HomeMy WebLinkAboutF2021-0626 - Misc�6u0 N�w�ltCt�rOr
Y),O-WA- Ob'lk
HC1
Systems Inc.
FIRE / LIFE SAFETY & LOW VOLTAGE SPECIALISTS
California Contractor's License # 905493
Fire Alarm System
Complete Material Submittal
Prepared for:
Windjammer Capital -Suite 650
Tenant Improvement
840 Newport Center Drive, Newport Beach, CA 92660
Ontario • San Diego • Irvine • Pleasanton • Pasadena • Fresno • Sacramento
Corporate Office: 1354 South Parkside Place, Ontario, CA 91761
Phone: (909) 628-7773 FAX: (909) 628-7774 24-Hour Service: (877) 331-2084 Website: www.hcisystems.net
Windjammer Capital -Suite 650
Tenant Improvement
840 Newport Center Drive, Newport Beach, CA 92660
Manufacturer Device Model # Description C.S.F.M. #
System Sensor SCWL Selectable Candela Ceiling -Mounted Speaker Strobe, White 7125-1653:0504
SYSTEM
`.` SENSOR
Indoor Selectable
Output Strobes and
Horn Strobes for
Ceiling Applications
System Sensor L-Series audible visible notification
products are rich with features guaranteed to cut
installation times and maximize profits with lower
current draw and modern aesthetics.
Features The System Sensor L-Serles offers the most versatile and
• Plug-in design with minimal intrusion into the back box
• Tamper -resistant construction
• Automatic selection of 12- or 24-volt operation
at 15 and 30 candela
• Field -selectable candela settings on ceiling units:
15, 30, 76, 95, 115, 150, and 177
• Horn rated at 88+ dBA at 16 volts
• Rotary switch for horn tone and two volume selections
• Universal mounting plate for ceiling units
• Mounting plate shorting spring feature checks wiring continuity
before device installation
• Electrically Compatible with legacy SpectrAlert and SpectrAlert
Advance devices
• Compatible with MDL3 sync module
• Listed for ceiling mounting only
Agency Listings
slaxnuxc
t
O
FM
VSTE0
APPPOVEO
95 2
FDA appr v deA,60
1125-165 ZU
$4011
for ALERTmW'1s
71R_1653..0501
W57W
easy -to -use line of horns, strobes, and horn strobes in the industry
with lower current draws and modern aesthetics. With white and red
plastic housings, wall and ceiling mounting options, System Sensor
L-Series can meet virtually any application requirement.
The entire LSeries product line of ceiling -mount strobes and horn
strobes include a variety of features that increase their application
versatility while simplifying installation. All devices feature a plug-in
design with minimal intrusion into the back box, making installations
fast and foolproof while virtually eliminating costly and time-
consuming ground faults.
To further simplify installation, the L-Series utilizes a universal
mounting plate so installers can mount them to a wide array of back
boxes. With an onboard shorting spring, installers can test wiring
continuity before the device is installed.
Installers can also easily adapt devices to a suit a wide range of
application requirements using field -selectable candela settings,
automatic selection of 12- or 24-volt operation, and a rotary switch
for horn tones with two volume selections.
AWS8 02• 120JN17• Paae3
L-Series Specifications
General
L-Series ceiling -mount strobes and horn strobes shall mount to a standard 4 x 4 x 1 Y2-inch back box, 4-inch octagon back box, or double -
gang back box. Two -wire products shall also mount to a single -gang 2 x 4 x 17/8-inch back box. A universal mounting plate shall be used
for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series
products, when used with the Sync•Circuit' Module accessory, shall be powered from a non -coded notification appliance circuit output
and shall operate on a nominal 12 or 24 volts. When used with the Sync -Circuit Module, 12-volt-rated notification appliance circuit outputs
shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor
L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full -wave rectified unfiltered power supply.
Ceiling strobes and horn strobes shall have field -selectable candela settings including 15, 30, 75, 95, 115, 150, and 177.
Strobe
The strobe shall be a System Sensor L-Series Model listed to UL 1971 and shall be approved for fire protective service. The strobe
shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible
signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and
associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor L-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective
service. The horn strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act
requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist
of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a
temporal three pattern and a non -temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe
models shall operate on a coded or non -coded power supply.
Synchronization Module
The module shall be a System Sensor Sync -Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module
shall synchronize L-Series strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns
on horn strobe models over a single pair of wires. The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch back box. The module shall also
control two Style Y (class R) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more
synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature 32'F to 120°F (0°C to 49'C)
Humidity Range 10 to 93 % non -condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 VDC or regulated 24 DC/FWR'
8 to 17.5 V(12V
Operating Voltage Range (MDL3) 8.5 to 17.5V (12 V nominal) or 16.5 to 33 V (24V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Ceiling -Mount Dimensions (including lens) 6.8" diameter x 2.5" high (173 mm diameter x 64 mm high)
Ceiling -Mount Surface Mount Back Box Skirt Dimensions 6.9" diameter x 3.4" high (175 mm diameter x 86 mm high)
(SBBCRL, SBBCWL)
Notes:
1. Full Wave Rectified (FWR) voltage is a non -regulated, time -varying power source that is used on some power supply and panel outputs
2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 30 ca.
AVDse68-02 • 1 VOI12017 • Page 2
UL Current Draw Data
8-17.5 Volts 16-33 Volts
Candela DC DC FWR
Candela 15 87 41f 60
Range 30 153 63 86
75
N/A
111
142
95
N/A
134
164
115
N/A
158
191
150
N/A
189
228
177
N/A
226
264
Sound Pattern
dB
8-17.5 Volts
DC
16-33 Volts
DC FWR
Temporal
High
39
44
54
Temporal
Low
28
32
54
Non -Temporal
High
43
47
54
Non -Temporal
Low
29
32
54
3.1 KHz Temporal
High
39
41
54
3.1 KHz Temporal
Low
29
32
54
3.1 KHz Non -Temporal
High
42
43
54
3.1 KHz Non -Temporal
Low
28
29
54
Coded
High
43
47
54
3.1 KHz Coded
Hiqh
42
43
54
UL Max. Current Draw (rnA
DC Input
RMS), Ceiling
8-17.5 Volts
15cd
Horn
30cd
Strobe, 16-33 Volts
15cd
30cd
75cd
95cd
115cd
150cd
177cd
Temporal High
103
167
71
90
143
165
187
217
254
Temporal Low
96
165
54
71
137
161
185
211
249
Non -Temporal High
106
173
71
90
141
165
187
230
273
Non-Temportal Low
95
166
54
71
124
161
170
216
258
3.1 K Temporal High
111
164
69
94
147
163
184
229
257
3.1 K Temporal Low
103
163
54
88
143
155
185
212
252
3.1 K Non -Temporal High
111
172
69
94
144
164
202
229
271
3.1 K Non -Temporal Low
103
169
54
88
131
155
187
217
259
FWR Input
16-33 Volts
15cd
30cd
75cd
95cd
115cd
150cd
177cd
Temporal High
107
135
179
198
223
254
286
Temporal Low
78
101
151
172
199
229
262
Non -Temporal High
107
135
179
198
223
254
286
Non-Temportal Low
78
101
151
172
199
229
262
3.1K Temporal High
108
135
179
200
225
255
289
3.1 K Temporal Low
79
101
150
171
196
229
260
3.1 K Non -Temporal High
108
135
179
200
225
255
289
3.1 K Non -Temporal Low
79
101
150
171
196
229
260
Horn Strobe Tones and Sound Output Data
Switch
Position Sound Pattern
8-17.5 16-33
Volts Volts
dB DC DC FWR
1
Temporal
High
84
89
89
2
Temporal
Low
75
83
83
3
Non -Temporal
High
85
90
90
4
Non -Temporal
Low
76
84
84
5
3.1 KHz Temporal
High
83
88
88
6
3.1 KHz Temporal
Low
76
82
82
7
3.1 KHz Non -Temporal
High
84
89
89
8
3.1 KHz Non -Temporal
Low
77
83
83
AVDS868 02 • M01/2017 • Page 3
L-Series Dimensions
6.83" d`—
(173 r
2.47" (62.7 mm)
1.37" (34.8 mm)
A0545-00
Ceiling -Mount Horn Strobes
01
2-Wire Ceiling Mount Horn Strobes
with Ceiling Surface Mount Back Box
L-Series Ordering Information
Ceiling Horn Strobes
PC2RL 2-Wire, Horn Strobe, Red
PC2WL
2-Wire, Horn Strobe, White
PC4RL
4-Wire, Horn Strobe, Red
PC4WL
4-Wire, Horn Strobe, White
For a ceiling -listed horn -only device, see AVDS865 "Indoor Selectable -
Output Horns, Strobes, and Horn Strobes for Wall Applications".
6.92" a =^
(175.
Ceiling Surface Mount Back Box
4-Wire Ceiling Mount Horn Strobes
with Ceiling Surface Mount Back Box
Ceiling Strobes
2.5"
(64 mm)
0
A0546-00
01
SCRL
Strobe, Red
SCWL
Strobe, White:
SCWL-CLR-ALERT
Strobe, White, ALERT
Accessories
TRC-2
Universal Ceiling Trim Ring Red
TRC-2W
Universal Ceiling Trim Ring White
SBBCRL
Ceiling Surface Mount Back Box, Red
SBBCWL
Ceiling Surface Mount Back Box, White
SYSTEM ®z0t7system without
force.
``1 3825 Ohio Avenue • St. Charles, IL 60174 Product specifications suniccuo char,eewimom ports. visnsystemsensornom
�� SENSOR' Phone: 800-SENSOR2 • Fax: 630-377-6495 for current product information incWdng to letter of this data sheet.
AVO586r-02•tvu1/2on
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE 0
LISTING No.
7125-1653:0504 Page 1 of 2
CATEGORY:
7125 -- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE:
System Sensor, Unincorporated Div of Honeywell Int'I Inc.3825 Ohio Ave, St. Charles, IL
60174
Contact: Lisa Brant (203) 484-6105 Fax (203) 484-7309
Email: lisa.brant@honeywell.com
DESIGN:
System Sensor Indoor 2-wire Models:
SRL, SWL, SGRL, SGWL, SRL-P SWL-P, SRL-SP, SWL-CLR-ALERT and SWL-ALERT
Wall Strobes;
SCRL, SCWLiand SCWL-CLR-ALERT Ceiling Strobes.
Wall Bezel Parts:
BZR-F, BZR-AL, BZR-AG, BZR-EV, BZR-P, BZR-SP, BZR-PG,
BZW-F, BZW-AL, BZW-AG, BZW-EV, BZW-P, BZW-SP, BZW-PG,
BZGR-F, BZGR-AL, BZGR-AG, BZGR-EV, BZGR-P, BZGR-SP, BZGR-PG,
BZGW-F, BZGW-AL, BZGW-AG, BZGW-EV, BZGW-P, BZGW-SP and BZGW-PG,
Ceiling Bezel Parts:
BZRC-F, BZRC-AL, BZRC-AG, BZRC-EV, BZRC-P, BZRC-SP, BZRC-PG,
BZWC-F, BZWC-AL; BZWC-AG, BZWC-EV, BZWC-P, BZWC-SP and BZWC-PG.
Color Lens:
.LENS-A2, LENS-B2, LENS-G2, LENS-R2, LENS-AC2, LENS-BC2, LENS-GC2 and
LENS-RC2.
WallTrim Rings:
TR2 and TR2W
CeilingTrim Rings:
TRC2 andTRC2W.
Wall Surface Mounted Back Boxes:
SBBRL, SBBGRL, SBBWL and SBBGWL,
Ceiling Surface Mounted Back Boxes:
SBBCRL and SBBCWL
Refer to listee's data sheet for detailed product description and operational considerations.
'Rev 04-04-19 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correctit
t
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2021 Listing Expires June 30, 2022
Authorized By: DAVID CASTILLO„ M.E., F.P.E.
Fire Engineering Division
Listing No. 7125-1653:0504
Page 2 of 2
RATING:
Regulated 12 VDC setting: 8-17.5 VDC
Regulated 24 VDC/fwr setting: 16-33 VDC
INSTALLATION:
In accordance with listee's printed installation instructions, NFPA 72, applicable codes &
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING:
Listee's name, model number, electrical rating, and UL label.
APPROVAL:
Listed as two wire strobe units used for synchronous application when used with separately
listed compatible fire alarm control units. Suitable for indoor use, vertical wall or horizontal
ceiling mounted. *Listed with software code, S05-0048-001 for low temperature
compensation. Authority having jurisdiction should be consulted prior to installation. Refer to
listee's Installation Instruction Manual for details.
*Rev 04-04-19 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2021 Listing Expires June 30, 2022
Authorized By: DAVID CASTILLO„ M.E., F.P.E.
Fire Engineering Division