HomeMy WebLinkAboutF2021-0352 - MiscConcealed Quick Response
Sprinkler Coverage
to20'x20'(6.Omx6.0m)
Features
1. Quick response performance.
2. Push on, thread off, sturdy convenient
cover plate.
3. Factory assembled sprinkler and cup,
shipped complete with protective
cap.
4. Sprinkler assembly and cover plate
separately packaged.
6. Rugged damage resistant assembly.
No exposed thermal element.
7. Utilizes the Model F1FR QREC
Pendent Sprinkler.
8. Aesthetic ceiling profile.
9. Standard finishes in white painted or
chrome plated. Other color -painted
and specialty finishes available.
For Model F1 FR QREC CCP 1/2" K 5.6 (80)
Sprinkler Types refer to Bulletin 028 for
technical specifications and approvals.
Product Description
Model F1 FR QREC Quick Response Extended Coverage
Concealed Sprinkler is an attractive, low profile concealed
sprinkler assembly. This sprinkler assembly utilizes a Model
F1 FR QREC pendent sprinkler in a Model CCP cup and
push -on thread -off cover plate assembly. The cup is securely
factory threaded on the sprinkler's inlet end. The assembly
is shipped with a protective cap. The sprinkler and cup are
easily installed into the sprinkler fitting using the Model GFR2
Sprinkler Wrench. The cover plate assembly is attached to the
sprinkler cup using a flexible tooth threaded engagement. The
cover plate is attached to the skirt using 135°F (57°C) ordinary
temperature classification solder.
When the ceiling temperature rises, the solder holding the
�('�
Bulletin 151 September p202�r
0 I v VL
Model F1 FR QREC CCP
Concealed Quick Response
Extended Coverage
Sprinkler
cover plate melts, allowing the release of this part and thus
exposing the Model F1 FR QREC sprinkler inside to the rising
ambient temperature. The Temperature rating of the sprinkler
identified by the color of the glass bulb.
Model F1 FR QREC automatic sprinkler utilizes a 3.0 mm
frangible glass bulb. This sprinkler has demonstrated response
times in laboratory tests which are five times faster than
standard response sprinklers. This quick response enables the
Model F1 FR QREC sprinkler to apply water to a fire faster than
standard sprinklers of the same temperature rating.
Approval Type:
Quick Response Extended Coverage — Light Hazard
Technical Data:
(1) 135°F (57°C) Only
Note: 1 bar - 100 kPa
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Sprinkler
Nominal
ThreadApproval
Ident.
Orifice
Size
a
Organizations
Number
(SIN)
/�
17/32" (20mm)
3/a" (R3/a)
cULus
R4842
Thread
Temp. Rating
Max.
Bulb
SprinJ'Jer
Size
Model
Color
Tern P•
3/" NPT
F1FR
135°5°F
100°F
Orange
(R3/)
QREC
57°7°C38°Cg3/"
NPT
F1FR
155°F
100°FRed
(R3/)
QREC
687°C
38°C
Coverage Area
Pressure
Flow Rate
psi (bar)
Max Enclosure Area
Bpm (Urn)
Width x Length
K=8.0
ftxft (mxm)
(Metric 115.3)
26 (98.4)
10.6 (0,7)
16 x 16 (4.9 x 4.9)
33(125.0)
17.0(1,2)
18x 18(5.5 x5.5)
40(151.4)
25.0(1,7)
20 x 200)(6.0 x 6.0)(1)
(1) 135°F (57°C) Only
Note: 1 bar - 100 kPa
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Application and Installation
Model F1 FR QREC Concealed Sprinklers use 135°F (57°C)
or 155OF (68°C) Model F1 FR QREC Pendent Sprinklers with
a threaded Model CCP cup which is factory attached to the
sprinkler. The assembly is completed by the installation of the
attractive, low profile, 135OF (57°C) rated cover plate assembly.
The cover plate and sprinkler cup are joined using a flexible
tooth threaded engagement.
Do not install these sprinklers in ceilings which have positive
pressure in the space above.
The sprinkler cup is factory attached to the Model F1 FR
QREC Sprinkler. A PTFE based thread sealant should be
applied to the sprinkler threads only.
After a 25A inch (67mm) diameter hole is cut in the ceiling,
the sprinkler is easily installed with the Model GFR2 Wrench.
When installing a sprinkler, the protective cap is removed and
the wrench is positioned into the sprinkler/cup assembly until
the two wrench faces engage the wrenching flats on the Model
F1 FR QREC Sprinkler. The sprinkler is then tightened into
the pipe fitting. When inserting or removing the wrench from
the sprinkler/cup assembly, care should be taken to prevent
damage to the sprinkler. DO NOT WRENCH ON ANY OTHER
PART OF THE SPRINKLER. The cover plate assembly is then
pressed into the cup. Final adjustment is made by turning
the cover plate until the skirt flange makes full contact with the
ceiling surface. Cover plate removal requires turning in the
counter clockwise direction.
After installation, inspect all sprinklers to ensure that there is
a gap between the cover plate and ceiling and that the four
cup slots are open and free from any air flow impediment to the
space above.
Concealed cover plate/cup assemblies are listed only for
use with specific sprinklers. The use of any other concealed
cover plate/cup assembly with the Model F1 FR QREC Pendent
Sprinkler or the use of the Model CCP concealed cover plate
assembly on any sprinkler with which it is not specifically listed
may prevent good fire protection and will void all guarantees,
warranties, listings and approvals.
1" x 3/4" REDUCING
TEE OR ELeow
A" [66 ]mm] ON.
2,y" (58, ]mmJ DNI — HOLE IN ..'
RA ca IS" (Je imm] AIAx
FACE OF F?ZINC
rO FACE OF GELLLNG
CAJENEION
CIDUNG
}" (127—' MAX.T
covEre A1111o✓usmENr
.1 PL1rE—
ASSEM6LY 3Ij" ($3Hmm]
SGRMKI£R
COVER PLArE. 1/2(127mm7 AOJUSiMENi
Maintenance
Model F1 FR QREC Concealed Sprinklers should be
inspected and the sprinkler system maintained in accordance
with NFPA 25. Do not clean sprinklers with soap and water,
ammonia or any other cleaning fluids. Remove dust by using
a soft brush or gentle vacuuming. Remove any sprinkler cover
plate assembly which has been painted (other than factory
applied) or damaged in any way. A stock of spare sprinklers
should be maintained to allow quick replacement of damaged
or operated sprinklers. Prior to installation, sprinklers should
be maintained in the original cartons and packaging until used
to minimize the potential for damage to sprinklers that would
cause improper operation or non -operation.
Approvals
cULus (Sprinklers, Automatic and Open. Quick Response Extended
Coverage Sprinklers)
NYC MEA 258-93-E
Ordering Information
Specify:Sprinkler Model:
1.F1FR QREC Pendent
3/4" NPT or ISO 7-R3/4 threads
2. Sprinkler Temp. Rating0):
135GF(57°C)or
155-F (68-C).
3.Cover plate Model: CCP
4.Cover plate temp. rating:
135-F (57°C).
5.Cover plate finish:
(1) 135°F (57°C) required for 20'x 20' (6.Om x 6.0m) coverage area
Installation Wrench
Model GFR2 Sprinkler Wrench
Installation Aid
A protective cap is included for use during installation.
Cover Plate Finishes(n
Standard Finishes
Chrome
White
Special Application Finishes
Bright Brass
Black Plating
Black Paint
Off White
Satin Chrome
(1) Other finishes and colors are available on
special order. Consult factory for details.
Note: Paint or any other coatings applied over the factory finish will void
all approvals and warranties.
Important: The F1 FR QREC Sprinkler with the Model CCP cover plate
is not an FM Approved combination.
The equipment presented in this bulletin is to be installed In accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc
(800) 431-1588
Sales Offices
(800) 848-6051
Sales Fax
(914) 829-2042
Corporate Offices
www.reliablesprinkler.com
Internet Address
®
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 09/20 PM 99999/0148
Coverage to 18 ft. x 22 ft.
(5.5m x 6.7m), 16 ft. x 24 ft.
(4.9m x 7.3m).
Features:
1. Flat cover plate.
2. K -factor of 8.0 (115 metric).
3. Listed as quick -response, extended coverage for
Light Hazard occupancies.
4. Sprinkler assembly and cover plate packaged
separately.
5. 1/4' (6.3mm) cover plate adjustment.
6. Model G6 Cover plate available in in a wide vari-
ety of colors and finishes.
Approval Organizations
1. Listed for use in Light Hazard occupancies by
Underwriters Laboratories Inc. and UL certified
for Canada (cULus).
UL Listing Category
Sprinklers, Automatic and Open
Quick Response Extended Coverage Sprinklers
Product Description
The Reliable Model G6-80 Concealed Quick Response
Extended Coverage Horizontal Sidewall Sprinkler is an at-
tractive, concealed sprinkler assembly that utilizes a push-
on/pull-off cover plate assembly. The sprinkler assembly is
shipped with a protective cap.
The flat cover plate is attached to the skirt using 135°F
(57°C) ordinary temperature classification solder. The sprin-
kler is installed into the sprinkler fitting using the Model G6
Sprinkler Wrench.
When the ambient temperature rises, the solder holding
the cover plate melts, allowing the release of this part and
thus exposing the sprinkler inside to the rising ambient tem-
�erature.
he Model G6-80 utilizes a Quick Response soldered link.
k -response sprinklers are designed to apply water to a
)ner than standard -response sprinklers of the same
lure rating.
+el G6-80 sprinkler is listed for a maximum service
175 psi (12,0 bar).
natic Sprinkler Co., Inc., 103
Bulletin 047 August 2019
Model G6-80 K8.0 (115 metric)
Concealed Quick Response
Extended Coverage Light Hazard
Horizontal Sidewall Sprinkler
(SIN RA4762)
Application and Installation
The Model G6-80 sprinkler is intended for installation in
light hazard occupancies in accordance with NFPA 13. This
sprinkler is especially well-suited for use in non -corrosive
environments in student dormitories, hotels, hospitals and
care facilities.
Model G6-80 Concealed Horizontal Sidewall sprinklers
utilize a sprinkler assembly with spring loaded deployable
deflector feature. The assembly is completed by the instal-
lation of the attractive, 135°F (57°C) push-on/pull-off cover
plate assembly, which provides 1/4" (6.3mm) of adjustment.
Apply a Teflon' - based thread sealant to the sprinkler
threads. After a 2 5/e' (66.7mm) diameter hole is cut in the
wall, the sprinkler is installed and properly oriented with the
Model G6 Wrench, as follows:
Do not remove factory installed plastic protective cap
since it is sized to fit inside the G6 wrench. Note that the
sprinkler can only mate when the sprinkler's deflector ori-
entation tab (Fig. 1) is aligned with wrench's key -way. The
G6 Wrench has a bubble level pad and TOP to assist the
installer in properly orienting the sprinkler. Final leveling can
be done after leak proof joint is obtained with a minimum to
maximum torque of 14 to 20 ft -lbs (19 to 27 N m). Do not
attempt to compensate for improper rough in dimensions of
fitting by over tightening the sprinkler assembly, but readjust
the sprinkler fitting instead. Leave the protective cap on to
assure sprinkler protection while the wall is plastered, wall-
papered or painted.
Concealed cover plate/cup assemblies are listed only for
use with specific sprinklers. The use of any other concealed
cover plate/cup assembly with the Model G6-80 Horizontal
Sidewall Sprinkler or the use of this dedicated concealed
cover plate assembly on any sprinkler with which it is not
specifically listed will void all guarantees, warranties, listings
and approvals.
DuPont Registered Trademark
Fairview Park Drive, Elmsford, New York 10523
Technical Data:
Nominal K -factor
Thread
Size
Temperature Rating
Maximum
Ambient
Temperature
Maximum Water
Working Pressure
us
Metric
Sprinkler
Cover
8.0
115
3/4" NPT
or ISO 7-R3/a
165°F
(74°C)
135°F
Y00°F
175 PSI
Coverage Area
Max. Installed
Coverage Area
Width x Length
Deflector to Ceiling
Dimension
Min. Required
Flow Rate
Min. Required
Pressure
ft. x ft.
m x m
inches
mm
gpm
Umin
psi
bar
14x22
4.3x6.7
4-6
102-152
31
117.3
15.0
1,03
14x22
4.3x6.7
6-12
152-305
35
132.5
19.1
1,3
14x24
4.3x7.3
4-6
102-152
35
132.5
19.1
1,3
14 x 24
4.3 x 7.3
6-12
152 -305
39
147.6
23.8
1,6
16 x 16
4.9 x 4.9
4-12
102-305
26
98.4
10.6
0,7
16 x 18
4.9 x 5.5
4-12
102-305
29
109.8
13.1
0,9
16x20
4.9x6.1
4-12
102-305
32
121.1
16.0
1,1
16 x 22
4.9 x 6.7
4-12
102-305
36
136.2
20.2
1,4
16x24
4.9x7.3
4-12
102-305
39
147.6
23.8
1,6
18x18
5.5x5.5
4-12
102-305
33
124.9
17.0
1,2
18 x 20
5.5 x 6.1
4-12
102-305
36
136.2
20.2
1,4
18x22
5.5x6.7
4-12
102-305
40
151.4
25.0
1,7
Approval Type
Quick Response Extended Coverage - Light Hazard Horizontal Sidewall.
Minimum spacing between sprinklers - 8 feet (2.4m).
Install below smooth, flat, horizontal ceilings only AS DEFINED BY NFPA 13.
FACE OF F
DEFLECTOR ORIENTATION
3/4--I4 NPd114
wmnrc
ALUUSTMENY
4" TO 12"
(IOI.B TO, 3048/AMT
TOP OF DERECTOR
PUSH ON/PULL OFF
EMT CO✓ERP(ATE
Sprinkler Identification
Number
(SIN)
RA4762
_...-"'1 TION TAB
NOTE DIMENSIONS IN BRACKETS ARE IN MM.
2.
FRONT ✓IEN
PUSH ON/PULL OFF COVERPLATE REMOVED
Maintenance
Model G6-80 Concealed Sprinklers should be inspected
and maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other clean-
ing fluids. Remove dust by using a soft brush or gentle
vacuuming. Replace any sprinkler or cover plate assem-
bly, which has been painted (other than factory applied) or
damaged in any way. A stock of spare sprinkler and cover
plate assemblies should be maintained to allow quick re-
placement of damaged or operated sprinklers. Prior to in-
stallation, sprinklers should be maintained in their original
cartons and packaging until used to minimize the potential
for damage to sprinklers that would cause improper opera-
tion or non -operation.
Model G6-80 Concealed Quick Response
Extended Coverage Light Hazard Horizontal
Sidewall Sprinkler Specification
Sprinklers shall be quick -response extended coverage
sprinklers that are cULus Listed for use in Light Hazard oc-
cupancies. Sprinklers to be of bronze frame construction
with brass cover plate and copper alloy retainer flange as-
sembly. Water seal assembly shall consist of a PTFE coated
Belleville spring washer and machined brass cup contain-
ing no plastic parts. Method of attaching the cover plate to
the sprinkler cup shall be a push -on and pull -off design al-
lowing a 1/4" cover plate adjustment. Sprinklers shall have a
nominal K -factor of 8.0 (115 metric). Sprinkler temperature
rating shall be 165°F (74°C) with a cover plate temperature
rating of 135°F (57°C). Sprinklers shall be capable of a max-
imum coverage area of 16 ft. x 24 ft. (4.9 m x 7.4 m) or 18
ft. x 22 ft (5.5 m x 6.7 m), with a minimum lateral spacing of
8 ft. (2.4 m). Rated working pressure shall be 175 psi (12,0
bar). A plastic protective cap shall be provided and fac-
tory installed inside the sprinkler cup to protect the sprinkler
from damage, which could occur during construction before
the cover plate is installed. Installation threads shall be [1 -
inch NPT] [ISO 7-R3/4]. "Cover plate finish: [Chrome] [White]
[Custom Color— specify]. Extended Coverage Concealed
horizontal sidewail sprinklers shall be Reliable Model G6-80.
SIN RA4762 (Bulletin 047).
Ordering Information
Specify:
1. Sprinkler: Model G6-80
2. Model G6 Cover Plate Finish
Installation Wrench
Model G6 Sprinkler Wrench
Installation Aid
A protective plastic cap is included for use during instal-
lation.
Cover Plate Finishesl'>
p
inishes
plication Finishes
Flat White Paint
(1) Other colors and finishes are available. Consult factory for details.
Note: Paint or any other coatings applied over the factory
finish will void all approvals and warranties.
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
,ualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
`aIctured by ® Recycled
Reliable Automatic Sprinkler Co., Inc. paper
® (800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax Revision lines indicate updated or new data.
(914) 829-2042 Corporate Offices EG. Printed in U.S.A. 08/19 P/N 9999970456
�� www.reliablesprinklencom Internet Address
Rellabld
Concealed Quick Response
Sprinkler Coverage
to20' x20' (6.0mx6.0m)
Features
1. Quick response performance.
2. Push on, thread off, sturdy convenient
cover plate.
3. Factory assembled sprinkler and cup,
shipped complete with protective
cap.
4. Sprinkler assembly and cover plate
separately packaged.
6. Rugged damage resistant assembly.
No exposed thermal element.
7. Utilizes the Model F1 FR QREC
Pendent Sprinkler.
8. Aesthetic ceiling profile.
9. Standard finishes in white painted or
chrome plated. Other color -painted
and specialty finishes available.
For Model F1 FR QREC CCP Ys" K 5.6 (80)
Sprinkler Types refer to Bulletin 028 for
technical specifications and approvals.
Product Description
Model F1 FR QREC Quick Response Extended Coverage
Concealed Sprinkler is an attractive, low profile concealed
sprinkler assembly This sprinkler assembly utilizes a Model
F1 FR QREC pendent sprinkler in a Model CCP cup and
push -on thread -off cover plate assembly The cup is securely
factory threaded on the sprinkle's inlet end. The assembly
is shipped with a protective cap. The sprinkler and cup are
easily installed into the sprinkler fitting using the Model GFR2
Sprinkler Wrench. The cover plate assembly is attached to the
sprinkler cup using a flexible tooth threaded engagement. The
cover plate is attached to the skirt using 135°F (57°C) ordinary
temperature classification solder.
When the ceiling temperature rises, the solder holding the
Bulletin 151 September 2029
Model 171 FR QREC CCP
Concealed Quick Response
Extended Coverage
Sprinkler
0
cover plate melts, allowing the release of this part and thus
exposing the Model F1 FR QREC sprinkler inside to the rising
ambient temperature. The Temperature rating of the sprinkler
identified by the color of the glass bulb.
Model F1 FR QREC automatic sprinkler utilizes a 3.0 mm
frangible glass bulb. This sprinkler has demonstrated response
times in laboratory tests which are five times faster than
standard response sprinklers. This quick response enables the
Model F1 FR QREC sprinkler to apply water to a fire faster than
standard sprinklers of the same temperature rating.
Approval Type:
Quick Response Extended Coverage — Light Hazard
Technical Data:
iQo F (3 "u) un y
Note: 1 bar = 100 kPa
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
K Factor
Sprinkler
Approval
(dent.
LNicnalThread
Size US Metric
Organizations
Number
(SIN)
3/" (R3/e) 8.0
115.3
cULus
R4842
Thread
Temp. Rating
Max.
Size
Model
Ceiling
Bulb
Color
Sprinkler
Cover
Temp.
3/" NPT
FIFR
135°F
135°F
100°F
(R3/)
QREC
57°C
57°C
38°C
Orange
a/a" NPT
FIFR
155°F
135°F
100°F
(R 3/4)
QREC
68°C
57°C
3g°C
Red
Coverage Area
Pressure
Flow Rate
psi (bar)
Max Enclosure Area
gpm (L/m)
Width x Length
K=8.0
(Metric 115.3)
ft x ft (m x m)
26 (98.4)
10.6 (0,7)
16 x 16 (4.9 x 4.9)
33(125.0)
17.0(1,2)
18x 18(5.5 x5.5)
40(151.4)
25.0(1,7)
20 x 20')(6.0 x 6.0)(1
iQo F (3 "u) un y
Note: 1 bar = 100 kPa
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Application and Installation
Model F1 FR QREC Concealed Sprinklers use 135°F (57°C)
or 155°F (68°C) Model F1 FR QREC Pendent Sprinklers with
a threaded Model CCP cup which is factory attached to the
sprinkler. The assembly is completed by the installation of the
attractive, low profile, 135°F (57°C) rated cover plate assembly.
The cover plate and sprinkler cup are joined using a flexible
tooth threaded engagement.
Do not install these sprinklers in ceilings which have positive
pressure in the space above.
The sprinkler cup is factory attached to the Model F1 FR
QREC Sprinkler. A PTFE based thread sealant should be
applied to the sprinkler threads only.
After a Th inch (67mm) diameter hole is cut in the ceiling,
the sprinkler is easily installed with the Model GFR2 Wrench.
When installing a sprinkler, the protective cap is removed and
the wrench is positioned into the sprinkler/cup assembly until
the two wrench faces engage the wrenching flats on the Model
F1 FR QREC Sprinkler. The sprinkler is then tightened into
the pipe fitting. When inserting or removing the wrench from
the sprinkler/cup assembly, care should be taken to prevent
damage to the sprinkler. DO NOT WRENCH ON ANY OTHER
PART OF THE SPRINKLER. The cover plate assembly is then
pressed into the cup. Final adjustment is made by turning
the cover plate until the skirt flange makes full contact with the
ceiling surface. Cover plate removal requires turning in the
counter clockwise direction.
After installation, inspect all sprinklers to ensure that there is
a gap between the cover plate and ceiling and that the four
cup slots are open and free from any air flow impediment to the
space above.
Concealed cover plate/cup assemblies are listed only for
use with specific sprinklers. The use of any other concealed
cover plate/cup assembly with the Model F1 FR QREC Pendent
Sprinkler or the use of the Madel CCP concealed cover plate
assembly on any sprinkler with which it is not specifically listed
may prevent good fire protection and will void all guarantees,
warranties, listings and approvals.
1' , 3/4" REDUCING
TEE OR E
OM.
A' 158 OIA-
HOLE IN CEILMG
- ---- T
RA CO
I}" [38.Imm] MAX
FACE OF RMNG
i0 FALE OF LERINL
CEWNC
GIVING'.
�
MAN
}" [12Jmm]
COVER AANSIMENr
COVEF PU IE -
pSSEMBLY�/[2�
SPRINNL£R
COVER PLATE,
1/2"
[r2 ] 7 ADJUSTMENT
I
Maintenance
Model F1 FR QREC Concealed Sprinklers should be
inspected and the sprinkler system maintained in accordance
with NFPA 25. Do not clean sprinklers with soap and water,
ammonia or any other cleaning fluids. Remove dust by using
a soft brush or gentle vacuuming. Remove any sprinkler cover
plate assembly which has been painted (other than factory
applied) or damaged in any way. A stock of spare sprinklers
should be maintained to allow quick replacement of damaged
or operated sprinklers. Prior to installation, sprinklers should
be maintained in the original cartons and packaging until used
to minimize the potential for damage to sprinklers that would
cause improper operation or nonoperation.
Approvals
cULus (Sprinklers, Automatic and Open. Quick Response Extended
Coverage Sprinklers)
NYC MEA 258-93-E
Ordering Information
Specify:Sprinkler Model:
1.F1FR QREC Pendent
3/4" NPT or ISO 7-R3/4 threads
2.Sprinkler Temp. Rating(':
135°F (57°C) or
155-F (68-C).
3.Cover plate Model: CCP
4.Cover plate temp. rating:
1351F (57'C).
5.Cover plate finish:
hI 135°F (57°C) required for 20'x 20' (6.Om x 6.0m) coverage area
Installation Wrench
Model GFR2Sprinkler Wrench
Installation Aid
A protective cap is included for use during installation.
Cover Plate Finishesm
Chrome
Bright Brass
Black Plating
Black Paint
Off White
(I) Other finishes and colors are available on
special order. Consult factory for details.
Note: Paint or any other coatings applied over the factory finish will void
all approvals and warranties.
Important: The F1FR QREC Sprinkler with the Model CCP cover plate
is not an FM Approved combination.
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced bythe most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by ® Recycled
The Reliable Automatic Sprinkler Co., Inc. Paper
(800) 431-1588 Sales Offices
Reliable ()848-6051 Sales Fax Revision lines indicate updated ornew data.
(914914) 829-2042 Corporate Offices Pnu 99999/0148
www.reliablesPrinkler.com Internet Address Eo. Printed in U.S.A. os/zo
Rel"iable
Coverage to 18 ft. x 22 ft.
(5.5m x 6.7m), 16 ft. x 24 ft.
(4.9m x 7.3m).
Features:
1. Flat cover plate.
2. K -factor of 8.0 (115 metric).
3. Listed as quick -response, extended coverage for
Light Hazard occupancies.
4. Sprinkler assembly and cover plate packaged
separately.
5. 1/4" (6.3mm) cover plate adjustment.
6. Model G6 Cover plate available in in a wide vari-
ety of colors and finishes.
Approval Organizations
1. Listed for use in Light Hazard occupancies by
Underwriters Laboratories Inc. and UL certified
for Canada (cULus).
LIL Listing Category
Sprinklers, Automatic and Open
Quick Response Extended Coverage Sprinklers
Product Description
The Reliable Model 36-80 Concealed Quick Response
Extended Coverage Horizontal Sidewall Sprinkler is an at-
tractive, concealed sprinkler assembly that utilizes a push-
on/pull-off cover plate assembly. The sprinkler assembly is
shipped with a protective cap.
The flat cover plate is attached to the skirt using 135°F
(57°C) ordinary temperature classification solder. The sprin-
kler is installed into the sprinkler fitting using the Model G6
Sprinkler Wrench.
When the ambient temperature rises, the solder holding
the cover plate melts, allowing the release of this part and
thus exposing the sprinkler inside to the rising ambient tem-
perature.
The Model G6-80 utilizes a Quick Response soldered link.
Quick -response sprinklers are designed to apply water to a
fire sooner than standard -response sprinklers of the same
temperature rating.
The Model 36-80 sprinkler is listed for a maximum service
pressure of 175 psi (12,0 bar).
Reliable Automatic Sprinkler Co., Inc., 103
Bulletin 047 August 2019
Model G6-80 K8.0 (115 metric)
Concealed Quick Response
Extended Coverage Light Hazard
Horizontal Sidewall Sprinkler
(SIN RA4762)
Application and Installation
The Model 36-80 sprinkler is intended for installation in
light hazard occupancies in accordance with NFPA 13. This
sprinkler is especially well-suited for use in non -corrosive
environments in student dormitories, hotels, hospitals and
care facilities.
Model G6-80 Concealed Horizontal Sidewall sprinklers
utilize a sprinkler assembly with spring loaded deployable
deflector feature. The assembly is completed by the instal-
lation of the attractive, 135°F (57°C) push-on/pull-off cover
plate assembly, which provides 1/4" (6.3mm) of adjustment.
Apply a Teflon' - based thread sealant to the sprinkler
threads. After a 2 s/e" (66.7mm) diameter hole is cut in the
wall, the sprinkler is installed and properly oriented with the
Model G6 Wrench, as follows:
Do not remove factory installed plastic protective cap
since it is sized to fit inside the G6 wrench. Note that the
sprinkler can only mate when the sprinkler's deflector ori-
entation tab (Fig. 1) is aligned with wrench's key -way. The
G6 Wrench has a bubble level pad and TOP to assist the
installer in properly orienting the sprinkler. Final leveling can
be done after leak proof joint is obtained with a minimum to
maximum torque of 14 to 20 ft -lbs (19 to 27 N m). Do not
attempt to compensate for improper rough in dimensions of
fitting by over tightening the sprinkler assembly, but readjust
the sprinkler fitting instead. Leave the protective cap on to
assure sprinkler protection while the wall is plastered, wall-
papered or painted.
Concealed cover plate/cup assemblies are listed only for
use with specific sprinklers. The use of any other concealed
cover plate/cup assembly with the Model G6-80 Horizontal
Sidewall Sprinkler or the use of this dedicated concealed
cover plate assembly on any sprinkler with which it is not
specifically listed will void all guarantees, warranties, listings
and approvals.
DuPont Registered Trademark
Fairview Park Drive, Elmsford, New York 10523
Technical Data:
Nominal K -factor
Thread
Size
Temperature Rating
Maximum
Ambient
Maximum Water
Working Pressure
Sprinkler Identification
Number
us
Metric
Sprinkler
Cover
Umin
psi
bar
14x22
4.3x6.7
Temperature
102-152
(SIN)
8.0
115
3/a" NPT
1650F
135OF
1000F
175 P31
RA4762
132.5
19.1
or ISO 7-193/4
(74°C)
(57°C)
(38°C)
(12 bar)
35
Coverage Area
Max. Installed
Coverage Area
Width x Length
Deflector to Ceiling
Dimension
Min. Required
Flow Rate
Min. Required
Pressure
ft. x ft.
m x m
inches
mm
gpm
Umin
psi
bar
14x22
4.3x6.7
4-6
102-152
31
117.3
15.0
1,03
14x22
4.3x6.7
6-12
152-305
35
132.5
19.1
1,3
14x24
4.3x7.3
4-6
102-152
35
132.5
19.1
1,3
14 x 24
4.3 x 7.3
6-12
152 -305
39
147.6
1 23.8
1,6
16 x 16
4.9 x 4.9
4-12
102-305
26
98.4
1 10.6
0,7
16 x 18
4.9 x 5.5
4-12
102-305
29
109.8
13.1
0,9
16x20
4.9x6.1
4-12
102-305
32
121.1
16.0
1,1
16 x 22
4.9 x 6.7
4-12
102-305
36
136.2
20.2
1,4
16 x 24
4.9 x 7.3
4-12
102-305
39
147.6
23.8
1,6
18x18
5.5x5.5
4-12
102-305
33
124.9
17.0
1,2
18 x 20
5.5 x 6.1
4-12
102-305
36
136.2
20.2
1,4
18x22
5.5x6.7
4-12
102-305
40
151.4
25.0
1,7
Approval Type
Quick Response Extended Coverage - Light Hazard Horizontal Sidewall.
Minimum spacing between sprinklers - 8 feet (2.4m).
Install below smooth, flat, horizontal ceilings only AS DEFINED BY NFPA 13.
2-3/8" tl/B MAXIMOM
[60.3 ti2.m]
FACE OF FITTING TO WALL
DIMENSION
DEFLECTOR ORIENTATION TAB
CEILING
DEFLECTOR ORIENTATION TAB
4" TD 12"
[101.6 TO 3048((]
TOP OF DEFLECTOR
0 B
RECOMMENDED
3/8" R..
® ® e
WALL HOLE -
__ - - __
_- [9511]
116-
DAM EB
02
1 08
[66. MlA]
PUS. ON PULL OFF
FAT COVERPATE
3/4"-14 NP
FRONT Vlf'N
PUSH ON/PULL OFF COVERPAIE REMOUEO
3/16"
14 BUY] BUY]1/4
NOTE DIMENSIONS IN BRACKETS ARE IN IAM
614(1
AOJ 5/MEN
figure
2.
Maintenance
Model G6-80 Concealed Sprinklers should be inspected
and maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other clean-
ing fluids. Remove dust by using a soft brush or gentle
vacuuming. Replace any sprinkler or cover plate assem-
bly, which has been painted (other than factory applied) or
damaged in any way. A stock of spare sprinkler and cover
plate assemblies should be maintained to allow quick re-
placement of damaged or operated sprinklers. Prior to in-
stallation, sprinklers should be maintained in their original
cartons and packaging until used to minimize the potential
for damage to sprinklers that would cause improper opera-
tion or non -operation.
Model 136-80 Concealed Quick Response
Extended Coverage Light Hazard Horizontal
Sidewall Sprinkler Specification
Sprinklers shall be quick -response extended coverage
sprinklers that are cULus Listed for use in Light Hazard oc-
cupancies. Sprinklers to be of bronze frame construction
with brass cover plate and copper alloy retainer flange as-
sembly. Water seal assembly shall consist of a PTFE coated
Belleville spring washer and machined brass cup contain-
ing no plastic parts. Method of attaching the cover plate to
the sprinkler cup shall be a push -on and pull -off design al-
lowing a 1/4" cover plate adjustment. Sprinklers shall have a
nominal K -factor of 8.0 (115 metric). Sprinkler temperature
rating shall be 165°F (74°C) with a cover plate temperature
rating of 135T (57°C). Sprinklers shall be capable of a max-
imum coverage area of 16 ft. x 24 ft. (4.9 m x 7.4 m) or 18
ft. x 22 ft (5.5 m x 6.7 m), with a minimum lateral spacing of
8 ft. (2.4 m). Rated working pressure shall be 175 psi (12,0
bar). A plastic protective cap shall be provided and fac-
tory installed inside the sprinkler cup to protect the sprinkler
from damage, which could occur during construction before
the cover plate is installed. Installation threads shall be [1 -
inch NPT] [ISO 7-R3/4]. Cover plate finish: [Chrome] [White]
[Custom Color— specify]. Extended Coverage Concealed
horizontal sidewall sprinklers shall be Reliable Model 36-80.
SIN RA4762 (Bulletin 047).
Ordering Information
Specify:
1. Sprinkler: Model 36-80
2. Model G6 Cover Plate Finish
Installation Wrench
Model G6 Sprinkler Wrench
Installation Aid
A protective plastic cap is included for use during instal-
lation.
Cover Plate Finishesttl
Standard Finishes
Chrome
White Paint
Special Application Finishes
Bronze
Black Paint
Flat White Paint
(1) Other colors and finishes are available. Consult factory for details.
Note: Paint or any other coatings applied over the factory
finish will void all approvals and warranties.
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
Reliable Automatic Sprinkler Co., Inc
(800) 431-1588
Sales Offices
(800) 848-6051
Sales Fax
(914) 829-2042
Corporate Offices
www.reliablesprinklencom
Internet Address
®
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 06/19 P/N 9999970456