
22.5
1.049
0.0
36.500
0.1618
5.907
Vel =
8.35
2
12
0.0
1.5
T
9.9
2.120
120
20.967
to
0.0
9.900
0.0
3
12
22.5
1.682
0.0
12.020
0.0162
0.195
Vel =
3.25
3
12
-1.41
1.5
0.0
12.000
120
21.162
to
0.0
0.0
0.0
4
12
21.09
1.682
0.0
12.000
0.0144
0.173
Vel =
3.05
4
12
22.59
1.5
T
9.9
6.840
120
21.335
to
0.0
9.900
0.0
5
12
43.68
1.682
0.0
16.740
0.0554
0.927
Vel =
6.31
5
12
22.71
2.5
0.0
10.000
120
22.262
to
0.0
0.0
0.0
6
12
66.39
2.635
0.0
10.000
0.0135
0.135
Vel =
3.91
6
12
-13.50
2.5
0.0
10.000
120
22.397
to
0.0
0.0
0.0
7
12
52.89
2.635
0.0
10.000
0.0089
0.089
Vel =
3.11
7
12
-12.32
2.5
0.0
10.000
120
22.486
to
0.0
0.0
0.0
8
12
40.57
2.635
0.0
10.000
0.0054
0.054
Vel =
2.39
8
12
-8.98
2.5
0.0
10.000
120
22.540
to
0.0
0.0
0.0
9
12
31.59
2.635
0.0
10.000
0.0034
0.034
Vel =
1.86
9
12
-7.61
2.5
0.0
10.000
120
22.574
to
0.0
0.0
0.0
10
12
23.98
2.635
0.0
10.000
0.0020
0.020
Vel =
1.41
10
12
-6.69
2.5
0.0
10.000
120
22.594
to
0.0
0.0
0.0
11
12
17.29
2.635
0.0
10.000
0.0012
0.012
Vel =
1.02
11
12
-6.13
2.5
0.0
10.000
120
22.606
to
0.0
0.0
0.0
12
12
11.16
2.635
0.0
10.000
0.0005
0.005
Vel =
0.66
12
12
-5.87
2.5
0.0
10.000
120
22.611
to
0.0
0.0
0.0
13
12
5.29
2.635
0.0
10.000
0.0001
0.001
Vel =
0.31
13
12
0.0
1.5
2T
16.0
67.860
120
22.612
to
0.0
16.000
0.0
14
12
5.29
1.61
0.0
83.860
0.0014
0.116
Vel =
0.83
14
12
0.0
2.5
0.0
10.000
120
22.728
to
0.0
0.0
0.0
15
12
5.29
2.635
0.0
10.000
0.0001
0.001
Vel =
0.31
15
12
5.87
2.5
0.0
10.000
120
22.729
to
0.0
0.0
0.0
16
12
11.16
2.635
0.0
10.000
0.0005
0.005
Vel =
0.66
16
12
6.13
2.5
0.0
10.000
120
22.734
to
0.0
0.0
0.0
17
12
17.29
2.635
0.0
10.000
0.0011
0.011
Vel =
1.02
Computer Programs by Hydratec Inc. Revision: 50.54.2
Final Calculations: Hazen -Williams
A&D FIRE SPRINKLERS INC Page 6
fAD1699 - HRC CLINIC recover Date
Nadel Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
17
12
6.69
2.5
0.0
10.000
120
22.745
to
0.0
0.0
0.0
18
12
23.98
2.635
0.0
10.000
0.0021
0.021
Vel =
1.41
18
12
7.61
2.5
0.0
10.000
120
22.766
to
0.0
0.0
0.0
19
12
31.59
2.635
0.0
10.000
0.0034
0.034
Vel =
1.86
19
12
8.98
2.5
2E
16.474
103.330
120
22.800
to
0.0
.16.474
0.0
20
12
40.57
2.635
0.0
119.804
0.0054
0.650
Vel =
2.39
20
12
12.32
2.5
0.0
10.000
120
23.450
to
0.0
0.0
0.0
21
12
52.89
2.635
0.0
10.000
0.0089
0.089
Vel =
3.11
21
12
13.50
2.5
0.0
10.000
120
23.539
to
0.0
0.0
0.0
22
12
66.39
2.635
0.0
10.000
0.0135
0.135
Vel =
3.91
22
12
23.91
2.5
0.0
10.000
120
23.674
to
0.0
0.0
0.0
23
12
90.3
2.635
0.0
10.000
0.0238
0.238
Vel =
5.31
23
12
24.93
2.5
0.0
10.000
120
23.912
to
0.0
0.0
0.0
24
12
115.23
2.635
0.0
10.000
0.0375
0.375
Vel =
6.78
24
12
18.42
2.5
0.0
10.000
120
24.287
to
0.0
0.0
0.0
25
12
133.65
2.635
0.0
10.000
0.0492
0.492
Vel =
7.86
25
12
23.96
2.5
0.0
10.000
120
24.779
to
0.0
0.0
0.0
26
12
157.61
2.635
0.0
10.000
0.0669
0.669
Vel =
9.27
26
12
23.45
2.5
0.0
7.130
120
25.448
to
0.0
0.0
4.981
TOR
.500
181.06
2.635
0.0
7.130
0.0863
0.615
Vel =
10.65
TOR
.500
0.0
2.5
B
9.61
11.500
120
31.044
to
S
19.22
28.830
0.217
BOR
0
181.06
2.635
0.0
40.330
0.0864
3.483
Vel =
10.65
100.00
Qa =
100.00
BOR
281.06
34.744
K Factor= 47.68
27
9.5
5.60 22.50
1
E
2.0
2.500
120
16.144
to
Eql
32.0
34.000
-1.083
28
12
22.5
1.049
0.0
36.500
0.1618
5.907
Vel =
8.35
28
12
0.0
1.5
T
9.9
2.120
120
20.968
to
0.0
9.900
0.0
29
12
22.5
1.682
0.0
12.020
0.0162
0.195
Vel =
3.25
29
12
1.41
1.5
T
9.9
128.350
120
21.163
to
0.0
9.900
0.0
22
12
23.91
1.682
0.0
138.250
0.0182
2.511
Vel =
3.45
0.0
22
23.91
23.674
K Factor= 4.91
30
9.5
5.60 22.59
1
E
2.0
2.500
120
16.271
to
Eql
32.0
34.000
-1.083
31
12
22.59
1.049
0.0
36.500
0.1630
5.950
Vel =
8.39
Computer Programs by Hydratec Inc. Revision: 50.54.2
Final Calculations: Hazen -Williams
A&D FIRE SPRINKLERS INC Page 7
-IAD1699 - HRC CLINIC recover Date
Nodal Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
31
12
0.0
1.5 T
9.9
2.120
120
21.138
16.171
to
to
0.0
9.900
32.0
0.0
-1.083
4
12
22.59
1.682
0.0
12.020
0.0164
0.197
Vel =
3.26
5.916
Vel =
0.0
37
12
0.0
1.5
T
9.9
1.880
4
21.004
22.59
to
21.335
K Factor= 4.89
3
12
1.41
1.5
0.0
14.000
120
21.162
22.52
1.682
to
0.0
11.780
0.0163
0.0
0.0
3.25
0.0
12
-2.41
29
12
1.41
1.682
0.0
14.000
0.0001
0.001
Vel =
0.20
0.0
0.0
0.0
0.0
39
29
20.11
1.41
0.0
12.000
0.0132
21.163
K Factor= 0.31
5
12
-22.71
2.5
0.0
10.000
120
22.262
120
21.354
to
to
0.0
0.0
0.0
9.900
32
12
-22.71
2.635
0.0
10.000
-0.0019
-0.019
Vel =
1.34
32
12
42.71
2.5
0.0
10.000
120
22.243
to
0.0
0.0
0.0
33
12
20.0
2.635
0.0
10.000
0.0015
0.015
Vel =
1.18
33
12
-18.41
2.5
0.0
10.000
120
22.258
to
32.0
34.000
0.0
0.0
0.0
12
22.52
34
12
1.59
2.635
0.0
10.000
0
0.0
Vel =
0.09
34
12
21.85
2.5
0.0
10.000
120
22.258
to
to
0.0
0.0
0.0
35
12
23.44
2.635
0.0
10.000
0.0020
0.020
Vel =
1.38
35
12
0.0
1.5 2T
19.799
161.190
120
22.278
to
0.0
19.799
0.0
26
12
23.44
1.682
0.0
180.989
0.0175
3.170
Vel =
3.38
0.0
25.448 K Factor= 4.65
36
9.5
5.60 22.52
1
E
2.0
2.500
120
16.171
to
Eql
32.0
34.000
-1.083
37
12
22.52
1.049
0.0
36.500
0.1621
5.916
Vel =
8.36
37
12
0.0
1.5
T
9.9
1.880
120
21.004
to
0.0
9.900
0.0
38
12
22.52
1.682
0.0
11.780
0.0163
0.192
Vel =
3.25
38
12
-2.41
1.5
0.0
12.000
120
21.196
to
0.0
0.0
0.0
39
12
20.11
1.682
0.0
12.000
0.0132
0.158
Vel =
2.90
39
12
22.60
1.5
T
9.9
6.840
120
21.354
to
0.0
9.900
0.0
32
12
42.71
1.682
0.0
16.740
0.0531
0.889
Vel =
6.17
0.0
32
42.71
22.243
K Factor= 9.06
40
9.5
5.60 22.52
1
E
2.0
2.500
120
16.174
to
Eql
32.0
34.000
-1.083
41
12
22.52
1.049
0.0
36.500
0.1621
5.917
Vel =
8.36
41
12
0.0
1.5
T
9.9
1.880
120
21.008
to
0.0
9.900
0.0
42
12
22.52
1.682
0.0
11.780
0.0162
0.191
Vel =
3.25
Computer Programs by Hydratec Inc. Revision: 50.54.2
Final Calculations: Hazen -Williams
A&D FIRE SPRINKLERS INC
12
1.06
1.5
0.0
12.000
120
22.001
Page
8
ILAD1699 - HRC CLINIC recover
0.0
0.0
0.0
47
Date
1.06
Nodal
Elev1
K
Qa
Nom
Fitting
Pipe
CFact
Pt
to
47
1.06
or
Ftngs
22.001 K Factor= 0.23
Pe
*'*****
Notes
Node2
Elev2
Fact
Qt
Act
Eqiv
Len
Total
Pf/Ft
Pf
19.799
42
12
12
2.41
1.5
T
9.9
128.350
120
21.199
to
0.0
9.900
0.0
23
12
24.93
1.682
0.0
138.250
0.0196
2.713
Vel = 3.60
0.0
23
24.93
23.912
K Factor =
5.10
43
9.5
5.60
22.60
1
E
2.0
2.500
120
16.288
to
Eql
32.0
34.000
-1.083
44
12
22.6
1.049
0.0
36.500
0.1632
5.956
Vel = 8.39
44
12
0.0
1.5
T
9.9
1.880
120
21.161
to
0.0
9.900
0.0
39
12
22.6
1.682
0.0
11.780
0.0164
0.193
Vel = 3.26
0.0
39
22.60
21.354
K Factor=
4.89
38
12
2.41
1.5
0.0
14.000
120
21.196
to
0.0
0.0
0.0
42
12
2.41
1.682
0.0
14.000
0.0002
0.003
Vel = 0.35
0.0
42
2.41
21.199
K Factor=
0.52
45
9.5
5.60
22.91
1
E
2.0
2.500
120
16.741
to
Eql
32.0
34.000
-1.083
46
12
22.91
1.049
0.0
36.500
0.1673
6.108
Vel = 8.50
46
12
0.0
1.5
T
9.9
4.120
120
21.766
to
0.0
9.900
0.0
47
12
22.91
1.682
0.0
14.020
0.0168
0.235
Vel = 3.31
47
12
1.06
1.5
T
9.9
142.350
120
22.001
to
0.0
9.900
0.0
25
12
23.97
1.682
0.0
152.250
0.0182
2.778
Vel = 3.46
0.0
25
23.97
24.779
K Factor=
4.82
48
9.5
5.60
22.91
1
E
2.0
2.500
120
16.740
to
Eql
32.0
34.000
-1.083
49
12
22.91
1.049
0.0
36.500
0.1673
6.108
Vel = 8.50
49
12
0.0
1.5
T
9.9
4.120
120
21.765
to
0.0
9.900
0.0
50
12
22.91
1.682
0.0
14.020
0.0168
0.236
Vel = 3.31
50
12
-1.05
1.5
T
9.9
6.840
120
22.001
to
0.0
9.900
0.0
34
12
21.86
1.682
0.0
16.740
0.0154
0.257
Vel = 3.16
0.0
f'�JV�.Y:1•:��T3i.Tg�:k1
50
12
1.06
1.5
0.0
12.000
120
22.001
to
0.0
0.0
0.0
47
12
1.06
1.682
0.0
12.000
0
0.0 Vel = 0.15
0.0
47
1.06
22.001 K Factor= 0.23
33
12
18.42
1.5 2T
19.799
161.190
120
22.258
to
0.0
19.799
0.0
24
12
18.42
1.682
0.0
180.989
0.0112
2.029 Vel = 2.66
Computer Programs by Hydratec Inc. Revision: 50.54.2
Final Calculations: Hazen -Williams
A$D FIRE SPRINKLERS INC
I.AD1699 - HRC CLINIC recover
Page 9
Date
Node1 Elev1 K
Qa
Nom Fitting
Pipe
CFact Pt
to
161.190
or
Ftngs
Pe ******* Notes ******
Node2 Elev2 Fact
Qt
Act Eqiv Len
Total
Pf/Ft Pf
0.0
24 18.42 24.287 K Factor= 3.74
6
12
13.50
1.5
2T
19.799
161.190
120
22.397
to
0.0
19.799
0.0
21
12
13.5
1.682
0.0
180.989
0.0063
1.142
Vel = 1.95
0.0
21
13.50
23.539
K Factor=
2.78
7
12
12.32
1.5
2T
19.799
161.190
120
22.486
to
0.0
19.799
0.0
20
12
12.32
1.682
0.0
180.989
0.0053
0.964
Vel = 1.78
0.0
20
12.32
23.450
K Factor=
2.54
8
12
8.98
1.5
2T
19.799
67.860
120
22.540
to
0.0
19.799
0.0
19
12
8.98
1.682
0.0
87.659
0.0030
0.260
Vel = 1.30
0.0
19
8.98
22.800
K Factor=
1.88
9
12
7.61
1.5
2T
19.799
67.860
120
22.574
to
0.0
19.799
0.0
18
12
7.61
1.682
0.0
87.659
0.0022
0.192
Vel = 1.10
0.0
18
7.61
22.766
K Factor=
1.59
10
12
6.69
1.5
2T
19.799
67.860
120
22.594
to
0.0
19.799
0.0
17
12
6.69
1.682
0.0
87.659
0.0017
0.151
Vel = 0.97
0.0
17
6.69
22.745
K Factor=
1.40
11
12
6.13
1.5
2T
19.799
67.860
120
22.606
to
0.0
19.799
0.0
16
12
6.13
1.682
0.0
87.659
0.0015
0.128
Vel = 0.89
0.0
16
6.13
22.734
K Factor=
1.29
12
12
5.87
1.5
2T
19.799
67.860
120
22.611
to
0.0
19.799
0.0
15
12
5.87
1.682
0.0
87.659
0.0013
0.118
Vel = 0.85
0.0
15 5.87 22.729 K Factor= 1.23
Computer Programs by Hydratec Inc. Revision: 50.54.2