HomeMy WebLinkAbout3.01_Cert of Installation CF2R_260800 1.8D - Commissioning of Electrical Tests & Certificates1730 S. ANAHEIM WAY  ANAHEIM WAY, CA 92805 PHONE (657) 276 0600 Switchgear: Tests & Certificates Submittal Specification Section 260800 – COMMISSIONING OF ELECTRICAL Approval Page CUSTOMER: Morrow Meadows AEC FILE NUMBER: WB13 REPORT PREPARED BY: Mike Kain REPORT DATE: 2016-11-22 HARBOR DAY SCHOOL Acceptance Testing Report CUSTOMER: Rosendin Electric AEC FILE NUMBER: 21E149-B-FR0-ATS REPORT PREPARED BY: Alexander Jackson REPORT DATE: June 2, 2021 ELECTRICAL ENGINEERING: Third-Party Certification • Design • Testing • Consulting 1105 N. Allen Avenue, Pasadena, CA 91104 ¥ (626) 398-3052 (800) 398-3052 Fax (626) 398-3053 APPLIED ENGINEERINGCONCEPTS MEMBER OF ACCEPTANCE TESTING REPORT June 2, 2021 Adam Dickelman Rosendin Electric 1730 Anaheim Way Anaheim, CA 92805 File Number: 21E149-B-FR0-ATS Dear Mr. Dickelman: At your request, Applied Engineering Concepts (AEC) has performed testing as described in the following paragraphs. 1.0 JOB SITE INFORMATION JOB SITE: Harbor Day School 3443 Pacific View Drive Corona Del Mar, CA 92625 2.0 SCOPE 2.1 AEC provided field testing services to include testing equipment, labor and technical supervision. Testing and inspections performed in compliance with the latest National Electrical Testing Association (NETA) standard Acceptance Testing Specifications for Electrical Power Distribution Equipment and Systems, NETA ATS-2021. 3.0 DISCUSSION AND RECOMMENDATIONS 3.1 The equipment as noted in the Table of Contents listed in Appendix 1 is manufactured and rated as indicated on the individual test forms. Inspection and testing of the equipment was performed as specified in Section 2.0 - Scope, and found to be acceptable in accordance with NETA ATS-2021, unless specifically indicated on the test result form. Where applicable, equipment status, along with recommendations or suggestions by AEC are noted in bold type in section 3.0. 3.2 SUMMARIZED TEST RESULTS 3.2.1 All equipment was found to be acceptable per NETA standards. All equipment is suitable for service. 3.3 REGULARLY SCHEDULED MAINTENANCE 3.3.1 As a minimum AEC recommends performing regularly scheduled maintenance every three years. This does not consider equipment condition, reliability, or environment. An ideal maintenance program is reliability based and unique to each piece of equipment. In the absence of a maintenance program, NETA has provided guidelines that can be used and are attached as Appendix A2 – Frequency of Maintenance Testing. 4.0 CONCLUSION 4.1 Our report is based on a visual inspection and the test results as indicated in this report. Unless otherwise noted, all equipment inspected and tested, as itemized in the Table of Contents, were in accordance with project specifications and/or the latest Acceptance Testing Specifications for Electrical Power Distribution Equipment and Systems ATS-2021 guideline by the National Electrical Testing Association, Inc., (NETA). Rosendin Electric Page 2 of 2 Corona Del Mar, CA ACCEPTANCE TESTING REPORT Applied Engineering Concepts June 2, 2021 AEC Job File Number: 21E149-B-FR0-ATS 4.2 The following field label has been attached to the equipment. 4.2.1 Blue - Equipment is acceptable ♦♦♦♦♦♦ Thank you for this opportunity to be of service. If you require further explanation or clarification or need additional information, feel free to call me. Sincerely, Applied Engineering Concepts A California Corporation Report By: Alex Jackson Field Supervisor NETA Level III Test Technician Alex.j@aec-us.com (626) 399-2297 Encl. Appendix “A1” Test Results Appendix “A2” Frequency of Maintenance Table Appendix “A1” Test Results HARBOR DAY SCHOOL ROSENDIN ELECTRIC ROSENDIN ELECTRICCustomer Plant Table of Contents Job #21E149-B-FR0 HLA1NMSB 1 User PagePositionSubstation / Panel NETA Section / Equipment 7.06.1 LOW VOLTAGE CIRCUIT BREAKER - MULTI .................... 1 of 1PAGE HLA1SMSB 27.06.1 LOW VOLTAGE CIRCUIT BREAKER - MULTI .................... HMA1NMSB 37.06.1 LOW VOLTAGE CIRCUIT BREAKER - MULTI .................... HMA1SMSB 47.06.1 LOW VOLTAGE CIRCUIT BREAKER - MULTI .................... HMDPBMSB 57.06.1 LOW VOLTAGE CIRCUIT BREAKER - MULTI .................... MAINMSB 67.06.1 LOW VOLTAGE CIRCUIT BREAKER - MULTI .................... TP154MSB 77.06.1 LOW VOLTAGE CIRCUIT BREAKER - MULTI .................... TP1S5MSB 87.06.1 LOW VOLTAGE CIRCUIT BREAKER - MULTI .................... TPA1NMSB 97.06.1 LOW VOLTAGE CIRCUIT BREAKER - MULTI .................... TPA1SMSB 107.06.1 LOW VOLTAGE CIRCUIT BREAKER - MULTI .................... CORONA DEL MAR, CA 92625ROSENDIN ELECTRIC FILE NUMBER: ROSENDIN ELECTRIC HARBOR DAY SCHOOL 6/2/2021 POSITION:HLA1N CLIENT: MSBLOCATION: TEST DATE:JOB SITE: SUB./BOARD: HARBOR DAY SCHOOLCR#:21E149-B-FR0 LOW VOLTAGE CIRCUIT BREAKER PAGE:1 of 10 NOTES / RECOMMENDATIONS Co m m e n t s De f i c i e n c i e s Cr i t i c a l D e f i c i e n c i e s Tested By:Witnessed By: Reviewed By:Name Name Name RECOMMENDATIONS: *STATUS: A-ACCEPTABLE C-CORRECTED NIS-NOT IN SCOPE NA-NOT APPLICABLE NAC-NOT ACCESSIBLE R-REPAIR, REPLACE, OR ADJUST ALEXANDER JACKSON Acceptable EQUIPMENT DATA SERIAL NO.: 65 KA @ 250 AMPSSYS. VOLTS -250 MAX AMPS:CAT./TYPE:250 600MAX VOLTS:SQUARE D JJA36250U31XYP AIC: BREAKER TYPE:INSULATED / MOLDED CASE BREAKERPOWER BREAKER LSIG SETTINGS: 480 L - LONG TIME S - SHORT TIME I - INSTANTANEOUS G - GROUND FAULT RATING PLUG: TRIP / SENS. RATING:MFR: TRIP UNIT TYPE:Solid State AMPS PART NUMBER:MICROLOGIC 3.2 BOLTED @SHUNT:NO UVR:NA NA@CONNECT:AUX SWITCHES:-NO AS FOUND AS LEFT AS FOUNDRANGES AS LEFTRANGES (225 (AMPS)LT DELAY (LTD)0.5-16 4 4AMPS)22570-250LONG TIME PICKUP (LTPU) INST. PU (IPU)Plug Sen LTPU AMPS)2,500102,500(AMPS)10 (1.5-12 STATUS NAMEPLATE VS DRAWINGS DRAWOUT MECHANISM EXTERIOR CONDITION PRIMARY CONNECTIONS SECONDARY DISCONNECT MAIN / ARCING CONTACTS NOTESITEM SPRING CHARGING MOTOR INTERLOCKS SHUNT TRIP / CLOSE AUXILIARY FEATURES SUCH AS ZSI & ANTIPUMP LUBRICATION MECHANISM OPERATION INDICATORS (CLOSE/OPEN, CHARGE/DISCHARGE) ITEM A NA A NAC NAC NA A NAC NA A NA A NA NA NOTES VISUAL & MECHANICAL INSPECTION ARC CHUTES STATUS 4522 1 1/5/20222015-64 CONTACT RESISTANCE:1/5/2022 2011-1092006-09 INSULATION RESISTANCE: RELATIVE HUMIDITY:AMBIENT TEMP.:%°C 2/23/2022 SEC.CURRENT INJECTION:0PRI.CURRENT INJECTION: TEST EQUIPMENT: ASSET NO. / CALIBRATION DUE DATE TEST RESULTS Results UNITS NOTESBYMIN/MAX TOLERANCE SECONDARY INJ.CURRENT INJECTION TEST AMPSTEST POINT % TEST METHOD PRIMARY INJ. TESTED @ SETTINGS 0.5 Mfr Mfr 100 %AMPS SECONDS - - 105 1.5 2.25 120 1.85LONG TIME (LT) DELAY LONG TIME (LT) PICKUP 115 300 100 % 100 300 AMPS Mfr375-337.5 412.5401INSTANTANEOUS PICKUP 375%100 PHASE ACCURACY MICROOHMS MILLIVOLTS @ VDC 9,999  9,999 ±50% 9,999  C-CB-B 9,999 A-A 9,999 BREAKER OPEN B-C 9,999 C-A 9,9999,999 C-GNDB-GNDA-GND BREAKER CLOSED CONTACT RESISTANCE INSULATION RESISTANCE 1,000 NETA NETA 100 4040 LTPU STPU GFPU A 114115 115 CB 9,999 A-B 44 MfrMETER INSTANTANEOUS -120105 CORONA DEL MAR, CA 92625ROSENDIN ELECTRIC FILE NUMBER: ROSENDIN ELECTRIC HARBOR DAY SCHOOL 6/2/2021 POSITION:HLA1S CLIENT: MSBLOCATION: TEST DATE:JOB SITE: SUB./BOARD: HARBOR DAY SCHOOLCR#:21E149-B-FR0 LOW VOLTAGE CIRCUIT BREAKER PAGE:2 of 10 NOTES / RECOMMENDATIONS Co m m e n t s De f i c i e n c i e s Cr i t i c a l D e f i c i e n c i e s Tested By:Witnessed By: Reviewed By:Name Name Name RECOMMENDATIONS: *STATUS: A-ACCEPTABLE C-CORRECTED NIS-NOT IN SCOPE NA-NOT APPLICABLE NAC-NOT ACCESSIBLE R-REPAIR, REPLACE, OR ADJUST ALEXANDER JACKSON Acceptable EQUIPMENT DATA SERIAL NO.: 65 KA @ 250 AMPSSYS. VOLTS -250 MAX AMPS:CAT./TYPE:250 600MAX VOLTS:SQUARE D JJA36250U31XYP AIC: BREAKER TYPE:INSULATED / MOLDED CASE BREAKERPOWER BREAKER LSIG SETTINGS: 480 L - LONG TIME S - SHORT TIME I - INSTANTANEOUS G - GROUND FAULT RATING PLUG: TRIP / SENS. RATING:MFR: TRIP UNIT TYPE:Solid State AMPS PART NUMBER:MICROLOGIC 3.2 BOLTED @SHUNT:NO UVR:NA NA@CONNECT:AUX SWITCHES:-NO AS FOUND AS LEFT AS FOUNDRANGES AS LEFTRANGES (225 (AMPS)LT DELAY (LTD)0.5-16 4 4AMPS)22570-250LONG TIME PICKUP (LTPU) INST. PU (IPU)Plug Sen LTPU AMPS)2,500102,500(AMPS)10 (1.5-12 STATUS NAMEPLATE VS DRAWINGS DRAWOUT MECHANISM EXTERIOR CONDITION PRIMARY CONNECTIONS SECONDARY DISCONNECT MAIN / ARCING CONTACTS NOTESITEM SPRING CHARGING MOTOR INTERLOCKS SHUNT TRIP / CLOSE AUXILIARY FEATURES SUCH AS ZSI & ANTIPUMP LUBRICATION MECHANISM OPERATION INDICATORS (CLOSE/OPEN, CHARGE/DISCHARGE) ITEM A NA A NAC NAC NA A NAC NA A NA A NA NA NOTES VISUAL & MECHANICAL INSPECTION ARC CHUTES STATUS 4522 1 1/5/20222015-64 CONTACT RESISTANCE:1/5/2022 2011-1092006-09 INSULATION RESISTANCE: RELATIVE HUMIDITY:AMBIENT TEMP.:%°C 2/23/2022 SEC.CURRENT INJECTION:0PRI.CURRENT INJECTION: TEST EQUIPMENT: ASSET NO. / CALIBRATION DUE DATE TEST RESULTS Results UNITS NOTESBYMIN/MAX TOLERANCE SECONDARY INJ.CURRENT INJECTION TEST AMPSTEST POINT % TEST METHOD PRIMARY INJ. TESTED @ SETTINGS 0.5 Mfr Mfr 100 %AMPS SECONDS - - 105 1.5 2.25 120 1.8LONG TIME (LT) DELAY LONG TIME (LT) PICKUP 115 300 100 % 100 300 AMPS Mfr375-337.5 412.5401INSTANTANEOUS PICKUP 375%100 PHASE ACCURACY MICROOHMS MILLIVOLTS @ VDC 9,999  9,999 ±50% 9,999  C-CB-B 9,999 A-A 9,999 BREAKER OPEN B-C 9,999 C-A 9,9999,999 C-GNDB-GNDA-GND BREAKER CLOSED CONTACT RESISTANCE INSULATION RESISTANCE 1,000 NETA NETA 100 3939 LTPU STPU GFPU A 115115 115 CB 9,999 A-B 43 MfrMETER INSTANTANEOUS -120105 CORONA DEL MAR, CA 92625ROSENDIN ELECTRIC FILE NUMBER: ROSENDIN ELECTRIC HARBOR DAY SCHOOL 6/2/2021 POSITION:HMA1N CLIENT: MSBLOCATION: TEST DATE:JOB SITE: SUB./BOARD: HARBOR DAY SCHOOLCR#:21E149-B-FR0 LOW VOLTAGE CIRCUIT BREAKER PAGE:3 of 10 NOTES / RECOMMENDATIONS Co m m e n t s De f i c i e n c i e s Cr i t i c a l D e f i c i e n c i e s 1 CIRCUIT BREAKER PROVIDES NO INDICATION OF LONG TIME PICKUP. Tested By:Witnessed By: Reviewed By:Name Name Name RECOMMENDATIONS: *STATUS: A-ACCEPTABLE C-CORRECTED NIS-NOT IN SCOPE NA-NOT APPLICABLE NAC-NOT ACCESSIBLE R-REPAIR, REPLACE, OR ADJUST ALEXANDER JACKSON Acceptable EQUIPMENT DATA SERIAL NO.: 65 KA @ 225 AMPSSYS. VOLTS -250 MAX AMPS:CAT./TYPE:250 600MAX VOLTS:SQUARE D JJA36225YP AIC: BREAKER TYPE:INSULATED / MOLDED CASE BREAKERPOWER BREAKER LSIG SETTINGS: 480 L - LONG TIME S - SHORT TIME I - INSTANTANEOUS G - GROUND FAULT RATING PLUG: TRIP / SENS. RATING:MFR: TRIP UNIT TYPE:Thermal AMPS PART NUMBER:- BOLTED @SHUNT:NO UVR:NA NA@CONNECT:AUX SWITCHES:-NO AS FOUND AS LEFT AS FOUNDRANGES AS LEFTRANGES (225 (AMPS)LT DELAY (LTD)FIXED FIXED FIXEDAMPS)225FIXEDLONG TIME PICKUP (LTPU) INST. PU (IPU)Plug Sen LTPU AMPS)2,2502,250(AMPS)(1125-2250 STATUSSTATUS NAMEPLATE VS DRAWINGS PHYSICAL & MECHANICAL CONDITION NOTESITEM CB OPERATION ANCHORAGE & ALIGNMENT ITEM A A A A A NA NOTES VISUAL & MECHANICAL INSPECTION CLEANLINESS SHUNT TRIP / CLOSE CONTACT RESISTANCE:1/5/2022 2011-1092006-09 INSULATION RESISTANCE:0 2/23/20222015-64CURRENT INJECTION: TEST EQUIPMENT: ASSET NO. / CALIBRATION DUE DATE 4522RELATIVE HUMIDITY:AMBIENT TEMP.: 1/5/2022 %°C 1 B C TOLERANCE BYMIN/MAX TEST RESULTS TESTPOINT %UNITS NOTESTEST AMPS ACURRENT INJECTION 121.7 104.9 Mfr Mfr % %300 225 675 1100LONG TIME (LT) PICKUP LONG TIME (LT) DELAY AMPS SECONDS 281- - 225 50 250117.4 1221 1302 Mfr%1,125100 1108 AMPSINSTANTANEOUS PICKUP 1,350-900 MILLIVOLTS @ VDC A-B 9,999 9,999  9,999 MICROOHMS 187 ±50% 9,999  C-CB-B 9,999 A-A 9,999 BREAKER OPEN B-C 9,999 C-A 9,9999,999 C-GNDB-GNDA-GND BREAKER CLOSED CONTACT RESISTANCE INSULATION RESISTANCE 1,000 NETA Mfr 100 202199 CORONA DEL MAR, CA 92625ROSENDIN ELECTRIC FILE NUMBER: ROSENDIN ELECTRIC HARBOR DAY SCHOOL 6/2/2021 POSITION:HMA1S CLIENT: MSBLOCATION: TEST DATE:JOB SITE: SUB./BOARD: HARBOR DAY SCHOOLCR#:21E149-B-FR0 LOW VOLTAGE CIRCUIT BREAKER PAGE:4 of 10 NOTES / RECOMMENDATIONS Co m m e n t s De f i c i e n c i e s Cr i t i c a l D e f i c i e n c i e s Tested By:Witnessed By: Reviewed By:Name Name Name RECOMMENDATIONS: *STATUS: A-ACCEPTABLE C-CORRECTED NIS-NOT IN SCOPE NA-NOT APPLICABLE NAC-NOT ACCESSIBLE R-REPAIR, REPLACE, OR ADJUST ALEXANDER JACKSON Acceptable EQUIPMENT DATA SERIAL NO.: 65 KA @ 400 AMPSSYS. VOLTS -400 MAX AMPS:CAT./TYPE:400 600MAX VOLTS:SQUARE D LJA36400U31XYP AIC: BREAKER TYPE:INSULATED / MOLDED CASE BREAKERPOWER BREAKER LSIG SETTINGS: 480 L - LONG TIME S - SHORT TIME I - INSTANTANEOUS G - GROUND FAULT RATING PLUG: TRIP / SENS. RATING:MFR: TRIP UNIT TYPE:Solid State AMPS PART NUMBER:MICROLOGIC 3.3 BOLTED @SHUNT:NO UVR:NA NA@CONNECT:AUX SWITCHES:-NO AS FOUND AS LEFT AS FOUNDRANGES AS LEFTRANGES (225 (AMPS)LT DELAY (LTD)0.5-16 0.5 0.5AMPS)225125-400LONG TIME PICKUP (LTPU) INST. PU (IPU)Plug Sen LTPU AMPS)2,00052,000(AMPS)5 (1.5-12 STATUS NAMEPLATE VS DRAWINGS DRAWOUT MECHANISM EXTERIOR CONDITION PRIMARY CONNECTIONS SECONDARY DISCONNECT MAIN / ARCING CONTACTS NOTESITEM SPRING CHARGING MOTOR INTERLOCKS SHUNT TRIP / CLOSE AUXILIARY FEATURES SUCH AS ZSI & ANTIPUMP LUBRICATION MECHANISM OPERATION INDICATORS (CLOSE/OPEN, CHARGE/DISCHARGE) ITEM A NA A NAC NAC NA A NAC NA A NA A NA NA NOTES VISUAL & MECHANICAL INSPECTION ARC CHUTES STATUS 4522 1 1/5/20222015-64 CONTACT RESISTANCE:1/5/2022 2011-1092006-09 INSULATION RESISTANCE: RELATIVE HUMIDITY:AMBIENT TEMP.:%°C 2/23/2022 SEC.CURRENT INJECTION:0PRI.CURRENT INJECTION: TEST EQUIPMENT: ASSET NO. / CALIBRATION DUE DATE TEST RESULTS Results UNITS NOTESBYMIN/MAX TOLERANCE SECONDARY INJ.CURRENT INJECTION TEST AMPSTEST POINT % TEST METHOD PRIMARY INJ. TESTED @ SETTINGS 0.5 Mfr Mfr 125 %AMPS SECONDS - - 125 1.5 2.25 150 1.813LONG TIME (LT) DELAY LONG TIME (LT) PICKUP 148 375 125 % 100 300 AMPS Mfr600-540 660653INSTANTANEOUS PICKUP 600%100 PHASE ACCURACY MICROOHMS MILLIVOLTS @ VDC 9,999  9,999 ±50% 9,999  C-CB-B 9,999 A-A 9,999 BREAKER OPEN B-C 9,999 C-A 9,9999,999 C-GNDB-GNDA-GND BREAKER CLOSED CONTACT RESISTANCE INSULATION RESISTANCE 1,000 NETA NETA 100 3835 LTPU STPU GFPU A 147148 147 CB 9,999 A-B 41 MfrMETER INSTANTANEOUS -150125 CORONA DEL MAR, CA 92625ROSENDIN ELECTRIC FILE NUMBER: ROSENDIN ELECTRIC HARBOR DAY SCHOOL 6/2/2021 POSITION:HMDPB CLIENT: MSBLOCATION: TEST DATE:JOB SITE: SUB./BOARD: HARBOR DAY SCHOOLCR#:21E149-B-FR0 LOW VOLTAGE CIRCUIT BREAKER PAGE:5 of 10 NOTES / RECOMMENDATIONS Co m m e n t s De f i c i e n c i e s Cr i t i c a l D e f i c i e n c i e s 1 CIRCUIT BREAKER PROVIDES NO INDICATION OF LONG TIME PICKUP. Tested By:Witnessed By: Reviewed By:Name Name Name RECOMMENDATIONS: *STATUS: A-ACCEPTABLE C-CORRECTED NIS-NOT IN SCOPE NA-NOT APPLICABLE NAC-NOT ACCESSIBLE R-REPAIR, REPLACE, OR ADJUST ALEXANDER JACKSON Acceptable EQUIPMENT DATA SERIAL NO.: 65 KA @ 800 AMPSSYS. VOLTS -800 MAX AMPS:CAT./TYPE:800 600MAX VOLTS:SQUARE D MJA36800YP AIC: BREAKER TYPE:INSULATED / MOLDED CASE BREAKERPOWER BREAKER LSIG SETTINGS: 480 L - LONG TIME S - SHORT TIME I - INSTANTANEOUS G - GROUND FAULT RATING PLUG: TRIP / SENS. RATING:MFR: TRIP UNIT TYPE:Thermal AMPS PART NUMBER:ET 1.0 BOLTED @SHUNT:NO UVR:NA NA@CONNECT:AUX SWITCHES:-NO AS FOUND AS LEFT AS FOUNDRANGES AS LEFTRANGES (800 (AMPS)LT DELAY (LTD)FIXED FIXED FIXEDAMPS)800FIXEDLONG TIME PICKUP (LTPU) INST. PU (IPU)Plug Sen LTPU AMPS)6,40086,400(AMPS)8 (2-10 STATUSSTATUS NAMEPLATE VS DRAWINGS PHYSICAL & MECHANICAL CONDITION NOTESITEM CB OPERATION ANCHORAGE & ALIGNMENT ITEM A A A A A NA NOTES VISUAL & MECHANICAL INSPECTION CLEANLINESS SHUNT TRIP / CLOSE CONTACT RESISTANCE:1/5/2022 2011-1092006-09 INSULATION RESISTANCE:0 2/23/20222015-64CURRENT INJECTION: TEST EQUIPMENT: ASSET NO. / CALIBRATION DUE DATE 4522RELATIVE HUMIDITY:AMBIENT TEMP.: 1/5/2022 %°C 1 B C TOLERANCE BYMIN/MAX TEST RESULTS TESTPOINT %UNITS NOTESTEST AMPS ACURRENT INJECTION 46.29 46.12 Mfr Mfr % %300 800 2,400 1100LONG TIME (LT) PICKUP LONG TIME (LT) DELAY AMPS SECONDS 960- - 880 40 6545.83 1579 1564 Mfr%1,600100 1651 AMPSINSTANTANEOUS PICKUP 1,760-1,440 MILLIVOLTS @ VDC A-B 9,999 9,999  9,999 MICROOHMS 337 ±50% 9,999  C-CB-B 9,999 A-A 9,999 BREAKER OPEN B-C 9,999 C-A 9,9999,999 C-GNDB-GNDA-GND BREAKER CLOSED CONTACT RESISTANCE INSULATION RESISTANCE 1,000 NETA Mfr 100 323350 CORONA DEL MAR, CA 92625ROSENDIN ELECTRIC FILE NUMBER: ROSENDIN ELECTRIC HARBOR DAY SCHOOL 6/2/2021 POSITION:MAIN CLIENT: MSBLOCATION: TEST DATE:JOB SITE: SUB./BOARD: HARBOR DAY SCHOOLCR#:21E149-B-FR0 LOW VOLTAGE CIRCUIT BREAKER PAGE:6 of 10 NOTES / RECOMMENDATIONS Co m m e n t s De f i c i e n c i e s Cr i t i c a l D e f i c i e n c i e s 1 NEUTRAL CT POLARITY TEST PERFORMED, RESULTS ACCEPTABLE. Tested By:Witnessed By: Reviewed By:Name Name Name RECOMMENDATIONS: *STATUS: A-ACCEPTABLE C-CORRECTED NIS-NOT IN SCOPE NA-NOT APPLICABLE NAC-NOT ACCESSIBLE R-REPAIR, REPLACE, OR ADJUST ALEXANDER JACKSON Acceptable EQUIPMENT DATA SERIAL NO.: 65 KA @ 2,000 AMPSSYS. VOLTS 0202416914260001 2,000 MAX AMPS:CAT./TYPE:2000 600MAX VOLTS:SQUARE D RKF36200U44AYP AIC: BREAKER TYPE:INSULATED / MOLDED CASE BREAKERPOWER BREAKER LSIG SETTINGS: 480 L - LONG TIME S - SHORT TIME I - INSTANTANEOUS G - GROUND FAULT RATING PLUG: TRIP / SENS. RATING:MFR: TRIP UNIT TYPE:Solid State AMPS PART NUMBER:MICROLOGIC 6.0A BOLTED @SHUNT:NO UVR:NA NA@CONNECT:AUX SWITCHES:-NO AS FOUND AS LEFT AS FOUNDRANGES AS LEFTRANGES (2,0001 1 (AMPS)LT DELAY (LTD)0.5-24 8 8AMPS)2,0000.4-1LONG TIME PICKUP (LTPU) SHORT TIME PU (STPU)Sen 4 4AMPS)((8,000 AMPS)8,000 ST DELAY (STD)0-0.4 I/O 0.1 OFF 0.1 OFF1.5-10LTPUPlug INST. PU (IPU)Plug Sen LTPU AMPS)30,0001530,000(AMPS)15 (OFF, 2-15 GROUND FAULT PU (GFPU)Plug Sen x AMPS)AMPS)1,200 1,200A-J (500-1200)J J GF DELAY (GFD)0-0.4 I/O 0.1 OFF 0.1 OFF(( STATUS NAMEPLATE VS DRAWINGS DRAWOUT MECHANISM EXTERIOR CONDITION PRIMARY CONNECTIONS SECONDARY DISCONNECT MAIN / ARCING CONTACTS NOTESITEM SPRING CHARGING MOTOR INTERLOCKS SHUNT TRIP / CLOSE AUXILIARY FEATURES SUCH AS ZSI & ANTIPUMP LUBRICATION MECHANISM OPERATION INDICATORS (CLOSE/OPEN, CHARGE/DISCHARGE) ITEM A NA A NAC NAC NA A NAC NA A NA A NA NA NOTES VISUAL & MECHANICAL INSPECTION ARC CHUTES STATUS 4522 1 20 1/5/20222015-64 CONTACT RESISTANCE:1/5/2022 2011-1092006-09 INSULATION RESISTANCE: RELATIVE HUMIDITY:AMBIENT TEMP.:%°C 2/23/2022 SEC.CURRENT INJECTION:3PRI.CURRENT INJECTION: TEST EQUIPMENT: ASSET NO. / CALIBRATION DUE DATE TEST RESULTS Results UNITS NOTESBYMIN/MAX TOLERANCE SECONDARY INJ.CURRENT INJECTION TEST AMPSTEST POINT % TEST METHOD PRIMARY INJ. TESTED @ SETTINGS 0.5 Mfr Mfr 800 %AMPS SECONDS - - 880 1.5 2.25 960 1.521LONG TIME (LT) DELAY LONG TIME (LT) PICKUP 918 2,400 800 % 100 300 SECONDS0.1 OFF Mfr Mfr 1,200 % AMPS - - 1,080 0.08 0.14 1,3201,242 0.115 SHORT TIME (ST) PICKUP SHORT TIME (ST) DELAY 1,800 1,200%100 150 AMPS Mfr4,000 -3,600 4,4004,108INSTANTANEOUS PICKUP 4,000%100 GROUND FAULT PICKUP 1AMPS SECONDS0.1 OFF Mfr Mfr 1,200 - - 1,080 0.08 0.14 1,3201,187 GROUND FAULT DELAY 0.122 1,200 1,800 % % 100 150 PHASE ACCURACY MICROOHMS MILLIVOLTS @ VDC 9,999  9,999 ±50% 9,999  C-CB-B 9,999 A-A 9,999 BREAKER OPEN B-C 9,999 C-A 9,9999,999 C-GNDB-GNDA-GND BREAKER CLOSED CONTACT RESISTANCE INSULATION RESISTANCE 1,000 NETA NETA 100 114156 LTPU STPU GFPU A 1,1881,187 1,187 CB 9,999 A-B 123 Mfr 1METER INSTANTANEOUS -1,3201,080 CORONA DEL MAR, CA 92625ROSENDIN ELECTRIC FILE NUMBER: ROSENDIN ELECTRIC HARBOR DAY SCHOOL 6/2/2021 POSITION:TP154 CLIENT: MSBLOCATION: TEST DATE:JOB SITE: SUB./BOARD: HARBOR DAY SCHOOLCR#:21E149-B-FR0 LOW VOLTAGE CIRCUIT BREAKER PAGE:7 of 10 NOTES / RECOMMENDATIONS Co m m e n t s De f i c i e n c i e s Cr i t i c a l D e f i c i e n c i e s Tested By:Witnessed By: Reviewed By:Name Name Name RECOMMENDATIONS: *STATUS: A-ACCEPTABLE C-CORRECTED NIS-NOT IN SCOPE NA-NOT APPLICABLE NAC-NOT ACCESSIBLE R-REPAIR, REPLACE, OR ADJUST ALEXANDER JACKSON Acceptable EQUIPMENT DATA SERIAL NO.: 65 KA @ 400 AMPSSYS. VOLTS -400 MAX AMPS:CAT./TYPE:400 600MAX VOLTS:SQUARE D LJA36400U31XYP AIC: BREAKER TYPE:INSULATED / MOLDED CASE BREAKERPOWER BREAKER LSIG SETTINGS: 480 L - LONG TIME S - SHORT TIME I - INSTANTANEOUS G - GROUND FAULT RATING PLUG: TRIP / SENS. RATING:MFR: TRIP UNIT TYPE:Solid State AMPS PART NUMBER:MICROLOGIC 3.3 BOLTED @SHUNT:NO UVR:NA NA@CONNECT:AUX SWITCHES:-NO AS FOUND AS LEFT AS FOUNDRANGES AS LEFTRANGES (350 (AMPS)LT DELAY (LTD)0.5-16 2 2AMPS)350125-400LONG TIME PICKUP (LTPU) INST. PU (IPU)Plug Sen LTPU AMPS)4,000104,000(AMPS)10 (1.5-12 STATUS NAMEPLATE VS DRAWINGS DRAWOUT MECHANISM EXTERIOR CONDITION PRIMARY CONNECTIONS SECONDARY DISCONNECT MAIN / ARCING CONTACTS NOTESITEM SPRING CHARGING MOTOR INTERLOCKS SHUNT TRIP / CLOSE AUXILIARY FEATURES SUCH AS ZSI & ANTIPUMP LUBRICATION MECHANISM OPERATION INDICATORS (CLOSE/OPEN, CHARGE/DISCHARGE) ITEM A NA A NAC NAC NA A NAC NA A NA A NA NA NOTES VISUAL & MECHANICAL INSPECTION ARC CHUTES STATUS 4522 1 1/5/20222015-64 CONTACT RESISTANCE:1/5/2022 2011-1092006-09 INSULATION RESISTANCE: RELATIVE HUMIDITY:AMBIENT TEMP.:%°C 2/23/2022 SEC.CURRENT INJECTION:0PRI.CURRENT INJECTION: TEST EQUIPMENT: ASSET NO. / CALIBRATION DUE DATE TEST RESULTS Results UNITS NOTESBYMIN/MAX TOLERANCE SECONDARY INJ.CURRENT INJECTION TEST AMPSTEST POINT % TEST METHOD PRIMARY INJ. TESTED @ SETTINGS 0.5 Mfr Mfr 125 %AMPS SECONDS - - 125 1.5 2.25 150 1.839LONG TIME (LT) DELAY LONG TIME (LT) PICKUP 146 375 125 % 100 300 AMPS Mfr600-540 660650INSTANTANEOUS PICKUP 600%100 PHASE ACCURACY MICROOHMS MILLIVOLTS @ VDC 9,999  9,999 ±50% 9,999  C-CB-B 9,999 A-A 9,999 BREAKER OPEN B-C 9,999 C-A 9,9999,999 C-GNDB-GNDA-GND BREAKER CLOSED CONTACT RESISTANCE INSULATION RESISTANCE 1,000 NETA NETA 100 3534 LTPU STPU GFPU A 146146 145 CB 9,999 A-B 43 MfrMETER INSTANTANEOUS -150125 CORONA DEL MAR, CA 92625ROSENDIN ELECTRIC FILE NUMBER: ROSENDIN ELECTRIC HARBOR DAY SCHOOL 6/2/2021 POSITION:TP1S5 CLIENT: MSBLOCATION: TEST DATE:JOB SITE: SUB./BOARD: HARBOR DAY SCHOOLCR#:21E149-B-FR0 LOW VOLTAGE CIRCUIT BREAKER PAGE:8 of 10 NOTES / RECOMMENDATIONS Co m m e n t s De f i c i e n c i e s Cr i t i c a l D e f i c i e n c i e s Tested By:Witnessed By: Reviewed By:Name Name Name RECOMMENDATIONS: *STATUS: A-ACCEPTABLE C-CORRECTED NIS-NOT IN SCOPE NA-NOT APPLICABLE NAC-NOT ACCESSIBLE R-REPAIR, REPLACE, OR ADJUST ALEXANDER JACKSON Acceptable EQUIPMENT DATA SERIAL NO.: 65 KA @ 250 AMPSSYS. VOLTS -250 MAX AMPS:CAT./TYPE:250 600MAX VOLTS:SQUARE D JJA36250U31XYP AIC: BREAKER TYPE:INSULATED / MOLDED CASE BREAKERPOWER BREAKER LSIG SETTINGS: 480 L - LONG TIME S - SHORT TIME I - INSTANTANEOUS G - GROUND FAULT RATING PLUG: TRIP / SENS. RATING:MFR: TRIP UNIT TYPE:Solid State AMPS PART NUMBER:MICROLOGIC 3.2 BOLTED @SHUNT:NO UVR:NA NA@CONNECT:AUX SWITCHES:-NO AS FOUND AS LEFT AS FOUNDRANGES AS LEFTRANGES (225 (AMPS)LT DELAY (LTD)0.5-16 4 4AMPS)22570-250LONG TIME PICKUP (LTPU) INST. PU (IPU)Plug Sen LTPU AMPS)3,000123,000(AMPS)12 (1.5-12 STATUS NAMEPLATE VS DRAWINGS DRAWOUT MECHANISM EXTERIOR CONDITION PRIMARY CONNECTIONS SECONDARY DISCONNECT MAIN / ARCING CONTACTS NOTESITEM SPRING CHARGING MOTOR INTERLOCKS SHUNT TRIP / CLOSE AUXILIARY FEATURES SUCH AS ZSI & ANTIPUMP LUBRICATION MECHANISM OPERATION INDICATORS (CLOSE/OPEN, CHARGE/DISCHARGE) ITEM A NA A NAC NAC NA A NAC NA A NA A NA NA NOTES VISUAL & MECHANICAL INSPECTION ARC CHUTES STATUS 4522 1 1/5/20222015-64 CONTACT RESISTANCE:1/5/2022 2011-1092006-09 INSULATION RESISTANCE: RELATIVE HUMIDITY:AMBIENT TEMP.:%°C 2/23/2022 SEC.CURRENT INJECTION:0PRI.CURRENT INJECTION: TEST EQUIPMENT: ASSET NO. / CALIBRATION DUE DATE TEST RESULTS Results UNITS NOTESBYMIN/MAX TOLERANCE SECONDARY INJ.CURRENT INJECTION TEST AMPSTEST POINT % TEST METHOD PRIMARY INJ. TESTED @ SETTINGS 0.5 Mfr Mfr 100 %AMPS SECONDS - - 105 1.5 2.25 120 1.855LONG TIME (LT) DELAY LONG TIME (LT) PICKUP 116 300 100 % 100 300 AMPS Mfr375-337.5 412.5397INSTANTANEOUS PICKUP 375%100 PHASE ACCURACY MICROOHMS MILLIVOLTS @ VDC 9,999  9,999 ±50% 9,999  C-CB-B 9,999 A-A 9,999 BREAKER OPEN B-C 9,999 C-A 9,9999,999 C-GNDB-GNDA-GND BREAKER CLOSED CONTACT RESISTANCE INSULATION RESISTANCE 1,000 NETA NETA 100 7370 LTPU STPU GFPU A 116116 116 CB 9,999 A-B 60 MfrMETER INSTANTANEOUS -120105 CORONA DEL MAR, CA 92625ROSENDIN ELECTRIC FILE NUMBER: ROSENDIN ELECTRIC HARBOR DAY SCHOOL 6/2/2021 POSITION:TPA1N CLIENT: MSBLOCATION: TEST DATE:JOB SITE: SUB./BOARD: HARBOR DAY SCHOOLCR#:21E149-B-FR0 LOW VOLTAGE CIRCUIT BREAKER PAGE:9 of 10 NOTES / RECOMMENDATIONS Co m m e n t s De f i c i e n c i e s Cr i t i c a l D e f i c i e n c i e s Tested By:Witnessed By: Reviewed By:Name Name Name RECOMMENDATIONS: *STATUS: A-ACCEPTABLE C-CORRECTED NIS-NOT IN SCOPE NA-NOT APPLICABLE NAC-NOT ACCESSIBLE R-REPAIR, REPLACE, OR ADJUST ALEXANDER JACKSON Acceptable EQUIPMENT DATA SERIAL NO.: 65 KA @ 250 AMPSSYS. VOLTS -250 MAX AMPS:CAT./TYPE:250 600MAX VOLTS:SQUARE D JJA36250U31XYP AIC: BREAKER TYPE:INSULATED / MOLDED CASE BREAKERPOWER BREAKER LSIG SETTINGS: 480 L - LONG TIME S - SHORT TIME I - INSTANTANEOUS G - GROUND FAULT RATING PLUG: TRIP / SENS. RATING:MFR: TRIP UNIT TYPE:Solid State AMPS PART NUMBER:MICROLOGIC 3.2 BOLTED @SHUNT:NO UVR:NA NA@CONNECT:AUX SWITCHES:-NO AS FOUND AS LEFT AS FOUNDRANGES AS LEFTRANGES (175 (AMPS)LT DELAY (LTD)0.5-16 4 4AMPS)17570-250LONG TIME PICKUP (LTPU) INST. PU (IPU)Plug Sen LTPU AMPS)2,500102,500(AMPS)10 (1.5-12 STATUS NAMEPLATE VS DRAWINGS DRAWOUT MECHANISM EXTERIOR CONDITION PRIMARY CONNECTIONS SECONDARY DISCONNECT MAIN / ARCING CONTACTS NOTESITEM SPRING CHARGING MOTOR INTERLOCKS SHUNT TRIP / CLOSE AUXILIARY FEATURES SUCH AS ZSI & ANTIPUMP LUBRICATION MECHANISM OPERATION INDICATORS (CLOSE/OPEN, CHARGE/DISCHARGE) ITEM A NA A NAC NAC NA A NAC NA A NA A NA NA NOTES VISUAL & MECHANICAL INSPECTION ARC CHUTES STATUS 4522 1 1/5/20222015-64 CONTACT RESISTANCE:1/5/2022 2011-1092006-09 INSULATION RESISTANCE: RELATIVE HUMIDITY:AMBIENT TEMP.:%°C 2/23/2022 SEC.CURRENT INJECTION:0PRI.CURRENT INJECTION: TEST EQUIPMENT: ASSET NO. / CALIBRATION DUE DATE TEST RESULTS Results UNITS NOTESBYMIN/MAX TOLERANCE SECONDARY INJ.CURRENT INJECTION TEST AMPSTEST POINT % TEST METHOD PRIMARY INJ. TESTED @ SETTINGS 0.5 Mfr Mfr 100 %AMPS SECONDS - - 105 1.5 2.25 120 1.829LONG TIME (LT) DELAY LONG TIME (LT) PICKUP 119 300 100 % 100 300 AMPS Mfr375-337.5 412.5400INSTANTANEOUS PICKUP 375%100 PHASE ACCURACY MICROOHMS MILLIVOLTS @ VDC 9,999  9,999 ±50% 9,999  C-CB-B 9,999 A-A 9,999 BREAKER OPEN B-C 9,999 C-A 9,9999,999 C-GNDB-GNDA-GND BREAKER CLOSED CONTACT RESISTANCE INSULATION RESISTANCE 1,000 NETA NETA 100 4046 LTPU STPU GFPU A 118119 118 CB 9,999 A-B 48 MfrMETER INSTANTANEOUS -120105 CORONA DEL MAR, CA 92625ROSENDIN ELECTRIC FILE NUMBER: ROSENDIN ELECTRIC HARBOR DAY SCHOOL 6/2/2021 POSITION:TPA1S CLIENT: MSBLOCATION: TEST DATE:JOB SITE: SUB./BOARD: HARBOR DAY SCHOOLCR#:21E149-B-FR0 LOW VOLTAGE CIRCUIT BREAKER PAGE:10 of 10 NOTES / RECOMMENDATIONS Co m m e n t s De f i c i e n c i e s Cr i t i c a l D e f i c i e n c i e s Tested By:Witnessed By: Reviewed By:Name Name Name RECOMMENDATIONS: *STATUS: A-ACCEPTABLE C-CORRECTED NIS-NOT IN SCOPE NA-NOT APPLICABLE NAC-NOT ACCESSIBLE R-REPAIR, REPLACE, OR ADJUST ALEXANDER JACKSON Acceptable EQUIPMENT DATA SERIAL NO.: 65 KA @ 250 AMPSSYS. VOLTS -250 MAX AMPS:CAT./TYPE:250 600MAX VOLTS:SQUARE D JJA36250U31XYP AIC: BREAKER TYPE:INSULATED / MOLDED CASE BREAKERPOWER BREAKER LSIG SETTINGS: 480 L - LONG TIME S - SHORT TIME I - INSTANTANEOUS G - GROUND FAULT RATING PLUG: TRIP / SENS. RATING:MFR: TRIP UNIT TYPE:Solid State AMPS PART NUMBER:MICROLOGIC 3.2 BOLTED @SHUNT:NO UVR:NA NA@CONNECT:AUX SWITCHES:-NO AS FOUND AS LEFT AS FOUNDRANGES AS LEFTRANGES (225 (AMPS)LT DELAY (LTD)0.5-16 4 4AMPS)22570-250LONG TIME PICKUP (LTPU) INST. PU (IPU)Plug Sen LTPU AMPS)3,000123,000(AMPS)12 (1.5-12 STATUS NAMEPLATE VS DRAWINGS DRAWOUT MECHANISM EXTERIOR CONDITION PRIMARY CONNECTIONS SECONDARY DISCONNECT MAIN / ARCING CONTACTS NOTESITEM SPRING CHARGING MOTOR INTERLOCKS SHUNT TRIP / CLOSE AUXILIARY FEATURES SUCH AS ZSI & ANTIPUMP LUBRICATION MECHANISM OPERATION INDICATORS (CLOSE/OPEN, CHARGE/DISCHARGE) ITEM A NA A NAC NAC NA A NAC NA A NA A NA NA NOTES VISUAL & MECHANICAL INSPECTION ARC CHUTES STATUS 4522 1 1/5/20222015-64 CONTACT RESISTANCE:1/5/2022 2011-1092006-09 INSULATION RESISTANCE: RELATIVE HUMIDITY:AMBIENT TEMP.:%°C 2/23/2022 SEC.CURRENT INJECTION:0PRI.CURRENT INJECTION: TEST EQUIPMENT: ASSET NO. / CALIBRATION DUE DATE TEST RESULTS Results UNITS NOTESBYMIN/MAX TOLERANCE SECONDARY INJ.CURRENT INJECTION TEST AMPSTEST POINT % TEST METHOD PRIMARY INJ. TESTED @ SETTINGS 0.5 Mfr Mfr 100 %AMPS SECONDS - - 105 1.5 2.25 120 1.753LONG TIME (LT) DELAY LONG TIME (LT) PICKUP 116 300 100 % 100 300 AMPS Mfr375-337.5 412.5401INSTANTANEOUS PICKUP 375%100 PHASE ACCURACY MICROOHMS MILLIVOLTS @ VDC 9,999  9,999 ±50% 9,999  C-CB-B 9,999 A-A 9,999 BREAKER OPEN B-C 9,999 C-A 9,9999,999 C-GNDB-GNDA-GND BREAKER CLOSED CONTACT RESISTANCE INSULATION RESISTANCE 1,000 NETA NETA 100 4141 LTPU STPU GFPU A 114116 114 CB 9,999 A-B 44 MfrMETER INSTANTANEOUS -120105 Appendix “A2” Frequency of Maintenance Testing APPENDIX B Frequency of Maintenance Tests Page 256 ANSI/NETA MTS-2019 NETA recognizes that the ideal maintenance program is reliability-based, unique to each plant and to each piece of equipment. NETA’s Standards Review Council presents the following time-based maintenance schedule and matrix. One should contact a NETA Accredited Company for a reliability-based evaluation. The following matrix is to be used in conjunction with Appendix B, Inspections and Tests. Application of the matrix is recognized as a guide only. Specific condition, criticality, and desired reliability must be determined to correctly apply the matrix. Application of the matrix, along with the culmination of historical testing data and trending, should provide a quality electrical preventive maintenance program. MAINTENANCE FREQUENCY MATRIX Equipment Condition Poor Average Good Eq u i p m e n t Re l i a b i l i t y Re q u i r e m e n t Low 1.0 2.0 2.5 Medium 0.50 1.0 1.5 High 0.25 0.50 0.75 Page 257 ANSI/NETA MTS-2019 APPENDIX B Frequency of Maintenance Tests Inspections and Tests Frequency in Months (Multiply These Values by the Factor in the Maintenance Frequency Matrix) Section Description Visual Visual & Mechanical Visual & Mechanical & Electrical 7.1 Switchgear & Switchboard Assemblies 12 12 24 7.2 Transformers 7.2.1.1 Small Dry-Type Transformers 2 12 36 7.2.1.2 Large Dry-Type Transformers 1 12 24 7.2.2 Liquid-Filled Transformers 1 12 24 Sampling – – 12 7.3 Cables 7.3.1 Low-Voltage, Low-Energy – – – 7.3.2 Low-Voltage, 600-Volt Maximum 2 12 36 7.3.3 Medium- and High-Voltage 2 12 36 7.4 Metal-Enclosed Busways 2 12 24 Infrared Only – – 12 7.5 Switches 7.5.1.1 Air, Low-Voltage 2 12 36 7.5.1.2 Air, Medium-Voltage, Metal-Enclosed – 12 24 7.5.1.3 Air, Medium- and High-Voltage Open 1 12 24 7.5.2 Oil, Medium-Voltage 1 12 24 7.5.3 Vacuum, Medium-Voltage 1 12 24 7.5.4 Medium-Voltage, SF6 1 12 24 7.5.5 Cutouts 12 24 24 7.6 Circuit Breakers 7.6.1.1 Air, Insulated-Case/Molded-Case 1 12 36 7.6.1.2 Air, Low-Voltage Power 1 12 36 7.6.1.3 Air, Medium-Voltage 1 12 36 7.6.2 Oil, Medium-Voltage 1 12 36 Sampling – – 12 7.6.2 Oil, High-Voltage 1 12 12 Sampling – – 12 7.6.3 Vacuum, Medium-Voltage 1 12 24 7.6.4 SF6 1 12 12 7.7 Circuit Switchers 1 12 12 7.8 Network Protectors 12 12 24 Page 258 ANSI/NETA MTS-2019 APPENDIX B Frequency of Maintenance Tests (continued) Inspections and Tests Frequency in Months (Multiply These Values by the Factor in the Maintenance Frequency Matrix) Section Description Visual Visual & Mechanical Visual & Mechanical & Electrical 7.9 Protective Relays 7.9.1 Electromechanical and Solid State 1 12 12 7.9.2 Microprocessor-Based 1 12 12 7.10 Instrument Transformers 7.10.1 Current Transformers 12 12 36 7.10.2 Voltage Transformers 12 12 36 7.10.3 Coupling-Capacitor Transformers 12 12 36 7.11 Metering Devices 7.11.1 Electromechanical and Solid-State 12 12 36 7.11.2 Microprocessor-Based 12 12 36 7.12 Regulating Apparatus 7.12.1.1 Step-Voltage Regulators 1 12 24 Sample Liquid – – 12 7.12.1.2 Induction Regulators 12 12 24 7.12.2 Current Regulators 1 12 24 7.12.3 Load Tap-changers 1 12 24 Sample Liquid – – 12 7.13 Grounding Systems 2 12 24 7.14 Ground-Fault Protection Systems 2 12 12 7.15 Rotating Machinery 7.15.1 AC Induction Motors and Generators 1 12 24 7.15.2 Synchronous Motors and Generators 1 12 24 7.15.3 DC Motors and Generators 1 12 24 7.16 Motor Control 7.16.1.1 Motor Starters, Low-Voltage 2 12 24 7.16.1.2 Motor Starters, Medium-Voltage 2 12 24 7.16.2.1 Motor Control Centers, Low-Voltage 2 12 24 7.16.2.2 Motor Control Centers, Medium-Voltage 2 12 24 7.17 Adjustable-Speed Drive Systems 1 12 24 7.18 Direct-Current Systems 7.18.1 Batteries 7.18.1.1 Flooded Lead-Acid 1 12 12 7.18.1.2 Vented Nickel-Cadmium 1 12 12 7.18.1.3 Valve-Regulated Lead-Acid 1 12 12 7.18.2 Battery Chargers 1 12 12 Page 259 ANSI/NETA MTS-2019 APPENDIX B Frequency of Maintenance Tests (continued) Inspections and Tests Frequency in Months (Multiply These Values by the Factor in the Maintenance Frequency Matrix) Section Description Visual Visual & Mechanical Visual & Mechanical & Electrical 7.18.3 Rectifiers 1 12 24 7.19 Surge Arresters 7.19.1 Low-Voltage Surge Protection Devices 2 12 24 7.19.2 Medium- and High-Voltage Surge Protection Devices 2 12 24 7.20 Capacitors and Reactors 7.20.1 Capacitors 1 12 12 7.20.2 Capacitor Control Devices 1 12 12 7.20.3.1 Reactors, (Shunt and Current-Limiting) Dry- Type 2 12 24 7.20.3.2 Reactors, (Shunt and Current-Limiting) Liquid- Filled 1 12 24 Sampling – – 12 7.21 Outdoor Bus Structures 1 12 36 7.22 Emergency Systems 7.22.1 Engine Generator 1 2 12 Functional Testing – – 2 7.22.2 Uninterruptible Power Systems 1 12 12 Functional Testing – – 2 7.22.3 Automatic Transfer Switches 1 12 12 Functional Testing – – 2 7.23 Communications - Reserved 7.24 Automatic Circuit Reclosers and Line Sectionalizers 7.24.1 Automatic Circuit Reclosers, Oil/Vacuum 1 12 24 Sample – – 12 7.24.2 Automatic Line Sectionalizers, Oil 1 12 24 Sample – – 12 9. Thermographic Survey – 12 – 10. Electromagnetic Field Survey – As Needed – – – 11. Online Partial Discharge Survey for Switchgear – – 12 Page 260 ANSI/NETA MTS-2019 APPENDIX C Frequency of Power System Studies Frequency Matrix Circumstance One-Line Diagram Update Short- circuit Study Coordination Study Incident Energy Analysis Load Flow Study New installation or system modification X X X X X Annual data verification X X X X X Change in utility or source X X X X X Change in system impedance, configuration, or loading1 X X X Change in protection devices or settings X X X X 5 years since last update X X X Notes: 1. Examples of changes: switch between delta and wye, solidly-grounded to resistance-grounded, kVA change, impedance, conductor length or size, adding motors, replacing motors with high- efficiency motors, change in horsepower, adding or removing power-factor correction capacitors.