CITY OF NEWPORT BEACH
BUILDING DEPARTMENT
3300 NEWPORT BLVD.
P.O.BOX 1768, NEWPORT BEACH, CA
(949) 644-3275
hoc o� c\c-
Plan Check No.: L 9 " 0i Date: 1 1—) (i— O
Plan Check Engineer: r a J' c GI-o `r1"" \
Submitted Valuation:
0K) 10\I 101C
Phone: 9 k7-69q- 328 l
Corrected Valuation:
Make the following corrections to the plans.
Return this correction sheet and check prints with corrected plans.
Indicate how each correction was resolved.
TENANT IMPROVEMENT CORRECTIONS
Note: This list is applicable to B/M/A3 occupancies.
0f 1. J Approval is required from.
// ✓ Building Department
Planning Department
Fire Department
Orange County Health Department
Other
2. Additional corrections:
In addition to corrections marked on this list, see additional corrections on plans, including:
a.
b.
c.
d.
Building
Electrical
Mechanical
Plumbing
Approved
Corrections
Submit completed hazardous material questionnaire form.
Building Data:
No. of Stories:
Occupancy Group(s):
Fire Sprinklers: ( ) Yes ( 1 No Fire Alarm: ( ' es
List building data above on drawing.
Correct building data on sheet as noted above.
f— PLA" e Wog
t aw^✓.astS— GAS-
1C) £o. cL fi\or
v.- cow sN.nnt
5. (a) Provide naie and address of building owner on plans.
(b) Provide na e of tenant on plans.
(c) Provide the uite number.
Provide the following drawings:
Architectural Plumbing (isometrics)
Electrical [circuit drawings, panel schedule(s) V Fire sprinkler
Mechanical (ducts, supply, return, dampers) vi Fire Alarm
Other
cj9R CAMw�%`^
A''6 ^
Provide a complete floo plan showing location of suite, exit access and exit. Specify the use
of each room.
8. Provide furniture layout ithin space.
9. Provide Hr. occup ncy separation between
10. occupancy is not p rmitted above the first floor in type of construction.
11. Interior partitions to be:
1 hr. non-combustibl construction; metal studs and 5/8-type "X" gypsum board
i both sides.
o.
f1 hr1.comliustible con truction; wood studs and 5/8-type "X" gypsum board both
• sided-
12. ' Occupant 1o4 exceeds 30 pro i de two exits or exit access doorways.
13. All floor occupants must have . cress to two exits.
14. Occupant load to be posted in a-sembly room. Write note on drawings.
15. Exits and exit access doorways o be separated by a distance equal to or greater than 1/2 the
diagonal of the suite.
16. Exit access may pass through a . aximum of one adjoining room after occupant load reaches 10.
17. Exit path to be 44" wide
(Serving more than 49 persons)
18. The maximum travel distance to : t least one exit shall be:
200 ft. in non-sprinklered buildi :. (300 ft. with rated corridor)
250 ft. in sprinklered building. (3.0 ft. with rated corridor)
19. Travel distance to exit exceeds ft.
20. Provide a 1-hr. corridor with 20 inute rated doors and automatic closer. Provide details of
corridor construction allowable tr: vel distance may be increased 100 ft..
21. In lieu of a rated corridor provide the following:
a. Automatic sprinklers thrghout the building.
•
rtment. Compartment walls to
magnetic hold open device
b. aximum occupant load of 100 per suite or compai
one hour rated. Doors to be one hour rated on
ac ivated by smoke detector.
c. E. h compartment to have two exit access doors
aprt.
nto common corridor 1/2 diagonal
22. Provide a d'or schedule.
23. Corridor doo (s) # to be minutes rated with automatic closer.
24. Exit access d
rs to swing in direction of travel when occupant load exceeds 50 occupants.
25. Exit access dos: s to have:
panic hardware
ever hardware, which retracts both locks with a single operation.
f exit access door has two leafs, only automatic flush bolt will be permitted.
Leaf containing I ush bolt shall not have hardware unless it is the main entrance door and
remains open dur ng business hours.
26. When more than . e exit or exit access doorway i required, exit access shall be arranged
such that there is n. dead end in hallways or corrido s exceeding 20 ft.
27. Openings in corrido walls other than doors, to be 3/4 hr. rated and limited to 25% of wall
area.
28. Only exit access door ays may open into rated exit enclosure.
29. Specify smoke and fi e dampers at duct penetrations through rated exit enclosure walls.
Damper to be activate s by smoke detector and installed per its listing.
30. Provide exit lighting p. wered from an emergency power source in:
suites in high .ise buildings
all other occupncies with more than 100 occupants.
31.
32.
Show location of exit si= s when two exits are required. Specify an alternate power source.
Provide low level exit s gns in assembly occupancy and in hotels. Sign to be 6 to 8 inches
above the floor and 4 inc es from the door frame.
33. Provide bathrooms acce• ible to customers if seating is provided in a restaurant. Unisex
bathroom is acceptable fo up to 20 seats.
34. Bathrooms for each sex a e required if the number of employees exceeds four.
35. Specify finishes on bathro.m walls and floors.
Bathroom floors and wall- to have hard, smooth, nonabsorbent finish to a height of 48" above
floor.
36. Show location of fire ex 'nguishers (2-A.10-B,C) on plan. Maximum distance to fire
extinguisher to be 75 feet. nimum one extinguisher per suite.
37. Glass in doors #'s and in windows #'s to be tempered and etch labeled.
38. Full height butt joined glass to be 1/2" thick minimum.
3
Fire Sprinkler
Codes and Standards Used: NFPA 13, 1999 Edition
Designer: Phone: ( )
1. Designer to have C-16 License Classification:
2. Specify the occupancy classification per section 2-1 and area per sprinkler (Per section 5-
6.2.2).
Light hazard
Ordinary hazard Group I
Ordinary hazard Group II
Ordinary hazard Group III
[1
[1
[1
Extra hazard Group I
Extra hazard Group II
High piled stock
3. Specify if the construction is obstructed or unobstructed 1.4.6.
[1
[
[ 1
Smooth ceiling
Beam and Girder
Bar joist
[ 1 Wood joint
[ ] Wood Truss Construction
4. Specify type of O.H. pipe to be used in accordance with Table 3-3.1.
5. Specify type of O.H. pipe fittings to be used in accordance with tables 3-5.1 and 3-5.2.
6. Hangers to be selected from Section 6-1.
7. If hangers are designed, they should support water filled pipe plus 250#. (6-1.1). Provide
hanger listing and detail.
8. Spacing of pipe hangers to be per Table 6-2.2.
9. Each pipe segment on branch line to have one hanger min. (6.2.3.1)
10. Maximum cantilevered pipe with end sprinkler to be 3' for 1" @ pipe, 4' for 1 1/4@ pipe and 5'
for 1 1/2"@ pipe. (6-2.3.3)
11. The maximum length of unsupported arm over pipe to a sprinkler to be 2' for steel pipe, 1' for
copper pipe. (6-2.3.4)
14. Design longitudinal and lateral bracing per 6-4.5.6
15. Longitudinal bracing shall be spaced at a maximum of 80 feet. 6-4.5.4
16. Lateral bracing shall be spaced for main and cross main at a maximum of 40 feet. 6-4.5.3
Exception #2 for 6 inch rods
Exception #3 for U-hooks
17. Provide specs and drawing for sway bracing or specify the NFPA standard bracing from
Tables 6-4.5.8, 6.4.5.9.
18. a) Specify sprinkler head and listing. Orifice size to be 1/2" nominal.
4
b) Dry pre -action system requires upright sprinkler heads or pendant heads listed for dry
use.
19. Sprinklers to be spaced per Table 5-6.2.2(a), (b), (c). Minimum distance between sprinklers
to be 6 feet per 5-6.3.4.
20. Sprinklers in concealed attic space shall be of intermediate temperature classification. 5-
3.1.4.2(6)
21. Sprinkler head to be at ft. from wall and not more than 9' from wall in small rooms
(800 ft2). 5-6.3.2.1
Min. distance to wall 4". 5-6.3.3
22. Sprinklers adjoining ceiling mounted obstructions must comply with Tables 5-6.5.1.2 and 5-
6.5.2.3 for floor mounted obstructions.
23. Sprinkler deflector to be 1" to 12" below smooth ceiling. (1" to 6" below structural members.
22" max. below deck for obstructed condition.) 5-6.4.1.1 and 5-6.4.1.2.
24. Sprinkler deflector to be parallel to sloped ceiling. 5-6.4.2
25. Minimum clearance below sprinkler is 18". 5-5.6.
26. Heat collectors (baffles) are not permitted in improved area. (Accepted only in shell space).
5
Fire Alarm
1. Plans and specifications shall include location of all alarm -initiating and alarm -signaling
devices; annunciation; power connection; voltage drop calculations; make, model and state
fire marshal listing number for all equipment, devices and materials requiring listing; and
wiring or cable type and sizes. (CFC 1001.3)
2. Provide a copy of the installing California State Contractors License with registration
number, class and expiration date.
3. Provide name and phone number of the project coordinator, owner, system designer and
supplier.
4. Specify all Initiating, Indicating, and Signaling line circuit styles currently installed and
what is being installed.
5. Provide a legend for all symbols.
6. Provide two copies of plans and equipment data sheets.
7. Highlight equipment data sheets for all fire alarm equipment to be installed (style, type,
model, amps, volts, mfg., etc.) for the fire alarm system(s) and security system if a
combination panel is used.
S. Provide voltage drop, circuit amperage, and power supply (battery) calculations to include
standby and alarm conditions, include security if a combination panel is installed on the
blueprint.
9. Provide voltage drop calculations for all circuit(s) 10% maximum (ordinance), point to point
method or OHM's law. Calculations are for the area that work is being performed.
10. Provide a diagram showing a typical wiring configuration for each of the system devices
and the point of connection at the panel. Dedicated zones shall be identified on these
drawings.
11. Indicate the location of all devices, end of line (EOL) devices, conduit/wire runs, conduit
sizes, number and size of conductors, list conduit fill (40% max. NEC 346-6) for each device
and/or circuit for the area work is being performed. Initiating Zone 1 shall be indicated as Z-
1 and Indicating Circuit 1 shall be indicated as C-1. The zone indication shall be placed
adjacent to the appropriate end -of -line device(s).
12. Provide a riser diagram indicating the device installation, wiring sequence, the number of
devices per zone and zone assignments for the area work is being performed. All other areas
just show the total amps and watts used per circuit and zone identification.
13. Provide a sequence of operation matrix.
14. Drawings shall also include details showing the installation of pull stations and strobes
(include installation height), FACP, door hold open devices, heat and smoke devices.
15. Automatic detection devices shall be located in accordance with their listing(s).
16. Control pad to have a single reset button.
6
17. Visual warning devices for the hearing impaired are required to be installed (added) within
the suite per T-24 requirements under one of the following conditions.
a. Building is equipped with visual warning devices.
b. Existing fire alarm panel can support visual warning devices for the entire building.
c. The fire alarm panel is being upgraded to support visual warning devices for the
entire building.
d. The occupancy group is changing.
7
TIT E 24 DISABLED ACCESS CORRECTION LIST
SITE DEVELOP NT & ACCESSIBLE ROUTE OF TRAVEL
4. Show on site .lan the accessible path of travel from parking to building entrance. Show all grade
changes, raps, etc.
ACCESSIBL PARKING
1. Provide disabled parking spaces as required by Table 11B-6 for parking
lot/struc ure (1129B.1).
Specify t, e total number of parking spaces and disabled parking spaces required by Table 11B-6.
2. Accessibl: parking spaces serving a particular building shall be located on the shortest
accessible oute of travel from adjacent parking to an accessible entrance (as near as practical
to an accessible entrance) (1129B.1 & 1129B.4)
3. Where singl: accessible parking spaces are provided, they shall be 14' wide and 18' long and
outlined to . ovide a 9' parking area and a 5' loading and unloading access aisle on the
passenger side .f the vehicle. (1129B.4.1, Fig 11B-18A)
4. One in every ei: t accessible spaces, but not less than one, shall be served by an access aisle
96" wide minimuand shall be designated "van accessible". All such spaces may be grouped
on one level of a pa ing structure. (1129B.4.2)
5. Accessible parking spes shall be so located that persons with disabilities are not compelled to
wheel or walk behind p ked cars other than their own. (1129B.4.3)
6. Curb ramps shall not enc .ach into any parking space, with the exception of a transition ramp
from a loading/unloading a ea to an adjacent walk/sidewalk. The transition ramp shall be a
minimum of 48" in width; a • aximum of 60" in length, with a maximum slope of 1:12 and with
flared side slopes of 1 vertical . 10 horizontal maximum. (1129B.4.3, Fig. 11B-18A, B &C)
7. Each parking space reserved fo persons with disabilities shall be identified by a reflectorized
sign permanently posted imm•diately adjacent to and visible from each stall or space,
consisting of a profile view of a eelchair with occupant in white on dark blue background.
The sign shall not be smaller than '0 square inches in area and, when in a path of travel, shall
be posted at a minimum height of 81" from the bottom of the sign to the parking space finished
grade. (1129B.5, Fig 11B-18A, B & C)
8. Signs to identify accessible parking sp es may also be centered on a wall at the interior end of
the parking space at a minimum height .f 36" from the parking space finished grade, ground or
sidewalk. (1129B.5)
9. Van accessible parking spaces shall have : n additional sign stating "Van Accessible" mounted
below the symbol of accessibility. (1129B.5)
10. An additional sign shall also be posted, in . conspicuous place, at each entrance to off-street
parking facilities, or immediately adjacent ti and visible from each stall or space. The sign
shall be not less than 17" by 22" in size with 1: ttering not less than 1" in height, which clearly
and conspicuously states the following:
(1129B.5)
"Unauthorized vehicles parked in designa d accessible spaces not displaying
distinguishing placards or license plates issue ' for persons with disabilities may be
towed away at owner's expense. Towed vehic es may be reclaimed by telephoning
the Police Dept. (949) 644-3681."
8
CITY OF NEWPORT BR,ACH
BUILDING DEPARTMENT
3300 NEWPORT BLVD.
P.O. BOX 1768, NEWPORT BEACH, CA 92658-8915
(949) 644-3275
PLAN CHECK REPORT
Project Address: Date:
Plan Check No.: Plan Check Engineer: David Groverman Phone: (949) 644-3281
Applicant to indicate in column at right where the correction was made on the p ans.
No.
Correction
Location
on Plans
Additional Corrections/Clarifications:
Regarding correction #6, before Bldg. Permit can be issued, the plans
for modifications to fire sprinklers and fire alarm must be submitted
into plan check, or, provide letters from sprinkler and alarm subs
stating that they are doing the work and when they will submit into
plan check.
0
Forms \P:c:-report DG 201. cnb m_blg@city.newpoa-beach.cn.us
• wcbpayc: u-.tw.cin..newport-beach.ca.us/huilding
Project Address:
CITY OF NEWPORT BE
BUILDING DEPARTMENT
3300 NEWPORT BLVD.
P.O. BOX 1768, NEWPORT BEACH, CA 9263
(949) 644-3273
PLAN CHECK REPORT
-Lav+4C2
;"Plan Check No.: CI”—O
Applicant to indicate in column at riiht where the correction was made on the plans.
Date: l O - 7-3 -0 7-
Plan Check Engineer: Cavnb C ck*RMAr1 Phone: 9'--644-3Z5I
No.
Correction
Location
on Plans
�‘ J
-,--.- \jam L.L. .. 5&iks. " x .%A
1—ter Arqa-
6)
''
—1-VP:"•"^ .
--.._. _
2-(:'au\a- o*". W • ay Tti .('a
/�
'
nM,c-\
Jl /�3W�R" \a'2A
1 afNei \a �T\at, ti C\Q V�Q, »'
j
I\OVJ4 - is b(2,
C � CLAt —Hoc -_. sJ. wfr .�h
, )
Z\+' �- 4 -�� o • , ,+ems w..,1-� he_ I YL H r .
1 %s ' l----)o \ our _ • fr \O✓\
�P ub" Co"�'L 9icnnii5
�a be-
bmc . •
-ik-�. \,":ig • ry
1
.Ifrr .iu uc U4:Clp ❑rl6(s tlectr lc
949-883-8688 P,1
Briggs Electric, Inc.
21-34-200 (
16862 Md'ikan Avenue
F. J. box 18650
Irvina, C&!ifomia 92606
(949) 863-9901
010-297830
April 30, 2002
Newport Beach Fire Provention
465 32nd Street
Newport Beach, CA. 92663
Reference: Hoag Memorial Hospital
Support Services Building
One Hoag Drive
Newport Beach, CA.
Plan Check # 2739-2001
Gentlemen,
We have been contracted to provide plans and the installation of the fire alarm
changes at the above mentioned project for the general contractor, Watson
Investment Devrlopment. We are currently in the process of engineering and will
submit the plans as soon as we have them available.
If you have any questions, Please do not hesitate to call me.
tAti
Randy Perry
Project Manager