The following calculations are forth structural engineering design of the photovoltaic panels and are valid
only for the structural info referenced in the stamped plan set. The verification of such info is the
responsibility of others.
After review, I certify that the roof structure has sufficient structural capacity for the applied PV loads.
All mounting equipment shall be designed and installed per manufacturer's approved installation
specifications.
Design Criteria:
Code: 2019 CBC
ASCE 7-16
Live Load: 20 psf
Ult Wind Speed: 96 mph
Exposure Cat: D
Ground Snow: 0 psf Min Roof Snow: NA
r���p,JlHgg�\
w
C 84486
Current Renewables Engineering Inc.
Professional Engineer
au
projects@creng.solar sTgr C1b1L-
EXP.09/30/2023
1960 Chicago Ave, Suite D15, Riverside, CA 92507
www.currentrenewableseng.com 951.254.5655
INTEGRITY ;' PROFESSIONALISM i CUSTOMER EXPERIENCE
Roof Properties:
Roof Type =
Roof 1
Flat Material
Roof Pitch (deg) =
1
Mean Roof Height (ft) =
13
Attachment Trib Width (ft) =
2.75
Attachment Spacing (ft) =
4
Framing Type=
Rafter
Framing Size =
2x14
Framing OC Spacing (in.) =
16
Section Thickness, b (in.) =
1.5
Section Depth, d (in.) =
13.25
Section Modulus, Sx (in .A3) =
43.9
Moment of Inertia, Ix (in .A4) =
290.8
Framing Span (ft) =
20
Deflection Limit D+L (in.) =
4
Deflection Limit S or W (in.) =
2.67
Framing Upgrade =
Adequate
Sister Size =
NA
Wood Species =
DF #2
Wood Fb (psi) =
900
Wood Fv (psi) =
180
Wood E (psi) =
1600000
CD (Wind) =
1.6
CD (Snow) =
1.15
CM=C,=CL=C;=
1.0
CF =
1.0
Cf. =
1.00
Cr =
1.15
F'b_wind (psi) =
1656
F'b_snow (psi) =
1190
F'v_wind (psi) =
288
F'v_snow (psi) =
207
M_allowable_wind (lb-ft) =
6057
M_allowable_snow (lb-ft) =
4353
V_allowable_wind (Ibs) =
3816
V_allowable_snow (Ibs) =
2743
1600000
Load Calculation:
1960 Chicago Ave, Suite D15, Riverside, CA 92507
www.currentrenewableseng.com { 951.254.5655
INTEGRITY a PROFESSIONALISM CUSTOMER EXPERIENCE
Dead Load Calculations:
Panels Dead Load (psf) = 3.0
Roof 1
Roofing Weight (psf) =
2.0
Decking Weight (psf) =
2.0
Framing Weight (psf) =
3.4
Misc. Additional Weight (psf) =
1.0
Existing Dead Load (psf) =
8.4
Total Dead Load (psf) =
11.4
Wind Load Calculations
Ultimate Wind Speed (mph) = 96
Directionality Factor, kd = 0.85
Topographic Factor, kzt = 1.0
Roof 1
Velocity Press Exp Factor, kz =
1.03
Ground Elevation Factor, ke =
1.00
Velocity Pressure, qz (psf) =
20.7
Array Edge Factor, yE =
1.25
Solar Equalization Factor, ya =
0.70
External Pressure Up, GCp_1=
-1.6
External Pressure Up, GCp_2 =
-2.15
External Pressure Up, GCp_3 =
-2.9
External Pressure Down, GCp =
0.25
Design Pressure Up, p_1(psf) _
-28.9
Design Pressure Up, p_2 (psf) _
-38.9
Design Pressure Up, p_3 (psf) _
-52.4
Design Pressure Down, p (psf) =
16.0
Tilt Up Array
�Lp Lp (ft) =
5.5 < 6.7
c w (deg) =
2.0 < 35
h1(in.)=
6.0 <24
h2 (in.) =
Ee
8.0 <48
ASCE 7-16 Sec 29.4.3 is Applicable.
h (ft) =
13.0
hp (ft) =
0.0
yp=min(1.2,0.9+hpt/h)=
0.9
yc = max(0.8 , 0.6+0.06Lp) =
0.9
yE =
1.50
(GCrn)nom =
1.4
1960 Chicago Ave, Suite D15, Riverside, CA 92507
www.currentrenewableseng.com ) 951.254.5655
INTEGRITY PROFESSIONALISM i CUSTOMER EXPERIENCE
Design Pressure, p (psf) _ -36.3
Hardware Checks:
Lae Screw Checks:
Roof 1
Ref. Widthrawal Value, W (lb/in) =
266
(CM =Ct=Ceg=1.0)CD=
1.6
Adjusted Widthrawal Value, W' (Ib/in) =
426
Lag Penetration, p (in.) =
2.5
Allowable Widthrawal Force, W'p (Ibs) =
1064
Applied Uplift Force (Ibs) _
-220
Uplift DCR =
0.21
Ref. Lateral Value, Z (Ibs) =
270
(CM =Ct=Co=Ceg=1.0)CD=
0.9
Adjusted Lateral Value, Z' (Ibs) =
243
Applied Laeral Force (Ibs) =
1
Angle of Resultant Force, a (deg) =
90
djusted Interaction Lateral Value, T. (Ibs) =
1064
Lateral DCR =
0.00
Roof Framing Checks:
Force Checks:
LC1: D+S
LC2: D+0.6W
Roof 1
Applied Moment (lb-ft) =
846
Applied Shear (Ibs) =
145
Allowable Moment (lb-ft) =
4353
Allowable Shear (Ibs) =
2743
Moment DCR =
0.19
Shear DCR =
0.05
Applied Moment (lb-ft) =
1756
Applied Shear (Ibs) =
251
Allowable Moment (lb-ft) =
6057
Allowable Shear (Ibs) =
3816
Moment DCR =
0.29
Shear DCR =
0.07
LC3: D+0.75(5+0.6W)
1960 Chicago Ave, Suite D15, Riverside, CA 92507
www.currentrenewableseng.com � 951.254.5655
INTEGRITY PROFESSIONALISM ; CUSTOMER EXPERIENCE
Job Code: GEORGE HEUSER
5of6
Applied Moment (lb-ft) =
1529
Applied Shear (Ibs) =
224
Allowable Moment (lb-ft) =
6057
Allowable Shear (Ibs) =
3816
Moment DCR =
0.25
Shear DCR =
0.06
LC4: 0.6D+0.6W
Applied Moment (lb-ft) =
447
Applied Shear (Ibs) =
104
Allowable Moment (lb-ft) =
6057
Allowable Shear (Ibs) =
3816
Moment DCR =
0.07
Shear DCR =
0.03
Deflection Checks (Service Level):
LC1: D+L
LC2: S
LC3: W (Down)
LC4: W (Up)
Seismic Check:
Existing Weight:
Roof 1
Deflection Limit (in.) = 4
Deflection DCR = 0.05
Deflection (in.) =
0.00
Deflection Limit (in.) =
2.67
Deflection DCR =
0.00
Deflection (in.) =
0.09
Deflection Limit (in.) =
2.67
Deflection DCR =
0.03
Deflection (in.) _ -0.08
Deflection Limit (in.) = 2.67
Deflection DCR = 0.03
See Attached for Framing Analysis Results.
Wall Weight (psf) =
17
Tributary Wall Area (ftZ) =
1100
Total Wall Weight (Ibs) =
18700
Roof Weight (psf) =
8
Roof Area (ft) =
2800
Total Roof Weight (Ibs) =
23565
1960 Chicago Ave, Suite D15, Riverside, CA 92507
www.currentrenewableseng.com 1 951.254.5655
INTEGRITY i PROFESSIONALISM '+ CUSTOMER EXPERIENCE
Current
Rr,')r r x c
aR
j
=14,
Total Existing Weight (Ibs) = 42265
Additional PV Weight:
Total Additional PV Weight (Ibs) = 3049
Weight Increase:
(Existing W +Additional W)/(Existing W) = 107%
Job Code: GEORGE HEUSER
6of6
The increase in weight as a result of the solar system is less than 10% of the existing structure and
therefore no further seismic analysis is required.
Limits of Scope of Work and Liability:
Existing structure is assumed to have been designed and constructed following appropriate codes at
time of erection, and assumed to have appropriate permits. The calculations produced are only for the
roof framing supporting the proposed PV installation referenced in the stamped planset and were
completed according to generally recognized structural analysis standards and procedures, professional
engineering and design experience, opinions and judgements. Existing deficiencies which are unknown or
were not observable during time of inspection are not included in this scope of work. All PV modules,
racking, and mounting equipment shall be designed and installed per manufacturer's approved
installation specifications. The Engineer of Record and the engineering consulting firm assume no
responsibility for misuse or improper installation. This analysis is not stamped for water leakage.
Framing was determined based on information in provided plans and/or photos, along with engineering
judgement. Prior to commencement of work, the contractor shall verify the framing sizes, spacings, and
spans noted in the stamped plans, calculations, and cert letter (where applicable) and notify the
Engineer of Record of any discrepancies prior to starting construction. Contractor shall also verify that
there is no damaged framing that was not addressed in stamped plans, calculations, and cert letter
(where applicable) and notify the Engineer of Record of any concerns prior to starting construction.