CITY OF NEWPORT BEACH September 28, 2020
Building Department Project No. RJ186.2
100 Civic Center Drive
Newport Beach, CA 92660
Subject: COMPACTION REPORT FOR PLACEMENT OF FILL
WITHIN LIMITS OF RESIDENTIAL BUILDING PAD AT
110 36T" STREET
NEWPORT BEACH, CALIFORNIA
City of Newport Beach Grading/Building Permit #: X2019-4127
Associated References:
1. "Geotechnical Investigation for Proposed Residential Development Located at 110 36" Street, Newport
Beach, California," by EGA Consultants, Inc., dated May 17, 2019.
2. 'Precise Grading Plan for Frost Residence, 110 36'" Street, Newport Beach, CA 92663," by CivilScapes
Engineering, dated March 17, 2020.
3. "Foundation Plan, The Frost Families, 110 36'" Street, Newport Beach, CA 92663," by RCE Consultants,
Inc., dated June 20, 2019.
4. "Response to City Review Comments dated 1/18/2020 for Proposed Residential Development Located at
110 36" Street, Newport Beach, California," by EGA Consultants, Inc., dated March 24, 2020.
To City Building/Grading Officials:
In accordance with the City of Newport Beach building requirements, we are submitting this
compaction report for the grading of the subject building pad. This report includes the test
results performed at the subject lot during the placement of on -site soil material in the area of
the proposed residential building pad. The site earthworks operations were performed by the
sub -contractor, Tim Greenleaf Engineering, Inc.
Excavation and grading of the subject lot commenced on September 17, 2020 and was
complete by September 25, 2020. To date, site grading included the removal of the upper 3
feet of the old fill and native material located within the limits of the proposed building pad. The
lot was roughly divided into front and rear halves; excavated, and recompacted to bring the
entire lot to finished subgrade.
One Caterpillar 289D track loader was utilized for the purpose of compaction and grading
control. On site soils were moisture treated via a 2-inch diameter water hose during the grading
process to bring the moisture content to near -optimum. For cohesion -treatment, 3 (three)
pallets Portland Cement were blended into the newly -placed fill. Each pallet contains 40 bags
dry mix, each weighing 94 pounds and approximately 1.33 cubic yards.
Prior to the placement of fill, the excavation bottoms were inspected and approved by a
Certified Engineering Geologist employed by EGA Consultants. The exposed surface was
scarified, moisture conditioned and recompacted to a minimum of 90% relative compaction.
Field density test results are tabulated on Table 1, Summary of Field Density Tests.
All earthwork operations were performed under continuous observations by this firm and were
performed in accordance with geotechnical specifications outlined in the soils report by EGA
Consultants, Inc., dated May 17, 2019.
375-C Monte Vista Avenue • Costa Mesa, CA 92627 • (949) 642-9309 • FAX (949) 642-1290
The building pad was graded in accordance with the 2019 CBC and the City of Newport Beach
Building standards and are approved for construction. Based on our continuous observations
and testing, the subject and adjacent sites are not impacted by the site grading operations to
date.
This report includes the test results performed at the subject site during the placement of on -
site soil material in the area of the proposed building pad. Additional observations and
testing are required in areas to receive exterior improvements (driveway approach, patio
flatwork, etc.) capillary break, and utility trench backfill.
I certify that all rough grading work was done in compliance with the above -referenced Soils
Report and the work complies with City of Newport Beach grading regulations. All soils values
and geotechnical specifications outlined in the above -referenced soils report remain valid.
This opportunity to be of service is appreciated. If you have any questions, please call.
Very truly yours,
EGA Consultants, Inc.
DAVID A. WORTHINGTON CEG 2124 b
David A.
Principal Engineering Geologist cc 110.
hG212
ENGINEERING
cc: (1)Addressee T•4 GEOLOGIST C
(1) Ron Carroll. GC
PAD CERTIFICATION REPORT:
110 36" Street, Newport Beach, CA
Project No. RJ186.2
September 28, 2020
TABLE 1
SUMMARY OF MOISTURE DENSITY RELATIONSHIPS
(ASTM: D1556)
Sample
Depth
Dry
Moisture
Maximum
Optimum
Relative
Number/
Below
Density
Content
Density
Moisture
Compaction
Location
Grade
(PCF)
N
(PCF)
N
N
ft
FD-1
3.0
109.1
13.0
119.0
11.0
92
NWC of
Bldg. Pad
FD-2
2.0
110.4
12.5
119.0
11.0
93
N. Central
Bldg. Pad
FD-3
1.5
110.5
12.4
119.0
11.0
93
NEC of
Bldg. Pad
FD-4
0.5
111.6
12.3
119.0
11.0
94
Central
Bldg Pad
FD-5
3.0
107.7
13.1
119.0
11.0
91
SEC of
Bld .Pad
FD-6
2.0
109.0
12.5
119.0
11.0
92
SW Edge
Bldg. Pad
FD-7
1.0
110.1
12.2
119.0
11.0
93
S. Central
Bldg Pad
G
112.6
12.1
119.0
11.0
95
4Pad
G
111 A
12.6
119.0
11.0
94
G
111.6
12.3
119.0
11.0
94
FD-11
FG
112.8
12.5
119.0
11.0
95
Garage
Pad
r u = meta uensity I est
FG" = Finish Grade (Ground Level Pad)
PAD CERTIFICATION REPORT:
110 36" Street, Newport Beach, CA
Project No. RJ186.2
September 28, 2020
TABLE 2
SUMMARY OF MAXIMUM DENSITY TEST
(ASTM D 1557)
Sample
Maximum
Optimum
Location
Density
Moisture
PcfM.
Fill/Native - Beach Sands
119.0
11.0
Per Lab Results by G3SoilWorks
dated April 10, 2019
PAD CERTIFICATION REPORT:
110 36" Street, Newport Beach, CA
Project No. RJ186.2
September 28, 2020
R
f
consultants
CITY OF NEWPORT BEACH
Building Department
100 Civic Center Drive
Newport Beach, CA 92660
Attention: Jason Rudenick, City Building Inspector II
Subject: FINAL GRADING CERTIFICATE
HARDSCAPE COMPACTION, UTILITY TRENCH BACKFILL
AT NEW RESIDENTIAL PROPERTY LOCATED at
110 36T" STREET
NEWPORT BEACH, CALIFORNIA
City of Newport Beach Grading/Building Permit #: X2019-4127
Associated Documents:
engineering
geotechnical
applications
February 23, 2022
Project No. RJ186.2
1. "Geotechnical Investigation for Proposed Residential Development Located at 110 36th Street, Newport Beach,
California," by EGA Consultants, Inc., dated May 17, 2019.
2. "Precise Grading Plan for Frost Residence, 110 36th Street, Newport Beach, CA 92663," by CivilScapes Engineering,
dated March 17, 2020.
3. "Foundation Plan, The Frost Families, 110 36th Street, Newport Beach, CA 92663," by RCE Consultants, Inc., dated
June 20, 2019.
4. 'Response to City Review Comments dated 1/18/2020 for Proposed Residential Development Located at 110 36th
Street, Newport Beach, California," by EGA Consultants, Inc., dated March 24, 2020.
5. "Compaction Report for Placement of Fill Within Limits of Residential Building Pad at 110 36TM Street, Newport Beach,
California," by EGA Consultants, Inc., dated September 28, 2020.
To City Building/Grading Officials:
In accordance with the City of Newport Beach building and grading requirements, we are
submitting this final compaction report for the grading of the subject building pad, utility trench
backfill, and exterior improvements. The site earthworks operations were performed by the sub-
contractor, Tim Greenleaf Engineering, Inc.
Excavation and grading of the subject lot commenced on September 17, 2020 and was
complete by September 25, 2020. All flatwork subgrade was completed by February 15, 2022.
Site grading included the removal of the upper 3 feet of the old fill and native material located
within the limits of the building pad.
Prior to the placement of fill, the excavation bottoms were inspected and approved by a
Certified Engineering Geologist employed by EGA Consultants. The exposed surface was
scarified, moisture conditioned and recompacted to a minimum of 90% relative compaction.
One CAT 289D track loader, a jumping jack Wacker, and vibratory plates were utilized for the
purpose of compaction and grading control. On site soils were moisture treated via a 2-inch
diameter water hose during the grading process to bring the moisture content to near -optimum.
For cohesion -treatment, 3 (three) pallets Portland Cement were blended into the newly -placed
fill. Each pallet contains 40 bags dry mix, each weighing 94 pounds and approximately 1.33
cubic yards.
375-C Monte Vista Avenue • Costa Mesa, CA 92627 • (949') 642-9309 • FAX (949) 642-1290
All earthwork operations were performed under continuous observations by this firm and were
performed in accordance with geotechnical specifications outlined in the soils report dated May
17, 2019,
I certify that all grading and compaction work was done in compliance with the soils report for
this project and the work complies with City of Newport Beach grading regulations. All soils
values and geotechnical specifications outlined in the soils report remain valid.
Based on our continuous observations and testing, the subject and adjacent sites are not
impacted by the site grading operations to date.
This opportunity to be of service is appreciated. If you have any questions, please call
Very truly yours,
EGA Consultants, Inc. qk,—" "KO1
�5 David A. C
ttr� Worthington
DAVID A. WORTHINGTON CEG 2124
* No. CEG2124 ;
Principal Engineering Geologist/President cEFmnED
tP, ENGINEERING J
cc: (1)Addressee
(1) Ron Carroll, GC
FINAL COMPACTION REPORT:
110 361" Street, Newport Beach, CA
Project No. RJ 186.2
February 23, 2022
TABLE 7
SUMMARY OF MOISTURE DENSITY RELATIONSHIPS
(ASTM: D1556)
Sample
Depth
Dry
Moisture
Maximum
Optimum
Relative
Number/
Below
Density
Content
Density
Moisture
Compaction
Location
Grade
(PCF)
("/o)
(PCF)
(°/,)
(^/,)
ft
FD-1
3.0
109.1
13.0
119.0
11.0
92
NWC of
Bldg, Pad
FD-2
2.0
110.4
12.5
119.0
11.0
93
N. Central
Bldg. Pad
FD-3
1.5
110.5
12.4
119.0
11.0
93
NEC of
Bldg. Pad
FD-4
0.5
111.6
12.3
119.0
11.0
94
Central
Bldg Pad
FD-5
3.0
107.7
13.1
119.0
11.0
91
SEC of
Bldg. Pad
FD-6
2.0
109.0
12.5
119.0
11.0
92
SW Edge
Bldg. Pad
FD-7
1.0
110.1
12.2
119.0
11.0
93
S. Central
-Bldg Pad
FD-8
FG
112.6
12.1
119.0
11.0
95
SWC of
Bldg Pad
FD-9
FG
111.4
12.6
119.0
11.0
94
NEC of
Bldg Pad
FD-10
FG
111.6
12.3
119.0
11.0
94
S. Central
Bldg. Pad
FD-11
FG
112.8
12.5
119.0
11.0
95
Garage
Pad
FD-10
FG
111.3
12.5
119.0
11.0
94
Utility
Trench
Backfill
FINAL COMPACTION REPORT:
110 36TH Street, Newport Beach, CA
Project No. RJ 186.2
February 23, 2022
FD-11
FG
110.7
12.2
119.0
11.0
93
Utility
Trench
Backfill
FD-12
FG
111.0
12.2
119.0
11.0
93
Flatwork
FD-13
FG
114.1
12.0
119.0
11.0
96
Drive
Approach
"FD" = Field Density Test
"FG" = Finish Grade (Ground Level Pad)
TABLE 2
SUMMARY OF MAXIMUM DENSITY TEST
(ASTM D 1557)
Sample
Maximum
Optimum
Location
Density
Moisture
Pc
%-
Fill/Native - Beach Sands
119.0
11.0
Per Soils Report dated May 17, 2019
FINAL COMPACTION REPORT:
110 36' Street, Newport Beach, CA
Project No. RJ186.2
February 23, 2022
CITY OF NEWPORT BEACH
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING DIVISION
100 Civic Center Drive I P.O. Box 1768 1 Newport Beach, CA 92658-8915
www.newportbeachca.gov 1 (949) 644-3200
CIVII. ENGINEER'S CERTIFICATION FORM
From: Date:
CIVILSCAPES ENGINEERING, INC. 3/5/2022
28052 CAMINO CAPISTRANO, STE 213
LAGUNA NIGUEL, CA 92677
ATTENTION: GRADING ENGINEER, BUILDING DIVISION
LOT 17
GPC No.: 2851-2019 Tract/Subdivision/Lot No.:TR 3813 Rough: _Final: X
Project Names: 110 36TH, NEWPORT BEACH
Owner/Developer: CHRISTINA FROST
Type of Project: Notes:
Tract: X Drainage NEW SINGLE-FAMILY RESIDENCE
_ Commercial Other
Industrial
Yardage for Project: Notes:
50 Cut: _ Borrow: YARDAGE SHOWN HEREON IS ESTIMATED, NOT
0 Fill: 40 Export: ACTUAL; QUANTITIES WERE TAKEN FROM PLANS
180 OVER -EX AND 10 SHRINKAGE AND YARDAGE USED FOR PERMIT APPLICATION.
I hereby approve the grading for this project in accordance with my responsibilities under the
City Grading Code. I have inspected the project and hereby certify that all areas exhibit positive
surface flow to public ways or City approved drainage devices. The grading has been
completed: SUBSTANTIALLY in conformance with, GRADING PLAN with the following
changes to the approved grading plan.
Description of Changes:
QROF Ess ion
Company: CIVILSCAPES ENGINEERING, INC.
Name: WILLIAM. D. ROLPH c 76698 s
(print)
License No.: 76698 (RCEIA fv
F cAt \
Forms\Civil Engineer's Certification Form 9-13
CITY OF NEWPORT BEACH
F°Y. Community Development Department I Building Division
100 Civic Center Dr.1 P.O. Box 17681 Newport Beach, CA 92658
www.newportbeachca.cov 1 (949) 644-3200
��lnoKN��
CALGREEN DOCUMENTATION COMPLIANCE CERTIFICATION
ADDRESS: 1 M ?,6-" `. k- PERMIT NO.: =0Iq 1�7
THIS FORM SHALL BE COMPLETED AND SIGNED PRIOR TO REQUEST FOR FINAL BUILDING
INSPECTION. ONE COPY OF THIS FORM SHALL BE SUBMITTED TO THE BUILDING INSPECTOR AT
FINAL INSPECTION AND ONE SHALL BE PROVIDED TO THE BUILDING OWNER AS PART OF THE CAL
GREEN CERTIFICATION PACKAGE.
The following section shall be completed by a person with overall responsibility for the planning and
design portion of the project.
REQUIRED DOCUMENTATIONS PROVIDED TO THE PROPERTY OWNER(S)
04 Franchise Hauler for Construction/Demolition Waste (65% min. reuse of nonhazardous waste)
A VOC Contents Limitation
S. Formaldehyde Emissions Limitation
X T-24 Energy Certificate of Installations (Env., QII, Lighting, Photovoltaic, Mach., Plumb.)
f f. T-24 Energy Certificate of Verifications or Acceptance ( Env., QIi, Lighting, Photovoltaic, Mach.,
Plumb., HERS)
Ig- Operations and Maintenance Manual
MOISTURE CONTENT OF BUILDING MATERIAL (RESIDENTIAL CONSTRUCTION ONLY)
I certify that the moisture content of the wall and floor framing is less than 19 percent as
determined in accordance with Section 4.505.3 of CAL Green prior to being enclosed.
DECLARATION STATEMENT
• 1 certify under penalty of perjury, under the laws of the State of California, the information
provided is true and correct.
• I certify that the installed measures, materials, components, or manufactured devices identified
on this certificate conform to all applicable codes and regulations, and the installation is
consistent with the plans and specifications approved by the enforcing agency.
Person's Name:
Date
�...�� , ........�. �......�..c�wuuu.. nyuonw wn rvun ♦mu
CilCIGn g
ELEVATOR
CORPORATION
3/17/2022
Dear Mr. Carroll:
The residential elevator installed at 110 3611 St, Newport Beach, CA 92663, was built
according to ASME A17.1 codes by the manufacturer and installed by McKinley Elevator
Corporation, a State -licensed conveyance company, in accordance with the national ASME
A17.1 5.3 2004 and the California Title 8-Group 4 Conveyance codes.
Attached are copies of both our state contractor's license and our certificate as a State -licensed
installer of conveyances.
If you have any questions regarding this elevator, I may be contacted at (949) 261-9244 or
mark 2.ntekinlevelevator.com.
Corporation
17611 Armstrong Avenue 555 Fulton Street. Suite 202
Irvine, Celifornie 92S14 ® San Francisco, California 94102
949/261-9244 4151526-9951
FAX 249/955-3875 www.mckinleyelevator.com FAX 415/626-9954
CONTRACTORS
dCC� STATE LICENSE BOARD
""^'""""""'°""'• ACTIVE LICENSE 10
w . 861406 �— CORP
H MCKINLEY ELEVATOR
CORPORATION
.MW�.C11 C61/D21 C61/024
hom
m. 07/31/2023 www.esib.ca.gov