TEST 8a BALANCE
TEST AND BALANCE
REPORT
PROJECT: AERIE / OFFLINE BY AERIE
LOCATION: 363 NEWPORT CENTER DRIVE, NEWPORT BEACH, CA 92660
REPORT DATE: MARCH 1 S, 2022
CONTRACTOR: AC ALL STAR
ARCHITECT:
ENGINEER:
CORTLAND MOROAN
Y V KULKARNI
�I
JAMES CONBOV
CERTIFICATION
3504
-IV. 3l3V22
Val
James Conboy
Supenoi Tes(nnO Babnce
TABB Supervisor
191099607E
MuO 31, 2023
e..uma. aaiospozz
861 E LEADORA AVENUE, GLENDORA CA 91741
TEL: 626.771.1012 SITE: WWW.SUPERIORTAB.COM
EMAIL: SUPERIORTAB@GMAIL.COM
INSTRUMENTATION:
DIGITAL MANOMETER
FLowHooD
TACHOMETER
DIGITAL VOLT -AMP METER
ROTATING VANE ANEMOMETER
THERMOMETER
DESCRIPTION OF TERMS:
SHORTRIDGE ADM-B6OC
SHORTRIDGE DIGITAL FLOWHOOD
EXTECH 461 B91
FLUKE 322
EXTECH AN31 ❑
FLUKE 5211
AK-
FREE AREA OF REGISTER, IN SQUARE FEET
ATM-
ATMOSPHERIC PRESSURE
CD-
CEILING DIFFUSER, SUPPLY
CE-
CEILING REGISTER, EXHAUST
CFM-
CUBIC FEET PER MINUTE
OR-
CEILING REGISTER, RETURN
DD-
DIRECT DRIVE MOTOR
FH-
READINGS TAKEN WITH FLOWHOOD, NO AK FACTOR
FLA-
FULL LOAD, AMPERAGE
FPM-
FEET PER MINUTE
FR-
FLOOR REGISTER, SUPPLY
FRR-
FLOOR REGISTER, RETURN
GPM-
GALLONS PER MINUTE
HP-
HORSE POWER
LD-
LINEAR DIFFUSER, SUPPLY
LR-
LINEAR REGISTER, RETURN
N/A-
NOT AVAILABLE OR NOT APPLICABLE
NL-
NOT LISTED
NVL-
NO VALID LOCATION
OSA-
OUTSIDE AIR
PSIG-
POUNDS PER SQUARE INCH, READ BY GAUGE
PSP-
PERFORATED SUPPLY PLENUM
RPM-
REVOLUTIONS PER MINUTE
SF-
SERVICE FACTOR, AMPERAGE
SP-
STATIC PRESSURE, IN INCHES OF WATER
SWE-
SIDE -WALL REGISTER, EXHAUST
SWR-
SIDE -WALL REGISTER, RETURN
SWS-
SIDE -WALL REGISTER, SUPPLY
TP-
THERMALLY PROTECTED, AMPERAGE RELATED RATING
VEL-
VELOCITY (FEET PER MINUTE)
AP-
DIFFERENTIAL PRESSURE (INCHES OF WATER OR PSI)
I
UPERIOR
Y O TEST & BALANCE
Fan Test Report
Project: Aerie / Offline by Aerie - Newport Beach
363 Newport Center Drive, Newport Beach, CA 92660
RTU-2
Location / Area Served
Roof
I Sales Area
Roof
I Sales Area
Manufacturer / Model
Carrier
I SDHCQDOMfiSAOAOGO
Cartier
I SOMM08MMMAGG0
Serial Number
23191330437
2319P30436
Motor Make
Marathon
Marathon
Motor HP / RPM / Frame
2.9
1670
56HZ
2.9
1670
56HZ
Volts / Phase / Hertz
208
3
60
208
3
60
F.L. Amps / S.F.
6.7
1.15
6.7
1.15
Motor Sheave Diam./Bore
VL44 x 5/8"
VL44 x 6/8"
Fan Sheave Diam./Bore
AFD74 x 1"
AFD74 x 1"
Belt Size / # of Belts
A48
1
A48
1
Sheave Closed %
30%
20%
Sheaves Center to Center
16118"
161/2"
TEST DATA
DESIGN
ACTUAL
DESIGN %
DESIGN I
ACTUAL
DESIGN %
DESIGN
ACTUAL
DESIGN %
Total Fan Airflow
3500
NVL
3500
NVL
Total Outlet Airflow
3575
3443
96%
3425
3427
100%
Return Airflow
2760
2619
950/6
2610
2590
99%
Minimum Outside Air
815
824
101%
815
837
103%
S.P. Supply /Return.
0.24"/0.52"
r
0.24 /0.51"
'
External S.P.
1.00"
0.76"
1.00"
0.75
Total S. P.
Fan Speed (RPM)
851
-
-
836
Voltaae
208
20212011200
..
208
202/202/201
NOTES:
1
�PRIO
Y O TEST Be BALANCE
Air Distribution Test Report
Project: Aerie / Offline by Aerie - Newport Beach
363 Newport Center Drive, Newport Beach, CA 92660
SYSTEM NAME /
AREA SERVED
OUTLET
DESIGN
PRELIMINARY
FINAL
% of
DESIGN
Note
#
#
TYPE
SIZE
AK
VEL
FLOW
VEL
FLOW
VEL
FLOW
RTU-1
Sales Area
1
CD
18" Round
FH
-
275
-
255
93%
Sales Area
2
CD
18" Round
FH
-
275
-
302
110%
Sales Area
3
CD
18" Round
FH
-
275
-
296
1 108%
Sales Area
4
CD
18" Round
FH
-
275
-
276
100%
Sales Area
5
CD
18" Round
FH
275
-
261
95%
Sales Area
6
CD
18" Round
FH
-
275
-
254
92%
Sales Area
7
CD
18" Round
FH
275
-
273
99%
Sales Area
8
CD
18" Round
FH
275
-
259
94%
Sales Area
9
CD
18" Round
FH
-
275
-
252
92%
Sales Area
10
CD
18" Round
FH
-
275
-
263
96%
Sales Area
11
CD
18" Round
FH
I -
275
-
247
90%
Stockroom
12
CD
24" x 24'
FH
-
200
-
181
91%
Fitting Rooms
13
CD
18" Round
FH
-
175
-
158
90%
Fitting Rooms
14
CD
18" Round
FH
-
175
-
166
95%
3575
3443
96%
Outside Air
OSA
Intake
35" x 18.5"
4.50
181
815
223
1004
183
824 1
101%
NOTES:
Notes correspond to
Note # above.
1
2
3
4
2
UPERIOR
Jr\I\\O TEST e< BALANCE
Air Distribution Test Report
Project: Aerie / Offline by Aerie - Newport Beach
363 Newport Center Drive, Newport Beach, CA 92660
SYSTEM NAME /
AREA SERVED
OUTLET
DESIGN
PRELIMINARY
FINAL
% of
DESIGN
Note
#
#
TYPE
SIZE
AK
VEL
FLOW
VEL
FLOW
VEL
FLOW
RTU-2
Sales Area
1
CD
18" Round
FH
-
275
-
296
108%
Sales Area
2
CD
18" Round
FH
-
275
-
272
99%
Sales Area
3
CD
18" Round
FH
-
275
-
253
92%
Sales Area
4
CD
18" Round
FH
-
275
-
263
96%
Sales Area
5
1 CD
18" Round
FH
-
275
-
277
101%
Sales Area
6
CD
18"Round
FH
-
275
-
251
91%
Sales Area
7
CD
22" Round
FH
-
600
-
586
98%
Stockroom
8
CD
24"x24"
FH
-
500
-
541
108%
Fitting Rooms
9
CD
18" Round
FH
-
300
-
320
107%
Fitting Rooms
10
CD
18" Round
FH
-
300
-
286
95%
Break Area
11
CD
24" x 24"
FH
-
75
-
82
109%
3425
3427
100%
Outside Air
OSA
Intake
35" x 18.5'
4.50
181
815
142
639
186
837 1
103%
EF-1
Restroom
1
CE
9" x 11"
FH
85
-
87
102%
NOTES:
Notes correspond to
Note # above.
1
2
3
4
3
4
0
COMPLIES
Enforcement Agency Use: Checked by/Date
SHUT-OFF LIGHTING CONTROL ACCEPTANCE DOCUMENT
Intent: This document is used to demonstrate compliance with acceptance requirements in §130.4(a)4 and Reference Nonresidential
Appendix NA7.6.2 for shut-off lighting controls. Attach additional sets of pages 1 through 2, as required, for all controls that must be
tested.
Indicate all types of shut-off controls tested for this project:
f Automatic time switch lighting controls (Sections A-1 and B-1 of this document should be
completed)
17 Occupant sensing lighting controls (including occupant sensors, partial -ON occupant sensors, partial -OFF occupant
sensors, and/or vacancy sensors) (Sections A-2 and B-2 of this document should be completed)
A-1. Automatic Time Switch Lighting Control Construction Inspection (NA7.6.2.4)
r a. Automatic time switch controls are programmed with acceptable weekday, weekend, and holiday (if applicable)
schedules. (NA7.6.2.4(a), §110.9(b)SAii, §130.1(c)lA, §130.1(c)4)
Iw b. Document for the owner weekday, weekend, and holidays schedules, as well as all set-up and preference program
settings. (NA7.6.2.4(b))
W c. The correct time and date are properly set in the time switch. (NA7.6.2.4(c))
r d. The battery backup (if applicable) is installed and energized. (NA7.6.2.4(d), §110.9(b)l)
Iw e. Override time limit is no more than 2 hours. (NA7.6.2.4(e), §110.9(b)SAi, §130.1(c)3B) OR The automatic time switch
control's override time is exempt from the 2-hour limit. (EXCEPTION to §130.1(c)3B)
W f. Override switches remote from area with controlled luminaires have annunciator lights. (NA7.6.2.4(f), §130.1(c)3A,
§130.1(a)) OR The manual override switch is exempt from being in the same enclosed area with the lighting it controls.
(EXCEPTION 1 to §130.1(a)2)
Construction Inspection Compliance(rJ Complies)'; Does Not Comply
CAL *' TP CaIlfornid'Advanced aphting
Cantiolsrr2fntng Program CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance This is page 1 of 5
B-1. Automatic Time Switch Lighting Control Functional Testing (NA7.6.2.5)
Confirm compliance (Y - yes / N - no) for the control being tested.
Building: aerie Floor: 1 Room: Back of House Control: Automatic Time Switch
Step 1: Simulate Occupied Condition. (NA7.6.2.5(a))
W
a. All lights can be turned on and off by their respective area control switch. (NA7.6.2.5(a)l)
F
b. The switch only operates lighting in the enclosed space (ceiling -height partitioned area) in which the switch is located.
(NA7.6.2.5(a)2, §130.1(c)1C)
r
c. For the area controlled by an automatic time switch control with a time override located in and for the area, the lighting can be
turned on manually by initiating the time override. The lighting is configured to remain on for no more than 2 hours, unless the area
is exempt from the 2-hour time override limit. (NA7.6.2.5(a)3, §110.9(b)lAi, §130.1(c)3B, EXCEPTION to §1301(c)3B)
r
d. For the area controlled by an automatic time switch control with an automatic holiday shut-off feature, the lighting in the area
can be turned off automatically by initiating the holiday shut-off. (NA7.6.2.5(a)4, §110.9(b)lAii, §130.1(c)4) OR The automatic
time switch control is exempt from incorporating an automatic holiday shut-off feature. (EXCEPTION to §130.1(c)4)
r
e. For the area controlled by an automatic time switch control with manual -on mode configured, the lighting in the area can be
turned on manually when it is manually activated. (NA7.6.2.5(a)5, §130.1(c)IE) OR The automatic time switch control does not
include or utilize a manual -on mode. (§130.1(c)IE)
Step 2: Simulate unoccupied condition. (NA7.6.2.5(b))
r
a. All non-exempt lighting turns off in accordance with the programmed time switch schedules. (NA7.6.2.5(b)1, §130.1(c)lA)
r
b. Manual override switch allows only the lights in the enclosed space (ceiling height partitioned) where the override switch is
located to turn on or remain on until the next scheduled shut off occurs. (NA7.6.2.5(b)2, §130.1(c)1C, §130.1(c)3)
Functional Testing Compliance:
Does Not Comply
i
CALGoTP Calltamtsivilanoi-Wimm
CaMitllshelningPmg2m`I
I CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Tllis is page 2 of
cEIZT1[TTc_1TE OF ACCEPTA.NCF cA-1il-oz _�
L�•_hvas comrw
Project Name:Auie Ne�cpart Beach
Evfarcemeat Aaeacv: CrfY OF NERTORT BEACH JJPe Number 2021-0338
Project Ad&r w: 363 Na .A Cemx Dnce
City: Newport Beach Zip Coda: 92633
A-2. Occupant Sensing Lighting Control Construction Inspection (NA7.6.2.2))
W a. Occupant sensors have been located to minimize false signals. (NA7.6.2.2(a))
r17 b. Occupant sensors are located no closer than four (4) feet from any HVAC diffuser. (NA7.6.2.2(b))
r c. Passive infrared sensor pattern does not enter into adjacent zones. (NA7.6.2.2(c))
r d. Occupant sensors do not encounter any obstructions that could adversely affect desired performance. (NA7.6.2.2(d))
W e. Ultrasonic occupant sensors do not emit audible sound. (NA7.6.2.2(e), §110.9(b)681i)
Construction Inspection Compliance: M Complies(, Does Not Comply
B-2. Occupant Sensing Lighting Control Functional Testing (NA7.6.2.3)
Confirm compliance (Y - yes / N - no) for the control being tested.
Building: aerie Floor: 1 Room: Stock Rm Control: Occ Sensors
IV
Control is representative of sample. (NA7.6.2.3) If sampling method is used, attach a page listing untested controls in sample.
Step
1: Simulate an unoccupied condition. (NA7.6.2.3(a))
ra
a.
Lights controlled by occupant sensing control turn off or partially off, if applicable, within a maximum of 20 minutes from start of
an unoccupied condition. (NA7.6.2.3(a)1, §110.9(b)4A)
In the partial off state, partial -OFF occupant sensors automatically reduce lighting power by at least 50% (§130.1(c)6A-C,
§130.1(c)7A), OR:
• For metal halide or high pressure sodium lighting in warehouses, automatically reduce lighting power by at least 40%
(EXCEPTION 2to §130.1(c)6A).
• In aisle ways and open areas in warehouses in which the installed lighting power is 80% or less of the value allowed under
the Area Category Method, automatically reduce lighting power by at least 40% (EXCEPTION 1 to §130.1(c)6A).
• In corridors and stairwells in which the installed lighting power is 80% or less of the value allowed under the Area Category
Method, automatically reduce lighting power by at least 40% (EXCEPTION to §130. 1(c)7A).
Occupant sensing controls in parking garages, parking areas, and loading and unloading areas have at least one control step
between 20 to 50% of design lighting power (§130.1(c)7B). OR Occupant sensing controls for metal halide luminaires with a lamp
plus ballast mean system efficacy of 75 lumens per watt in parking garages, parking areas, and loading and unloading areas have
at least one control step between 20 to 50% of design lighting power (EXCEPTION to §130.1(c)7B).
r
b.
The occupant sensing control does not trigger
p g gger a false "on" from movement in an area adjacent to the controlled space or from
HVAC operation. (NA7.6.2.3(a)2)
W
c.
Signal sensitivity is adequate to achieve desired control. (NA7.6.2.3(a)3) For library book stacks or warehouse aisles, activity
beyond the stack or aisle shall not activate the lighting in the stack or aisle. (§130.1(c)6A, §130.1(c)6B)
Step
2: Simulate an occupied condition. (NA7.6.2.3(b))
r
a.
Status indicator or annunciator operates correctly. (NA7.6.2.3(b)Y, §110.9(b)4C)
b.
Immediately upon an occupied condition (NA7.6.2.3(b)2):
• Lights controlled by an occupant sensor or a partial -OFF occupant sensor turn on; OR:
• A vacancy sensor indicates a space is "occupied" and lights may be turned on manually; OR:
• The first stage of a partial -ON occupant sensor automatically activates between 50 to 700/c of the lighting.
(§130.1(c)SA)OR:
After the first stage occurs for partial -ON occupant sensors, manual switches allow an occupant to activate the alternate set of
lights, activate 100% of the lighting power, and manually deactivate all of the lights.
Functional Testing Compliance:
�, TF' CaliPomiAduanced ldph11
Hng
r Coi hilaatningRmli am
CA BH ld n Energy Efficiency Standards - 2019 Nonresidential Compliance Thus is page 3 of 5
OF
M Compliesr, Does Not Comply
Celltom1am-li edLighdn@ I
�iTr CaMrors7afrinAt9!dA�m
CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance This is page 4 of 5
CERTIF gkTE�OFACCEP XNCE NRCA-LTI-02-A
Loup, Comral
PrajM Yame: derie Newport Beach E@brcement Agency: CITY OF Nn?oRT BEACH
Permit Number 1021-0558
ProjMAddce u: 363 Nenmort Center Dtnx City: Newport Beach
Zip Cade: 92658
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
I certify that this Certificate of Acceptance documentation is accurate and complete.
Documentation Author Company Name
Harry Stallmach Adec, Inc
Name
Address City/State/Zlp
2545 W. 237ih Street, Suite M Torrance, CA 90505
Phone CEA/ATT Certification
(330)_ 0-6399 Identification (if TC-AS13033
applicable)
Author Signature
Date of Signature: 03/17/2022
FIELD TECHNICIAN'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided an this Certificate of Acceptance is true and correct.
2. I am the person who performed the acceptance verification reported on this Certificate of Acceptance (Field Technician).
3. The construction or installation identified on this Certificate of Acceptance complies .vith the applicable acceptance requirements Indicated in the plans and
specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference
Nonresidential Appendix NA].
4. I have confirmed that the Certificate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and
signed by the responsible builder/installer and has been posted or made available with the building permits) issued for the building.
Field Technician Name Harry Stallmach Company Name Adec, Inc
Address: City/State/Zip
2545 W. 237th Street, Suite M Torrance, CA 90505
Phone ATT Certification
(310)540-6399 Identification TC-A813033
Positio wi Company CEO Field Technician Signature
Date of Signature:
03/17/2022
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this
Certificate of Acceptance.
2. I am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction
or Installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the
declarations in this statement (responsible acceptance person).
3. The information provided on this Certificate of Acceptance substantiates that the construction or installation identified on this Certificate of Acceptance complies
with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance
requirements and procedures specified in Reference Nonresidential Appendix NA7.
4. I have confirmed that the Certificates) of installation for the construction or installation identified on this Certificate of Acceptance has been completed and is
posted or made available with the building permits) issued for the building.
5. I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the
building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certifcate of Acceptance is
required to be included with the documentation the builder provides to the building owner at occupancy.
Responsible Acceptance Harry Stallmach Company Name Adec, [nc
Person Name
Address: City/State/Zip
2545 W. 237th Street, Suite M Torrance, CA 90505
Phone CSLB License
(310)540-6399 640304
Position with C pony CEO Responsible Acceptance Person Signature
(Title}
//A/O
Date of Signature:
03/17/2022