HomeMy WebLinkAboutE2022-0272 - MiscCHARGING INSTALLATION: 240 VOLT NEMA 14-30 OUTLET
The Mobile Connector is included as standard equipment withal new vehicles. This is a 20 -foot -long cable with interchangeable adapters
which can be used to plug in to different outlets. This guide provides detail on installing a NEMA 14-30 outlet for home charging with the
Mobile Connector. Adapter purchased separately.
GROUND TO TOC
NEMA 14-30 DETAILS
/
. Circuit Breaker: 30 amps
G
• Voltage: Single phase, 208-250 volt AC supply, 60 hertz
5PV
`�
. Four Wire Configuration: Line 1 - Line 2 - Ground - Neutral
.Conductors: 10 AWG copper wire for circuits up to 100 feet
• Outlet: Use a high quality, industrial grade outlet
• Ground Pin Orientation: Top position of outlet
. Ventilation: Not Required
INSTALL LOCATIONS
CHARGEPORT
RECOMMENDED INSTALLATION AREA
USING THE MOBILE CONNECTOR
Attach adapter to Mobile Connector, plug into outlet and then into vehicle to begin
charging. The NEMA 14-30 adapter will allow a Tesla to draw up to 24 amps (5.7 kW at
240 volts). Recharge speeds will vary between different models.
MILES OF RANGE PER HOUR OF CHARGE
MODEL S
17
ADDITIONAL SUPPORT
EMAIL
CHARGINGINS"FALLATION@TESLA.COM
PHONE
650.681.6133 (M -F 8:30 AM - 5:30 PM PST)
24/7 VEHICLE TECH SUPPORT
877,798.3752
WEB
TESLA.COWSUPPORT
ONLINE STORE
_.—-SI-TOP,TES-EA .COM
T = S L n 0 2017 TESLA, INC. I NA -US I NEMA 14-30 OUTLET I GEN 2 MOBILE CONNECTOR
-11
j
4
�
u
b
�I
�r
CITY OF NEWPORT BEACH
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING DIVISION
100 Civic Center Drive I P.O. Box 1768 1 Newport Beach, CA 92658-8915
www.newportbeachca.gov 1 (949) 644-3200
SMOKE DETECTOR AND CARBON MONOXIDE
SELF -CERTIFICATION
(this certification is to be filled out by the permittee or homeowner)
Project Address: 5'1001[6IMIll pha 0lyay pov oeo ICA 4gL6
Permit Number: .15� T. Ga') Z
Property Owner:1�G
Licensed Contractor:
Lic #:
The State of California now requires that smoke and carbon monoxide detectors must be
installed in all residential buildings
California Residential Code (CRC) Section R314.1, CRC R315.2 states in part that
existing dwellings be "retrofitted with smoke detectors and carbon monoxide detectors.
CRC Section R314.3, CRC R315.3 defines required locations.
Both boxes below must be checked.
�1❑ Carbon Monoxide Alarm: On the ceiling or wall outside of each separate
sleeping area in the immediate vicinity of bedrooms or in each hallway outside of
the rooms, and each level of the dwelling. Detectors are also required in
bedrooms with gas fired appliances
Smoke Alarms: Installed in each room used for sleeping purposes, outside
each sleeping area, and on each level of the dwelling unit.
Retrofitted detectors may be battery operated for buildings where no alterations are
performed on the interior. Multiple -purpose alarms (carbon monoxide and smoke alarms)
shall comply with all applicable standards and must be approved by the State Fire
Marshall. The devices must be installed per manufacturer's specifications.
I, the undersigned, hereby certify that I am the permittee or homeowner of the
project. I further certify that smoke alarms and carbon monoxide alarms are
present and tested to be functional in all the following locations:
Signature:
Date: fa 3 ZZ
NOTE:_ This-self-kertification_ is -only -used for projects -to the exterior of the structure where -access -to -the -
interior
s -only used -for -projects -to -the -exterior -of -the -structure -where -access -to -the -
interior of the dwelling by the City of Newport Beach Building Inspector is not achieved during the course of
construction.
Forms\SmokeDetectorandCarbonMonozideSelfCert 08/12/16
CITY OF NEWPORT BEACH
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING DIVISION
100 Civic Center Drive I P.O. Box 1768 1 Newport Beach, CA 92658-8915
www.newportbeachca.gov 1 (949) 644-3200
SMOKE DETECTOR AND CARBON MONOXIDE
SELF -CERTIFICATION
(this certification is to be filled out by the permittee)
Project Address:._ CbJL) (k) -ST 4y`CCt)f�)�- ( l gj}q a
Permit Number:
Property Owner:
Licensed Contra
Lic #: /6— 2,1-D
The State of California now requires that smoke and carbon monoxide detectors must be
installed in all residential buildings
California Residential Code (CRC) Section R314.1, CRC R315.2 states in part that
existing dwellings be "retrofitted with smoke detectors and carbon monoxide detectors.
CRC Section R314.3, CRC R315.3 defines required locations.
Both boxes below must be checked.
Carbon Monoxide Alarm: On the ceiling or wall outside of each separate sleeping
area in the immediate vicinity of bedrooms or in each hallway outside of the rooms,
and each level of the dwelling. Detectors are also required in bedrooms with gas
fired appliances
Smoke Alarms: Installed in each room used for sleeping purposes, outside each
sleeping area, and on each level of the dwelling unit.
Retrofitted detectors may be battery operated for buildings where no alterations are
performed on the interior. Multiple -purpose alarms (carbon monoxide and smoke alarms)
shall comply with all applicable standards and must be approved by the State Fire
Marshall. The devices must be installed per manufacturer's specifications.
I, the undersigned, hereby certify that I am the permittee of the project. I further
certify that smoke alarms and carbon monoxide alarms are present and tested to
be functional in all the followina locations:
Signature:
interior of the dwelling by the City of Newport
construction.
FormslSmokeDete tomndCarbonMonoxideSelfCert 04/23/13
Date: C=, 2
Building Inspector is not achieved during the course of