HomeMy WebLinkAboutX2020-2830 - CalcsI.DE
723 ! M Claudina Street `
Anaheim. CA 92805 pE�
Date:
Project: o\0
Job #: 20-124
A
E wlqtR%
Building Division
JUL 2 7 2020
By: D.E.A.
Code: 2019 California Building Code
Notice: The content of these documents is understood to be an expression of
professional opinion. It is based on our best knowledge, information and belief.
No guarantee or warranty is expressed or implied.
LWGINEIJESIGNENGMER" . . . . . .. . . . . . . ... . . . . . . .. .
Design Loads
Roof Load
Slope per Foot
Roofing, Asphalt Shingles
Sheathing,15/32"
Framing, roof trusses
Insulation, R30
Framing, for Ceiling
Finish, 5/8" dw
Mech. & Elect.
Total Dead Load
Live Load
Total Load
Floor Load Tvp.
Finish
Sheathing, 1 1/8"
Framing, 14" TJI 210@16' o/c
Insulation, R30
Finish, 5/8" dw
Mech. & Elect.
Mic
Total Dead Load
Live Load
Total Load
4.00 : 12
s 6.00 psf
s 1.66 psf
s 2.28 psf
s 0.38 psf
1.28 psf
1.90 psf
0.50 psf
14.00 psf
20.00 psf
34.00 psf
4.00 psf
4.00 psf
3.12 psf
0.38 psf
3.00 psf
0.50 psf
1.00 nsf
16.00 psf
40.00 psf
56.00 lost
Exterior Wall
Stucco, 7/8"
Sheathing, 3/8"
Framing
Insulation
Finish, 1-5/8" dw
Item
Allowance
Total Dead Load
Interior Wall
Finish, 1-5/8" dw
Sheathing, 3/8"
Framing
Insulation
Finish, 1-5/8" dw
Item
Allowance
Total Dead Load
9.00 psf
1.25 psf
2.26 psf
0.15 psf
2.80 psf
0.00 psf
0.54 psf
16.00 psf
2.80 psf
1.25 psf
1.44 psf
0.15 psf
2.80 psf
1.00 psf
0.56 psf
10.00 psf
BEAM 01
L = 12.50 ft.
Loads: TL FLL+DL DL At To Load Derivation:
w1,plf= 563 263 263 0.00 12.50 ft. Roof15+Bm Wt
R1 =
3518 1643
1643 lbs
V reduced at
Neither Support
4749 2709
R2 =
3518 1643
1643 lbs
Vmax ---->
0 lbs
3518 lbs
Try:
At x =
6.25 ft V,x =
0 lbs
b =
M =
131.9 in -kips
To
Try:
P
LDF = 1.25
A =
39.38 inA2
Fv= 363
b =
3.5 in
Case: 1
Total Load
ps
CL =
1.00
d =
9.25 in
LDF = 1.25
E,min = 987
ks
A =
32.38 inA2
Fv= 363
psi
fv=
163 psi
45.0%
S =
49.9 inA3
Fb = 3731
psi
fb =
2643 psi
70.8%
1 =
231 inA4
E = 2000
ksi
d,TL =
0.51 in L /
292
E,min = 987
ksi
d,LL =
0.27 in L /
548
BEAM 02
L =
16.00 ft.
Loads:
TL FLL+DL
DL At
To
Load Derivation:
w1,plf=
794 454
364 0.00
16.00 ft.
Roof`17+Ceiling Joist*9+Bm Wt
R1 =
6351 3631
2911 lbs
V reduced at
Neither Support
R2 =
6351 3631
2911 lbs
Vmax ---->
6351 lbs
At x =
8.00 ft V,x =
0 lbs
M =
304.9 in -kips
Try:
P
b =
3.5 in
Case: 1
Total Load
CL =
1.00
d =
14.00 in
LDF = 1.25
A=
49.00 inA2
Fv= 363
psi
fv=
194 psi
53.6%
S =
114.3 inA3
Fb = 3563
psi
fb =
2666 psi
74.8%
1 =
800 inA4
E = 2000
ksi
d,TL =
0.56 in L /
341
E,min = 987
ksi
d,LL =
0.31 in L /
629
BEAM 03
L = 12.00 ft.
Loads: TL FLL+DL DL At To
w1,plf= 792 452 362 0.00 12.00 ft
R1 =
4749 2709
2169 lbs
49.9%
R2 =
4749 2709
2169 lbs
63.4%
At x =
6.00 ft V,x =
0 lbs
420
Try:
P
in L/
773
b =
3.5 in
Case: 1
To
d =
11.25 in
LDF = 1.25
A =
39.38 inA2
Fv= 363
ps
S =
73.8 inA3
Fb = 3651
ps
I =
415 inA4
E = 2000
ks
E,min = 987
ks
Load Derivation:
Roof 17+Ceiling Joist*9+Bm Wt
V reduced at Neither Support
Vmax ----> 4749 lbs
M = 171.0 in -kips
tal Load CL = 1.00
fv=
181
psi
49.9%
fb =
2316
psi
63.4%
d,TL =
0.34
in Lf
420
d,LL =
0.19
in L/
773
3 1/2 x 9 1/4 PSL
3 1/2 x 14 PSL
3 1/2 x 11 1/4 PSL
0
BEAM 04
L=
Loads:
w1, plf =
P1,lbs =
R1 =
R2 =
Atx=
Try:
b=
d=
A=
S=
1=
12.00 ft.
TL FLL+DL DL At To
84 44 44 0.00 12.00 ft.
4749 2169 2169 2.50 ft.
4261 1979
1979 lbs
psi
1491 713
713 lbs
1689
2.50 ft V,x =
0 lbs at P1
d,TL =
P
in L/
580
3.5 in
Case: 1
To
11.25 in
OF = 1.25
39.38 inA2
Fv = 363
ps
73.8 iO3
Fb = 3651
ps
415 inA4
E = 2000
ks
E,min = 987
ks
Load Derivation:
Roof"2+Bm Wt
+BEAM 03
V reduced at Neither Support
Vmax ----> 4261 lbs
M = 124.7 in -kips
Tot Load CL = 1.00
fv=
162
psi
44.8%
fb =
1689
psi
46.3%
d,TL =
0.25
in L/
580
d,LL =
0.13
in L/
1090
3 1/2 x 11 114 PSL
a—
------------------
I I
I I
I I
I I
T1
4
508 De Anza Dr, Corona Del Mar, CA 92625, USA
Latitude, Longitude: 33.5927175, -117.8611798
Se4ecdb`�/7ol
Or &pace
Five Crowns o
Tempera rllyt closed -
1 'y
o a,
o Y
to -
'-Seams Fa
oypO�d m <<� � kora
Ga p a° oI
cA a
i, �¢F day
j.C70Ggl2o
0\1"ooyRa,. nPRa
Date
Design Code Reference Document
Risk Category
Site Class
7/19/2020,10:51:58 PM
ASCE7-16
II
D - Default (See Section 11.4.3)
OSHPD
SUr`e
0
Map data 02020
Type
Value
y�
Description
,.
Ss
1.343
MCER ground motion (for 0.2 second period)
Sr
0.476
MCER ground motion. (for 1.0s period)
SMs
1.612
Site -modified spectral acceleration value
Sur
null -See Section 11.4.8
Site -modified spectral acceleration value
SDS
1.074
Numeric seismic design value at 0.2 second SA
Sm
null -See Section 11.4.8
Numeric seismic design value at 1.0 second SA '..
Type
Value
Description '.
SDC
null -See Section 11.4.8
Seismic design category
F,
1.2
Site amplification factor at 0.2 second
Fv
null -See Section 11.4.8
Site amplification factor at 1.0 second
PGA
0.586
MCEc peak ground acceleration
FPGA
1.2
Site amplification factor at PGA
PGAM
0.703
Site modified peak ground acceleration
TL
8
Long -period transition period in seconds
I
SsRT
1.343
Probabilistic risk -targeted ground motion. (0.2 second)
SsUH
1.476
Factored uniform -hazard (2% probability of exceedance in 50 years) spectral acceleration
SsD
2.643
Factored deterministic acceleration value. (0.2 second)
S1RT
0.476
Probabilistic risk -targeted ground motion. (1.0 second)',
S1UH
0.516
Factored uniform -hazard (2% probability of exceedance in 50 years) spectral acceleration.
SID
0.825
Factored deterministic acceleration value. (1.0 second)
PGAd
i
1.064
Factored deterministic acceleration value. (Peak Ground Acceleration)
CRs
0.91
Mapped value of the risk coefficient at short periods
Type Value Description
CRi 0.922 Mapped value of the risk coefficient at a penod of 1 s '..
DISCLAIMER
While the information presented on this website is believed to be correct, SEAOC /OSHPD and its sponsors and contributors assume no
responsibility or liability for its accuracy. The material presented in this web application should not be used or relied upon for any specific application
without competent examination and verification of its accuracy, suitability and applicability by engineers or other licensed professionals. SEAOC /
OSHPD do not intend that the use of this information replace the sound judgment of such competent professionals, having experience and
knowledge in the field of practice, nor to substitute for the standard of care required of such professionals in interpreting and applying the results of
the seismic data provided by this website. Users of the information from this website assume all liability arising from such use. Use of the output of
this website does not imply approval by the governing building code bodies responsible for building code approval and interpretation for the building
site described by latitude/longitude location in the search results of this website.
Derivation of Lateral Strip Loads
Structure Geometry. Use Alternate ASD Load Combinations
Pitch: . ; a' / 12
1st story:ft. plate Podium: Ift. above grade
Long. Width= 'S�,'#jft Trans. Width = Vjmft
Mean Roof Height = 11.88 ft
Wind Load - per ASCE 7-16
Exposure: BEW
Kz = 0.85
0' to 15'
0.90
at 20'
0.95
at 25'
0.98
at 30'
1.01
at 35'
1.04
at 40'
q = .00256*Kz*Kzt*Kd *VA 2*Iw =
K,z interpolated for heights over 15'
L/B
h/L
CP
V= _ mph (3 -second gust)
Kzt = 1.0 Topographic Factor
Kd = 0.85 Directionality Factor
I,w = 1
21.76 * Kz
Longitudinal
Transverse
= 1.15
0.87
= 0.26
0.22
= 0.8
0.8
-0.5
-0.5
EM
EM
1.8
1.8
-1.2
-1.2
0= 18.435 degrees
at windward wall elements
at leeward wall elements
at windward sloping roof
at leeward sloping roof
at windward parapet walls
at leeward parapet walls
GC,pi = 0.18 gGC,pi = 3.3 psf Internal Press. (pos. & neg.)
G = 0.85 For Rigid Structures
m = 1.3 Wind Load Factor for Alternate ASD Loads
P = w * (q*G*Cp * q*GC,pi)
i
Seismic Load -Equivalent Lateral Force Procedure per ASCE 7-16
Site Class: $Assumed Occupancy Category
F,a= 0.85 SDS=2/3*F,a*Ss
Ss- ',ig SDS= 1.07
F,v=#N/A S,D1=2/3*F,v*S1
S,1 = Mg S,D1 = 0.54
Seismic Design Category. OD
.2*S,DS = 0.21 1+.2*S,DS/1.4 = 1.15 * D
Net Seismic D.L. Resisting Factor= .9-.2*S,DS/1.4 = 0.75 * D
I,e =
Determine Structure Period.
CA = 0.02 for light -framed buildings
x = 0.75
k = 1 Vertical Distribution Exponent
Seismic Response Coefficient:
P-11
C,base = S,D1 * I / RT
C,max = S,DS * I / R
C,min =.044*S,DS *I
Seismic Design Category E or F:
C,min = 0.5 *S1 *I/R
C's = [p]* C / 1.4
Reliability/Redundancy Factor:
E= [p]* C,s*W+.2*S,DS*D
R
h,n = 8.00 ft
T = 0.095 = C,t (h,n)AX
Longitudinal
Transverse
i.,� 1 s.ESsem �^ a, �MA
` 4 . amps "a4�'r;
0.872
0.872
0.165
0.165
0.047
0.047
--- >1 0.000 10.000 <---
Vs = 1 0.153 10.153
p -
Longitudinal
Transverse
i.,� 1 s.ESsem �^ a, �MA
` 4 . amps "a4�'r;
1.30
Derive Strip Loads:
Longitudinal Direction
RDL=ROOF DL
FDL=Floor DL
DDL=Ext,wall
WDL=Int,wall
L1
1
Story condition
d to ridges
d to ridge:
rs
D
/12
pitch:
4.0
/12
8.00
ft plt
from
w,trib:
13.67
s _ + _
46.50
h,avg =
12.00
ftfor
53.67
ft
Wind
--------
Windward Surface -----------
----------
Leeward Surface
-----------
h,bot
h,eff
h,top
h,bot h,eff Kz avg
Cp
h,top
h,bot
h,eff
Kz avg
Cp
5.67
Roof
12.00
8.00 4.00 0.8500
0.2
12.00
8.00
4.00
0.8500
-0.7
0.8500
Wall 1:
8.00
0.00 4.00 0.8500
0.8
8.00
0.00
4.00
0.8500
-0.5
180 plf
Seismic
Roof:
0.153 * ( +RDL*49+DDL*8*2+WDL*8*2)
wx
hx
wx*hx
factor
184 plf
Seismic
Distribution
wx
hx
wx*hx
factor
Seismic
Distribution
R
1200
8.00
9600
0.153
Transverse Direction
T1
1
Story condition
d to ridges
pitch:
4.0
/12
8.00
ft pit
from
w,trib:
z
h,avg =
13.67
It for
46.50
ft
Qd9
Wind
---------
Windward Surface -----------
----------
Leeward Surface
-----------
h,top
h,bot h,eff Kz avg
Cp h,top
h,bot
h,eff
Kz avg
Cp
Roof
13.67
8.00 5.67 0.8500
0.2 13.67
8.00
5.67
0.8500
-0.7
Wall 1:
8.00
0.00 4.00 0.8500
0.8 8.00
0.00
4.00
0.8500
-0.5
211 plf
Seismic
Roof:
0.153 * ( +RDL*53+DDL*8*2+WDL*8*2)
194 plf
wx
hx
wx*hx
factor
Seismic
Distribution
R 1264
8.00
10112
0.153
to
to
Line:
1 Wall: a b
c d
e f
L,wall:
14.00 ft total > E q D0 1,O QQ E O OO x 0 00
O D0 ObO r
V,w =
rt
2338 lbs = L1 R*26/2
=
2338 lbs
L1R*16/2
V,s(f) =
2394 lbs (flexible diaphragm)
=
1439 lbs
Sum and individual wall seismic loads W rigid diaphragm:
V,abv
V,s(r) _
v,wall =
0 lbs ----> 0 0
171 plf vs = 171.03 plf-->
0 0
85.513 Ib/nail
0 0§,
e,n = 0.0031 ter^
L, top plt =
0.00 ft
Wall 1:
4.00 ft Fdtn Hldn
V,abv
V,s(r) =
Ht =
8.00 ft h/w = 2.00
OK *
######
OTM =
5472 ft-lbs P = 1368
lbs
184 plf vs =
RM =
2419 ft-lbs = 0.747
Ib/nail
e,n = 0.0039
Uplift =
763 lbs
4.00 ft
r(Tt n7 H I d n
Wall 2:
10.00 ftFdtn Hldn
Ht =
Ht =
8.00 ft h/w = 0.80
OK
OTM =
13680 ft-lbs P = 1368
lbs
P = 1472
RM =
15120 ft-lbs =
RM =
Uplift =
-144 lbs
Line:
2 Wall:
a b
c
d
e f
L,wall:
8.00 ft total ->
V,w =
1439 lbs =
L1R*16/2
=
1439 lbs
V,s(f) =
1473 lbs (flexible
diaphragm)
Sum and individual wall seismic loads W rigid diaphragm:
V,abv
V,s(r) =
0 lbs ---->
0 0
0
0
0 0
v,wall =
184 plf vs =
184.18 plf-->
92.091
Ib/nail
e,n = 0.0039
Wall 1:
4.00 ft
r(Tt n7 H I d n
Ht =
8.00 ft
h/w = 2.00
* OK *
######
OTM =
5888 ft -lbs
P = 1472
lbs
RM =
1382 ft -lbs =
0.747
Uplift =
1126 lbs
Line: 3 Wall: a b c d e f
L,wall: 12.00 ft total -> a
V,w = 1474 lbs = T1R*14/2
1474 lbs
V,s(f) = 1358 lbs (flexible diaphragm)
Type #7
A35's 24 in o/c
HDU2 Holddown
OK at corner condition
No Holddowns req'd
Type #7
HDU2 Holddonw
OK at corner condition
Sum and individual wall seismic loads w/ rigid diaphragm: V,abv
V,s(r) = 0 lbs ----> 0 0 0 0 0 0
v,wall = 123 plf v,s = 113.17 plf--> 56.585 Ib/nail e,n = 0.0009 , Type #7
Wall 1: 12.00 ft FF -d -t —n -I H I d n
Ht = 8.00 ft h/w = 0.67 OK * ######
OTM = 11808 ft -lbs P = 984 lbs AB's: 5/8 in 72 in o/c
RM = 14515 ft -lbs = 0.667 No Holddowns req'd
Uplift = -226 lbs
IRE
723 % N. Claudina Street
Anaheim, CA 92805
Date:
December 05, 2020
Project:
Structural engineering for House Remodel.
Subject:
Calculations for Field Revision.
BUILDING DIV
DC.0 P
0
Code:
Notice:
IMAGINE DESIGN ENGINEER
Job #: 20-124
2019 California Building Code
The content of these documents is understood to be an expression of
professional opinion. It is based on our best knowledge, information and belief.
No guarantee or warranty is expressed or implied.
Design Loads
Roof Load
Exterior Wall
Slope per Foot
4.00: 12
Stucco, 7/8"
Roofing, Asphalt Shingles
s 6.00 psf
Sheathing, 3/8"
Sheathing, 15/32"
s 1.66 psf
Framing
Framing, roof trusses
s 2.28 psf
Insulation
Insulation, R30
s 0.38 psf
Finish, 1-5/8" dw
Framing, for Ceiling
1.28 psf
Item
Finish, 5/8" dw
1.90 psf
Allowance
Mech. & Elect.
0.50 psf
Total Dead Load
Total Dead Load
14.00 psf
Live Load
20.00 psf
Interior Wall
Total Load
34.00 psf
Finish, 1-5/8" dw
Sheathing, 3/8"
Floor Load Tvo.
Framing
Finish
4.00 psf
Insulation
Sheathing, 1 1/8"
4.00 psf
Finish, 1-5/8" dw
Framing, 14"TJI210@16' o/c
3.12 psf
Item
Insulation, R30
0.38 psf
Allowance
Finish, 5/8" dw
3.00 psf
Total Dead Load
Mech. & Elect.
0.50 psf
Mic
1.00 psf
Total Dead Load
16.00 psf
Live Load
40.00 psf
Total Load
56.00 psf
9.00 psf
1.25 psf
2.26 psf
0.15 psf
2.80 psf
0.00 psf
0.54 psf
16.00 psf
2.80 psf
1.25 psf
1.44 psf
0.15 psf
2.80 psf
1.00 psf
0.56 psf
10.00 psf
BEAM 02
L =
16.00 ft.
Joist at 16 in oc
Loads.
Loads:
Loads:
TL FLL+DL
DL At
To
W1,plf=
Load Derivation:
95 95
W1,plf=
794 454
364 0.00
16.00 ft.
R1 =
Roof*17+Ceiling Joist*9+Bm Wt
P1,lbs =
851 401
401 8.00
ft.
R2 =
+BEAM 05 (4x12)
401 lbs
R1 =
6777 3832
3112 lbs
V reduced at
Neither Support
0 lbs
R2 =
6777 3832
3112 lbs
Vmax ---->
S
6777 lbs
At x =
8.00 ft V,x =
0 lbs at P1
3.5 in
M =
345.7 in -kips
CL =
Try:
P
11.25 in
LDF = 1.25
Cr =
1.00
A=
b =
3.5 in
Case: 1
Total Load
32 psi
CL =
1.00
d =
14.00 in
LDF = 1.25
623 psi
50.3% 4x12 DF #2
1=
415 inA4
A=
49.00inA2
F'v= 363
psi
fv=
207 psi
57.2%
S =
114.3inA3
F'b = 3563
psi
fb =
3024 psi
84.9% 3 1/2 x 14 PSL
I =
800 inA4
E = 2000
ksi
d,TL =
0.64 in L /
300
E,min = 987
ksi
d,LL =
0.35 in L/
556
4X12 FLUSH BEAM
L =
18.00 ft.
Joist at 16 in oc
Loads.
Loads:
TL FLL+DL
DL At
To
Load Derivation:
W1,plf=
W1,plf=
95 95
45 0.00
18.00 ft.
+Ceiling joist*5+Bm
Wt
R1 =
851 851
401 lbs
V reduced at
Neither Support
R2 =
R2 =
851 851
401 lbs
Vmax --->
851 lbs
At x =
At x =
9.00 ft V,x =
0 lbs
M =
46.0 in -kips
Try:
Try:
S
b =
b =
3.5 in
Case: 2
F,LL + DL
CL =
1.00 -
d =
11.25 in
LDF = 1.25
Cr =
1.00
A=
A=
39.38inA2
Fv= 225
psi fv=
32 psi
14.4%
S =
73.8 W3
Pb = 1238
psi fb =
623 psi
50.3% 4x12 DF #2
1=
415 inA4
E = 1600
ksi d,TL =
0.34 in L /
643
E,min = 580
E,min = 580
ksi d,LL =
0.18 in L/
1215
FLOOR JOIST REIFORCEMENT
L =
6.00 ft.
Joist at 16 in oc
Loads.
TL FLL+DL
DL At
To
Load Derivation:
W1,plf=
72 72
19 0.00
6.00 ft.
+Floor*1.33
R1 =
215 215
56 lbs
V reduced at
Neither Support
R2 =
215 215
56 lbs
Vmax --->
215 lbs
At x =
3.00 ft V,x =
0 lbs
M =
3.9 in -kips
Try:
S
b =
3 in
Case: 2
F, LL + DL
CL =
1.00
d =
3.50 in
LDF = 1.00
Cr =
1.15
A=
10.50inA2
F'v= 180
psi fv=
31 psi
17.1%
S =
6.1 inA3
F'b = 1553
psi fb =
633 psi
40.8% (2) 2x4 DF #2
1=
11 inA4
E = 1600
ksi d,TL =
0.12 in L/
590
E,min = 580
ksi d,LL =
0.09 in L/
796