HomeMy WebLinkAbout7.02_Misc Files (TAB Chlorination)_20360 Harbor Day Certified 11-15-2021# #
AIR BALANCE CO., INC.
PROFESSIONAL AIR & HYDRONIG SYSTEM TESTING • BUILDING SYSTEMS COMMISSIONING
CERTIFIED TEST,
ADJUST & BALANCE REPORT
PROJECT
PROJECT/JOB#
CONTRACTOR
ARCHITECT
ENGINEER
CERTIFICATION:
The data presented in this report is a record of system measurements and final adjustments that have been
obtained in accordance with the current edition of the NEBB Procedural Standard for Testing, Adjusting and
Balancing of Environmental Systems. The measurements shown, and the information given, in this report are
certified to be accurate and complete, at the time and date the information was gathered. Any variances from
design quantities, which exceed NEBB tolerances, are noted in the TAB report project summary.
NEBB CERTIFICATION NUMBER 2756
TECHNICIAN
APPROVED
DATE
RTIRCATIO
3/31/22
dronic
1240 N. Jefferson St., Suite H • Anatneim, CA92807-1632 • Ptione (714) 630-3796 • Fax (714) 630-3998
3330 W. Hacienda Ave., Suite 407 • Las Vegas, NV 89118 • Phone (702)270-2688 • Fax (702) 270-0788
7525 Mission Gorge Rd., Suite E • San Diego, CA 92120 • Phone (800) 339-3796
www.precisionairbalance.com Email: sales@precisionairbalance.com
CA STATE LICENSE #633805
ACCO ENGINEERED SYSTEMS
888 EAST WALNUT ST., PASADENA, CA 91101
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR., CORONA DEL MAR, CA 92625
20360
NOT AVAILABLE
ACCO ENGINEERED SYSTEMS
J. HOWARD
D. FOX
11/15/2021
(' P�m� AIR BALANCE co .• INC.
PROFESSIONAL AIR & HYDRONIC SYSTEM TESTING• BUILDING SYSTEMS COMMISSIONING
INSTRUMENTATION LIST
INSTRUMENT MANUFACTURER MODEL# SERIAL# CALIBRATION
DUE DATE
AMP PROBE FLUKE 373 38750507 12/23/2021
AIR DATA MULTIMETER SHORTRIDGE ADM-860 M88050 12/22/2021
DIGITAL ANEMOMETER ALNOR TSI INC. RVA801 A04780 6/17/2022
TACHOMETER HERMAN STICHT MT-1B B16C85068P 12/23/2021
-WDRONIC MANOMETEF ALNOR TSI INC.HM-685 72025020 7/27/2022
HOOD #18
J.HOWARD
1240 N. Jefferson St., Suite H • Anaheim, CA 92807-1632 • Phone (714) 630-3796 • Fax (714) 630-3998
3330 W. Hacienda Ave., Suite 407 • Las Vegas, NV 89118 • Phone (702) 270-2688 • Fax (702) 270-0788 7525 Mission Gorge Rd., Suite E • San Diego, CA 92120 • Phone (800) 339-3796 www.precisionairbalance.com Email: sales@precisionairbalance.com
CA STATE LICENSE #633805
AIR BALANCE CO-, INC.
PROFESSIONAL AIR & HYDRONIC SYSTEM TESTING • BUILDING SYSTEMS COMMISSIONING
Ni
MASTER CODE SHEETS
AIR DISTRIBUTION CODES
CD CEILING DIFFUSER
CG CEILING GRILLE
CR CEILING REGISTER
RG RETURN GRILLE
SR SUPPLY REGISTER
RR RETURN REGISTER
DO DUCT OPENING
FG FLOOR GRILLE
FR FLOOR REGISTER
AB AIR BAR
LR LINEAR RETURN
LD LINEAR DIFFUSER
EG EXHAUST GRILLE
ER EXHAUST REGISTER
SG SUPPLY GRILLE
SO SCREENED OPENING
HO HOOD OPENING
LT LIGHT TROFFER
DT DUCT TRAVERSE
FO FILTER OPENING
1240 N. Jefferson St., Suite H • Anaheim. CA 92807-1632 • Phone (714) 630-3796 • Fax (714) 630-3998
^ 3330 W. Hacienda Ave., Suite 407 • Las Vegas. NV 89118 • Phone (702) 270-2688 • Fax (702) 270-0788
7525 Mission Gorge Rd., Suite E • San Diego. CA 92120 • Phone (800) 339-3796
www.precisionairbalance.com Emaii: saies@prectsionairbalance.com
* CA STATE LICENSE #633805
Date:10/25/2021
Page:1
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 265 273 1,250 1,290
Total CFM - Outlet 265 273 1,260 1,290
R/A CFM NS 252 NS 1,017
O/A CFM 20 22 (3)270 273 (3)
Static Pressure (Total/Ext)0.00"DUCTLESS 0.35"0.44"
Inlet Pressure DUCTLESS -0.15"
Discharge Pressure DUCTLESS 0.29"
Fan RPM 3 SPEED HIGH SPD.(1)3 SPEED HIGH SPD.(2)
Specified Actual Specified Actual
Motor Manufacturer NS NA
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 206
Amperage 0.2 0.1 2.5 1.4
Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
AIR MOVING EQUIPMENT TEST SHEET
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
(3) FOR O.S.A. SEE SF 1-1 AIR DISTRIBUTION SHEET.
(2) CODE 3 / FAN SPEED 4 / 106 ESP SETTING. ALL FAN SPEEDS SET TO 106 ESP.
(1) CODE 3 / FAN SPEED 4 / 47 ESP SETTING. ALL FAN SPEEDS SET TO 47 ESP
DIRECT DRIVEDIRECT DRIVE
011KCY1C282
ARNU283M3A4
LG
100 L0BBY
100 LOBBY
DIRECT DRIVEDIRECT DRIVE
SYSTEM FC-A1-1
130D ADMISSIONS DIRECTOR
130D ADMISSIONS DIRECTOR
FC-A1-2
DIRECT DRIVEDIRECT DRIVE
LG
ARNU053TRD4
011KCPY0U184
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
100A 1 DO 14" X 14"1.36 195 265 201 273
TOTAL (265)(273)
REMARKS:
10/25/2021
AIR DISTRIBUTION
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
2
FC-A1-1
HARBOR DAY SCHOOL
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
100 1 CD 2410 1.0 *420 *437
100 2 CD 2410 1.0 *420 *432
100 3 CD 2410 1.0 *420 *421
TOTAL (1,260)(1,290)
REMARKS:
10/25/2021
3
FC-A1-2
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/25/2021
Page:4
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 265 272 285 292
Total CFM - Outlet 265 272 285 292
R/A CFM NS 237 285 292
O/A CFM 35 38 (3)0 0 (4)
Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS
Inlet Pressure DUCTLESS DUCTLESS
Discharge Pressure DUCTLESS DUCTLESS
Fan RPM 3 SPEED HIGH SPD.(1)3 SPEED HIGH SPD.(2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 206
Amperage 0.2 0.1 0.2 0.1
Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-A1-3 FC-A1-4
101 NURSE 107 CONFERENCE ROOM
101 NURSE 107 CONFERENCE ROOM
LG LG
ARNU073TRD4 ARNU093TRD4
010KCLH0D304 012KCJZ0TW80
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3 / FAN SPEED 4 / 49 ESP SETTING. ALL FAN SPEEDS SET TO 49 ESP
(2) CODE 3 / FAN SPEED 4 / 55 ESP SETTING. ALL FAN SPEEDS SET TO 55 ESP.
(3) FOR O.S.A. SEE SF 1-1 AIR DISTRIBUTION SHEET.
(4) O.S.A. SUPPLIED BY SF 1-1 WITH SEPARATE SUPPLY GRILLE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
101 1 DO 14" X 14"1.36 195 265 200 272
TOTAL (265)(272)
REMARKS:
10/25/2021
5
FC-A1-3
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
107 1 DO 14" X 14"1.36 210 285 215 292
TOTAL (285)(292)
REMARKS:
10/25/2021
6
FC-A1-4
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/25/2021
Page:7
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 265 272 310 302
Total CFM - Outlet 265 272 310 302
R/A CFM NS 245 310 302
O/A CFM 25 27 (3)0 0 (4)
Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS
Inlet Pressure DUCTLESS DUCTLESS
Discharge Pressure DUCTLESS DUCTLESS
Fan RPM 3 SPEED HIGH SPD.(1)3 SPEED HIGH SPD.(2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 206
Amperage 0.2 0.1 0.2 0.1
Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-A1-5 FC-A1-6
102 LOWER DIRECTOR 159 OPEN OFFICE
102 LOWER DIRECTOR 159 OPEN OFFICE
LG LG
ARNU053TRD4 ARNU123TRD4
011KCYQU186 012KCLH0UT76
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3 / FAN SPEED 4 / 49 ESP SETTING. ALL FAN SPEEDS SET TO 49 ESP
(2) CODE 3 / FAN SPEED 4 / 58 ESP SETTING. ALL FAN SPEEDS SET TO 58 ESP.
(3) FOR O.S.A. SEE SF 1-1 AIR DISTRIBUTION SHEET.
(3) O.S.A. SUPPLIED BY SF 1-1 WITH SEPARATE SUPPLY GRILLE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
102 1 DO 14" X 14"1.36 195 265 200 272
TOTAL (265)(272)
REMARKS:
10/25/2021
8
FC-A1-5
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
159 1 DO 14" X 14"1.36 228 310 222 302
TOTAL (310)(302)
REMARKS:
10/25/2021
9
FC-A1-7
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/25/2021
Page:10
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 265 269 265 267
Total CFM - Outlet 265 269 265 267
R/A CFM NS 236 NS 234
O/A CFM 30 33 (3)35 33 (3)
Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS
Inlet Pressure DUCTLESS DUCTLESS
Discharge Pressure DUCTLESS DUCTLESS
Fan RPM 3 SPEED HIGH SPD.(1)3 SPEED HIGH SPD.(2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 206
Amperage 0.2 0.1 0.2 0.1
Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-A1-7 FC-A1-8
103 HEAD ASSISTANT 104 HEAD OF SCHOOL
103 HEAD ASSISTANT 104 HEAD OF SCHOOL
LG LG
ARNU053TRD4 ARNU073TRD4
011KCPY0U184 010KCUK0D310
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3 / FAN SPEED 4 / 51 ESP SETTING. ALL FAN SPEEDS SET TO 51 ESP
(2) CODE 3 / FAN SPEED 4 / 53 ESP SETTING. ALL FAN SPEEDS SET TO 53 ESP.
(3) FOR O.S.A. SEE SF 1-1 AIR DISTRIBUTION SHEET.
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
103 1 DO 14" X 14"1.36 195 265 198 269
TOTAL (265)(269)
REMARKS:
10/25/2021
11
FC-A1-7
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
104 1 DO 14" X 14"1.36 195 265 196 267
TOTAL (265)(267)
REMARKS:
10/25/2021
12
FC-A1-8
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/25/2021
Page:13
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 265 272 310 320
Total CFM - Outlet 265 272 310 320
R/A CFM NS 252 310 320
O/A CFM 20 22 (3)0 0 (4)
Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS
Inlet Pressure DUCTLESS DUCTLESS
Discharge Pressure DUCTLESS DUCTLESS
Fan RPM 3 SPEED HIGH SPD.(1)3 SPEED HIGH SPD.(2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 206
Amperage 0.2 0.1 0.2 0.1
Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-A1-9 FC-A1-10
105 FACILITIES DIRECTOR 106 WORKROOM
105 FACILITIES DIRECTOR 106 WORKROOM
LG LG
ARNU053TRD4 ARNU123TRD4
011KCVU0U159 012KCXM0U018
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3 / FAN SPEED 4 / 50 ESP SETTING. ALL FAN SPEEDS SET TO 50 ESP
(2) CODE 3 / FAN SPEED 4 / 60 ESP SETTING. ALL FAN SPEEDS SET TO 60 ESP.
(3) FOR O.S.A. SEE SF 1-1 AIR DISTRIBUTION SHEET.
(4) O.S.A. SUPPLIED BY SF 1-1 WITH SEPARATE SUPPLY GRILLE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
105 1 DO 14" X 14"1.36 195 265 200 272
TOTAL (265)(272)
REMARKS:
10/25/2021
14
FC-A1-9
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
106 1 DO 14" X 14"1.36 228 310 235 320
TOTAL (310)(320)
REMARKS:
10/25/2021
15
FC-A1-10
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/5/2021
Page:16
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 240 260 918 950
Total CFM - Outlet 240 260 918 950
R/A CFM 240 260 918 950
O/A CFM -0--0--0--0-
Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS
Inlet Pressure DUCTLESS DUCTLESS
Discharge Pressure DUCTLESS DUCTLESS
Fan RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 209 208/230 209
Amperage 0.25 0.1 0.81 0.6
Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-A1-11 FC-A1-12
109 DATA 110 ELECTRICAL
109 DATA 110 ELECTRICAL
LG LG
ARNU123TRD4 ARNU363SVA4
011KCJZ0RR80 903KCCV0UB91
DIRECT DRIVE DIRECT DRIVE
(2) CODE 3/ FAN SPEED 4/ 95 ESP SETTING. ALL FAN SPEEDS SET TO 95 ESP
(2) CODE 3/ FAN SPEED 4/ 185 ESP SETTING. ALL FAN SPEEDS SET TO 185 ESP
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
110 1 S.O.23" X 3"0.48 500 240 533 260
TOTAL (240)(260)
REMARKS:
11/5/2021
17
FC-A1-12
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
110 1 S.O.30 1/2 X 3 1/2 0.74 1,240 918 1,283 950
TOTAL (918)(950)
REMARKS:
11/5/2021
18
FC-A1-12
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/25/2021
Page:19
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 310 315 265 279
Total CFM - Outlet 310 315 265 279
R/A CFM 310 315 NS 246
O/A CFM 0 0 (3)30 33 (4)
Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS
Inlet Pressure DUCTLESS DUCTLESS
Discharge Pressure DUCTLESS DUCTLESS
Fan RPM 3 SPEED HIGH SPD.(1)3 SPEED HIGH SPD.(2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 206
Amperage 0.2 0.1 0.2 0.1
Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (1)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-A1-13 FC-A1-14
134 ASSOCIATES 137A PSYCH
134 ASSOCIATES 137A PSYCH
LG LG
ARNU123TRD4 ARNU053TRD4
012KCJZ0U044 011KCCV0U211
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3 / FAN SPEED 4 / 61 ESP SETTING. ALL FAN SPEEDS SET TO 61 ESP
(2) CODE 3 / FAN SPEED 4 / 51 ESP SETTING. ALL FAN SPEEDS SET TO 51 ESP.
(3) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE
(4) FOR O.S.A. SEE SF 1-2 AIR DISTRIBUTION SHEET.
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
134 1 DO 14" X 14"1.36 228 310 231 315
TOTAL (310)(315)
REMARKS:
10/25/2021
20
FC-A1-13
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
137A 1 DO 14" X 14"1.36 195 265 205 279
TOTAL (265)(279)
REMARKS:
10/25/2021
21
FC-A1-14
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/25/2021
Page:22
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 265 274 310 309
Total CFM - Outlet 265 274 310 309
R/A CFM NS 246 310 309
O/A CFM 30 28 (3)0 0 (4)
Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS
Inlet Pressure DUCTLESS DUCTLESS
Discharge Pressure DUCTLESS DUCTLESS
Fan RPM 3 SPEED HIGH SPD.(1)3 SPEED HIGH SPD.(2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 206
Amperage 0.2 0.1 0.2 0.1
Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-A1-15 FC-A1-16
137B LANGUAGE ARTS SPECIALIST 137 SMALL GROUP AREA
137B LANGUAGE ARTS SPECIALIST 137 SMALL GROUP AREA
LG LG
ARNU053TRD4 ARNU123TRD4
011KCHE0U209 012KCCV0UT71
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3 / FAN SPEED 4 / 50 ESP SETTING. ALL FAN SPEEDS SET TO 50 ESP
(2) CODE 3 / FAN SPEED 4 / 60 ESP SETTING. ALL FAN SPEEDS SET TO 60 ESP.
(3) FOR O.S.A. SEE SF 1-2 AIR DISTRIBUTION SHEET.
(4) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
137B 1 DO 14" X 14"1.36 195 265 201 274
TOTAL (265)(274)
REMARKS:
10/25/2021
23
FC-A1-15
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
137 1 DO 14" X 14"1.36 228 310 227 309
TOTAL (310)(309)
REMARKS:
10/25/2021
24
FC-A1-16
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/4/2021
Page:25
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 265 276 1,450 1,482
Total CFM - Outlet 265 276 1,450 1,482
R/A CFM NS 249 NS 887
O/A CFM 25 27 (3)560 595
Static Pressure (Total/Ext)0.00"DUCTLESS 0.70"0.45"
Inlet Pressure DUCTLESS -0.14"
Discharge Pressure DUCTLESS 0.31"
Fan RPM 3 SPEED HIGH SPD.(1)3 SPEED HIGH SPD. (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 206
Amperage 0.2 0.1 2.5 1.8
Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-A1-17 FC-A1-18A
137C MATH SPECIALIST 132 STORY TELLING
137C MATH SPECIALIST 132 STORY TELLING
LG LG
ARNU053TRD4 ARNU363M3A4
011KCYUQ0U210 008KCDG16M34
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3 / FAN SPEED 4 / 52 ESP SETTING. ALL FAN SPEEDS SET TO 52 ESP
(2) CODE 3 / FAN SPEED 4 / 113 ESP SETTING. ALL FAN SPEEDS SET TO 113 ESP.
(3) FOR O.S.A. SEE SF 1-2 AIR DISTRIBUTION SHEET.
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
137C 1 DO 14" X 14"1.36 195 265 203 276
TOTAL (265)(276)
REMARKS:
10/25/2021
26
FC-A1-15
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
131 1 CD 2412 1.0 *365 *361
131 2 CD 2412 1.0 *365 *365
132 3 CD 2412 1.0 *365 *348
132 4 CD 2412 1.0 *365 *366
TOTAL (1,460)(1,440)
OUTSIDE AIR
LOUVER 1 RG 42'' X 18''1.0 *560 *595
TOTAL (560)(595)
REMARKS:
11/4/2021
27
FC-A1-18A
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/2/2021
Page:28
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 1,450 1,463 310 320
Total CFM - Outlet 1,450 1,463 310 320
R/A CFM NS 1,038 310 320
O/A CFM 405 425 125 0 (3)
Static Pressure (Total/Ext)0.70"0.45"0.00"DUCTLESS
Inlet Pressure -0.25"DUCTLESS
Discharge Pressure 0.20"DUCTLESS
Fan RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD.(2)
Specified Actual Specified Actual
Motor Manufacturer NA NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 115 121 208/230 206
Amperage 2.5 1.3 0.2 0.1
Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-A1-18B FC-A1-19
133 LIBRARY 133 TINKER AREA
133 LIBRARY 133 TINKER AREA
LG LG
ARNU363M3A4 ARNU123TRD4
008KCLH16M32 012KCRN0U046
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3 / FAN SPEED 4 / 53 ESP SETTING. ALL FAN SPEEDS SET TO 53 ESP
(2) CODE 3 / FAN SPEED 4 / 59 ESP SETTING. ALL FAN SPEEDS SET TO 59 ESP
(3) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
131 1 CD 2410 1.0 *365 *371
131 2 CD 2410 1.0 *365 *363
131 3 CD 2410 1.0 *365 *368
131 4 CD 2410 1.0 *365 *361
TOTAL (1,460)(1,463)
OUTSIDE AIR
LOUVER 1 RG 42" X 18"1.0 *405 *425
TOTAL (405)(425)
REMARKS:
11/4/2021
29
FC-A1-18B
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
133 1 DO 14" X 14"1.36 227 310 235 320
TOTAL (310)(320)
REMARKS:
11/2/2021
30
FC-A1-1
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/2/2021
Page:31
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 390 398 390 396
Total CFM - Outlet 390 398 390 396
R/A CFM 390 398 390 396
O/A CFM 145 0 (3)150 0 (3)
Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS
Inlet Pressure DUCTLESS DUCTLESS
Discharge Pressure DUCTLESS DUCTLESS
Fan RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 206
Amperage 0.2 0.1 0.2 0.1
Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (1)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-A1-20 FC-A1-21
131A WORKROOM 131B TEACHING AREA
131A WORKROOM 131B TEACHING AREA
LG LG
ARNU153TQD4 ARNU153TQD4
010KCEA1AY16 010KCMR1AY15
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3 / FAN SPEED 4 / 53 ESP SETTING. ALL FAN SPEEDS SET TO 53 ESP
(2) CODE 3 / FAN SPEED 4 / 53 ESP SETTING. ALL FAN SPEEDS SET TO 53 ESP
(3) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
131A 1 DO 14" X 14"1.36 287 390 293 398
TOTAL (390)(398)
REMARKS:
11/2/2021
32
FC-A1-20
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
131B 1 DO 14" X 14"1.36 287 390 291 396
TOTAL (390)(396)
REMARKS:
11/2/2021
33
FC-A1-21
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/25/2021
Page:34
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 390 406 2,260 1,784
Total CFM - Outlet 390 406 1,740 1,784
R/A CFM 390 406 1325 1,333
O/A CFM 135 0 (3)415 451 (4)
Static Pressure (Total/Ext)0.00"DUCTLESS 0.35"0.22"
Inlet Pressure DUCTLESS -0.06"
Discharge Pressure DUCTLESS 0.16"
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 205
Amperage 0.20 0.1 5.2 1.8
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-A2-1 FC-A2-2
ABOVE CEILING ABOVE CEILING
208 WORKROOM 207 STAFF LOUNGE
LG LG
ARNU153TQD4 ARNU763B8A4
012KCTB0569 011KCBD0L325
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 56 ESP SETTING. ALL FAN SPEEDS SET TO 56 ESP
(2) CODE 3 / FAN SPEED 4/ 69 ESP SETTING. ALL FAN SPEEDS SET TO 69 ESP
(3) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE
(4) FOR O.S.A. SEE SF 1-2 AIR DISTRIBUTION SHEET.
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
208 1 DO 14 X 14 1.36 286 390 299 406
TOTAL (390)(406)
REMARKS:
10/25/2021
35
FC-A2-1
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
207 1 CD 2410 1.0 *435 *439
207 2 CD 2410 1.0 *435 *435
207 3 CD 2410 1.0 *435 *458
207 4 CD 2410 1.0 *435 *452
TOTAL (1,740)(1,784)
REMARKS:
10/25/2021
36
FC-A2-2
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/25/2021
Page:37
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 265 276 265 274
Total CFM - Outlet 265 276 265 274
R/A CFM NS 255 NS 255
O/A CFM 20 21 (3)20 19 (3)
Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS
Inlet Pressure DUCTLESS DUCTLESS
Discharge Pressure DUCTLESS DUCTLESS
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 205 208/230 208
Amperage 0.20 0.1 0.20 0.1
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-A2-3 FC-A2-4
ABOVE CEILING ABOVE CEILING
210 DIRECTOR OF TECH 209 SYSTEMS ADMIN
LG LG
ARNU053TRD4 ARNU053TRD4
011KCBD0U205 011KCVU0U207
DIRECT DRIVE DIRECT DIRVE
(1) CODE 3/ FAN SPEED 4/ 49 ESP SETTING. ALL FAN SPEEDS SET TO 49 ESP
(2) CODE 3/ FAN SPEED 4/ 50 ESP SETTING. ALL FAN SPEEDS SET TO 50 ESP
(4) FOR O.S.A. SEE SF 1-2 AIR DISTRIBUTION SHEET.
DIRECT DRIVE DIRECT DIRVEDIRECT DRIVE DIRECT DIRVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
210 1 DO 14 X 14 1.36 194 265 203 276
TOTAL (265)(276)
REMARKS:
10/25/2021
38
FC-A2-3
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
209 1 DO 14 X 14 1.36 194 265 202 274
TOTAL (265)(274)
REMARKS:
10/25/2021
39
FC-A2-4
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/25/2021
Page:40
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 265 272 265 276
Total CFM - Outlet 265 272 265 276
R/A CFM NS 250 265 276
O/A CFM 20 22 (3)70 0 (3)
Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS
Inlet Pressure DUCTLESS DUCTLESS
Discharge Pressure DUCTLESS DUCTLESS
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 205
Amperage 0.20 0.1 0.20 0.1
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-A2-5 FC-A2-6
ABOVE CEILING ABOVE CEILING
BUSINESS OFFICE MOTHERS ROOM
LG LG
ARNU053TRD4 ARNU053TRD4
011KCJZ0U204 011KCFT0U203
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 50 ESP SETTING. ALL FAN SPEEDS SET TO 50 ESP
(2) CODE 3/ FAN SPEED 4/ 50 ESP SETTING. ALL FAN SPEEDS SET TO 50 ESP
(4) FOR O.S.A. SEE SF 1-2 AIR DISTRIBUTION SHEET.
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
206 1 DO 14 X 14 1.36 194 265 200 272
TOTAL (265)(272)
REMARKS:
10/25/2021
41
FC-A2-5
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
207A 1 DO 14 X 14 1.36 194 265 203 276
TOTAL (265)(276)
REMARKS:
10/25/2021
42
FC-A2-6
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/25/2021
Page:43
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 265 277 310 320
Total CFM - Outlet 265 277 310 320
R/A CFM NS 258 310 320
O/A CFM 25 19 (3)125 0 (4)
Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS
Inlet Pressure DUCTLESS DUCTLESS
Discharge Pressure DUCTLESS DUCTLESS
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 208
Amperage 0.20 0.1 0.20 0.1
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-A2-7 FC-A2-8
ABOVE CEILING ABOVE CEILING
206 ASSISTANT BUSINESS 252 OPEN OFFICE
LG LG
ARNU053TRD4 ARNU123TRD4
011KCFT0U203 012KCXM0U042
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 50 ESP SETTING. ALL FAN SPEEDS SET TO 50 ESP
(2) CODE 3/ FAN SPEED 4/ 60 ESP SETTING. ALL FAN SPEEDS SET TO 60 ESP
(3) FOR O.S.A. SEE SF 1-2 AIR DISTRIBUTION SHEET.
(4) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
205 1 DO 14 X 14 1.36 194 265 204 277
TOTAL (265)(277)
REMARKS:
10/25/2021
44
FC-A2-7
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
252 1 DO 14 X 14 1.36 228 (310)236 320
TOTAL (310)(320)
REMARKS:
10/25/2021
45
FC-A2-8
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/26/2021
Page:46
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 265 272 265 280
Total CFM - Outlet 265 272 265 280
R/A CFM NS 245 NS 259
O/A CFM 25 27 (3)20 21 (3)
Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS
Inlet Pressure DUCTLESS DUCTLESS
Discharge Pressure DUCTLESS DUCTLESS
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 208
Amperage 0.20 0.1 0.20 0.1
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-A2-9 FC-A2-10
ABOVE CEILING ABOVE CEILING
204 DIRECTOR OF DEVELOPMENT 201DIR. OF DEVELOPMENT ASSIST.
LG LG
ARNU053TRD4 ARNU053TRD4
011KCAS0U200 011KCRN0U206
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 51 ESP SETTING. ALL FAN SPEEDS SET TO 51 ESP
(2) CODE 3/ FAN SPEED 4/ 48 ESP SETTING. ALL FAN SPEEDS SET TO 48 ESP
(3) FOR O.S.A. SEE SF 1-2 AIR DISTRIBUTION SHEET.
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
204 1 DO 14 X 14 1.36 194 265 200 272
TOTAL (265)(272)
REMARKS:
10/26/2021
47
FC-A2-9
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
201 1 DO 14 X 14 1.36 194 265 206 280
TOTAL (265)(280)
REMARKS:
10/26/2021
48
FC-A2-10
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/26/2021
Page:49
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 265 278 265 281
Total CFM - Outlet 265 278 265 281
R/A CFM NS 262 NS 248
O/A CFM 15 16 (3)35 33 (3)
Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS
Inlet Pressure DUCTLESS DUCTLESS
Discharge Pressure DUCTLESS DUCTLESS
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 206
Amperage 0.20 0.1 0.20 0.1
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-A2-11 FC-A2-12
ABOVE CEILING ABOVE CEILING
202 DIRECTOR OF DEVELOPMENT 203 UPPER DIRECTOR
LG LG
ARNU053TRD4 ARNU073TRD4
011KCXM0U202 010KCLH0D328
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 50 ESP SETTING. ALL FAN SPEEDS SET TO 50 ESP
(2) CODE 3/ FAN SPEED 4/ 50 ESP SETTING. ALL FAN SPEEDS SET TO 50 ESP
(3) FOR O.S.A. SEE SF 1-2 AIR DISTRIBUTION SHEET.
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
202 1 DO 14 X 14 1.36 194 265 205 278
TOTAL (265)(278)
REMARKS:
10/26/2021
50
FC-A2-11
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
203 1 DO 14 X 14 1.36 194 265 207 281
TOTAL (265)(281)
REMARKS:
10/26/2021
51
FC-A2-12
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/26/2021
Page:52
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 240 244 375 382
Total CFM - Outlet 240 244 375 382
R/A CFM 240 244 375 382
O/A CFM 0 0 0 0
Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS
Inlet Pressure DUCTLESS DUCTLESS
Discharge Pressure DUCTLESS DUCTLESS
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 207 208/230 207
Amperage 0.25 0.1 0.25 0.1
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-A2-13 FC-A2-14
WALL MOUNT WALL MOUNT
241 ELECTRICAL 240 DATA
LG LG
ARNU053SJA4 ARNU153SJA4
011KCVU0RR83 011KCUK13D62
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 46 ESP SETTING. ALL FAN SPEEDS SET TO 46 ESP
(2) CODE 3/ FAN SPEED 4/ 64 ESP SETTING. ALL FAN SPEEDS SET TO 64 ESP
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
241 1 DO 4" X 28"0.77 312 240 318 244
TOTAL (240)(244)
REMARKS:
10/26/2021
53
FC-A2-13
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
240 1 DO 4" X 28"0.77 488 375 497 382
TOTAL (375)(382)
REMARKS:
10/26/2021
54
FC-A2-14
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/27/2021
Page:55
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 800 NVL 1,250 1,267
Total CFM - Outlet 800 823 1,250 1,267
R/A CFM NS 574 NS 849
O/A CFM 310 328 415 418
Static Pressure (Total/Ext)0.35 0.28"0.35 0.34"
Inlet Pressure -0.25"-0.14"
Discharge Pressure 0.03"0.20"
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD. (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 207 208/230 206
Amperage 2.3 1.1 2.5 1.0
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD. (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-A2-15 FC-B1-1
ABOVE CEILING 108 KINDERGARTEN
211 5TH GRADE CLASSROOM 108 KINDERGARTEN
LG LG
ARNU243M2A4 ARNU283M3A4
011KCZP0G701 011KCQX1C284
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 84 ESP SETTING. ALL FAN SPEEDS SET TO 84 ESP
(2) CODE 3 / FAN SPEED 4 / 98 ESP SETTING. ALL FAN SPEEDS SET TO 98 ESP.
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
211 1 CD 2410 1.0 *200 *201
211 2 CD 2410 1.0 *200 *212
211 3 CD 2410 1.0 *200 *197
211 4 CD 2410 1.0 *200 *213
TOTAL (800)(823)
OUTSIDE AIR SYSTEM
207 1 RD 10" RD 0.55 563 310 609 335
TOTAL (310)(335)
REMARKS:
10/26/2021
56
FC-A2-15
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
PROJECT:
POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE
A-1 221 B-1 316 1 " Dia x 0.026 ="
A-2 413 B-2 444 2 " Dia x 0.082 ="
A-3 401 B-3 689 3 " Dia x 0.146 ="
A-4 374 B-4 803 4 " Dia x 0.226 ="
A-5 814 B-5 547 5 " Dia x 0.342 ="
A-6 863 B-6 422 6 " Dia x 0.685 ="
A-7 877 B-7 730 7 " Dia x 0.774 ="
A-8 890 B-8 764 8 " Dia x 0.854 ="
A-9 B-9 9 " Dia x 0.918 ="
A-10 B-10 10 " Dia x 0.974 ="
SUBTOTAL SUBTOTAL
(TOTAL FPM)DIVIDED
BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM
9,568 16 598 0.55 329
COMMENTS:D DUCT SIZE 10"
E AREA 0.55
S FPM 563
I CFM 310
G
N
T DUCT SIZE O.D.10"
E DUCT SIZE I.D.10"
S AREA 0.55
T CENTERLINE S.P.-0.13
AVERAGE FPM 598
D CFM MEASURED 329
A TEMP. CORRECTION 0
T ALT. CORRECTION 0
A ACTUAL CFM 329
INSTRUMENT USED: AIRFOIL
SYSTEM #:FC-A2-15 OSA57
11/10/2021
ROUND DUCT TRAVERSE READINGS
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
108 1 CD 2410 1.0 *315 *309
108 2 CD 2410 1.0 *315 *319
108 3 CD 2410 1.0 *315 *314
108 4 CD 2410 1.0 *315 *325
TOTAL (1,260)(1,267)
OUTSIDE AIR
LOUVER 1 RG 42" X 18"1.0 *415 *418
TOTAL (415)(418)
REMARKS:
10/27/2021
58
FC-B1-4
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/29/2021
Page:59
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 254 275 285 293
Total CFM - Outlet 254 275 285 293
R/A CFM 254 275 285 293
O/A CFM 0 0 60 0 (3)
Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS
Inlet Pressure DUCTLESS DUCTLESS
Discharge Pressure DUCTLESS DUCTLESS
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 207 208/230 206
Amperage 0.25 0.1 0.20 0.1
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-B1-2 FC-B1-3
CEILING MOUNT 163 ABOVE CEILING 108C
163 ELECTRICAL 108C WORKROOM
LG LG
ARNU073SJA4 ARNU093TRD4
008KCYQ0YK22 012KCGW0TW91
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 65 ESP SETTING. ALL FAN SPEEDS SET TO 65 ESP
(2) CODE 3/ FAN SPEED 4/ 58 ESP SETTING. ALL FAN SPEEDS SET TO 58 ESP
(3) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
163 1 DO 4" X 28"0.77 329 254 358 275
TOTAL (254)(275)
REMARKS:
10/29/2021
60
FC-B1-2
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
203 1 DO 14 X 14 1.36 209 (285)216 293
TOTAL (285)(293)
REMARKS:
10/29/2021
61
FC-B1-3
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/27/2021
Page:62
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 1,250 1,278 1,250 1,262
Total CFM - Outlet 1,260 1,278 1,260 1,262
R/A CFM NS 856 NS 878
O/A CFM 410 422 350 384
Static Pressure (Total/Ext)0.35"0.33"0.35"0.27"
Inlet Pressure -0.14"-0.10"
Discharge Pressure 0.19"0.17"
Fan RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 206
Amperage 2.5 1.0 2.5 1.0
Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-B1-4 FC-B1-5
111 KINDERGARTEN 112 1ST GRADE CLASSROOM
111 KINDERGARTEN 112 1ST GRADE CLASSROOM
LG LG
ARNU283M3A4 ARNU283M3A4
012KCQX0GS64 011KCCV1C283
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3 / FAN SPEED 4 / 94 ESP SETTING. ALL FAN SPEEDS SET TO 94 ESP
(2) CODE 3 / FAN SPEED 4 / 91 ESP SETTING. ALL FAN SPEEDS SET TO 91 ESP
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
111 1 CD 2410 1.0 *315 *327
111 2 CD 2410 1.0 *315 *312
111 3 CD 2410 1.0 *315 *321
111 4 CD 2410 1.0 *315 *318
TOTAL (1,260)(1,278)
OUTSIDE AIR
LOUVER 1 RG 42" X 18"1.0 *410 *422
TOTAL (410)(422)
REMARKS:
10/27/2021
63
FC-B1-4
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
112 1 CD 2410 1.0 *315 *319
112 2 CD 2410 1.0 *315 *312
112 3 CD 2410 1.0 *315 *309
112 4 CD 2410 1.0 *315 *322
TOTAL (1,260)(1,262)
OUTSIDE AIR
LOUVER 1 SWG 42" X 18"1.0 *370 *384
TOTAL (370)(384)
REMARKS:
10/27/2021
64
FC-B1-5
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/2/2021
Page:65
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 310 326 1,250 1,260
Total CFM - Outlet 310 326 1,260 1,260
R/A CFM 310 326 NS 886
O/A CFM 110 0 (3)370 374
Static Pressure (Total/Ext)0.00"DUCTLESS 0.35"0.27"
Inlet Pressure DUCTLESS -0.12"
Discharge Pressure DUCTLESS 0.15"
Fan RPM 3 SPEED HIGH SPD.(1)3 SPEED HIGH SPD. (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 206
Amperage 0.2 0.1 2.5 1.0
Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-B1-6 FC-B1-7
113 SMALL GROUP 114 1ST GRADE CLASSROOM
113 SMALL GROUP 114 1ST GRADE CLASSROOM
LG LG
ARNU283M3A4 ARNU283M3A4
012KCSF0UT74 011KCEA1L324
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3 / FAN SPEED 4 / 58 ESP SETTING. ALL FAN SPEEDS SET TO 58 ESP
(2) CODE 3 / FAN SPEED 4 / 93 ESP SETTING. ALL FAN SPEEDS SET TO 93 ESP
(3) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
113 1 DO 14" X 14"1.36 227 310 240 326
TOTAL (310)(326)
REMARKS:
11/2/2021
66
FC-A1-1
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
114 1 CD 2410 1.0 *315 *322
114 2 CD 2410 1.0 *315 *307
114 3 CD 2410 1.0 *315 *314
114 4 CD 2410 1.0 *315 *317
TOTAL (1,260)(1,260)
OUTSIDE AIR
LOUVER 1 RG 42" X 18"1.0 *370 *374
TOTAL (370)(374)
REMARKS:
10/27/2021
67
FC-B1-7
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/29/2021
Page:68
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 1,250 1,263 310 320
Total CFM - Outlet 1,250 1,263 310 320
R/A CFM NS 865 310 320
O/A CFM 370 398 75 80 (3)
Static Pressure (Total/Ext)0.35"0.31"0.00"DUCTLESS
Inlet Pressure -0.14"DUCTLESS
Discharge Pressure 0.17"DUCTLESS
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 208
Amperage 2.5 1.2 0.20 0.10
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-B1-8 FC-B1-9
ABOVE CEILING RM 155 ABOVE CEILING RM 115A
155 2ND GRADE CLASSROOM 115A SMALL GROUP
LG LG
ARNU283M3A4 ARNU123TRD4
012KCCV0GS63 012KCHEOUT68
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 96 ESP SETTING. ALL FAN SPEEDS SET TO 96 ESP
(2) CODE 3/ FAN SPEED 4/ 57 ESP SETTING. ALL FAN SPEEDS SET TO 57 ESP
(3) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
114 1 CD 2410 1.0 *315 *309
114 2 CD 2410 1.0 *315 *313
114 3 CD 2410 1.0 *315 *316
114 4 CD 2410 1.0 *315 *325
TOTAL (1,260)(1,263)
OUTSIDE AIR
LOUVER 1 RG 42" X 18"1.0 *370 *398
TOTAL (370)(398)
REMARKS:
10/29/2021
69
FC-B1-8
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
203 1 DO 14 X 14 1.36 227 310 236 320
TOTAL (310)(320)
REMARKS:
10/29/2021
70
FC-B1-9
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/29/2021
Page:71
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 800 827 800 818
Total CFM - Outlet 800 827 800 818
R/A CFM NS 510 NS 496
O/A CFM 310 317 310 322
Static Pressure (Total/Ext)0.35"0.17"0.35"0.13"
Inlet Pressure -0.12"-0.07"
Discharge Pressure 0.05"0.06"
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 208 208/230 207
Amperage 2.3 1.3 2.3 1.1
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-B1-10 FC-B1-11
ABOCE CEILING RM 116 ABOVE CEILING RM 117
116 2ND GRADE CLASSROOM 117 3RD GRADE CLASSROOM
LG LG
ARNU243M2A4 ARNU243M2A4
011KCLH0G680 011KCRN0G742
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 84 ESP SETTING. ALL FAN SPEEDS SET TO 84 ESP
(2) CODE 3/ FAN SPEED 4/ 82 ESP SETTING. ALL FAN SPEEDS SET TO 82 ESP
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
116 1 CD 2410 1.0 *200 *213
116 2 CD 2410 1.0 *200 *209
116 3 CD 2410 1.0 *200 *200
116 4 CD 2410 1.0 *200 *205
TOTAL (800)(827)
OUTSIDE AIR
LOUVER 1 RG 34" X 16"1.0 *310 *317
TOTAL (310)(317)
REMARKS:
10/29/2021
72
FC-B1-10
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
117 1 CD 2410 1.0 *200 *206
117 2 CD 2410 1.0 *200 *198
117 3 CD 2410 1.0 *200 *213
117 4 CD 2412 1.0 *200 *201
TOTAL (800)(818)
OUTSIDE AIR
LOUVER 1 RG 34" X 16"1.0 *310 *322
TOTAL (310)(322)
REMARKS:
10/29/2021
73
FC-B1-11
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/29/2021
Page:74
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 310 318 800 829
Total CFM - Outlet 310 318 800 829
R/A CFM 310 318 NS 505
O/A CFM 80 0 (3)310 324
Static Pressure (Total/Ext)0.00"DUCTLESS 0.35"0.17"
Inlet Pressure DUCTLESS -0.03"
Discharge Pressure DUCTLESS 0.14"
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 207 208/230 208
Amperage 0.20 0.10 2.3 1.1
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-B1-12 FC-B1-13
ABOVE CEILING RM 117A ABOVE CEILING 118
117A SMALL GROUP 118 3RD GRADE CLASSROOM
LG LG
ARNU123TRD4 ARNU243M2A4
012KCAS0U040 011KCJZD0G740
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 54 ESP SETTING. ALL FAN SPEEDS SET TO 54 ESP
(2) CODE 3/ FAN SPEED 4/ 85 ESP SETTING. ALL FAN SPEEDS SET TO 85 ESP
(3) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
117A 1 DO 14 X 14 1.36 227 310 234 318
TOTAL (310)(318)
REMARKS:
10/29/2021
75
FC-B1-12
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
118 1 CD 2410 1.0 *200 *208
118 2 CD 2410 1.0 *200 *201
118 3 CD 2410 1.0 *200 *217
118 4 CD 2410 1.0 *200 *203
TOTAL (800)(829)
OUTSIDE AIR
LOUVER 1 RG 34" X 16"1.0 *310 *324
TOTAL (310)(324)
REMARKS:
10/29/2021
76
FC-B1-13
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
119 1 CD 2410 1.0 *315 *326
119 2 CD 2410 1.0 *315 *327
119 3 CD 2410 1.0 *315 *331
119 4 CD 2410 1.0 *315 *314
TOTAL (1,260)(1,298)
OUTSIDE AIR
LOUVER 1 RG 42" X 18"1.0 *370 *381
TOTAL (370)(381)
REMARKS:
11/1/2021
78
FC-B1-14
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/1/2021
Page:77
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 1,250 1,298 310 323
Total CFM - Outlet 1,250 1,298 310 323
R/A CFM NS 917 310 323
O/A CFM 370 381 105 0 (3)
Static Pressure (Total/Ext)0.35"0.18"0.00"DUCTLESS
Inlet Pressure -0.15"DUCTLESS
Discharge Pressure 0.13"DUCTLESS
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 207 208/230 206
Amperage 2.5 1.3 0.20 0.1
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-B1-14 FC-B1-15
ABOVE CEILING RM 119 ABOVE CEILING RM 119A
119 4TH GRADE CLASSROOM 119A SMALL GROUP
LG LG
ARNU283M3A4 ARNU123TRD4
011KCVU1C279 012KCVU0U047
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 92 ESP SETTING. ALL FAN SPEEDS SET TO 92 ESP
(2) CODE 3/ FAN SPEED 4/ 54 ESP SETTING. ALL FAN SPEEDS SET TO 54 ESP
(3) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE
DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
117A 1 DO 14 X 14 1.36 227 310 238 323
TOTAL (310)(323)
REMARKS:
10/29/2021
79
FC-B1-15
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/1/2021
Page:80
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 1,450 1,478 800 825
Total CFM - Outlet 1,450 1,478 800 825
R/A CFM NS 1,072 NS 506
O/A CFM 395 406 310 319
Static Pressure (Total/Ext)0.35"0.35"0.35"0.16"
Inlet Pressure -0.13"-0.07"
Discharge Pressure 0.22"0.09"
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 207 208/230 208
Amperage 2.5 1.5 2.3 0.9
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-B1-16 FC-B1-17
ABOVE CEILING RM 120 ABOVE CEILING RM 121
120 4TH GRADE CLASSROOM 121 WORLD ALNGUAGE CLASSRM
LG LG
ARNU363M3A4 ARNU243M2A4
008KCEA16M36 011KCXM0G738
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 101 ESP SETTING. ALL FAN SPEEDS SET TO 101 ESP
(2) CODE 3/ FAN SPEED 4/ 82 ESP SETTING. ALL FAN SPEEDS SET TO 82 ESP
DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
120 1 CD 2410 1.0 *365 *368
120 2 CD 2410 1.0 *365 *362
120 3 CD 2410 1.0 *365 *377
120 4 CD 2410 1.0 *365 *371
TOTAL (1,460)(1478)
OUTSIDE AIR
LOUVER 1 RG 42" X 18"1.0 *395 *406
TOTAL (395)(406)
REMARKS:
11/1/2021
81
FC-B1-16
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
121 1 CD 2410 1.0 *200 *203
121 2 CD 2410 1.0 *200 *201
121 3 CD 2410 1.0 *200 *207
121 4 CD 2410 1.0 *200 *214
TOTAL (800)(825)
OUTSIDE AIR
LOUVER 1 RG 42" X 18"1.0 *310 *319
TOTAL (310)(319)
REMARKS:
11/1/2021
82
FC-B1-17
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/5/2021
Page:83
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 1,450 1,486 1,450 1,470
Total CFM - Outlet 1450 1,486 1,450 1,470
R/A CFM NS 1,030 1,450 1,470
O/A CFM 450 456 -0--0-
Static Pressure (Total/Ext)0.35"0.31"0.00"DUCTLESS
Inlet Pressure -0.09"DUCTLESS
Discharge Pressure 0.22"DUCTLESS
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD. (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 207 208/230 207
Amperage 2.5 1.4 2.5 0.1
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD. (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-B1-18 FC-B1-19
ABOVE CEILING RM 122 128 ELECTRICAL
122 LOWER SCHOOL SCIENCE LAB 128 ELECTRICAL
LG LG
ARNU363M3A4 ARNU363M3A4
008KCSF16M30 009KCFT11U59
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 101 ESP SETTING. ALL FAN SPEEDS SET TO 101 ESP
(2) CODE 3/ FAN SPEED 4/ 71 ESP SETTING. ALL FAN SPEEDS SET TO 71 ESP
DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
122 1 CD 2410 1.0 *365 *372
122 2 CD 2410 1.0 *365 *369
122 3 CD 2410 1.0 *365 *368
122 4 CD 2410 1.0 *365 *377
TOTAL (1,460)(1,486)
OUTSIDE AIR
LOUVER 1 RG 42" X 18"1.0 *450 *456
TOTAL (450)(456)
REMARKS:
11/1/2021
84
FC-B1-18
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
128 1 DO 12 X 48 4.0 363 1,450 368 1,470
TOTAL (1,450)(1,470)
REMARKS:
11/5/2021
85
FC-B1-19
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/1/2021
Page:86
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 240 257 285 293
Total CFM - Outlet 240 257 285 293
R/A CFM 240 257 NS 293
O/A CFM -0--0-90 0 (3)
Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS
Inlet Pressure DUCTLESS DUCTLESS
Discharge Pressure DUCTLESS DUCTLESS
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 206
Amperage 0.25 0.1 0.20 0.1
Motor RPM 3 SPEED HIGH SPD (2)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-B1-20 FC-C2-2
127 DATA ROM ABOVE CEILING
127 DATA 211A COLLAB
LG LG
ARNU053SJA4 ARNU093TRD4
010KCDG1AD58 012KCCV0TW87
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 58 ESP SETTING. ALL FAN SPEEDS SET TO 58 ESP
(2) CODE 3/ FAN SPEED 4/ 54 ESP SETTING. ALL FAN SPEEDS SET TO 54 ESP
(3) O.S.A. SUPPLIED BY SF 2-2 WITH SEPARATE SUPPLY GRILLE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
127 1 DO 4" X 28"0.77 311 240 334 257
TOTAL (240)(257)
REMARKS:
11/1/2021
87
FC-B1-20
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
211A 1 DO 14 X 14 1.36 209 285 216 293
TOTAL (285)(293)
REMARKS:
10/26/2021
88
FC-C2-2
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/26/2021
Page:89
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 800 803 800 805
Total CFM - Outlet 800 803 800 805
R/A CFM NS 479 NS 434
O/A CFM 310 324 310 321
Static Pressure (Total/Ext)0.35 0.15"0.35"0.20"
Inlet Pressure -0.09"-0.05"
Discharge Pressure 0.06"0.15"
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 208
Amperage 2.3 1.4 2.3 1.2
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-C2-3 FC-C2-4
ABOVE CEILING ABOVE CEILING
212 5TH GRADE CLASSROOM 213 6TH-8TH CLASSROOM
LG LG
ARNU243M2A4 ARNU243M2A4
011KCCV0G699 011KCHE0G697
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 84 ESP SETTING. ALL FAN SPEEDS SET TO 84 ESP
(2) CODE 3/ FAN SPEED 4/ 92 ESP SETTING. ALL FAN SPEEDS SET TO 92 ESP
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
212 1 CD 2410 1.0 *200 *203
212 2 CD 2410 1.0 *200 *192
212 3 CD 2410 1.0 *200 *211
212 4 CD 2410 1.0 *200 *197
TOTAL (800)(803)
OUTSIDE AIR SYSTEM
207 1 DT 10" RD 0.55 564 310 590 324
TOTAL (310)(324)
REMARKS:
10/26/2021
90
FC-C2-3
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
PROJECT:
POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE
A-1 743 B-1 689 1 " Dia x 0.026 ="
A-2 739 B-2 703 2 " Dia x 0.082 ="
A-3 754 B-3 688 3 " Dia x 0.146 ="
A-4 727 B-4 582 4 " Dia x 0.226 ="
A-5 356 B-5 541 5 " Dia x 0.342 ="
A-6 358 B-6 587 6 " Dia x 0.685 ="
A-7 273 B-7 652 7 " Dia x 0.774 ="
A-8 303 B-8 739 8 " Dia x 0.854 ="
A-9 B-9 9 " Dia x 0.918 ="
A-10 B-10 10 " Dia x 0.974 ="
SUBTOTAL SUBTOTAL
(TOTAL FPM)DIVIDED
BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM
9,434 16 590 0.55 324
COMMENTS:D DUCT SIZE 10"
E AREA 1
S FPM 564
I CFM 310
G
N
T DUCT SIZE O.D.10"
E DUCT SIZE I.D.10"
S AREA 0.55
T CENTERLINE S.P.-0.04
AVERAGE FPM 590
D CFM MEASURED 324
A TEMP. CORRECTION 0
T ALT. CORRECTION 0
A ACTUAL CFM 324
10/26/2021
91SYSTEM #:FC-C2-3
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
ROUND DUCT TRAVERSE READINGS
INSTRUMENT USED: ARIFOIL
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
213 1 CD 2410 1.0 *200 *198
213 2 CD 2410 1.0 *200 *203
213 3 CD 2410 1.0 *200 *196
213 4 CD 2410 1.0 *200 *208
TOTAL (800)(805)
OUTSIDE AIR SYSTEM
213 1 DT 10" RD 0.55 564 310 584 321
TOTAL (310)(321)
REMARKS:
10/26/2021
92
FC-C2-4
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
PROJECT:
POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE
A-1 579 B-1 475 1 " Dia x 0.026 ="
A-2 533 B-2 574 2 " Dia x 0.082 ="
A-3 595 B-3 457 3 " Dia x 0.146 ="
A-4 572 B-4 633 4 " Dia x 0.226 ="
A-5 553 B-5 697 5 " Dia x 0.342 ="
A-6 528 B-6 691 6 " Dia x 0.685 ="
A-7 582 B-7 700 7 " Dia x 0.774 ="
A-8 585 B-8 583 8 " Dia x 0.854 ="
A-9 B-9 9 " Dia x 0.918 ="
A-10 B-10 10 " Dia x 0.974 ="
SUBTOTAL SUBTOTAL
(TOTAL FPM)DIVIDED
BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM
9,336 16 584 0.55 321
COMMENTS:D DUCT SIZE 10"
E AREA 1
S FPM 564
I CFM 310
G
N
T DUCT SIZE O.D.10"
E DUCT SIZE I.D.10"
S AREA 0.55
T CENTERLINE S.P.-0.03
AVERAGE FPM 584
D CFM MEASURED 321
A TEMP. CORRECTION 0
T ALT. CORRECTION 0
A ACTUAL CFM 321
10/26/2021
93SYSTEM #:FC-C2-4 OSA
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
ROUND DUCT TRAVERSE READINGS
INSTRUMENT USED: AIRFOIL
Date:10/28/2021
Page:94
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 800 806 800 801
Total CFM - Outlet 800 806 800 801
R/A CFM NS 488 NS 465
O/A CFM 310 317 310 334
Static Pressure (Total/Ext)0.35"0.18"0.35"0.20"
Inlet Pressure -0.04"-0.04"
Discharge Pressure 0.14"0.16"
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 207 208/230 206
Amperage 2.3 1.3 2.3 0.9
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-C2-5 FC-C2-6
ABOVE CEILING ABOVE CEILING
214 6TH 8TH CLASSROOM 215 6TH 8TH CLASSROOM
LG LG
ARNU243M2A4 ARNU243M2A4
011KCZP0G725 011KCVU0G695
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 90 ESP SETTING. ALL FAN SPEEDS SET TO 90 ESP
(2) CODE 3/ FAN SPEED 4/ 91 ESP SETTING. ALL FAN SPEEDS SET TO 91 ESP
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
214 1 CD 2410 1.0 *200 *198
214 2 CD 2410 1.0 *200 *191
214 3 CD 2410 1.0 *200 *206
214 4 CD 2410 1.0 *200 *211
TOTAL (800)(806)
OUTSIDE AIR SYSTEM
214 1 DT 10" RD 0.55 564 310 578 317
TOTAL (310)(317)
REMARKS:
10/26/2021
95
FC-C2-5
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
PROJECT:
POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE
A-1 575 B-1 573 1 " Dia x 0.026 ="
A-2 556 B-2 628 2 " Dia x 0.082 ="
A-3 591 B-3 573 3 " Dia x 0.146 ="
A-4 580 B-4 616 4 " Dia x 0.226 ="
A-5 571 B-5 663 5 " Dia x 0.342 ="
A-6 502 B-6 595 6 " Dia x 0.685 ="
A-7 513 B-7 652 7 " Dia x 0.774 ="
A-8 288 B-8 674 8 " Dia x 0.854 ="
A-9 B-9 9 " Dia x 0.918 ="
A-10 B-10 10 " Dia x 0.974 ="
SUBTOTAL SUBTOTAL
(TOTAL FPM)DIVIDED
BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM
9,252 16 578 0.55 317
COMMENTS:D DUCT SIZE 10"
E AREA 1
S FPM 564
I CFM 310
G
N
T DUCT SIZE O.D.10"
E DUCT SIZE I.D.10"
S AREA 0.55
T CENTERLINE S.P.-0.04
AVERAGE FPM 578
D CFM MEASURED 317
A TEMP. CORRECTION 0
T ALT. CORRECTION 0
A ACTUAL CFM 317
10/26/2021
96SYSTEM #:FC-C2-5 OSA
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
ROUND DUCT TRAVERSE READINGS
INSTRUMENT USED: AIRFOIL
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
215 1 CD 2410 1.0 *200 *199
215 2 CD 2410 1.0 *200 *203
215 3 CD 2410 1.0 *200 *205
215 4 CD 2410 1.0 *200 *194
TOTAL (800)(801)
OUTSIDE AIR SYSTEM
215 1 DT 10" RD 0.55 564 310 609 334
TOTAL (310)(334)
REMARKS:
10/28/2021
97
FC-C2-6
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
PROJECT:
POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE
A-1 626 B-1 626 1 " Dia x 0.026 ="
A-2 630 B-2 607 2 " Dia x 0.082 ="
A-3 614 B-3 624 3 " Dia x 0.146 ="
A-4 613 B-4 625 4 " Dia x 0.226 ="
A-5 647 B-5 559 5 " Dia x 0.342 ="
A-6 608 B-6 542 6 " Dia x 0.685 ="
A-7 614 B-7 561 7 " Dia x 0.774 ="
A-8 670 B-8 582 8 " Dia x 0.854 ="
A-9 B-9 9 " Dia x 0.918 ="
A-10 B-10 10 " Dia x 0.974 ="
SUBTOTAL SUBTOTAL
(TOTAL FPM)DIVIDED
BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM
9,748 16 609 0.55 334
COMMENTS:D DUCT SIZE 10"
E AREA 1
S FPM 564
I CFM 310
G
N
T DUCT SIZE O.D.10"
E DUCT SIZE I.D.10"
S AREA 0.55
T CENTERLINE S.P.-0.04
AVERAGE FPM 609
D CFM MEASURED 334
A TEMP. CORRECTION 0
T ALT. CORRECTION 0
A ACTUAL CFM 309
10/28/2021
98SYSTEM #:FC-C2-6 OSA
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
ROUND DUCT TRAVERSE READINGS
INSTRUMENT USED: AIRFOIL
Date:10/28/2021
Page:99
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 310 314 800 802
Total CFM - Outlet 310 314 800 802
R/A CFM 310 314 NS 479
O/A CFM 105 0 (3)310 322
Static Pressure (Total/Ext)DUCTLESS 0.35"0.23"
Inlet Pressure DUCTLESS -0.05"
Discharge Pressure DUCTLESS 0.18"
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 206
Amperage 0.20 0.1 2.3 1.1
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-C2-7 FC-C2-8
ABOVE CEILING ABOVE CEILING
249 COLLAB 216 6TH 8TH GRADE
LG LG
ARNU123TRD4 ARNU243M2A4
012KCZP0U053 011KCBD0G693
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 56 ESP SETTING. ALL FAN SPEEDS SET TO 56 ESP
(2) CODE 3/ FAN SPEED 4/ 92 ESP SETTING. ALL FAN SPEEDS SET TO 92 ESP
(3) O.S.A. SUPPLIED BY SF 2-2 WITH SEPARATE SUPPLY GRILLE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
211A 1 DO 14 X 14 1.36 228 310 231 314
TOTAL (310)(314)
REMARKS:
10/28/2021
99
FC-C2-7
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
216 1 CD 2410 1.0 *200 *209
216 2 CD 2410 1.0 *200 *198
216 3 CD 2410 1.0 *200 *202
216 4 CD 2410 1.0 *200 *193
TOTAL (800)(802)
OUTSIDE AIR SYSTEM
216 1 DT 10" RD 0.55 564 310 588 323
TOTAL (310)(323)
REMARKS:
10/28/2021
100
FC-C2-8
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
PROJECT:
POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE
A-1 585 B-1 488 1 " Dia x 0.026 ="
A-2 537 B-2 612 2 " Dia x 0.082 ="
A-3 550 B-3 627 3 " Dia x 0.146 ="
A-4 593 B-4 607 4 " Dia x 0.226 ="
A-5 608 B-5 618 5 " Dia x 0.342 ="
A-6 579 B-6 585 6 " Dia x 0.685 ="
A-7 602 B-7 638 7 " Dia x 0.774 ="
A-8 534 B-8 651 8 " Dia x 0.854 ="
A-9 B-9 9 " Dia x 0.918 ="
A-10 B-10 10 " Dia x 0.974 ="
SUBTOTAL SUBTOTAL
(TOTAL FPM)DIVIDED
BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM
9,413 16 588 0.55 323
COMMENTS:D DUCT SIZE 10"
E AREA 1
S FPM 564
I CFM 310
G
N
T DUCT SIZE O.D.10"
E DUCT SIZE I.D.10"
S AREA 0.55
T CENTERLINE S.P.-0.04
AVERAGE FPM 588
D CFM MEASURED 323
A TEMP. CORRECTION 0
T ALT. CORRECTION 0
A ACTUAL CFM 323
10/28/2021
101SYSTEM #:FC-C2-8 OSA
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
ROUND DUCT TRAVERSE READINGS
INSTRUMENT USED: AIRFOIL
Date:10/28/2021
Page:102
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 800 804 390 406
Total CFM - Outlet 800 804 390 406
R/A CFM NS 486 390 406
O/A CFM 310 319 135 0 (3)
Static Pressure (Total/Ext)0.35"0.15"0.00"DUCTLESS
Inlet Pressure -0.03"DUCTLESS
Discharge Pressure 0.12"DUCTLESS
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 207 208/230 206
Amperage 2.3 1.1 0.20 0.1
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-C2-9 FC-C2-10
ABOVE CEILING ABOVE CEILING
217 6TH 8TH GRADE CLASSROOM 218 COLLAB
LG LG
ARNU243M2A4 ARNU153TQD4
011KCZP0G677 012KCFT0AY79
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 89 ESP SETTING. ALL FAN SPEEDS SET TO 89 ESP
(2) CODE 3/ FAN SPEED 4/ 60 ESP SETTING. ALL FAN SPEEDS SET TO 60 ESP
(3) O.S.A. SUPPLIED BY SF 2-3 WITH SEPARATE SUPPLY GRILLE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
217 1 CD 2410 1.0 *200 *204
217 2 CD 2410 1.0 *200 *201
217 3 CD 2410 1.0 *200 *191
217 4 CD 2410 1.0 *200 *208
TOTAL (800)(804)
OUTSIDE AIR
217 1 DT 10" RD 0.55 564 310 581 319
TOTAL (310)(319)
REMARKS:
10/28/2021
103
FC-C2-9
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
PROJECT:
POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE
A-1 614 B-1 600 1 " Dia x 0.026 ="
A-2 571 B-2 572 2 " Dia x 0.082 ="
A-3 554 B-3 571 3 " Dia x 0.146 ="
A-4 575 B-4 613 4 " Dia x 0.226 ="
A-5 593 B-5 558 5 " Dia x 0.342 ="
A-6 587 B-6 558 6 " Dia x 0.685 ="
A-7 611 B-7 533 7 " Dia x 0.774 ="
A-8 588 B-8 598 8 " Dia x 0.854 ="
A-9 B-9 9 " Dia x 0.918 ="
A-10 B-10 10 " Dia x 0.974 ="
SUBTOTAL SUBTOTAL
(TOTAL FPM)DIVIDED
BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM
9,296 16 581 0.55 319
COMMENTS:D DUCT SIZE 10"
E AREA 1
S FPM 564
I CFM 310
G
N
T DUCT SIZE O.D.10"
E DUCT SIZE I.D.10"
S AREA 0.55
T CENTERLINE S.P.-0.02
AVERAGE FPM 581
D CFM MEASURED 319
A TEMP. CORRECTION 0
T ALT. CORRECTION 0
A ACTUAL CFM 319
10/28/2021
104SYSTEM #:FC-C2-9 OSA
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
ROUND DUCT TRAVERSE READINGS
INSTRUMENT USED: AIRFOIL
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
218 1 DO 14 X 14 1.36 286 390 299 406
TOTAL (390)(406)
REMARKS:
11/1/2021
105
FC-C2-10
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/28/2021
Page:106
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 800 821 390 401
Total CFM - Outlet 800 821 390 401
R/A CFM NS 504 390 401
O/A CFM 310 318 120 0 (3)
Static Pressure (Total/Ext)0.35"0.23"0.00"DUCTLESS
Inlet Pressure -0.06"DUCTLESS
Discharge Pressure 0.17"DUCTLESS
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 206
Amperage 2.3 1.3 0.2 0.1
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-C2-11 FC-C2-12
ABOVE CEILING ABOVE CEILING
219 6TH 8TH CLASSROOM 254 COLLAB
LG LG
ARNU243M2A4 ARNU153TQD4
011KCDG0G682 012KCDG0N570
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 94 ESP SETTING. ALL FAN SPEEDS SET TO 94 ESP
(2) CODE 3/ FAN SPEED 4/ 58 ESP SETTING. ALL FAN SPEEDS SET TO 58 ESP
(3) O.S.A. SUPPLIED BY SF 2-3 WITH SEPARATE SUPPLY GRILLE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
219 1 CD 2410 1.0 *200 *208
219 2 CD 2410 1.0 *200 *198
219 3 CD 2410 1.0 *200 *205
219 4 CD 2410 1.0 *200 *210
TOTAL (800)(821)
OUTSIDE AIR
219 1 DT 10" RD 0.55 564 310 578 318
TOTAL (310)(318)
REMARKS:
10/28/2021
107
FC-C2-11
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
PROJECT:
POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE
A-1 576 B-1 573 1 " Dia x 0.026 ="
A-2 581 B-2 610 2 " Dia x 0.082 ="
A-3 589 B-3 663 3 " Dia x 0.146 ="
A-4 596 B-4 683 4 " Dia x 0.226 ="
A-5 544 B-5 510 5 " Dia x 0.342 ="
A-6 549 B-6 571 6 " Dia x 0.685 ="
A-7 517 B-7 518 7 " Dia x 0.774 ="
A-8 563 B-8 600 8 " Dia x 0.854 ="
A-9 B-9 9 " Dia x 0.918 ="
A-10 B-10 10 " Dia x 0.974 ="
SUBTOTAL SUBTOTAL
(TOTAL FPM)DIVIDED
BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM
9,242 16 578 0.55 318
COMMENTS:D DUCT SIZE 10"
E AREA 1
S FPM 564
I CFM 310
G
N
T DUCT SIZE O.D.10"
E DUCT SIZE I.D.10"
S AREA 0.55
T CENTERLINE S.P.-0.02
AVERAGE FPM 578
D CFM MEASURED 318
A TEMP. CORRECTION 0
T ALT. CORRECTION 0
A ACTUAL CFM 318
10/28/2021
108SYSTEM #:FC-C2-11 OSA
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
ROUND DUCT TRAVERSE READINGS
INSTRUMENT USED: AIRFOIL
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
254 1 DO 14 X 14 1.36 286 390 295 401
TOTAL (390)(401)
REMARKS:
10/28/2021
109
FC-C2-12
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:10/28/2021
Page:110
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 800 824 800 801
Total CFM - Outlet 800 824 800 801
R/A CFM NS 498 NS 492
O/A CFM 310 327 310 310
Static Pressure (Total/Ext)0.35"0.19"0.35"0.21"
Inlet Pressure -0.07"-0.03"
Discharge Pressure 0.12"0.18"
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 208 208/230 206
Amperage 2.3 0.9 2.3 1.2
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-C2-13 FC-C2-14
ABOVE CEILING ABOVE CEILING
220 6TH 8TH CLASSROOM 221 6TH 8TH CLASSROOM
LG LG
ARNU243M2A4 ARNU243M2A4
011KCCV0G675 011KCHE0G673
DIRECT DIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 90 ESP SETTING. ALL FAN SPEEDS SET TO 90 ESP
(2) CODE 3/ FAN SPEED 4/ 97 ESP SETTING. ALL FAN SPEEDS SET TO 97 ESP
DIRECT DIVE DIRECT DRIVEDIRECT DIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
220 1 CD 2410 1.0 *200 *218
220 2 CD 2410 1.0 *200 *197
220 3 CD 2410 1.0 *200 *217
220 4 CD 2410 1.0 *200 *192
TOTAL (800)(824)
OUTSIDE AIR
220 1 DT 10" RD 0.55 564 310 595 327
TOTAL (310)(327)
REMARKS:
10/28/2021
111
FC-C2-13
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
PROJECT:
POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE
A-1 -387 B-1 764 1 " Dia x 0.026 ="
A-2 719 B-2 825 2 " Dia x 0.082 ="
A-3 665 B-3 710 3 " Dia x 0.146 ="
A-4 594 B-4 783 4 " Dia x 0.226 ="
A-5 470 B-5 629 5 " Dia x 0.342 ="
A-6 662 B-6 635 6 " Dia x 0.685 ="
A-7 659 B-7 644 7 " Dia x 0.774 ="
A-8 694 B-8 460 8 " Dia x 0.854 ="
A-9 B-9 9 " Dia x 0.918 ="
A-10 B-10 10 " Dia x 0.974 ="
SUBTOTAL SUBTOTAL
(TOTAL FPM)DIVIDED
BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM
9,526 16 595 0.55 327
COMMENTS:D DUCT SIZE 10"
E AREA 1
S FPM 564
I CFM 310
G
N
T DUCT SIZE O.D.10"
E DUCT SIZE I.D.10"
S AREA 0.55
T CENTERLINE S.P.-0.02
AVERAGE FPM 578
D CFM MEASURED 327
A TEMP. CORRECTION 0
T ALT. CORRECTION 0
A ACTUAL CFM 327
10/28/2021
112SYSTEM #:FC-C2-13 OSA
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
ROUND DUCT TRAVERSE READINGS
INSTRUMENT USED: AIRFOIL
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
221 1 CD 2410 1.0 *200 *208
221 2 CD 2410 1.0 *200 *203
221 3 CD 2410 1.0 *200 *196
221 4 CD 2410 1.0 *200 *194
TOTAL (800)(801)
OUTSIDE AIR
221 1 DT 10" RD 0.55 564 310 564 310
TOTAL (310)(310)
REMARKS:
10/28/2021
113
FC-C2-14
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
PROJECT:
POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE
A-1 546 B-1 521 1 " Dia x 0.026 ="
A-2 604 B-2 533 2 " Dia x 0.082 ="
A-3 600 B-3 510 3 " Dia x 0.146 ="
A-4 565 B-4 566 4 " Dia x 0.226 ="
A-5 585 B-5 588 5 " Dia x 0.342 ="
A-6 577 B-6 585 6 " Dia x 0.685 ="
A-7 558 B-7 5567 7 " Dia x 0.774 ="
A-8 525 B-8 608 8 " Dia x 0.854 ="
A-9 B-9 9 " Dia x 0.918 ="
A-10 B-10 10 " Dia x 0.974 ="
SUBTOTAL SUBTOTAL
(TOTAL FPM)DIVIDED
BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM
9,038 16 564 0.55 310
COMMENTS:D DUCT SIZE 10"
E AREA 1
S FPM 564
I CFM 310
G
N
T DUCT SIZE O.D.10"
E DUCT SIZE I.D.10"
S AREA 0.55
T CENTERLINE S.P.-0.04
AVERAGE FPM 564
D CFM MEASURED 310
A TEMP. CORRECTION 0
T ALT. CORRECTION 0
A ACTUAL CFM 310
10/28/2021
114SYSTEM #:FC-C2-14
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
ROUND DUCT TRAVERSE READINGS
INSTRUMENT USED: AIRFOIL
Date:11/3/2021
Page:115
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 800 829 800 820
Total CFM - Outlet 800 829 800 820
R/A CFM NS 520 NS 486
O/A CFM 310 309 310 334
Static Pressure (Total/Ext)0.35"0.19"0.35"0.19"
Inlet Pressure -0.04"-0.03"
Discharge Pressure 0.15"0.16"
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 208 208/230 206
Amperage 2.3 1.4 2.3 1.1
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
(1) CODE 3/ FAN SPEED 4/ 93 ESP SETTING. ALL FAN SPEEDS SET TO 93 ESP
(2) CODE 3/ FAN SPEED 4/ 92 ESP SETTING. ALL FAN SPEEDS SET TO 92 ESP
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
011KCLH0G776 011KCSF0G774
DIRECT DRIVE DIRECT DRIVE
LG LG
ARNU243M2A4 ARNU243M2A4
ABOVE CEILING RM 222 ABOVE CEILING RM 223
222 6TH 8TH CLASSROOM 223 6TH 8TH CLASSROOM
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-C2-15 FC-C2-16
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
222 1 CD 2410 1.0 *200 *208
222 2 CD 2410 1.0 *200 *200
222 3 CD 2410 1.0 *200 *212
222 4 CD 2410 1.0 *200 *209
TOTAL (800)(829)
OUTSIDE AIR
222 1 DT 10" RD 0.55 564 310 563 309
TOTAL (310)(309)
REMARKS:
11/3/2021
116
FC-C2-15
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
PROJECT:
POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE
A-1 596 B-1 565 1 " Dia x 0.026 =0.32 "
A-2 576 B-2 544 2 " Dia x 0.082 =1.05 "
A-3 587 B-3 568 3 " Dia x 0.146 =1.94 "
A-4 586 B-4 606 4 " Dia x 0.226 =3.23 "
A-5 558 B-5 606 5 " Dia x 0.342 =6.77 "
A-6 554 B-6 596 6 " Dia x 0.685 =8.06 "
A-7 564 B-7 513 7 " Dia x 0.774 =8.95 "
A-8 583 B-8 406 8 " Dia x 0.854 =9.68 "
A-9 B-9 9 " Dia x 0.918 ="
A-10 B-10 10 " Dia x 0.974 ="
SUBTOTAL SUBTOTAL
(TOTAL FPM)DIVIDED
BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM
9007 16 563 0.55 309
COMMENTS:D DUCT SIZE 10"
E AREA 1
S FPM 564
I CFM 310
G
N
T DUCT SIZE O.D.10"
E DUCT SIZE I.D.10"
S AREA 0.55
T CENTERLINE S.P.-0.02
AVERAGE FPM 563
D CFM MEASURED 309
A TEMP. CORRECTION NA
T ALT. CORRECTION NA
A ACTUAL CFM 309
11/3/2021
117SYSTEM #:FC-C2-15
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
ROUND DUCT TRAVERSE READINGS
INSTRUMENT USED: AIRFOIL
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
223 1 CD 2410 1.0 *200 *208
223 2 CD 2410 1.0 *200 *204
223 3 CD 2410 1.0 *200 *195
223 4 CD 2410 1.0 *200 *213
TOTAL (800)(820)
OUTSIDE AIR
223 1 DT 10" RD 0.55 564 310 608 334
TOTAL (310)(334)
REMARKS:
11/3/2021
18
FC-C2-16
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
PROJECT:
POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE
A-1 591 B-1 615 1 " Dia x 0.026 =0.32 "
A-2 553 B-2 520 2 " Dia x 0.082 =1.05 "
A-3 579 B-3 655 3 " Dia x 0.146 =1.94 "
A-4 632 B-4 598 4 " Dia x 0.226 =3.23 "
A-5 620 B-5 673 5 " Dia x 0.342 =6.77 "
A-6 598 B-6 644 6 " Dia x 0.685 =8.06 "
A-7 619 B-7 638 7 " Dia x 0.774 =8.95 "
A-8 599 B-8 592 8 " Dia x 0.854 =9.68 "
A-9 B-9 9 " Dia x 0.918 ="
A-10 B-10 10 " Dia x 0.974 ="
SUBTOTAL SUBTOTAL
(TOTAL FPM)DIVIDED
BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM
9,726 16 608 0.55 334
COMMENTS:D DUCT SIZE 10"
E AREA 1
S FPM 564
I CFM 310
G
N
T DUCT SIZE O.D.10"
E DUCT SIZE I.D.10"
S AREA 0.55
T CENTERLINE S.P.-0.04
AVERAGE FPM 608
D CFM MEASURED 334
A TEMP. CORRECTION 0
T ALT. CORRECTION 0
A ACTUAL CFM 334
11/3/2021
119SYSTEM #:FC-C2-16 OSA
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
ROUND DUCT TRAVERSE READINGS
INSTRUMENT USED:AIRFOIL
Date:11/3/2021
Page:120
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 800 809 800 813
Total CFM - Outlet 800 809 800 813
R/A CFM NS 499 NS 585
O/A CFM 310 310 230 228
Static Pressure (Total/Ext)0.35"0.18"0.35"0.23"
Inlet Pressure -0.06"-0.05"
Discharge Pressure 0.12"0.18"
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 207 208/230 207
Amperage 2.3 0.9 2.3 1.2
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
(1) CODE 3/ FAN SPEED 4/ 88 ESP SETTING. ALL FAN SPEEDS SET TO 88 ESP
(2) CODE 3/ FAN SPEED 4/ 90 ESP SETTING. ALL FAN SPEEDS SET TO 90 ESP
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
011KCKJ0G613 012KCAS0EW76
DIRECT DRIVE DIRECT DRIVE
LG LG
ARNU243M2A4 ARNU243M2A4
ABOVE CEILING 224 ABOVE CEILING 225
224 6TH 8TH CLASSROOM 225 6TH 8TH CLASSROOM
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-C2-17 FC-C2-18
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
224 1 CD 2410 1.0 *200 *195
224 2 CD 2410 1.0 *200 *198
224 3 CD 2410 1.0 *200 *203
224 4 CD 2410 1.0 *200 *213
TOTAL (800)(809)
OUTSIDE AIR
224 1 DT 10" RD 0.55 564 310 564 310
TOTAL (310)(310)
REMARKS:
11/3/2021
121
FC-C2-17
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
PROJECT:
POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE
A-1 496 B-1 639 1 " Dia x 0.026 =0.32 "
A-2 499 B-2 613 2 " Dia x 0.082 =1.05 "
A-3 572 B-3 663 3 " Dia x 0.146 =1.94 "
A-4 566 B-4 517 4 " Dia x 0.226 =3.23 "
A-5 561 B-5 541 5 " Dia x 0.342 =6.77 "
A-6 526 B-6 606 6 " Dia x 0.685 =8.06 "
A-7 559 B-7 575 7 " Dia x 0.774 =8.95 "
A-8 571 B-8 514 8 " Dia x 0.854 =9.68 "
A-9 B-9 9 " Dia x 0.918 ="
A-10 B-10 10 " Dia x 0.974 ="
SUBTOTAL SUBTOTAL
(TOTAL FPM)DIVIDED
BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM
9,017 16 564 0.55 310
COMMENTS:D DUCT SIZE 10"
E AREA 1
S FPM 564
I CFM 310
G
N
T DUCT SIZE O.D.10"
E DUCT SIZE I.D.10"
S AREA 0.55
T CENTERLINE S.P.-0.05
AVERAGE FPM 564
D CFM MEASURED 310
A TEMP. CORRECTION NA
T ALT. CORRECTION NA
A ACTUAL CFM 310
11/3/2021
122SYSTEM #:FC-C2-17 OSA
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
ROUND DUCT TRAVERSE READINGS
INSTRUMENT USED: AIRFOIL
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
225 1 CD 2410 1.0 *200 *195
225 2 CD 2410 1.0 *200 *205
225 3 CD 2410 1.0 *200 *200
225 4 CD 2410 1.0 *200 *213
TOTAL (800)(813)
OUTSIDE AIR
225 1 DT 10" RD 0.55 418 230 416 228
TOTAL (230)(228)
REMARKS:
11/3/2021
123
FC-C2-18
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
PROJECT:
POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE
A-1 356 B-1 490 1 " Dia x 0.026 =0.32 "
A-2 406 B-2 468 2 " Dia x 0.082 =1.05 "
A-3 380 B-3 488 3 " Dia x 0.146 =1.94 "
A-4 367 B-4 489 4 " Dia x 0.226 =3.23 "
A-5 449 B-5 434 5 " Dia x 0.342 =6.77 "
A-6 392 B-6 369 6 " Dia x 0.685 =8.06 "
A-7 444 B-7 393 7 " Dia x 0.774 =8.95 "
A-8 358 B-8 378 8 " Dia x 0.854 =9.68 "
A-9 B-9 9 " Dia x 0.918 ="
A-10 B-10 10 " Dia x 0.974 ="
SUBTOTAL SUBTOTAL
(TOTAL FPM)DIVIDED
BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM
6,661 16 416 0.55 228
COMMENTS:D DUCT SIZE 10"
E AREA 1
S FPM 418
I CFM 230
G
N
T DUCT SIZE O.D.10"
E DUCT SIZE I.D.10"
S AREA 0.55
T CENTERLINE S.P.-0.02
AVERAGE FPM 416
D CFM MEASURED 228
A TEMP. CORRECTION NA
T ALT. CORRECTION NA
A ACTUAL CFM 228
11/3/2021
124SYSTEM #:FC-C2-18
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
ROUND DUCT TRAVERSE READINGS
INSTRUMENT USED: AIRFOIL
Date:11/4/2021
Page:125
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 800 828 500 514
Total CFM - Outlet 800 828 500 514
R/A CFM NS 597 500 514
O/A CFM 230 231 -0--0-
Static Pressure (Total/Ext)0.35"0.16"0.00"DUCTLESS
Inlet Pressure -0.03"DUCTLESS
Discharge Pressure 0.13"DUCTLESS
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED LOW SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 207
Amperage 2.3 1.4 0.52 0.3
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED LOW SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
(1) CODE 3/ FAN SPEED 4/ 88 ESP SETTING. ALL FAN SPEEDS SET TO 88 ESP
(2) CODE 3/ FAN SPEED 4/ 20 ESP SETTING. ALL FAN SPEEDS SET TO 20 ESP
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
012KCSF0EW66 009KCYQ16M58
DIRECT DRIVE DIRECT DRIVE
LG LG
ARNU183M2A4 ARNU183SKA4
ABOVE CEILING RM 226 WAL MOUNT 243
226 6TH 8TH CLASSROOM 233 ELECTRICAL
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-C2-19 FC-C2-20
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
226 1 CD 2410 1.0 *200 *200
226 2 CD 2410 1.0 *200 *211
226 3 CD 2410 1.0 *200 *209
226 4 CD 2410 1.0 *200 *208
TOTAL (800)(828)
OUTSIDE AIR
226 1 DT 10" RD 0.55 418 230 421 231
TOTAL (230)(231)
REMARKS:
11/4/2021
126
FC-C2-19
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
PROJECT:
POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE
A-1 460 B-1 491 1 " Dia x 0.026 =0.32 "
A-2 512 B-2 485 2 " Dia x 0.082 =1.05 "
A-3 467 B-3 479 3 " Dia x 0.146 =1.94 "
A-4 341 B-4 447 4 " Dia x 0.226 =3.23 "
A-5 320 B-5 419 5 " Dia x 0.342 =6.77 "
A-6 328 B-6 371 6 " Dia x 0.685 =8.06 "
A-7 392 B-7 455 7 " Dia x 0.774 =8.95 "
A-8 366 B-8 408 8 " Dia x 0.854 =9.68 "
A-9 B-9 9 " Dia x 0.918 ="
A-10 B-10 10 " Dia x 0.974 ="
SUBTOTAL SUBTOTAL
(TOTAL FPM)DIVIDED
BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM
6,741 16 421 0.55 231
COMMENTS:D DUCT SIZE 10"
E AREA 1
S FPM 418
I CFM 230
G
N
T DUCT SIZE O.D.10"
E DUCT SIZE I.D.10"
S AREA 0.55
T CENTERLINE S.P.-0.03
AVERAGE FPM 421
D CFM MEASURED 231
A TEMP. CORRECTION NA
T ALT. CORRECTION NA
A ACTUAL CFM 231
11/4/2021
127SYSTEM #:FC-C2-19 OSA
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
ROUND DUCT TRAVERSE READINGS
INSTRUMENT USED: AIRFOIL
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
223 1 DO 34" X 4"0.94 531 500 547 514
TOTAL (500)(514)
REMARKS:
(1) T STAT IS NOT WORKING, UNABLE TO BALANCE 11/4/2021
11/4/2021
128
FC-C2-20
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/4/2021
Page:129
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 240 258 1,730 1754
Total CFM - Outlet 240 258 1,730 1754
R/A CFM 240 258 NS 1076
O/A CFM -0--0-665 678
Static Pressure (Total/Ext)0.00"DUCTLESS 0.47"0.40"
Inlet Pressure DUCTLESS -0.12"
Discharge Pressure DUCTLESS 0.28"
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 207 208/230 206
Amperage 0.25 0.1 5.2 2.3
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
(1) CODE 3/ FAN SPEED 4/ 74 ESP SETTING. ALL FAN SPEEDS SET TO 74 ESP
(2) CODE 3/ FAN SPEED 4/ 78 ESP SETTING. ALL FAN SPEEDS SET TO 78 ESP
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
010KCKJ1AD61 104KCYQ04258
DIRECT DRIVE DIRECT DRIVE
LG LG
ARNU053SJA4 ARNU363B8A4
WAL MOUNT RM 233B ABOVE CEILING RM 126
233B DATA 126 LOWER SCHOOL ART LAB
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-C2-21 FC-D1-1
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
223 1 DO 3" X 28"0.58 413 240 445 258
TOTAL (240)(258)
REMARKS:
11/4/2021
130
FC-C2-21
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
126 1 CD 2410 1.0 *290 *294
126 2 CD 2410 1.0 *290 *281
126 3 CD 2410 1.0 *290 *306
126 4 CD 2410 1.0 *290 *278
126 5 CD 2410 1.0 *290 *297
126 6 CD 2410 1.0 *290 *298
TOTAL (1,740)*(1754)
OUTSIDE AIR
LOUVER 1 RG 48" X 12"1.0 *665 *678
TOTAL (665)(678)
REMARKS:
11/1/2021
131
FC-D1-1
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/2/2021
Page:132
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 1,915 2,015 800 812
Total CFM - Outlet 1,915 2,015 800 812
R/A CFM NS 1,297 NS 489
O/A CFM 705 718 310 323
Static Pressure (Total/Ext)0.47"0.39"0.45"0.26"
Inlet Pressure 0.21"-0.08"
Discharge Pressure -0.18"0.18"
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 207 208/230 206
Amperage 5.2 1.2 2.3 1.1
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
(1) CODE 3/ FAN SPEED 4/ 80 ESP SETTING. ALL FAN SPEEDS SET TO 80 ESP
(2) CODE 3/ FAN SPEED 4/ 92 ESP SETTING. ALL FAN SPEEDS SET TO 92 ESP
DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
012KCYQ10698 011KCCV0G723
DIRECT DRIVE DIRECT DRIVE
LG LG
ARNU423B8A4 ARNU243M2A4
ABOVE CEILING RM 125 ABOVE CEILING RM 125A
125 LOWER SCHOOL ART LAB 125A CERAMICS
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-D1-3 FC-D1-4
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
125 1 CD 2410 1.0 *320 *326
125 2 CD 2410 1.0 *320 *342
125 3 CD 2410 1.0 *320 *328
125 4 CD 2410 1.0 *320 *337
125 5 CD 2410 1.0 *320 *344
125 6 CD 2410 1.0 *320 *338
TOTAL (1,920)(2,015)
OUTSIDE AIR
125 1 RG 48" X 12"1.0 *705 *718
TOTAL (705)(718)
REMARKS:
11/1/2021
133
FC-D1-3
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
125A 1 CD 2410 1.0 *195 *196
125A 2 CD 2410 1.0 *195 *183
125A 3 CD 2410 1.0 *195 *199
125A 4 CD 2410 1.0 *195 *201
125B 5 SWG 10" X 6"1.0 *30 *33
TOTAL (810)(812)
OUTSIDE AIR
125A 1 RG 48" X 12"1.0 *310 *323
TOTAL (310)(323)
REMARKS:
11/2/2021
134
FC-D1-4
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/2/2021
Page:135
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model A
Serial Number
Specified Actual Specified Actual
Total CFM - fan 1,750 1,743 265 277
Total CFM - Outlet 1,750 1,743 265 277
R/A CFM NS 1,052 NS 244
O/A CFM 655 691 30 33 (3)
Static Pressure (Total/Ext)0.35"0.19"0.00"DUCTLESS
Inlet Pressure -0.15"DUCTLESS
Discharge Pressure 0.04"DUCTLESS
Fan RPM 3 SPEED HIGH SPD. (1) 3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NA NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 207 208/230 207
Amperage 2.5 1.8 0.20 0.1
Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
(1) CODE 3/ FAN SPEED 4/ 110 ESP SETTING. ALL FAN SPEEDS SET TO 110 ESP
(2) CODE 3/ FAN SPEED 4/ 51 ESP SETTING. ALL FAN SPEEDS SET TO 51 ESP
(3) FOR O.S.A. SEE SF 1-3 AIR DISTRIBUTION SHEET.
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
011KCCV0RT87 011KCPY0U208
DIRECT DRIVE DIRECT DRIVE
LG LG
ARNU543M3A4 ARNU053TRD4
ABOVE CEILING 124 WOODSHOP ABOVE CEILING RM
124 WOODSHOP 124A OFFICE
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-D1-5 FC-D1-6
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
124 1 SG 16" X 10"0.88 500 440 412 363
124 2 SG 16" X 10"0.88 500 440 340 299
124 3 SG 16" X 10"0.88 500 440 536 472
124 4 SG 16" X 10"0.88 500 440 692 609
TOTAL (1,760)(1,743)
OUTSIDE AIR
LOUVER 1 RG 46" X 18"1.0 *655 *691
TOTAL (655)(691)
REMARKS:
11/5/2021
136
FC-D1-5
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
124A 1 DO 14" X 14"1.36 195 265 198 270
TOTAL (265)(270)
REMARKS:
10/25/2021
137
FC-A1-3
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/2/2021
Page:138
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 2,260 2,188 1,250 1,264
Total CFM - Outlet 2,260 2,188 1,250 1,264
R/A CFM NS 1,384 NS 853
O/A CFM 765 804 400 411
Static Pressure (Total/Ext)0.4"0.44"0.35"0.28"
Inlet Pressure -0.39"-0.12"
Discharge Pressure 0.05"0.16"
Fan RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2)
Specified Actual Specified Actual
Motor Manufacturer NA NA
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 206
Amperage 5.2 2.5 2.5 1.4
Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-D1-7 FC-D1-8
123 MAKERSPACE 123A TECH LAB
123 MAKERSPACE 123A TECH LAB
LG LG
ARNU763B8A4 ARNU283M3A4
011KCVU0L327 011KCPY1C280
DIRECT DRIVE DIRECT DRIVE
(1) CODE 3/ FAN SPEED 4/ 84 ESP SETTING. ALL FAN SPEEDS SET TO 84 ESP
(2) CODE 3/ FAN SPEED 4/ 92 ESP SETTING. ALL FAN SPEEDS SET TO 92 ESP
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
123 1 SG 16" X 10"0.83 337 280 322 267
123 2 SG 16" X 10"0.83 337 280 327 272
123 3 SG 16" X 8"0.66"424 280 253 167
123 4 SG 16" X 8"0.66"424 280 455 300
123 5 SG 16" X 10"0.83 337 280 304 252
123 6 SG 16" X 10"0.83 337 280 487 389
123 7 SG 16" X 8"0.66"424 280 332 219
123 8 SG 16" X 8"0.66"424 280 487 322
TOTAL (2,240)(1)(2,188)
OUTSIDE AIR
LOUVER 1 RG 42" X 18"1.0 *765 *804
TOTAL (765)(804)
REMARKS:
(1) DAMPERS INSTALLED FOR BRANCHES BUT NOT INDIVIDUAL GRILLES. SET FOR TOTAL . SERVES COMMON AREA.
11/2/2021
139
FC-D1-7
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
123A 1 CD 2410 1.0 *315 *322
123A 2 CD 2410 1.0 *315 *315
123A 3 CD 2410 1.0 *315 *317
123A 4 CD 2410 1.0 *315 *310
TOTAL (1,260)(1,264)
OUTSIDE AIR
LOUVER 1 RG 42" X 18"1.0 *400 *411
TOTAL (400)(411)
REMARKS:
11/2/2021
140
FC-D1-8
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/5/2021
Page:141
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 2,545 2,593 800 834
Total CFM - Outlet 2,545 2,593 800 834
R/A CFM NS 2,593 NS 600
O/A CFM -0--0-225 234
Static Pressure (Total/Ext)0.25"DUCTLESS 0.35"0.20"
Inlet Pressure DUCTLESS -0.04"
Discharge Pressure DUCTLESS 0.16"
Fan RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NA NA
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 209 208/230 207
Amperage 2.5 1.7 2.3 0.9
Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
(1) CODE 3/ FAN SPEED 4/ ESP SETTING. ALL FAN SPEEDS SET TO ESP
(2) CODE 3/ FAN SPEED 4/ 90 ESP SETTING. ALL FAN SPEEDS SET TO 90 ESP
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
011KCCV0RT87 012KCLH0EW68
DIRECT DRIVE DIRECT DRIVE
LG LG
ARNU963B8A4 ARNU183M2A4
125B KILN ROOM ABOVE CEILING RM 277
125B KILN ROOM 277 6TH 8TH CLASSROOM
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-D1-9 FC-D2-1
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
128 1 DO 60" X 15"6.25 407 2,545 415 2,593
TOTAL (2,545)(2,593)
REMARKS:
11/5/2021
142
FC-B1-19
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
227 1 CD 2410 1.0 *200 *202
227 2 CD 2410 1.0 *200 *213
227 3 CD 2410 1.0 *200 *209
227 4 CD 2410 1.0 *200 *210
TOTAL (800)(834)
OUTSIDE AIR
227 1 DT 10" RD 0.55 409 225 427 234
TOTAL (225)(234)
REMARKS:
11/2/2021
143
FC-D2-1
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
PROJECT:
POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE
A-1 396 B-1 412 1 " Dia x 0.026 =0.32 "
A-2 387 B-2 435 2 " Dia x 0.082 =1.05 "
A-3 378 B-3 305 3 " Dia x 0.146 =1.94 "
A-4 370 B-4 417 4 " Dia x 0.226 =3.23 "
A-5 474 B-5 385 5 " Dia x 0.342 =6.77 "
A-6 498 B-6 465 6 " Dia x 0.685 =8.06 "
A-7 495 B-7 464 7 " Dia x 0.774 =8.95 "
A-8 464 B-8 493 8 " Dia x 0.854 =9.68 "
A-9 B-9 9 " Dia x 0.918 ="
A-10 B-10 10 " Dia x 0.974 ="
SUBTOTAL SUBTOTAL
(TOTAL FPM)DIVIDED
BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM
3,838 16 427 0.55 234
COMMENTS:D DUCT SIZE 10" RD
E AREA 0.55
S FPM 409
I CFM 225
G
N
T DUCT SIZE O.D.10" RD
E DUCT SIZE I.D.10" RD
S AREA 0.55
T CENTERLINE S.P.-0.04
AVERAGE FPM 427
D CFM MEASURED 234
A TEMP. CORRECTION 0
T ALT. CORRECTION 0
A ACTUAL CFM 234
11/2/2021
144SYSTEM #:FC-D2-1 OSA
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 32925
ROUND DUCT TRAVERSE READINGS
INSTRUMENT USED: AIRFOIL
Date:11/2/2021
Page:145
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 390 401 1,750 1,767
Total CFM - Outlet 390 401 1,750 1,767
R/A CFM NS 401 NS 1,100
O/A CFM 135 0 (3)660 667
Static Pressure (Total/Ext)0.00"DUCTLESS 0.50"0.40"
Inlet Pressure DUCTLESS -0.07"
Discharge Pressure DUCTLESS 0.33"
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 207
Amperage 0.20 0.1 2.5 1.8
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
(1) CODE 3/ FAN SPEED 4/ 56 ESP SETTING. ALL FAN SPEEDS SET TO 56 ESP
(2) CODE 3/ FAN SPEED 4/ 112 ESP SETTING. ALL FAN SPEEDS SET TO 112 ESP
(4) O.S.A. SUPPLIED BY SF 2-2 WITH SEPARATE SUPPLY GRILLE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
010KCTB1AY13 011KCHE0RT85
DIRECT DRIVE DIRECT DRIVE
LG LG
ARNU153TQD4 ARNU543M3A4
ABOVE CEILING RM 228 ABOVE CEILING RM 229
228 WORKROOM 229 UPPER SCHOOL SCIENCE LAB
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-D2-2 FC-D2-3
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
228 1 DO 14 X 14 1.36 287 390 295 401
TOTAL (390)(401)
REMARKS:
11/2/2021
146
FC-D2-2
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
229 1 CD 2408 1.0 *295 *289
229 2 CD 2408 1.0 *295 *296
229 3 CD 2408 1.0 *295 *299
229 4 CD 2408 1.0 *295 *287
229 5 CD 2408 1.0 *295 *301
229 6 CD 2408 1.0 *295 *295
TOTAL (1,770)(1,767)
RETURN AIR SYSTEM
229 1 DT 12" RD 0.79 NS NS 703 555
229 2 DT 12" RD 0.79 NS NS 691 545
TOTAL (NS)(1,100)
OUTSIDE AIR
229 1 16''RD 660 667
TOTAL (660)(1)(667)
REMARKS:
(1) UNABLE TO TRAVERSE OSA DUCT. SUPPLY MINUS RETURN = OSA
11/2/2021
147
FC-D2-3
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/2/2021
Page:148
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 390 403 1,750 1,769
Total CFM - Outlet 390 403 1,750 1,769
R/A CFM NS 403 NS 1,145
O/A CFM 135 0 (3)610 624
Static Pressure (Total/Ext)0.00"DUCTLESS 0.50"0.43"
Inlet Pressure DUCTLESS -0.12"
Discharge Pressure DUCTLESS 0.31"
Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 208
Amperage 0.20 0.1 2.5 1.4
Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
(1) CODE 3/ FAN SPEED 4/ 54 ESP SETTING. ALL FAN SPEEDS SET TO 54 ESP
(2) CODE 3/ FAN SPEED 4/ 116 ESP SETTING. ALL FAN SPEEDS SET TO 116 ESP
(4) O.S.A. SUPPLIED BY SF 2-4 WITH SEPARATE SUPPLY GRILLE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
009KCXM07Q10 011KCV0U0RT83
DIRECT DRIVE DIRECT DRIVE
LG LG
ARNU153TQD4 ARNU543M3A4
ABOVE CEILING RM 226A ABOVE CEILING RM 230
226A PREP ROOM 230 UPPER SCHOOL SCIENCE LAB
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-D2-4 FC-D2-5
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
226A 1 DO 14 X 14 1.36 287 390 297 403
TOTAL (390)(403)
REMARKS:
11/2/2021
149
FC-D2-4
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
230 1 CD 2408 1.0 *295 *288
230 2 CD 2408 1.0 *295 *290
230 3 CD 2408 1.0 *295 *293
230 4 CD 2408 1.0 *295 *303
230 5 CD 2408 1.0 *295 *304
230 6 CD 2408 1.0 *295 *291
TOTAL (1,770)(1,769)
RETURN AIR SYSTEM
230 1 DT 12" RD 0.79 NS NS 713 563
230 2 DT 12" RD 0.79 NS NS 738 582
TOTAL (NS)(1)(1,145)
OUTSIDE AIR
230 1 16"RD 610 624
TOTAL (610)(1)(624)
REMARKS:
(1) UNABLE TO TRAVERSE OSA DUCT. SUPPLY MINUS RETURN = OSA
11/2/2021
150
FC-D2-5
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/2/2021
Page:151
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 1,450 1,415
Total CFM - Outlet 1,450 1,415
R/A CFM NS 1,051
O/A CFM 350 364
Static Pressure (Total/Ext)0.35"0.26"
Inlet Pressure -0.09"
Discharge Pressure 0.17"
Fan RPM 3 SPEED HIGH SPD (1)
Specified Actual Specified Actual
Motor Manufacturer NS
Motor H.P.NS NS
Phase 1 1
Voltage 208/230 207
Amperage 2.5 1.4
Motor RPM 3 SPEED HIGH SPD (1)
Motor Service Factor NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
(1) CODE 3/ FAN SPEED 4/ 92 ESP SETTING. ALL FAN SPEEDS SET TO 92 ESP
DIRECT DRIVE DIRECT DRIVE
008KCUK16L62
DIRECT DRIVE
LG
ARNU363M3A4
ABOVE CEILING RM 231
231 COLLAB
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM FC-D2-6
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
231 1 CD 2412 1.0 *365 *363
231 2 CD 2412 1.0 *365 *368
231 3 CD 2412 1.0 *365 *329
231 4 CD 2412 1.0 *365 *375
TOTAL (1,460)(1,435)
OUTSIDE AIR
231 1 DT 10" RD 0.55 648 350 663 364
TOTAL (350)(364)
REMARKS:
11/2/2021
152
FC-D2-6
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
PROJECT:
POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE
A-1 648 B-1 686 1 " Dia x 0.026 =0.32 "
A-2 696 B-2 709 2 " Dia x 0.082 =1.05 "
A-3 681 B-3 710 3 " Dia x 0.146 =1.94 "
A-4 671 B-4 700 4 " Dia x 0.226 =3.23 "
A-5 674 B-5 686 5 " Dia x 0.342 =6.77 "
A-6 625 B-6 636 6 " Dia x 0.685 =8.06 "
A-7 600 B-7 627 7 " Dia x 0.774 =8.95 "
A-8 585 B-8 671 8 " Dia x 0.854 =9.68 "
A-9 B-9 9 " Dia x 0.918 ="
A-10 B-10 10 " Dia x 0.974 ="
SUBTOTAL SUBTOTAL
(TOTAL FPM)DIVIDED
BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM
10,607 16 663 0.55 364
COMMENTS:D DUCT SIZE 10" RD
E AREA 0.55
S FPM 648
I CFM 350
G
N
T DUCT SIZE O.D.10" RD
E DUCT SIZE I.D.10" RD
S AREA 0.55
T CENTERLINE S.P.-0.06
AVERAGE FPM 663
D CFM MEASURED 364
A TEMP. CORRECTION NA
T ALT. CORRECTION NA
A ACTUAL CFM 364
11/2/2021
153SYSTEM #:FC-D2-6
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 32925
ROUND DUCT TRAVERSE READINGS
INSTRUMENT USED: AIRFOIL
Date:11/3/2021
Page:154
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 200 200 1,215 1,175
Total CFM - Outlet 200 200 1,215 1,175
R/A CFM -0--0--0-
O/A CFM -0--0--0-
Static Pressure (Total/Ext)0.40"0.20"0.65"0.88"
Inlet Pressure -0.15"-0.33"
Discharge Pressure 0.05"0.55"
Fan RPM SPD. DIAL 0-100%40%SPD. DIAL 0-100%100%
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 115 121 115 121
Amperage 1.42 0.6 7.4 7.1
Motor RPM SPD. DIAL 0-100%40%SPD. DIAL 0-100%100%
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM EF1-1 EF1-2
NORTHEAST 1ST FLOOR RR'S NORTH 1ST FLOOR RR'S
NORTHEAST 1ST FLOOR RR'S NORTH 1ST FLOOR RR'S
GREENHECK GREENHECK
CSP-A390 CSP-A1410
NS NS
DIRECT DRIVE DIRECT DRIVE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
EXHAUST AIR SYSTEM
100A 1 CE 2408 1.0 *100 *101
100B 2 CE 2408 1.0 *100 *99
TOTAL (200)(200)
REMARKS:
11/4/2021
155
EF 1-1
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
EXHAUST AIR SYSTEM
111A 1 CE 2408 1.0 *100 *101
108A 2 CE 2408 1.0 *100 *103
144 3 CE 2410 1.0 *300 *283
142 4 CE 2408 1.0 *100 *103
145 5 CE 2408 1.0 *100 *92
136 6 EG 17" X 4"0.43 500 215 477 205
143 7 CE 2410 1.0 *300 *288
TOTAL (1,215)(1,175)
REMARKS:
11/3/2021
156
EF 1-2
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/3/2021
Page:157
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 940 965 670 1,231
Total CFM - Outlet 940 965 1,220 1,231
R/A CFM -0--0--0--0-
O/A CFM -0--0--0--0-
Static Pressure (Total/Ext)0.75"0.57"0.40"0.63"
Inlet Pressure -0.41"-0.26"
Discharge Pressure 0.16"0.37"
Fan RPM SPD. DIAL 0-100%50%SPD. DIAL 0-100%100%
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 115 121 115 121
Amperage 7.4 7.0 7.4 7.0
Motor RPM SPD. DIAL 0-100%50%SPD. DIAL 0-100%100%
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM EF 1-3 EF 1-4
SOUTH RR'S LOWER SCHOOL SCIENCE LAB
SOUTH RR'S LOWER SCHOOL SCIENCE LAB
GREENHECK GREENHECK
CSP-A1410 CSP-A14110
NS NS
DIRECT DRIVE DIRECT DRIVE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
EXHAUST AIR SYSTEM
140 1 CE 2410 1.0 *300 *303
139 2 CE 2410 1.0 *300 *308
151 3 EG 10" X 4"0.25 560 140 594 149
152 4 CE 2408 1.0 *100 *101
153 5 CE 2408 1.0 *100 *104
TOTAL (940)(965)
REMARKS:
11/3/2021
158
EF 1-3
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
EXHAUST AIR SYSTEM
122 1 CE 2416 1.0 *1,220 *1,231
TOTAL (1,220)(1,231)
REMARKS:
11/3/2021
159
EF 1-4
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/3/2021
Page:160
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 670 813 (1)760 762
Total CFM - Outlet 710 813 (1)760 762
R/A CFM -0--0--0--0-
O/A CFM -0--0--0--0-
Static Pressure (Total/Ext)0.40"0.20"0.40"0.30"
Inlet Pressure -0.13"-0.19"
Discharge Pressure 0.07"0.11"
Fan RPM SPD. DIAL 0-100%10%SPD. DIAL 0-100%40%
Specified Actual Specified Actual
Motor Manufacturer NA NA
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 115 121 115 121
Amperage 7.4 5.3 3.0 2.1
Motor RPM SPD. DIAL 0-100%10%SPD. DIAL 0-100%40%
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM EF 1-5 EF 1-6
MAKERSPACE WOODSHOP
MAKERSPACE WOODSHOP
GREENHECK GREENHECK
CSP-A1410 CSP-A900
NS NS
DIRECT DRIVE DIRECT DRIVE
(1) EXHAUST FAN TESTED AT LOWEST POSSIBLE SPEED.
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
EXHAUST AIR SYSTEM
123 1 EG 12" X 8"1.0 *355 *398
123 2 EG 12" X 8"1.0 *355 *415
TOTAL (710)(813)
REMARKS:
11/3/2021
161
EF 1-6
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
EXHAUST AIR SYSTEM
124 1 EG 12" X 10"1.0 *380 *358
124 2 EG 12" X 10"1.0 *380 *404
TOTAL (760)(762)
REMARKS:
11/3/2021
162
EF 1-6
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/3/2021
Page:162
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 1,920 1,559 (1)940 948
Total CFM - Outlet 1,920 1,559 (1)950 948
R/A CFM -0--0--0--0-
O/A CFM -0--0--0--0-
Static Pressure (Total/Ext)0.50"0.28"0.45"0.30"
Inlet Pressure -0.26"-0.24"
Discharge Pressure 0.02"0.06"
Fan RPM SPD. DIAL LOW/HI HIGH SPD.SPD. DIAL 0-100%35%
Specified Actual Specified Actual
Motor Manufacturer NA NA
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 115 121 115 121
Amperage 11.6 9.8 7.4 5.8
Motor RPM SPD. DIAL LOW/HI HIGH SPD.SPD. DIAL 0-100%35%
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM EF 1-8 EF 2-1
ART LABS 2ND FLOOR SOUTH RR'S
ART LABS 2ND FLOOR SOUTH RR'S
GREENHECK GREENHECK
CSP-A2150 CSP-A1410
17752097 NS
DIRECT DRIVE DIRECT DRIVE
(1) EXHAUST FAN TESTED AT 100% FAN SPEED
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
EXHAUST AIR SYSTEM
126 1 CE 2414 1.0 *960 *781
125 2 CE 2414 1.0 *960 *778
TOTAL (1,920)(1,559)
REMARKS:
11/3/2021
164
EF 1-8
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
EXHAUST AIR SYSTEM
245 1 CE 2410 1.0 *300 *291
247 2 CE 2408 1.0 *100 *98
244 3 CE 2408 1.0 *100 *105
246 4 CE 2410 1.0 *300 *299
242 5 EG 17" X 4"0.43 348 150 360 155
TOTAL (950)(948)
REMARKS:
11/5/2021
165
EF 2-1
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/4/2021
Page:166
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 940 932 1,290 960
Total CFM - Outlet 940 932 1,290 960
R/A CFM -0--0--0--0-
O/A CFM -0--0--0--0-
Static Pressure (Total/Ext)0.75"0.32"0.45"0.28"
Inlet Pressure -0.24"-0.18"
Discharge Pressure 0.08"0.10"
Fan RPM SPD. DIAL 0-100%100%SPD. DIAL 0-100%DIAL @ 100%
Specified Actual Specified Actual
Motor Manufacturer NS NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 120 120 115
Amperage 7.4 6.6 7.4 6.3
Motor RPM SPD. DIAL 0-100%100%SPD. DIAL 0-100%DIAL @ 100%
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
NS NS
DIRECT DRIVE DIRECT DRIVE
GREENHECK GREENHECK
CSP-A1410 CSP-A1410
ABOVE CEILING HALLWAY ABOVE CEILING RM 229
2ND FLOOR SOUTH RR'S 229 UPPER SCHOOL SCIENCE LAB
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM EF 2-2 EF 2-3
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
EXHAUST AIR SYSTEM
238 1 CE 2410 1.0 *300 *284
237 2 CE 2410 1.0 *300 *294
235 3 EG 16" X 4"0.44 327 140 333 146
239 4 CE 2408 1.0 *100 *103
236 5 CE 2408 1.0 *100 *105
TOTAL (940)(932)
REMARKS:
11/4/2021
167
EF 2-2
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
EXHAUST AIR SYSTEM
229 1 CE 22" X 22"1.0 *1,290 *960
TOTAL (1,290)(960)
REMARKS:
11/4/2021
168
EF 2-3
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/4/2021
Page:169
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 1,290 1,248
Total CFM - Outlet 1,290 1,248
R/A CFM -0--0-
O/A CFM -0--0-
Static Pressure (Total/Ext)0.45"0.21"
Inlet Pressure -0.18"
Discharge Pressure 0.03"
Fan RPM SPD. DIAL 0-100%100%
Specified Actual Specified Actual
Motor Manufacturer NS
Motor H.P.NS NS
Phase 1 1
Voltage 115 116
Amperage 7.4 6.8
Motor RPM SPD. DIAL 0-100%100%
Motor Service Factor NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
DIRECT DRIVEDIRECT DRIVE
NS
DIRECT DRIVE
GREENHECK
CSP-A1410
ABOVE CEILING RM 230
230 UPPER SCHOOL SCIENCE LAB
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM EF 2-4
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
EXHAUST AIR SYSTEM
230 1 CE 22" X 22"1.0 *1,290 *1,248
TOTAL (1,290)(1,248)
REMARKS:
11/4/2021
170
EF 2-4
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/5/2021
Page:171
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 540 512 540 552
Total CFM - Outlet 540 512 540 552
R/A CFM -0--0--0--0-
O/A CFM -0--0--0--0-
Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS
Inlet Pressure DUCTLESS DUCTLESS
Discharge Pressure DUCTLESS DUCTLESS
Fan RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2)
Specified Actual Specified Actual
Motor Manufacturer NA NA
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 208/230 206 208/230 206
Amperage 0.52 0.4 0.52 0.4
Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2)
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM SS-1 SS 1-2
ELEVATOR MACHINE ROOM ELEVATOR MACHINE ROOM
ELEVATOR MACHINE ROOM NORTH ELEVATOR MACHINE ROOM SOUTH
LG LG
ARNU243SKA4 ARNU243SKA4
011KCH0RE53 011KCH0RE37
DIRECT DRIVE DIRECT DRIVE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
234 1 D.O.34" X 3"0.71 761 540 721 512
TOTAL (540)(512)
REMARKS:
11/5/2021
172
SS-1
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
SUPPLY AIR SYSTEM
234 1 D.O.34 X 3 0.71 761 540 778 552
TOTAL (540)(552)
REMARKS:
11/5/2021
173
SS-2
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/5/2021
Page:174
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 700 696 1,145 1,166
Total CFM - Outlet 705 696 1,145 1,166
R/A CFM -0--0--0--0-
O/A CFM 705 696 1,145 1,166
Static Pressure (Total/Ext)0.75"0.22"1.15 0.57"
Inlet Pressure -0.16"-0.46"
Discharge Pressure 0.06"0.11"
Fan RPM SPD. DIAL 0-100%25%SPD. DIAL 0-100 100%
Specified Actual Specified Actual
Motor Manufacturer NA NA
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 115 121 115 121
Amperage 5.0 3.3 7.4 5.5
Motor RPM SPD. DIAL 0-100%25%SPD. DIAL 0-100%100%
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM SF 1-1 SF 1-2
HEAD ASST. 103 MATH SPECIALIST
FC'S OSA FC'S OSA
GREENHECK GREENHECK
CSP-A1050 CSP-A1050
NS NS
DIRECT DRIVE DIRECT DRIVE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
OUTSIDE AIR SYSTEM
FC-A1-1 1 DT 6"0.2 100 20 110 22
FC-A1-3 2 DT 6"0.2 175 35 190 38
107 3 CD 2406 1.0 *90 *94
FC-A1-2 4 DT 10"0.55 490 270 496 273
FC-A1-5 5 DT 6"0.2 125 25 135 27
159 6 CD 2406 1.0 *95 *98
FC-A1-7 7 DT 6"0.2 150 30 165 33
106 8 CD 2406 1.0 *60 *63
FC-A1-9 9 DT 6"0.2 100 20 110 22
FC-A1-8 10 DT 6"0.2 175 35 165 33
TOTAL (680)(703)
REMARKS:
11/5/2021
175
SF 1-1
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
OUTSIDE AIR SYSTEM
108C 1 CD 2406 1.0 *60 *64
113 2 CD 2408 1.0 *110 *109
FC-A1-14 3 DT 6"0.2 150 30 165 33
FC-A1-15 4 DT 6"0.2 150 30 140 28
137 5 CD 2408 1.0 *120 *112
FC-A1-17 6 DT 6"0.2 125 25 135 27
134 7 CD 2406 1.0 *90 *87
115A 8 CD 2406 1.0 *75 *80
133 9 CD 2408 1.0 *125 *128
117A 10 CD 2406 1.0 *NS *85
131A 11 CD 2408 1.0 *145 *151
131B 12 CD 2408 1.0 *150 *155
119A 13 CD 2408 1.0 *105 *107
TOTAL (1,065)(1,166)
REMARKS:
11/5/2021
176
SF 1-2
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/3/2021
Page:177
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 135 145 925 994
Total CFM - Outlet 135 145 925 959
R/A CFM -0--0--0--0-
O/A CFM 135 145 925 994
Static Pressure (Total/Ext)0.50"0.23"0.85"0.18"
Inlet Pressure -0.03"-0.14"
Discharge Pressure 0.20"0.04"
Fan RPM SPD. DIAL 0-100%5%SPD. DIAL 0-100%50%
Specified Actual Specified Actual
Motor Manufacturer NA NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 115 121 115 116
Amperage 0.79 0.2 7.4 4.8
Motor RPM SPD. DIAL 0-100%5%SPD. DIAL 0-100%50%
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
NS NS
DIRECT DRIVE DIRECT DRIVE
GREENHECK GREENHECK
CSP-A250 CSP-A1410
ART LAB 126 STAFF LOUNGE 207
FC'S OSA FC,S OSA
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM SF 1-3 SF 2-1
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
OUTSIDE AIR SYSTEM
162 1 SG 12" X 12"1.0 *105 *112
FC-D1-6 2 DT 6"0.2 150 30 165 33
TOTAL (135)(145)
REMARKS:
11/5/2021
178
SF 1-3
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
OUTSIDE AIR SYSTEM
208 1 CD 2408 1.0 *135 *137
FC-A2-3 2 DT 6"0.20 100 20 106 21
FC-A2-4 3 DT 6"0.20 100 20 95 19
FC-A2-5 4 DT 6"0.20 100 20 110 22
FC-A2-2 5 DT 12"0.79 525 415 572 451
207A 6 CD 2406 1.0 *70 *72
FC-A2-7 7 DT 6"0.20 100 25 96 19
252 8 CD 2408 1.0 *125 *121
FC-A2-9 9 DT 6"0.20 125 25 137 27
FC-A2-12 10 DT 6"0.20 175 35 166 33
FC-A2-11 11 DT 6"0.20 75 15 81 16
FC-A2-10 12 DT 6"0.20 100 20 109 21
TOTAL (925)(959)
REMARKS:
11/3/2021
179
SF 2-1
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/5/2021
Page:180
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 195 199 255 244
Total CFM - Outlet 195 199 255 244
R/A CFM -0--0--0--0-
O/A CFM 195 199 255 244
Static Pressure (Total/Ext)0.80"0.16"0.60"0.10"
Inlet Pressure -0.09"-0.06"
Discharge Pressure 0.07"0.04"
Fan RPM SPD. DIAL 0-100%NS SPD. DIAL 0-100%100%
Specified Actual Specified Actual
Motor Manufacturer NA NS
Motor H.P.NS NS NS NS
Phase 1 1 1 1
Voltage 115 121 115 121
Amperage 1.33 0.6 1.42 0.7
Motor RPM SPD. DIAL 0-100%NS SPD. DIAL 0-100%100%
Motor Service Factor NS NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM SF 2-2 SF 2-3
6TH-8TH CLASSROOM 213 COLAB 218
FC'S OSA FC'S OSA
GREENHECK GREENHECK
CSP-A390 CSP-A390
NS NS
DIRECT DRIVE DIRECT DRIVE
DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
OUTSIDE AIR SYSTEM
211A 1 CD 2408 1.0 *90 *91
249 2 CD 2408 1.0 *105 *108
TOTAL (195)(199)
REMARKS:
11/3/2021
181
SF 2-2
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
OUTSIDE AIR SYSTEM
218 1 CD 2406 1.0 *135 *131
254 2 CD 2406 1.0 *120 *113
TOTAL (255)(244)
REMARKS:
11/4/2021
182
SF 2-3
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
Date:11/4/2021
Page:183
Project Name:
Equipment Location
Area Served
Equipment Manufacturer
Model
Serial Number
Specified Actual Specified Actual
Total CFM - fan 270 272
Total CFM - Outlet 270 272
R/A CFM -0--0-
O/A CFM 270 272
Static Pressure (Total/Ext)0.75"0.14"
Inlet Pressure -0.10"
Discharge Pressure 0.04"
Fan RPM SPD. DIAL 0-100%70%
Specified Actual Specified Actual
Motor Manufacturer NS
Motor H.P.NS NS
Phase 1 1
Voltage 115 121
Amperage 1.42 0.4
Motor RPM SPD. DIAL 0-100%70%
Motor Service Factor NS
Motor Sheave Pitch
Motor Sheave & Shaft Size
Fan Sheave & Shaft SizeBelts
Remarks:
..
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM SF 2-2
SCIENCE LAB 229
FC'S OSA
GREENHECK
CSP-A390
NS
DIRECT DRIVE
DIRECT DRIVEDIRECT DRIVE
DATE:
PAGE:
SYSTEM #:
PROJECT:
ROOM NO.CODE SIZE AK
FACTOR
REQUIRED
F.P.M.
REQUIRED
C.F.M.
ACTUAL
F.P.M.
ACTUAL
C.F.M.
OUTSIDE AIR SYSTEM
229A 1 CD 2408 1.0 *135 *139
228 2 CD 2408 1.0 *135 *133
TOTAL (270)(272)
REMARKS:
11/4/2021
184
SF 2-4
HARBOR DAY SCHOOL
3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625
AIR DISTRIBUTION
APPLICABLE CODES
CALIFORNIA MECHANICAL PROJECTS:
ALL WORK SHALL BE IN FULL ACCORDANCE WITH APPLICABLE
LOCAL, STATE, AND FEDERAL CODES, LAWS AND REGULATIONS.
ALL WORK AND MATERIALS SHALL BE IN FULL ACCORDANCE WITH,
BUT NOT LIMITED TO:
• CALIFORNIA CODE OF REGULATIONS (CCR)
• 2016 CALIFORNIA BUILDING CODE -CCR TITLE 24 PART 2
• 2016 CALIFORNIA ELECTRICAL CODE -CCR TITLE 24 PART 3
• 2016 CALIFORNIA MECHANICAL CODE -CCR TITLE 24 PART 4
• 2016 CALIFORNIA PLUMBING CODE -CCR TITLE 24 PART 5
• 2016 CALIFORNIA ENERGY CODE -CCR TITLE 24 PART 6
• 2016 CALIFORNIA FIRE CODE -CCR TITLE 24 PART 9
• 2016 CALIFORNIA GREEN BUILDING STANDARDS CODE -CCR
TITLE 24 PART 11
ALL WORK SHALL BE IN ACCORDANCE WITH THE FOLLOWING
ADDITIONAL GUIDELINES WHERE REQUIRED BY CODE:
• AMERICAN SOCIETY OF SANITARY ENGINEERS (ASSE)
• AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)
• AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
• NATIONAL FIRE PROTECTION AGENCY (NFPA)
• OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA)
• LOCAL UTILITY GUIDELINES AND REGULATIONS
• LOCAL AIR QUALITY MANAGEMENT DISTRICTS
SCOPE OF WORK
AT 3443 PACIFIC VIEW DRIVE, A NEW TWO-STORY BUILDING IS BEING
CONSTRUCTED. THE MECHANICAL SCOPE OF WORK INCLUDES A VRF
SYSTEM TO SUPPLY HEATING AND COOLING TO THE BUILDING, OUTSIDE AIR
FANS TO SUPPLY OUTSIDE AIR TO THE VRF FAN COILS, AND EXHAUST FANS
TO EXHAUST ENVIRONMENTAL AIR FROM THE SPACE TO THE OUTDOORS.
CORRESPONDING REFRIGERANT LINES, DUCTWORK, DIFFUSERS, AND
PERMANANT OPENINGS WILL BE INSTALLED TO ADEQUATELY PROVIDE
THESE SERVICES.
DRAWING INDEX
DRAWING INDEX KEY
NOT INCLUDED WITH ISSUE
NEW OR REVISED
NO CHANGES
DR
A
W
I
N
G
I
S
S
U
E
DA
T
E
SHEET
NO.SHEET TITLE
REVISION
AFF
AHJ
ASD
BDD
BF
BOD
BOI
BOP
CS
CR
CE
CL
CLG
CFM
CHWR
CHWS
CMU
CONC
CONT'R
CWR
CWS
COND
DSD
DWG
(E)
EA
EG
ELB
ELEC
EQ
EXH
EXT
(F)
FD
FLEX
FLR
FR
FS
FSD
ABOVE FINISHED FLOOR
AUTHORITY HAVING JURISDICTION
AREA SMOKE DETECTOR
BACKDRAFT DAMPER
BOTTOM FLAT
BOTTOM OF DUCT
BOTTOM OF INSULATION
BOTTOM OF PIPE
CEILING SUPPLY
CEILING RETURN
CEILING EXHAUST
CENTERLINE
CEILING
CUBIC FEET PER MINUTE
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONCRETE MASONRY UNIT
CONCRETE
CONTRACTOR
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
CONDENSATE
DUCT SMOKE DETECTOR
DRAWING
EXISTING
EXHAUST AIR
EXHAUST AIR GRILLE
ELBOW
ELECTRICAL
EQUIPMENT
EXHAUST
EXTERIOR
FUTURE
FIRE DAMPER
FLEXIBLE
FLOOR
FLOOR RETURN
FLOOR SUPPLY
FIRE SMOKE DAMPER
GA
GALV
GC
GPH
GPM
GYP BD
HT
HOA
HWR
HWS
ID
INS
INT
(L)
LR
LS
MA
MECH
MFR
MTD
MTL
MUA
MVD
(N)
N/A
NC
NIC
NO
NTS
OBD
OC
OD
OPN'G
OSA
POC
GAUGE
GALVANIZED
GENERAL CONTRACTOR
GALLONS PER HOUR
GALLONS PER MINUTE
GYPSUM BOARD
HEIGHT
HAND-OFF-AUTO
HOT WATER RETURN
HOT WATER SUPPLY
INSIDE DIMENSION
INSULATION
INTERIOR
LINED
LINEAR RETURN
LINEAR SUPPLY
MIXED AIR
MECHANICAL
MANUFACTURER
MOUNTED
METAL
MAKE UP AIR
MANUAL VOLUME DAMPER
NEW
NOT APPLICABLE
NORMALLY CLOSED
NOT IN CONTRACT
NORMALLY OPEN
NOT TO SCALE
OPPOSED BLADE DAMPER
ON CENTER
OUTSIDE DIMENSION
OPENING
OUTSIDE AIR
POINT OF CONNECTION
(R)
RA
RG
RMF
RND
REQ'D
SA
SG
SM
SS
STD
TF
TOD
TOP
T'STAT
UBC
UC
UG
UMC
UNO
UTR
V
VAV
VFD
VOL
WMS
XFER
RELOCATE
RETURN AIR
RETURN OR TRANSFER GRILLE
RAPID MOUNT FRAME
ROUND
REQUIRED
SUPPLY AIR
SUPPLY GRILLE
SHEET METAL
STAINLESS STEEL
STANDARD
TOP FLAT
TOP OF DUCT
TOP OF PIPE
THERMOSTAT
UNIFORM BUILDING CODE
UNDERCUT
UNDERGROUND
UNIFORM MECHANICAL CODE
UNLESS NOTED OTHERWISE
UP THROUGH ROOF
VENT
VARIABLE AIR VOLUME
VARIABLE SPEED DRIVE
VOLUME
WIRE MESH SCREEN
TRANSFER
ABBREVIATIONS
ABBR.DESCRIPTION ABBR. DESCRIPTION ABBR. DESCRIPTION
HVAC LEGEND
LEGEND PIPING SYMBOL LEGEND
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
PIPING SYMBOL LEGEND
SYMBOL DESCRIPTION
LEGEND
SYMBOL DESCRIPTION
NEW (N) & EXISTING (E) RECTANGULAR SUPPLY AIR DUCT RISER SUPPLY AIR DIFFUSER (NEW & EXISTING - 24X24)PNEUMATIC 2W-CV FLEX CONNECTOR
NEW (N) & EXISTING (E) RECTANGULAR RETURN AIR DUCT RISER RETURN AIR GRILLE (NEW & EXISTING - 24X24)PNEUMATIC 3W-CV TWIN RUBBER SPHERICAL CONNECTOR
NEW (N) & EXISTING (E) RECTANGULAR EXHAUST AIR DUCT RISER RETURN AIR GRILLE (NEW & EXISTING - 24X12)PNEUMATIC BUTTERFLY 2W-CV TRIPLE GROOVED COUPLINGS
NEW (N) & EXISTING (E) ROUND AIR DUCT RISER SUPPLY AIR GRILLE (NEW & EXISTING - 24X24)PNEUMATIC BUTTERFLY 3W-CV (DIVERTING)END CAP
NEW SINGLE LINE & DOUBLE LINE RECTANGULAR OR ROUND DUCT RETURN AIR GRILLE (NEW & EXISTING - 24X24 WITH ROUND NECK)PNEUMATIC BUTTERFLY 3W-CV (MIXING)BLIND FLANGE
EXISTING SINGLE LINE & DOUBLE LINE RECTANGULAR OR ROUND DUCT EXHAUST AIR GRILLE (NEW & EXISTING - 24X24 WITH ROUND NECK)MOTORIZED 2W-CV CONCENTRIC REDUCER
EXISTING SINGLE LINE DUCTWORK TO BE DEMOLISHED ("X"
OPTION)
EXISTING DOUBLE LINE DUCTWORK TO BE DEMOLISHED ("X"
OPTION)
EXHAUST GRILLE (NEW & EXISTING - 24X24)MOTORIZED 3W-CV ECCENTRIC REDUCER
EXISTING DUCTWORK TO BE DEMOLISHED (HATCH OPTION)ROUND DIFFUSER MOTORIZED BUTTERFLY 2W-CV UNION
DUCT WITH LINING. DIMENSIONS SHOWN ARE O.D. OF SHEETMETAL (W
X H).
THICKNESS OF INSULATION AS SHOWN ON PLANS
SIDE WALL GRILLE MOTORIZED BUTTERFLY 3W-CV (DIVERTING)SCHRAEDER VALVE
SINGLE & DOUBLE LINE DUCTWORK WITH TRANSITIONAL FITTING LINEAR DIFFUSER (SUPPLY)MOTORIZED BUTTERFLY 3W-CV (MIXING)FLOW ARROW
DOUBLE LINE SQUARE TO ROUND TRANSITIONAL FITTING WALL LOUVER GATE VALVE PRESSURE GAUGE WITH SHUT-OFF VALVE
90° RADIUS ELBOW 90° SQUARE ELBOW WITH TURNING VANES SPIRAL SIDEWALL (WITH EXTRACTOR & WITHOUT EXTRACTOR)BALL VALVE TEMPERATURE SENSOR & THERMO WELL
ROUND DUCT TURNING VERTICAL RECT. DUCT TURNING VERTICAL FLEXIBLE DUCT BALL VALVE WITH MEMORY STOP THERMOMETER
SINGLE LINE MANUAL VOLUME
DAMPER
DOUBLE LINE MANUAL VOLUME
DAMPER
SECTION NUMBER SECTION CALL
OUT
SYMBOL SHEET NUMBER
GLOBE VALVE PETE'S PLUG
MOTORIZED DAMPER (ELECTRIC)
GRILLE TYPE - DIFFUSER NECK SIZE
AIR VOLUME CUBIC FEET PER MINUTE - AIR THROW
PATTERN
BUTTERFLY VALVE FLOW SWITCH
MOTORIZED DAMPER (PNEUMATIC)EQUIPMENT LABEL TAG CHECK VALVE TRIPLE DUTY VALVE
FIRE DAMPER (SINGLE LINE AND DOUBLE LINE)COOLING ONLY VAV BOX TAG STRAINER RELIEF VALVE
FIRE/SMOKE DAMPER (SINGLE LINE AND DOUBLE LINE)REHEAT VAV BOX TAG STRAINER WITH BLOWDOWN VALVE 3-WAY WAX VALVE
SMOKE DETECTOR (DUCT TYPE)CEILING OR DUCT ACCESS PANEL BY GENERAL CONTRACTOR BASKET STRAINER VACUUM BREAKER
SMOKE DETECTOR (AREA TYPE)COOLING ONLY VAV BOX WITH SQUARE TO ROUND OUTLET SUCTION DIFFUSER STEAM TRAP
THERMOSTAT WITH ZONE NUMBER REHEAT VAV BOX WITH SQUARE TO ROUND OUTLET AIR VENT - MANUAL ANGLE VALVE
CO2 SENSOR COOLING ONLY VAV BOX WITH RECTANGULAR LINED SHEET METAL PLENUM AIR VENT - AUTO SIGHT GLASS
CO SENSOR REHEAT VAV BOX WITH RECTANGULAR LINED SHEET METAL PLENUM PRESSURE REDUCING VALVE FILTER DRIER
WALL SWITCH FLOW ARROW PRESSURE SUSTAINING VALVE SOLENOID VALVE
POINT OF CONNECTION FLOW ARROW - CURVED AUTO FLOW CONTROL TXV WITH SENSING BULB
REVISION DELTA REVISION CLOUD CIRCUIT SETTER PRESSURE GAUGE - STEAM
GAS STUB-UP BY PLUMBING CONTRACTOR
CONDENSATE LINE WITH TRAP TO APPROVED RECEPTOR BY
PLUMBING
CONTRACTOR
BALL VALVE WITH HOSE CONNECTION DIFFERENTIAL PRESSURE SENSOR
COLD WATER STUB-UP BY PLUMBING CONTRACTOR
FLOOR SINK WITH TRAP TO APPROVED RECEPTOR BY
PLUMBING
CONTRACTOR
FLOW METER INLINE HOSE BIBB
ELECTRICAL EQUIPMENT CONNECTION
LOCATION BY ELECTRICAL
CONTRACTOR
FLOW METER TURBINE
FM
DP
T
FS
T
S
FM
T
(N) (E)
ROUNDSQUARE
(E)(N)
(E)(N)
(E)(N)
EQ
#
CS-1- 12"
500 4W
10
10
10
10
CO2
CO
$
X
VAV-CO
XX-YY-ZZ
VAV-RH
XX-YY-ZZ
24X12(1"L)
1 2
21
1 2
1 2
#
E
P
E E
P
E
ASD
DSD
A
#
HARBOR DAY SCHOOL
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
2/
5
/
2
0
2
1
3
:
3
8
:
4
5
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC0.00
COVER SHEET & DRAWING
INDEX
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
N/A
AC0.00 COVER SHEET & DRAWING INDEX
AC0.01 EQUIPMENT SCHEDULES AND GENERAL NOTES
AC0.02 EQUIPMENT SCHEDULES
AC0.03 EQUIPMENT SCHEDULES
AC0.05 TITLE-24, MANDATORY MEASURES, & GENERAL NOTES
AC0.06 TITLE-24 (CONT.)
AC0.07 ENERGY COMPLIANCE
AC0.08 ENERGY COMPLIANCE (CONT.)
AC0.09 ENERGY COMPLIANCE (CONT.)
AC1.01 MECHANICAL LEVEL 01 FLOOR PLAN OVERALL
AC1.01A MECHANICAL LEVEL 01 FLOOR PLAN NORTH
AC1.01B MECHANICAL LEVEL 01 FLOOR PLAN SOUTH
AC1.02 MECHANICAL LEVEL 02 FLOOR PLAN OVERALL
AC1.02A MECHANICAL LEVEL 02 FLOOR PLAN NORTH
AC1.02B MECHANICAL LEVEL 02 FLOOR PLAN SOUTH
AC1.03 MECHANICAL ROOF FLOOR PLAN OVERALL
AC1.03A MECHANICAL ROOF FLOOR PLAN NORTH
AC1.03B MECHANICAL ROOF FLOOR PLAN SOUTH
AC2.01 MECHANICAL PIPING LEVEL 01 FLOOR PLAN OVERALL
AC2.01A MECHANICAL PIPING LEVEL 01 FLOOR PLAN NORTH
AC2.01B MECHANICAL PIPING LEVEL 01 FLOOR PLAN SOUTH
AC2.02 MECHANICAL PIPING LEVEL 02 FLOOR PLAN OVERALL
AC2.02A MECHANICAL PIPING LEVEL 02 FLOOR PLAN NORTH
AC2.02B MECHANICAL PIPING LEVEL 02 FLOOR PLAN SOUTH
AC4.01 MECHANICAL ENLARGED PLANS
AC5.01 MECHANICAL DETAILS
AC5.02 MECHANICAL DETAIL (CONT.)
AC5.03 MECHANICAL DETAIL (CONT.)
AC6.01 MECHANICAL VRF PIPING DIAGRAM
AC6.02 MECHANICAL VRF PIPING DIAGRAMS (CONT.)
AC7.01 POWER LOAD DIAGRAMS
AC7.02 POWER LOAD DIAGRAMS (CONT.)
AC7.03 SEQUENCE OF OPERATIONS
AC9.01 MECHANICAL LEVEL 01 HVAC ZONE PLAN
AC9.02 MECHANICAL LEVEL 02 HVAC ZONE PLAN
10
0
%
D
E
S
I
G
N
D
E
V
E
L
O
P
M
E
N
T
08
/
1
6
/
1
9
A
1S
T
C
I
T
Y
S
U
B
M
I
T
T
A
L
10
/
2
5
/
1
9
B
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
0 09/11/20 ISSUED FOR
CONSTRUCTION
CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
2 xx/xx ACOUSTICAL CHANGES DN
C
2N
D
C
I
T
Y
S
U
B
M
I
T
T
A
L
02
/
1
4
/
2
0
D
3R
D
C
I
T
Y
S
U
B
M
I
T
T
A
L
05
/
0
1
/
2
0
IS
S
U
E
D
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
09
/
1
1
/
2
0
0
CI
T
Y
P
E
R
M
I
T
A
M
E
N
D
M
E
N
T
09
/
1
1
/
2
0
1
AC
O
U
S
T
I
C
A
L
C
H
A
N
G
E
S
2
xx
/
x
x
CU-A ARUM408DTE5 VRF FC'S 34 R410-A 408.0 87.0 459.0 39.0
(a) ARUM192DTE5 35.7 50 460V-3ɸ-60 5 N
9.7 3.22 N 1325 117% -(b) ARUM216DTE5 38.3 50 460V-3ɸ-60 5 N
N/A N/A N/A N/A N/A - -
CU-B ARUM408DTE5 VRF FC'S 34 R410-A 408.0 87.0 459.0 39.0
(a) ARUM192DTE5 35.7 50 460V-3ɸ-60 5 N
9.7 3.22 N 1325 108% -(b) ARUM216DTE5 38.3 50 460V-3ɸ-60 5 N
N/A N/A N/A N/A N/A - -
CU-C ARUM384DTE5 VRF FC'S 32 R410-A 384.0 87.0 432.0 39.0
(a) ARUM168DTE5 28.5 35 460V-3ɸ-60 5 N
9.8 3.22 N 1305 104% -(b) ARUM216DTE5 38.3 50 460V-3ɸ-60 5 N
(c) N/A N/A N/A N/A - -
CU-D ARUM504DTE5 VRF FC'S 42 R410-A 504.0 87.0 567.0 39.0
(a) ARUM121DTE5 18.4 25 460V-3ɸ-60 5 N
9.6 3.21 N 1664 112% -(b) ARUM168DTE5 28.5 35 460V-3ɸ-60 5 N
(c) ARUM192DTE5 38.3 50 460V-3ɸ-60 5 N
FC-A1-1 LG
ARNU053TRD4
130D ADMISSIONS
DIRECTOR 0.46 20 265 0 - R410A 5.5 - 78.8 - 6.1 69.5 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A1-2 LG
ARNU283M3A4 100 LOBBY 2.5 270 1250 0.35 - R410A 28.0 - 80.2 - 31.5 64.9 - 2.5 650 109 208/230V-1ɸ-60 N - Y 100
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH
FC-A1-3 LG
ARNU073TRD4 101 NURSE 0.63 35 265 0 - R410A 7.5 - 79.3 - 8.5 67.6 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A1-4 LG
ARNU093TRD4
107 CONFERENCE
ROOM 0.8 90 285 0 - R410A 9.6 - 81.2 - 10.9 61.6 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A1-5 LG
ARNU053TRD4
102 LOWER
DIRECTOR 0.45 25 265 0 - R410A 5.5 - 78.9 - 6.1 68.9 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A1-6 LG
ARNU123TRD4 159 OPEN OFFICE 1.0 95 310 0 - R410A 12.3 - 81.1 - 13.6 61.9 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A1-7 LG
ARNU053TRD4
103 HEAD
ASSISTANT 0.63 30 265 0 - R410A 5.5 - 79.1 - 6.1 68.3 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A1-8 LG
ARNU073TRD4
104 HEAD OF
SCHOOL 0.63 35 265 0 - R410A 7.5 - 79.3 - 8.5 67.6 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A1-9 LG
ARNU053TRD4
105 FACILITIES
DIRECTOR 0.45 20 265 0 - R410A 5.5 - 78.8 - 6.1 69.5 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A1-10 LG
ARNU123TRD4 106 WORKROOM 1.0 60 310 0 - R410A 12.3 - 79.9 - 13.6 65.6 - 0.20 -30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A1-11 LG
ARNU053SJA4 109 DATA 0.46 N/A 240 0 - R410A 5.5 - - - 6.1 - - 0.25 - 30 208/230V-1ɸ-60 N 8 Y 20
INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE
OVERFLOW SWITCH
FC-A1-12 LG
ARNU363SVA4 110 ELECT. 3.0 N/A 918 0 - R410A 35.5 - - - 37.0 - - 0.81 - 104 208/230V-1ɸ-60 N 8 Y 40
INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE
OVERFLOW SWITCH
FC-A1-13 LG
ARNU123TRD4 134 ASSOCIATES 1.0 90 310 0 - R410A 12.3 - 80.9 - 13.6 62.4 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A1-14 LG
ARNU053TRD4 137A PSYCH 0.45 30 265 0 - R410A 5.5 - 79.1 - 6.1 68.3 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A1-15 LG
ARNU053TRD4
137B LANGUAGE
ARTS SPECIALIST 0.45 30 265 0 - R410A 5.5 - 79.1 - 6.1 68.3 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A1-16 LG
ARNU123TRD4
137 SMALL GROUP
AREA 1.0 120 310 0 - R410A 12.3 - 81.9 - 13.6 59.2 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A1-17 LG
ARNU053TRD4
137C MATH
SPECIALIST 0.45 25 265 0 - R410A 5.5 - 78.9 - 6.1 68.9 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A1-18A LG
ARNU363M3A4
132 STORY
TELLING 3.0 560 1450 0.70 - R410A 36.2 - 81.9 - 40.6 59.3 - 2.5 650 161 208/230V-1ɸ-60 N 8 Y 100
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL
CONDENSATE OVERFLOW SWITCH
FC-A1-18B LG
ARNU363M3A4 133 LIBRARY 3.0 405 1450 0.70 - R410A 36.2 - 80.8 - 40.6 62.7 - 2.5 650 161 208/230V-1ɸ-60 N 8 Y 100
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL
CONDENSATE OVERFLOW SWITCH
FC-A1-19 LG
ARNU123TRD4 133 TINKER AREA 1.0 125 310 0 - R410A 12.3 - 82.0 - 13.6 58.7 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A1-20 LG
ARNU153TQD4 131A WORKROOM 1.3 145 390 0 - R410A 15.4 - 81.7 - 17.1 59.7 - 0.20 - 30 208/230V-1ɸ-60 N - N 45
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A1-21 LG
ARNU153TQD4
131B TEACHING
AREA 1.3 150 390 0 - R410A 15.4 - 81.8 - 17.1 59.3 - 0.20 - 30 208/230V-1ɸ-60 N - N 45
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A2-1 LG
ARNU153TQD4 208 WORKROOM 1.3 135 390 0 - R410A 15.4 - 81.5 - 17.1 60.6 - 0.20 - 30 208/230V-1ɸ-60 N - N 45
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A2-2 LG
ARNU763B8A4
207 STAFF
LOUNGE 6.4 415 2260 0.35 - R410A 76.4 - 79.8 - 86.0 65.9 - 5.2 800 765 208/230V-1ɸ-60 N - Y 200
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH
FC-A2-3 LG
ARNU053TRD4
210 DIRECTOR OF
TECH 0.45 20 265 0 - R410A 5.5 - 78.8 - 6.1 69.5 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A2-4 LG
ARNU053TRD4
209 SYSTEMS
ADMIN 0.45 20 265 0 - R410A 5.5 - 78.8 - 6.1 69.5 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A2-5 LG
ARNU053TRD4 BUSINESS OFFICE 0.45 20 265 0 - R410A 5.5 - 78.8 - 6.1 69.5 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A2-6 LG
ARNU053TRD4 MOTHERS ROOM 0.45 70 265 0 - R410A 5.5 - 80.6 - 6.1 63.3 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A2-7 LG
ARNU053TRD4
206 ASSISTANT
BUSINESS 0.45 25 265 0 - R410A 5.5 - 78.9 - 6.1 68.9 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A2-8 LG
ARNU123TRD4 252 OPEN OFFICE 1.0 125 310 0 - R410A 12.3 - 82.0 - 13.6 58.7 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A2-9 LG
ARNU053TRD4
204 DIRECTOR OF
DEVELOPMENT 0.45 25 265 0 - R410A 5.5 - 78.9 - 6.1 68.9 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A2-10 LG
ARNU053TRD4
201 DIR. OF
DEVELOPMENT
ASST
0.45 20 265 0 - R410A 5.5 - 78.8 - 6.1 69.5 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A2-11 LG
ARNU053TRD4
202 DIRECTOR OF
DEVELOPMENT 0.45 15 265 0 - R410A 5.5 - 78.6 - 6.1 70.1 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A2-12 LG
ARNU073TRD4
203 UPPER
DIRECTOR 0.63 35 265 0 - R410A 7.5 - 79.3 - 8.5 67.6 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-A2-13 LG
ARNU053SJA4 241 ELECT. 0.46 N/A 240 0 - R410A 5.5 - - - 6.1 - - 0.25 - 30 208/230V-1ɸ-60 N 8 Y 20
INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE
OVERFLOW SWITCH
FC-A2-14 LG
ARNU153SJA4 240 DATA 1.3 N/A 375 0 - R410A 15.4 - - - 17.1 - - 0.25 - 30 208/230V-1ɸ-60 N 8 Y 20
INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE
OVERFLOW SWITCH
FC-A2-15 LG
ARNU243M2A4
211 5TH GRADE
CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE
OVERFLOW SWITCH
FC-B1-1 LG
ARNU283M3A4
108
KINDERGARTEN 2.3 415 1250 0.35 - R410A 28.0 - 81.3 - 31.5 61.0 - 2.5 650 109 208/230V-1ɸ-60 N 8 Y 100
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL
CONDENSATE OVERFLOW SWITCH
FC-B1-2 LG
ARNU073SJA4 163 ELECTRICAL 0.63 N/A 254 0 - R410A 7.5 - - - 8.5 - - 0.25 - 30 208/230V-1ɸ-60 N 8 Y 20
INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE
OVERFLOW SWITCH
FC-B1-3 LG
ARNU093TRD4 108C WORKROOM 0.8 60 285 0 - R410A 9.6 - 80.1 - 10.9 65.1 - 0.20 -30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP,
INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE
FC-B1-4 LG
ARNU283M3A4
111
KINDERGARTEN 2.3 410 1250 0.35 - R410A 28.0 - 81.3 - 31.5 61.2 - 2.5 650 109 208/230V-1ɸ-60 N 8 Y 100
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL
CONDENSATE OVERFLOW SWITCH
FC-B1-5 LG
ARNU283M3A4
112 1ST GRADE
CLASSROOM 2.3 370 1250 0.35 - R410A 28.0 - 81.0 - 31.5 62.2 - 2.5 650 109 208/230V-1ɸ-60 N 8 Y 100
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL
CONDENSATE OVERFLOW SWITCH
SYMBOL MANUFACTURER &
MODEL No.SERVING NOMINAL
TON REF. TYPE
COOLING HEATING ELECTRICAL RATED EFFICIENCY @ AHRI
CAPACITY / POWER INPUT VIB.
ISO
TOTAL
WEIGHT
(lbs)
CONNECTIVITY RATIO
(>50% & <130%)REMARKSTOTAL
MBH
AMB
(°F)
TOTAL
MBH
AMB
(°F)FRAME FRAME
MODEL MCA MOCP VOLTAGE
SCCR
(KAIC)E-PWR
COOLING HEATING
EER COP
SYMBOL MANUFACTURER &
MODEL No.SERVING NOMINAL
TON OSA CFM CFM
E.S.P.
(IN.)RPM REF. TYPE
COOLING HEATING
RLA
MAX
POWER
INPUT (W)
POWER
INPUT
(W)
VOLTAGE EMERGENCY
POWER
FILTER
MERV VIB. ISO WEIGHT (lbs)REMARKSTOTAL
MBH
SENSIBLE
MBH EDB (°F)LDB/LWB
(°F)
TOTAL
MBH
EDB
(°F)
LDB
(°F)
AIR COOLED CONDENSING UNIT (VRF)
FAN COIL (VRF)
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
2/
5
/
2
0
2
1
3
:
1
0
:
1
7
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC0.01
EQUIPMENT SCHEDULES
AND GENERAL NOTES
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
N/A
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
0 09/11/20 ISSUED FOR
CONSTRUCTION
CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
FC-B1-6 LG
ARNU123TRD4
113 SMALL
GROUP 1.0 110 310 0 - R410A 12.3 - 81.5 - 13.6 60.3 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED
CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN
SETTING: HIGH, TRUE 2'X2' GRILLE
FC-B1-7 LG
ARNU283M3A4
114 1ST
GRADE
CLASSROOM
2.3 370 1250 0.35 - R410A 28.0 - 81.0 - 31.5 62.2 - 2.5 650 109 208/230V-1ɸ-60 N 8 Y 100
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-B1-8 LG
ARNU283M3A4
115 2ND
GRADE
CLASSROOM
2.3 370 1250 0.35 - R410A 28.0 - 81.0 - 31.5 62.2 - 2.5 650 109 208/230V-1ɸ-60 N 8 Y 100
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-B1-9 LG
ARNU123TRD4
115A SMALL
GROUP 1.0 75 310 0 - R410A 12.3 - 80.4 - 13.6 64.0 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED
CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN
SETTING: HIGH, TRUE 2'X2' GRILLE
FC-B1-10 LG
ARNU243M2A4
116 2ND
GRADE
CLASSROOM
2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-B1-11 LG
ARNU243M2A4
117 3RD
GRADE
CLASSROOM
2.0 310 800 0.45 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-B1-12 LG
ARNU123TRD4
117A SMALL
GROUP 1.0 80 310 0 - R410A 12.3 - 80.6 - 13.6 63.5 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED
CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN
SETTING: HIGH, TRUE 2'X2' GRILLE
FC-B1-13 LG
ARNU243M2A4
118 3RD
GRADE
CLASSROOM
2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-B1-14 LG
ARNU283M3A4
119 4TH
GRADE
CLASSROOM
2.3 370 1250 0.35 - R410A 28.0 - 81.0 - 31.5 62.2 - 2.5 650 109 208/230V-1ɸ-60 N 8 Y 100
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-B1-15 LG
ARNU123TRD4
119A SMALL
GROUP 1.0 105 310 0 - R410A 12.3 - 81.4 - 13.6 60.8 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED
CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN
SETTING: HIGH, TRUE 2'X2' GRILLE
FC-B1-16 LG
ARNU363M3A4
120 4TH
GRADE
CLASSROOM
3.0 395 1450 0.35 - R410A 36.2 - 80.7 - 40.6 63.0 - 2.5 650 161 208/230V-1ɸ-60 N 8 Y 100
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-B1-17 LG
ARNU243M2A4
121 WORLD
LANGUAGE
CLASSROOM
2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-B1-18 LG
ARNU363M3A4
122 LOWER
SCHOOL
SCIENCE LAB
3.0 450 1450 0.45 - R410A 36.2 - 81.1 - 40.6 61.8 - 2.5 650 161 208/230V-1ɸ-60 N 8 Y 100
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-B1-19 LG
ARNU363M3A4 128 ELECT. 3.0 N/A 1450 0.35 - R410A 36.2 - - - 40.6 - - 2.5 650 161 208/230V-1ɸ-60 N 8 Y 100
INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL
CONDENSATE OVERFLOW SWITCH
FC-B1-20 LG
ARNU053SJA4 127 DATA 2.0 N/A 240 0 - R410A 5.5 - - - 6.1 - - 0.25 - 30 208/230V-1ɸ-60 N 8 Y 20
INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL
CONDENSATE OVERFLOW SWITCH
FC-C2-2 LG
ARNU093TRD4 211A COLLAB 0.8 90 285 0 - R410A 9.6 - 81.2 - 10.9 61.6 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED
CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN
SETTING: HIGH, TRUE 2'X2' GRILLE
FC-C2-3 LG
ARNU243M2A4
212 5TH
GRADE
CLASSROOM
2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-C2-4 LG
ARNU243M2A4
213 6TH 8TH
CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-C2-5 LG
ARNU243M2A4
214 6TH 8TH
CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-C2-6 LG
ARNU243M2A4
215 6TH 8TH
CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-C2-7 LG
ARNU123TRD4 249 COLLAB 1.0 105 310 0 - R410A 12.3 - 81.4 - 13.6 60.8 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED
CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN
SETTING: HIGH, TRUE 2'X2' GRILLE
FC-C2-8 LG
ARNU243M2A4
216 6TH 8TH
CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-C2-9 LG
ARNU243M2A4
217 6TH 8TH
CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-C2-10 LG
ARNU153TQD4 218 COLLAB 1.3 135 390 0 - R410A 15.4 - 81.5 - 17.1 60.6 - 0.20 - 30 208/230V-1ɸ-60 N - N 45
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED
CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN
SETTING: HIGH, TRUE 2'X2' GRILLE
FC-C2-11 LG
ARNU243M2A4
6TH 8TH
CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-C2-12 LG
ARNU153TQD4 254 COLLAB 1.3 120 390 0 - R410A 15.4 - 81.1 - 17.1 61.8 - 0.20 - 30 208/230V-1ɸ-60 N - N 45
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED
CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN
SETTING: HIGH, TRUE 2'X2' GRILLE
FC-C2-13 LG
ARNU243M2A4
6TH 8TH
CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-C2-14 LG
ARNU243M2A4
6TH 8TH
CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-C2-15 LG
ARNU243M2A4
6TH 8TH
CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-C2-16 LG
ARNU243M2A4
223 6TH 8TH
CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-C2-17 LG
ARNU243M2A4
224 6TH 8TH
CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-C2-18 LG
ARNU183M2A4
225 6TH 8TH
CLASSROOM 1.6 230 800 0.35 - R410A 19.1 - 80.9 - 21.5 62.5 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-C2-19 LG
ARNU183M2A4
226 6TH 8TH
CLASSROOM 1.6 230 800 0.35 - R410A 19.1 - 80.9 - 21.5 62.5 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-C2-20 LG
ARNU183SKA4 234 ELECT. 1.6 N/A 500 0 - R410A 19.1 - - - 21.5 - - 0.52 - 53 208/230V-1ɸ-60 N 8 Y 30
INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL
CONDENSATE OVERFLOW SWITCH,
FC-C2-21 LG
ARNU053SJA4 233 DATA 0.46 N/A 240 0 - R410A 5.5 - - - 6.1 - - 0.25 - 30 208/230V-1ɸ-60 N 8 Y 20
INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL
CONDENSATE OVERFLOW SWITCH,
FC-D1-1 LG
ARNU363B8A4
126 UPPER
SCHOOL ART
LAB
3.0 665 1730 0.47 - R410A 36.2 - 81.8 - 40.6 59.3 - 2.5 800 478 208/230V-1ɸ-60 N 8 Y 222
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-D1-2 (NOT USED) - - - - - - - - - - - - - - - - - - - - - - --
FC-D1-3 LG
ARNU423B8A4
125 LOWER
SCHOOL ART
LAB
3.5 705 1915 0.47 - R410A 42.0 - 81.7 - 43.5 59.1 - 2.5 800 528 208/230V-1ɸ-60 N 8 Y 222
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-D1-4 LG
ARNU243M2A4
125A
CERAMICS 2.0 310 800 0.45 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-D1-5 LG
ARNU543M3A4
124
WOODSHOP 4.5 655 1750 0.35 - R410A 54.0 - 81.7 - 61.4 59.6 - 2.5 650 260 208/230V-1ɸ-60 N 8 Y 100
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-D1-6 LG
ARNU053TRD4 124A OFFICE 0.46 30 265 0 - R410A 5.5 - 79.1 - 6.1 68.3 - 0.20 - 30 208/230V-1ɸ-60 N - N 40
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED
CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN
SETTING: HIGH, TRUE 2'X2' GRILLE
FC-D1-7 LG
ARNU763B8A4
123
MAKERSPACE 6.4 765 2260 0.4 - R410A 76.4 - 81.4 - 86.0 60.8 - 5.2 800 765 208/230V-1ɸ-60 N 8 Y 200
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-D1-8 LG
ARNU283M3A4
123A TECH
LAB 2.3 400 1250 0.35 - R410A 28.0 - 81.2 - 31.5 61.4 - 2.5 650 109 208/230V-1ɸ-60 N 8 Y 100
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-D1-9 LG
ARNU963B8A4
125B KILN
ROOM 8.0 N/A 2545 0.25 - R410A 95.9 - - - 107.5 - - 5.2 800 800 208/230V-1ɸ-60 N 8 Y 200
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-D2-1 LG
ARNU183M2A4
227 6TH 8TH
CLASSROOM 1.6 225 800 0.35 - R410A 19.1 - 80.8 - 21.5 62.7 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-D2-2 LG
ARNU153TQD4
228
WORKROOM 1.3 135 390 0 - R410A 15.4 - 81.5 - 17.1 60.6 - 0.20 - 30 208/230V-1ɸ-60 N - N 45
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED
CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN
SETTING: HIGH, TRUE 2'X2' GRILLE
FC-D2-3 LG
ARNU543M3A4
229 UPPER
SCHOOL
SCIENCE LAB
4.5 660 1750 0.5 - R410A 54.0 - 81.8 - 61.4 59.6 - 2.5 650 260 208/230V-1ɸ-60 N 8 Y 100
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-D2-4 LG
ARNU153TQD4
229A PREP
ROOM 1.3 135 390 0 - R410A 15.4 - 81.5 - 17.1 60.6 - 0.20 - 30 208/230V-1ɸ-60 N - N 45
OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED
CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN
SETTING: HIGH, TRUE 2'X2' GRILLE
FC-D2-5 LG
ARNU543M3A4
230 UPPER
SCHOOL
SCIENCE LAB
4.5 610 1750 0.5 - R410A 54.0 - 81.5 - 61.4 60.5 - 2.5 650 260 208/230V-1ɸ-60 N 8 Y 100
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
FC-D2-6 LG
ARNU363M3A4 231 COLLAB 3.0 350 1450 0.35 - R410A 36.2 - 80.4 - 40.6 64.1 - 2.5 650 161 208/230V-1ɸ-60 N 8 Y 100
W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE
PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH
SYMBOL MANUFACTURER &
MODEL No.SERVING NOMINAL
TON OSA CFM CFM
E.S.P.
(IN.)RPM REF. TYPE
COOLING HEATING
RLA
MAX
POWER
INPUT (W)
POWER
INPUT
(W)
VOLTAGE EMERGENCY
POWER
FILTER
MERV VIB. ISO WEIGHT (lbs)REMARKSTOTAL
MBH
SENSIBLE
MBH EDB (°F)LDB/LWB
(°F)
TOTAL
MBH
EDB
(°F)
LDB
(°F)
FAN COIL (VRF)
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
2/
5
/
2
0
2
1
3
:
1
0
:
1
8
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC0.02
EQUIPMENT SCHEDULES
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
N/A
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
0 09/11/20 ISSUED FOR
CONSTRUCTION
CD
018 12/07/20 CCD-018 DN
1 01/22/21 CITY PERMIT
AMENDMENT
CD
SKUTT
KM/KMT-1027-3 KILN ROOM 3 208V-1ɸ-60 48.0 9984 10 2350°F 6.4 6-50 18,940
KILNS PROVIDED AND INSTALLED BY OWNER. ACCESSORIES: SKUTT ENIVROLINK, SKUTT ENVIROVENT 2 DOWNDRAFT
VENTING SYSTEM.
MANUFACTURER &
MODEL No.LOCATION QTY VOLTAGE
POWER MAXIMUM CHAMBER NEMA
RECEPTACLE BTU's REMARKSAMPS WATTS CONE TEMP CU. FT.
KILN (FOR REFERENCE ONLY)
EF1-1 -
GREENHECK
CSP-A390
NORTHEAST
1ST FLOOR
RR'S
200 0.40 935 - - - ODP 0.05 - 1.42 115V/1ɸ/60 - Y 25 1.5
W/ BDD, SPEED
CONTROLLER
EF1-2 -
GREENHECK
CSP-A1410
NORTH 1ST
FLOOR RR'S 1,215 0.65 1,360 - - - ODP 0.72 - 7.4 115V/1ɸ/60 - Y 60 3.0
W/ BDD, SPEED
CONTROLLER
EF1-3 -
GREENHECK
CSP-A1410 SOUTH RR'S 940 0.75 1,207 - - - ODP 0.44 - 7.4 115V/1ɸ/60 - Y 60 2.0 W/ BDD, SPEED
CONTROLLER
EF1-4 -
GREENHECK
CSP-A1410
LOWER
SCHOOL
SCIENCE LAB
1,220 0.40 1,275 - - - ODP 0.65 - 7.4 115V/1ɸ/60 - Y 60 2.0
W/ BDD, SPEED
CONTROLLER
EF1-5 -
GREENHECK
CSP-A1410 MAKERSPACE 670 0.40 871 - - - ODP 0.16 - 7.4 115V/1ɸ/60 - Y 60 0.8
W/ BDD, SPEED
CONTROLLER
EF1-6 -
GREENHECK
CSP-A900 WOODSHOP 760 0.40 866 - - - ODP 0.43 - 3.0 115V/1ɸ/60 - Y 60 0.8
W/ BDD, SPEED
CONTROLLER
(NOT USED) - - - - - - - - - - - - - - - - - - -
EF1-8 -
GREENHECK
CSP-A2150 ART LABS 1,920 0.50 790 - --ODP 1.72 - 11.6 115V/1ɸ/60 - Y 69 3.5
W/ BDD, SPEED
CONTROLLER
EF2-1 -
GREENHECK
CSP-A1410
2ND FLOOR
NORTH RR'S 940 0.45 1,087 - - - ODP 0.36 - 7.4 115V/1ɸ/60 - Y 60 1.0
W/ BDD, SPEED
CONTROLLER
EF2-2 -
GREENHECK
CSP-A1410
2ND FLOOR
SOUTH RR'S 940 0.75 1,207 - - - ODP 0.44 - 7.4 115V/1ɸ/60 - Y 60 2.0
W/ BDD, SPEED
CONTROLLER
EF2-3 -
GREENHECK
CSP-A1410
UPPER
SCHOOL
SCIENCE LAB
1,290 0.45 1,290 - - - ODP 0.77 - 7.4 115V/1ɸ/60 - Y 60 2.5
W/ BDD, SPEED
CONTROLLER
EF2-4 -
GREENHECK
CSP-A1410
UPPER
SCHOOL
SCIENCE LAB
1,290 0.45 1,290 - - - ODP 0.77 - 7.4 115V/1ɸ/60 - Y 60 2.5
W/ BDD, SPEED
CONTROLLER
FSD-1 POTTORFF
FSD
RA - 1000 FPM
SA - 1800 FPM II 1-1/2 165°F N/A 120V/1ɸ/60 N Y SEE PLANS FOR SIZE AND LOCATION, HORIZONTAL POSITION
CS1 SUPPLY
PRICE
SPD 24"X24" LAY-IN STEEL - WHITE N N -
CR1 RETURN
PRICE
PDDR 24"X24" LAY-IN STEEL - WHITE N N -
CE1 EXHAUST
PRICE
PDDR 24"X24"SURFACE
MOUNT STEEL FLUSH WHITE Y N -
CE2 EXHAUST
PRICE
PDDR 24"X24" LAY-IN STEEL - WHITE N N -
CT1 TRANSFER
PRICE
PDDR 24"X24" LAY-IN STEEL - WHITE N N -
CT2 TRANSFER
PRICE
PDDR 24"X24"SURFACE
MOUNT STEEL FLUSH WHITE Y N -
SWG1 SUPPLY
PRICE
SDGE SEE PLANS DUCT
MOUNTED STEEL FLUSH DUCT N N W/ AIR SCOOP
SWG2 RETURN /
TRANSFER
PRICE
530 SEE PLANS WALL
MOUNTED STEEL FLUSH WHITE N N -
SWG3 SUPPLY
PRICE
520 SEE PLANS WALL
MOUNTED STEEL FLUSH WHITE N N -
L-1 PER PLANS
CONSTRUCTION
SPECIALTIES A2097 PER PLANS PER PLANS - -
CU-1 -
LG
ARUN024GSS4 SS-1 R-410A 24 - - - - 19.6 30 - 208V/1ɸ/60 N 10.70 N 180 -
CU-2 -
LG
ARUN024GSS4 SS-1 R-410A 24 - - - - 19.6 30 - 208V/1ɸ/60 N 10.70 N 180 -
BS-A1 LG
PRHR083A FC'S 1 8 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 -
BS-A2 LG
PRHR043A FC'S 1 4 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 -
BS-A3 LG
PRHR083A FC'S 1 8 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 -
BS-A4 LG
PRHR023A FC'S 1 2 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 -
BS-A5 LG
PRHR083A FC'S 1 8 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 -
BS-A6 LG
PRHR083A FC'S 1 8 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 -
BS-B1 LG
PRHR083A FC'S 1 8 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 -
BS-B2 LG
PRHR063A FC'S 1 6 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 -
BS-B3 LG
PRHR083A FC'S 1 8 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 -
BS-C1 LG
PRHR063A FC'S 1 6 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 -
BS-C2 LG
PRHR063A FC'S 1 6 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 -
BS-C3 LG
PRHR023A FC'S 1 2 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 -
BS-C4 LG
PRHR063A FC'S 1 6 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 -
BS-D1 LG
PRHR083A FC'S 1 8 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 -
BS-D2 LG
PRHR043A FC'S 1 4 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 -
BS-D3 LG
PRHR043A FC'S 1 4 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 -
BS-D4 LG
PRHR043A FC'S 1 4 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 -
SF-1-1 HEAD ASST.
103
GREENHECK
CSP-A1050 FC'S OSA 700 0.75 1,013 0.63 - 8 30x14x1 5.0 115V/1ɸ/60 N - Y 60 W/ FILTER, BDD, & SPEED CONTROLLER
SF-1-2
MATH
SPECIALIST
137C
GREENHECK
CSP-A1410 FC'S OSA 1,145 1.15 1,450 0.75 - 8 24x18x1 7.4 115V/1ɸ/60 N - Y 60 W/ FILTER, BDD, & SPEED CONTROLLER
SF-1-3 ART LAB 126
GREENHECK
CSP-A250 FC'S OSA 135 0.50 1,000 0.03 - 8 12x12x1 0.79 115V/1ɸ/60 N - Y 25 W/ FILTER, BDD, & SPEED CONTROLLER
SF-2-1 STAFF
LOUNGE 207
GREENHECK
CSP-A1410 FC'S OSA 925 0.85 1,238 0.45 - 8 24x16x1 7.4 115V/1ɸ/60 N - Y 60 W/ FILTER, BDD, & SPEED CONTROLLER
SF-2-2
6TH-8TH
CLASSROOM
213
GREENHECK
CSP-A390 FC'S OSA 195 0.80 1,532 0.08 - 8 12x12x1 1.33 115V/1ɸ/60 N - Y 25 W/ FILTER, BDD, & SPEED CONTROLLER
SF-2-3 COLAB 218
GREENHECK
CSP-A390 FC'S OSA 255 0.60 1,166 0.11 - 8 16x16x1 1.42 115V/1ɸ/60 N - Y 24 W/ FILTER, BDD, & SPEED CONTROLLER
SF-2-4 SCIENCE
LAB 229
GREENHECK
CSP-A390 FC'S OSA 270 0.75 1,272 0.14 - 8 16x16x1 1.42 115V/1ɸ/60 N - Y 24 W/ FILTER, BDD, & SPEED CONTROLLER
FAN COILS TO AIR DISTRIBUTION GALVANIZED STEEL 2" (+)
SUPPLY OUTSIDE AIR DUCT GALVANIZED STEEL 2" (+)
ALL EXHAUST AIR DUCT GALVANIZED STEEL 2" (-)
KILN EXHAUST AIR DUCT GALVANIZED STEEL 2" (-)
DUST COLLECTOR EXHAUST
DUCT
GALVANIZED STEEL,
WELDED OR FLANGED MIN. 18 GA.
PIPE FROM CONDENSING
UNITS TO BRANCH
SELECTORS
HARD DRAWN, ACR
TUBE
SEE PLANS FOR
ROUTING AND SIZES.
PIPE FROM BRANCH
SELECTORS TO FAN COILS
SOFT COPPER, LINE
SETS
SEE PLANS FOR
ROUTING AND SIZES.
DC-1 (NOT USED) - - - - - - - - - - - - - - - -
GV-1 ROOF GREENHECK GSR-20
UPPER
SCHOOL
SCIENCE LAB
1290 0.04 573 20"Ø 24 4 HOODED GRAVITY RELIEF VENTILATOR. 1/4" WIRE MESH BIRDSCREEN. SLOPED ROOF CURB. BDD.
GV-2 ROOF GREENHECK GRSI-15
UPPER
SCHOOL
SCIENCE LAB
660 0.057 589 15"Ø 13 2 HOODED GRAVITY INTAKE VENTILATOR. 1/4" WIRE MESH BIRDSCREEN. SLOPED ROOF CURB. BDD.
GV-3 ROOF GREENHECK GRSI-10
SECOND
FLOOR
CLASSROOMS
300 0.046 526 10"Ø 8 18 HOODED GRAVITY INTAKE VENTILATOR. 1/4" WIRE MESH BIRDSCREEN. SLOPED ROOF CURB. BDD.
SKUTT
ENVIROVENT-2 KILN ROOM 3 KILN 140 160°F 12 ODP 1.4 115V/1ɸ/60 N N UL LISTED, WALL MOUNTED BLOWER.
SS-1
ELEVATOR
MACHINE
ROOM
LG
ARNU243SKA4
ELEVATOR
MACHINE
ROOM NORTH
540 - - R-410A 24 - - 0.52 53 208V/1ɸ/60 N N 30
CONDENSATE
PUMP
SS-2
ELEVATOR
MACHINE
ROOM
LG
ARNU243SKA4
ELEVATOR
MACHINE
ROOM SOUTH
540 - - R-410A 24 - - 0.52 53 208V/1ɸ/60 N N 30
CONDENSATE
PUMP
SYMBOL LOCATION
MANUFACTURER &
MODEL No.SERVING CFM
ESP
(IN.)FRPM MOTOR
POSITION ROT DIS
MOTOR
ENCL.BHP HP FLA VOLTAGE
VFD
(Y/N)VIB. ISO WEIGHT (lbs) SONES REMARKSSYMBOLMANUFACTURER &
MODEL No.
MAX
VELOCITY /
BLADE TYPE
LEAKAGE
CLASS
RESISTANCE
RATING
(HOURS)
FIRE CLOSURE
TEMPERATURE &
DEVICE
SMOKE CONTROL
(PASSIVE & ACTIVE)
ACTUATOR
VOLTAGE
EMERGENCY
POWER
POSITION
SWITCHES REMARKS
SYMBOL TYPE
MANUFACTURER &
MODEL No.
MODULE
SIZE
BORDER
TYPE MATERIAL FACE TYPE COLOR RAPID MOUNT FRAME OBD REMARKS
SYMBOL LOCATION
MANUFACTURER &
MODEL No.SERVING SIZE
(W" x H")
FREE
AREA (%)
POINT OF WATER
PENETRATION (FPM)REMARKS
SYMBOL LOCATION
MANUFACTURER &
MODEL No.SERVING
COOLING COMP'R SINGLE POINT POWER EER
@
ARI
VIB. ISO WEIGHT (lbs) REMARKS
REF. TYPE TOTAL MBH
SUCT.
°F
AMB
(°F)QTY.# OF
CIRCUITS MCA MFA/
MOCP
SCCR
(KA)VOLTAGE EMERGENCY
POWER
SYMBOL MANUFACTURER &
MODEL No.SERVING QUANTITY PORTS REF. TYPE
MAX PORT
CAPACITY
(MBH)
MAX UNIT
CAPACITY
(MBH)
MCA FLA MFA VOLTAGE
EMERGENCY
POWER VIB. ISO. WEIGHT (lbs) REMARKS
SYMBOL LOCATION
MANUFACTURER &
MODEL No.SERVING
SUPPLY FAN FILTER SINGLE POINT POWER
VFD
(Y/N)VIB. ISO WEIGHT
(lbs)REMARKSCFME.S.P.
(IN.)FRPM BHP HP MERV SIZE FLA VOLTAGE
EMERGENCY
POWER
CRITERIA MATERIAL DETAILS
CRITERIA MATERIAL DETAILS
SYMBOL LOCATION
MANUFACTURER &
MODEL No.SERVING
EXHAUST FANS SINGLE POINT POWER
VIB. ISO UNIT
WEIGHT (lbs)
SILENCER
WEIGHT (lbs)
TOTAL
WEIGHT (lbs)REMARKS
CFM E.S.P.
(IN. WG)HP RPM FLA
MFA/
MOCP VOLTAGE EMERGENCY
POWER
SYMBOL LOCATION
MANUFACTURER &
MODEL No.SERVING CFM S.P.
THROAT
VELOCITY THROAT SIZE WEIGHT
(lbs)QTY.REMARKS
MANUFACTURER &
MODEL No.LOCATION QTY SERVING CFM
MAXIMUM MOTOR
ENCL.FLA VOLTAGE
VFD
(Y/N)VIB. ISO REMARKSTEMP CU. FT. SERVED
SYMBOL LOCATION
MANUFACTURER &
MODEL No.SERVING
SUPPLY FAN
REF. TYPE
DX COOLING COIL
RLA POWER
INPUT (W)VOLTAGE EMERGENCY
POWER VIB. ISO WEIGHT (lbs) REMARKS
CFM FRPM HP
TOTAL
MBH
EDB/EWB
(°F)
LDB/LWB
(°F)
WEATHER ASSUMPTIONS
SYSTEM ASSUMPTIONS
SUPPLY
RETURN
ELEVATION (FT)
LATITUDE (DEG)
SUMMER DB/WB (°F, 0.1%)
WINTER DB (°F, 0.2%)
SUPPLY TEMP
VENTILATION (CFM/PERSON)
THERMOSTAT SETPOINTS
COOLING/HEATING
EXHAUST
10
33.68°N
87°F / 68°F
39°F
55°F
15
76°F/70°F
ACH . . . . . AIR CHANGES PER HOUR
AMB . . . . . AMBIENT TEMPERATURE
CONN AIF . . CONNECTION-AIR IN FACE
DIS . . . . . DISCHARGE
DpA . . . . . AIR PRESSURE DROP
Dpw . . . . . WATER PRESSURE DROP
EDB . . . . . ENTERING DRY BULB
EWB . . . . . ENTERING WET BULB
EWT . . . . . ENTERING WATER TEMPERATURE
FPM . . . . . FEET PER MINUTE
FLA . . . . . FULL LOAD AMPS.
RETURN AIR PLENUM 78°F
JANITOR'S CLOSET: 1.0 CFM/SQ.FT.
RR: 100 CFM/FIXTURE
SCIENCE LABS: 1.0 CFM/SQ.FT
ART LABS: 0.7 CFM/SQ.FT.
LOW PRESSURE DUCT SUPPLY 0.10"/100'
THROUGH FSD <1000 FPM
THROUGH FSD <1800 FPM
MAKERSPACE: 0.5 CFM/SQ.FT.
LDB . . . . . LEAVING DRY BULB
LWB . . . . . LEAVING WET BULB
LWT . . . . . LEAVING WATER TEMPERATURE
MCA . . . . . MINIMUM CURRANT AMPACITY
MFA . . . . . MAXIMUM FUSE AMPS.
MOCP . . . . MAXIMUM OVER CURRANT
PROTECTION
REF . . . . . REFRIGERANT TYPE
RLA . . . . . RATED LOAD AMPS.
ROT . . . . . ROTATION
RR . . . . . . RESTROOMS
BASIS OF DESIGN
DUCT SIZING CRITERIA
ABBREVIATIONS
GENERAL NOTES
EXHAUST FANFIRE / SMOKE DAMPER
AIR DISTRIBUTION
LOUVER
SPLIT SYSTEM CONDENSING UNIT
BRANCH SELECTOR (VRF)
SUPPLY FAN
DUCT CONSTRUCTION
SCHEDULE
PIPE CONSTRUCTION
SCHEDULE
DUST COLLECTOR
GRAVITY AIR VENT
KILN DOWNDRAFT VENT SYSTEM
FAN COIL (DX) SPLIT SYSTEM
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
2/
5
/
2
0
2
1
3
:
1
0
:
1
9
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC0.03
EQUIPMENT SCHEDULES
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
N/A
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
0 09/11/20 ISSUED FOR
CONSTRUCTION
CD
016 12/09/20 CCD-016 DN
1 01/22/21 CITY PERMIT
AMENDMENT
CD
ANY APPLIANCE FOR WHICH THERE IS A CALIFORNIA STANDARD ESTABLISHED IN THE APPLIANCE EFFICIENCY
REGULATIONS MAY BE INSTALLED ONLY IF THE MANUFACTURER HAS CERTIFIED TO THE COMMISSION THAT THE
APPLIANCE COMPLIES WITH THE APPLICABLE STANDARD FOR THAT APPLIANCE.
MECHANICAL EQUIPMENT INSTALLED IN A BUILDING SUBJECT TO THESE REGULATIONS MUST BE CERTIFIED AS
MEETING CERTAIN MINIMUM EFFICIENCY. THESE REQUIREMENTS ARE CONTAINED IN §112. THE AFUE, COP, EER, IPLV,
COMBUSTION EFFICIENCY, AND THERMAL EFFICIENCY VALUES OF ALL EQUIPMENT MUST BE DETERMINED USING THE
APPLICABLE TEST METHOD SPECIFIED IN THE STANDARDS.
THE FOLLOWING SPACE-CONDITIONING EQUIPMENT MAY BE INSTALLED ONLY IF THE MANUFACTURER HAS CERTIFIED
THAT THE EQUIPMENT MEETS OR EXCEEDS ALL APPLICABLE EFFICIENCY REQUIREMENTS OF THE STANDARDS:
ALL AIR CONDITIONERS, HEAT PUMPS AND CONDENSING UNITS >135,000 BTU/HR; ALL WATER CHILLERS;
ALL GAS AND OIL FIRED AIR FURNACES WITH INPUT RATING >225,000 BTU/HR SHALL HAVE AN INTERMITTENT IGNITION
OR INTERRUPTED DEVICE (IDD), AND HAVE EITHER POWER VENTING OR A FLUE DAMPER.
ALL ENCLOSED SPACES IN A BUILDING THAT ARE NORMALLY USED BY HUMANS SHALL BE VENTILATED IN ACCORDANCE
WITH THE REQUIREMENTS OF THIS SECTION AND THE CBC.
THE OUTDOOR AIR-VENTILATION RATE AND AIR-DISTRIBUTION ASSUMPTIONS MADE IN THE DESIGN OF THE VENTILATING
SYSTEM SHALL BE CLEARLY IDENTIFIED ON THE BUILDING PLANS REQUIRED BY §10-103 OF TITLE 24, PART 1.
EVERY SPACE IN A BUILDING SHALL BE DESIGNED TO HAVE OUTDOOR AIR-VENTILATION EITHER BY NATURAL
VENTILATION OR MECHANICAL VENTILATION.
TIMES OF OCCUPANCY. THE MINIMUM RATE OF OUTDOOR AIR REQUIRED BY SECTION 120.1 SHALL BE SUPPLIED TO
EACH SPACE AT ALL TIMES WHEN THE SPACE IS USUALLY OCCUPIED.
DUCTING FOR ZONAL HEATING AND COOLING UNITS. WHERE A RETURN PLENUM IS USED TO DISTRIBUTE OUTDOOR AIR
TO A ZONAL HEATING OR COOLING UNIT WHICH THEN SUPPLIES THE AIR TO A SPACE IN ORDER TO MEET THE
REQUIREMENTS OF SECTION 120.1(d), THE OUTDOOR AIR SHALL BE DUCTED TO DISCHARGE EITHER: WITHIN 5 FEET OF
THE UNIT; OR WITHIN 15 FEET OF THE UNIT, SUBSTANTIALLY TOWARD THE UNIT, AND AT A VELOCITY NOT LESS THAN
500 FEET PER MINUTE.
DESIGN AND CONTROL REQUIREMENTS FOR QUANTITIES OF OUTDOOR AIR. ALL MECHANICAL VENTILATION AND
SPACE-CONDITIONING SYSTEMS SHALL BE DESIGNED WITH AND HAVE INSTALLED DUCTWORK, DAMPERS, AND
CONTROLS TO ALLOW OUTSIDE AIR RATES TO BE OPERATED AT THE LARGER OF (1) THE MINIMUM LEVELS SPECIFIED IN
SECTION 120.1(b) 1 OR 2 THE RATE REQUIRED FOR MAKE-UP OF EXHAUST SYSTEMS THAT ARE REQUIRED FOR A
PROCESS, FOR CONTROL OF ODORS, OR FOR THE REMOVAL OF CONTAMINANTS WITHIN THE SPACE.
EVERY SPACE REQUIRING DEMAND CONTROL VENTILATION. THEY MUST HAVE AN AIR ECONOMIZER; AND THEY SERVE
A SPACE WITH A DESIGN OCCUPANT DENSITY, OR A MAXIMUM OCCUPANT LOAD FACTOR FOR EGRESS PURPOSES,
GREATER THAN OR EQUAL TO 25 PEOPLE PER 1000 FT² (40 FT² PER PERSON); AND IS EITHER A SINGLE ZONE SYSTEM
WITH ANY CONTROLS OR MULTIPLE ZONE SYSTEMS WITH DIRECT DIGITAL CONTROLS (DDC) TO THE ZONE LEVEL.
HEAT PUMPS WITH SUPPLEMENTARY ELECTRIC RESISTANCE HEATERS; SHOULD PREVENT SUPPLEMENTARY HEATER
OPERATION WHEN THE HEATING LOAD CAN BE MET BY THE HEAT PUMP ALONE; AND
IN WHICH THE CUT-ON TEMPERATURE FOR COMPRESSION HEATING IS HIGHER THAN THE CUT-ON TEMPERATURE FOR
SUPPLEMENTARY HEATING, AND THE CUT-OFF TEMPERATURE FOR COMPRESSION HEATING IS HIGHER THAN THE
CUT-OFF TEMPERATURE FOR SUPPLEMENTARY HEATING.
THERMOSTATS, ALL UNITARY HEATING AND/OR COOLING SYSTEMS HEAT PUMPS THAT ARE NOT CONTROLLED BY
A CENTRAL ENERGY MANAGEMENT CONTROL SYSTEM (CEMS) SHALL HAVE A SETBACK THERMOSTAT.
THERMOSTATIC CONTROLS FOR EACH ZONE. THE SUPPLY OF HEATING AND COOLING ENERGY TO EACH
SPACE-CONDITIONING ZONE OR DWELLING UNIT SHALL BE CONTROLLED BY AN INDIVIDUAL THERMOSTATIC CONTROL
THAT RESPONDS TO TEMPERATURE WITHIN THE ZONE AND THAT MEETS THE APPLICABLE REQUIREMENTS OF
SECTION 120.2(a).
CRITERIA FOR ZONAL THERMOSTATIC CONTROLS. THE INDIVIDUAL THERMOSTATIC CONTROLS REQUIRED BY
SECTION 120.2(b) SHALL MEET REQUIREMENTS; FOR HEATING SHALL BE CAPABLE OF BEING SET, LOCALLY OR
REMOTELY, DOWN TO 55°F OR LOWER. OR FOR COOLING IT SHALL BE CAPABLE OF BEING SET, LOCALLY OR REMOTELY,
UP TO 85°F OR HIGHER.
FOR HOTEL/MOTEL GUEST ROOM AND HIGH-RISE RESIDENTIAL DWELLING UNIT THERMOSTATS; SHALL HAVE:
NUMERIC TEMPERATURE SETPOINTS IN °F; AND SETPOINT STOPS ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL,
TO RESTRICT OVER-HEATING AND OVER-COOLING AND MEET SECTION 150(i).
HEAT PUMP CONTROLS. ALL HEAT PUMPS WITH SUPPLEMENTARY ELECTRIC RESISTANCE HEATERS SHALL BE
INSTALLED WITH CONTROLS THAT COMPLY WITH SECTION 110.2(b).
SHUT-OFF AND RESET CONTROLS FOR SPACE-CONDITIONING SYSTEMS; SHALL BE INSTALLED WITH CONTROLS THAT
COMPLY WITH CONTROLS CAPABLE OF AUTOMATICALLY SHUTTING OFF THE SYSTEM DURING PERIODS OF NONUSE
AND SHALL HAVE BY HAVING AN AUTOMATIC TIME SWITCH CONTROL DEVICE AND ACCESSIBLE MANUAL OVERRIDE THAT
ALLOWS OPERATION OF THE SYSTEM FOR UP TO 4 HOURS.
DAMPERS FOR AIR SUPPLY AND EXHAUST EQUIPMENT. OUTDOOR AIR SUPPLY AND EXHAUST EQUIPMENT SHALL BE
INSTALLED WITH DAMPERS THAT AUTOMATICALLY CLOSE UPON FAN SHUTDOWN.
ISOLATION AREA DEVICES. EACH SPACE-CONDITIONING SYSTEM SERVING MULTIPLE ZONES WITH A COMBINED
CONDITIONED FLOOR AREA OF MORE THAN 25,000 SQUARE FEET SHALL BE DESIGNED, INSTALLED, AND CONTROLLED
TO SERVE ISOLATION AREAS.
AUTOMATIC DEMAND SHED CONTROLS. HVAC SYSTEMS WITH DDC TO THE ZONE LEVEL SHALL BE PROGRAMMED TO
ALLOW CENTRALIZED DEMAND SHED FOR NON-CRITICAL ZONES.
THE PIPING FOR ALL SPACE-CONDITIONING AND SERVICE WATER-HEATING SYSTEMS WITH FLUID TEMPERATURES
LISTED IN TABLE 120.3-A SHALL INSTALL THE AMOUNT OF INSULATION SPECIFIED.
ALL AIR DISTRIBUTION SYSTEM DUCTS AND PLENUMS, INCLUDING, BUT NOT LIMITED TO, BUILDING CAVITIES,
MECHANICAL CLOSETS, AIR-HANDLER BOXES AND SUPPORT PLATFORMS USED AS DUCTS OR PLENUMS, SHALL BE
INSTALLED, SEALED AND INSULATED TO MEET THE REQUIREMENTS OF THE 2016 CMC SECTIONS 601, 602, 603, 604, 605,
AND SMACNA-006-2006 HVAC DUCT CONSTRUCTION STANDARDS METAL & FLEXIBLE, 3RD EDITION.
BEFORE AN OCCUPANCY PERMIT IS GRANTED THE CERTIFICATE OF ACCEPTANCE SHALL BE SUBMITTED TO THE
ENFORCEMENT AGENCY THAT CERTIFIES THAT THE EQUIPMENT AND SYSTEMS MEET THE ACCEPTANCE REQUIREMENTS.
ALL NEWLY INSTALLED AIR COOLED PACKAGED DX UNITS GREATER THAN 54,000 BTU/HR WITH AN ECONOMIZER SHALL
HAVE FAULT DETECTION AND DIAGNOSTICS.
DDC CONTROLS TO ZONE SHALL BE PROVIDED AS SPECIFIED BY TABLE 120.2-A. SPACE CONDITIONING SYSTEMS
WITH DDC CONTROLS SHALL HAVE OPTIMUM START/STOP CONTROLS.
NEW NONRESIDENTIAL BUILDINGS SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF SECTIONS 120.8(a)
THROUGH 120.8(i) IN THE BUILDING DESIGN AND CONSTRUCTION PROCESSES.
ALL NEW BOILERS OVER 2,500,000 BTU/HR SHALL COMPLY WITH COMBUSTION AIR AND COMBUSTION AIR FAN
REQUIREMENTS.
MECHANICAL
MANDATORY MEASURES
2016
Certification of Equipment Efficiencies (§110.2 thru §110.11)
HVAC Equipment Efficiencies (§110.2)
Ventilation (§120.1)
Demand Controlled Ventilation (§120.1(c)3)
Controls (§120.2)
Pipe Insulation (§120.3)
Duct Construction and Insulation (§120.4)
Acceptance Tests (§120.5 and Reference Nonresidential NA7.5)
Nonresidential Building Commissioning (§120.8)
Commercial Boilers (§120.9)
GENERAL NOTES
1.REMOVABLE CEILING PANEL OR PANELS AT FACE OF ALL FIRE AND FIRE/SMOKE DAMPERS BY GENERAL
CONTRACTOR (24" x 24" MIN.) UNLESS OTHERWISE NOTED.
2.INCOMBUSTIBLE PLENUM ABOVE CEILING FOR RETURN/RECIRCULATING AIR BY GENERAL CONTRACTOR. CONCEALED
BUILDING SPACES USED AS RETURN AIR PLENUMS SHALL BE IN COMPLIANCE WITH CMC 602.2.
3.ACCESS DOORS AND/OR ACCESS PANELS THROUGH FIRE RATED WALLS, SHAFTS, CEILINGS, ETC., MUST EQUAL THE
MATERIAL PENETRATED.
4. ALL AIR SHAFTS SHALL BE MADE AIR TIGHT BY GENERAL CONTRACTOR.
5. ALL UNDERCUT DOORS AND DOOR LOUVERS ARE BY GENERAL CONTRACTOR.
6. ALL APPLIANCES DESIGNED TO BE FIXED IN POSITION SHALL BE SECURELY FASTENED IN PLACE.
7. ALL SPACE CONDITIONING EQUIPMENT SHALL BE LABELED AS TO WHICH AREA IT SERVES.
ACCO INSTALLATION PRACTICES OF SOFT-COPPER REFRIGERANT PIPING FOLLOW THE INTERPRETATION THAT CEILING
STRUCTURES AND WALL STRUCTURES MEET THE REQUIREMENTS OF PIPING PROTECTION REQUIRED BY 2016 CMC
1109.7
8.
FOR NEW BUILDINGS 10,000 SQUARE FEET AND OVER, BUILDING COMMISSIONING SHALL BE INCLUDED IN THE DESIGN
AND CONSTRUCTION PROCESSES OF THE BUILDING PROJECT TO VERIFY THAT THE BUILDING SYSTEMS AND
COMPONENTS MEET THE OWNER OR OWNER'S REPRESENTATIVE'S PROJECT REQUIREMENTS.
IF THE HVAC SYSTEM IS USED DURING CONSTRUCTION, USE RETURN AIR FILTERS WITH A MERV 8 RATING. REPLACE ALL
FILTERS IMMEDIATELY PRIOR TO OCCUPANCY, OR, IF THE BUILDING IS OCCUPIED DURING ALTERATION, AT THE
CONCLUSION OF CONSTRUCTION.
TESTING AND ADJUSTING OF SYSTEMS SHALL BE REQUIRED FOR BUILDINGS LESS THAN 10,000 SQUARE FEET.
AT THE TIME OF ROUGH INSTALLATION, OR DURING THE STORAGE ON THE CONSTRUCTION SITE AND UNTIL FINAL
STARTUP OF THE HEATING AND COOLING EQUIPMENT, ALL DUCT AND OTHER RELATED AIR DISTRIBUTION COMPONENT
OPENINGS SHALL BE COVERED.
IN MECHANICALLY VENTILATED BUILDING, PROVIDE REGULARLY OCCUPIED AREA OF THE BUILDING WITH AIR FILTRATION
MEDIA FOR OUTSIDE AND RETURN AIR PRIOR TO OCCUPANCY THAT PROVIDES AT LEAST MERV OF 8. INSTALLED
FILTERS SHALL BE CLEARLY LABELED BY THE MANUFACTURER INDICATING THE MERV RATING.
WHERE OUTDOOR AREAS ARE PROVIDED FOR SMOKING, PROHIBIT SMOKING WITHIN 25 FT OF BUILDING ENTRIES,
OUTDOOR AIR INTAKES, AND OPERABLE WINDOWS AND WITHIN THE BUILDING AS ALREADY PROHIBITED BY OTHER LAWS
OR REGULATIONS.
BUILDINGS SHALL MEET OR EXCEED THE PROVISIONS OF CALIFORNIA BUILDING CODE, CCR, TITLE 24, PART 2, SECTIONS
1203 (VENTILATION) AND CHAPTER 14 (EXTERIOR WALLS).
BUILDINGS SHALL MEET OR EXCEED THE PROVISIONS OF CALIFORNIA BUILDING CODE, CCR, TITLE 24, PART 2, SECTIONS
1203 (VENTILATION) AND CHAPTER 14 (EXTERIOR WALLS).
FOR BUILDINGS EQUIPPED WITH DEMAND CONTROL VENTILATION, CO2 SENSORS AND VENTILATION CONTROLS SHALL
BE SPECIFIED AND INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE CURRENT EDITION OF THE
CALIFORNIA ENERGY CODE, CCR, TITLE 24, PART 6, SECTION 120.1(c)(3)
INSTALL HVAC, REFRIGERATION, AND FIRE SUPPRESSION EQUIPMENT THAT DO NOT CONTAIN CFCS OR HALONS.
CALGREEN
MANDATORY MEASURES
COMMISSIONING (§ 5.410.2)
POLLUTANT CONTROL (§ 5.504)
INDOOR MOISTURE CONTROL (§ 5.505)
INDOOR AIR QUALITY (§ 5.506)
OUTDOOR AIR QUALITY (§ 5.508)
CEC-NRCC-MCH-01-E (Revised 01/16)CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-01-E
Mechanical Systems (Page 1 of 4)
A. MECHANICAL COMPLIANCE FORMS & WORKSHEETS (check box if worksheet is included)
YES NO Form/Worksheet #Title
NRCC-MCH-01-E (Part 1 of 3) Certificate of Compliance, Declaration. Required on plans for all submittals.
NRCC-MCH-01-E (Part 2 of 3) Certificate of Compliance, Required Acceptance Tests (MCH-02A to 11A). Required on plans for all submittals.
NRCC-MCH-01-E (Part 3 of 3) Certificate of Compliance, Required Acceptance Tests (MCH-12A to 18A). Required on plans where applicable.
NRCC-MCH-02-E (Part 1 of 2) Mechanical Dry Equipment Summary is required for all submittals with Central Air Systems. It is optional on plans.
NRCC-MCH-02-E (Part 2 of 2) Mechanical Wet Equipment Summary is required for all submittals with chilled water, hot water or condenser water
systems. It is optional on plans.
NRCC-MCH-03-E Mechanical Ventilation and Reheat is required for all submittals with multiple zone heating and cooling systems. It is
optional on plans.
Project Name:Date Prepared:
NRCC-MCH-07-E (Part 1 of 2) Powered Consumption of Fans. Required on plans where applicable.
NRCC-MCH-07-E (Part 2 of 2) Powered Consumption of Fans. Declaration. Required on plans where applicable.
For detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, refer to the 2016 Nonresidential Manual Note: The Enforcement Agency may
require all forms to be incorporated onto the building plans.
Test Description MCH-02A MCH-03A MCH-04A MCH-05A MCH-06A MCH-07A MCH-08A MCH-09A MCH-10A MCH-11A
Equipment
Requiring
Testing or
Verification
# of units Outdoor
Air
Single Zone
Unitary
Air
Distribution
Ducts
Economizer
Controls
Demand
Controlled
Ventilation
(DCV)
Supply Fan
VAV
Valve
Leakage
Test
Supply
Water
Temp. Reset
Hydronic
System
Variable
Flow Control
Automatic
Demand
Shed Control
CEC-NRCC-MCH-01-E (Revised 01/16)CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-01-E
Mechanical Systems (Page 2 of 4)
Project Name:Date Prepared:
B. MECHANICAL HVAC ACCEPTANCE FORMS (check box for required forms)
Test Performed By:
Designer:
This compliance document is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for HVAC systems. The designer is required to check the applicable boxes
for all acceptance tests that apply and list all equipment that requires an acceptance test. All equipment of the same type that requires a test, list the equipment description and the number of systems.
Installing Contractor:
The contractor who installed the equipment is responsible to either conduct the acceptance test themselves or have a qualified entity run the test for them. If more than one person has responsibility
for the acceptance testing, each person shall sign and submit the Certificate of Acceptance applicable to the portion of the construction or installation for which they are responsible.
Enforcement Agency:
Plancheck -- The NRCC-MCH-01-E compliance document is not considered a completed document and is not to be accepted by the building department unless the correct boxes are checked.
Inspector - Before occupancy permit is granted all newly installed process systems must be tested to ensure proper operations.
CEC-NRCC-MCH-01-E (Revised 01/16)CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-01-E
Mechanical Systems (Page 3 of 4)
C. MECHANICAL HVAC ACCEPTANCE FORMS (check box for required forms)
Test Description MCH-12A MCH-13A MCH-14A MCH-15A MCH-16A MCH-17A MCH-18A
Equipment
Requiring Testing
or Verification
# of
units
Fault Detection &
Diagnostics for DX
Units
Automatic Fault
Detection &
Diagnostics for Air
& Zone
Distributed Energy
Storage DX AC
Systems
Thermal Energy
Storage (TES)
Systems
Supply Air
Temperature Reset
Controls
Condenser Water
Reset Controls ECMS
Project Name:Date Prepared:
Designer:
This compliance document is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for HVAC systems. The designer is required to check
the applicable boxes for all acceptance tests that apply and list all equipment that requires an acceptance test. All equipment of the same type that requires a test, list the
equipment description and the number of systems.
Installing Contractor:
The contractor who installed the equipment is responsible to either conduct the acceptance test themselves or have a qualified entity run the test for them. If more than one person
has responsibility for the acceptance testing, each person shall sign and submit the Certificate of Acceptance applicable to the portion of the construction or installation for which
they are responsible.
Enforcement Agency:
Plancheck -- The NRCC-MCH-01-E compliance document is not considered a completed document and is not to be accepted by the building department unless the correct boxes
are checked. Inspector - Before occupancy permit is granted all newly installed process systems must be tested to ensure proper operations.
CEC-NRCC-MCH-02-E (Revised 01/16)CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-02-E
HVAC Dry System Requirements (Page 1 of 3)
A. Equipment Tags and System Description 1
MANDATORY MEASURES T-24 Sections Reference to the Requirements in the Contract Documents 2
Heating Equipment Efficiency 3 110.1 or 110.2(a)
Cooling Equipment Efficiency 3 110.1 or 110.2(a)
HVAC or Heat Pump Thermostats 110.2(b), 110.2(c)
Furnace Standby Loss Control 110.2(d)
Low leakage AHUs 110.2(f)
Ventilation4 120.1(b)
Demand Control Ventilation 5 120.1(c)4
Occupant Sensor Ventilation Control 6 120.1(c)5, 120.2(e)3
Shutoff and Reset Controls 7 120.2(e)
Outdoor Air and Exhaust Damper Control 120.2(f)
Isolation Zones 120.2(g)
Automatic Demand Shed Controls 120.2(h)
Economizer FDD 120.2(i)
Duct Insulation 120.4
PRESCRIPTIVE MEASURES
Equipment is sized in conformance with
140.4 (a & b)140.4(a & b)
Supply Fan Pressure Control 140.4(c)
Simultaneous Heat/Cool 8 140.4(d)
Economizer 140.4(e)
Heat and Cool Air Supply Reset 140.4(f)
Electric Resistance Heating 9 140.4(g)
Duct Leakage Sealing and Testing 10 140.4(l)
Project Name:Date Prepared:
Yes No Yes No Yes No
Notes:
1. Provide equipment tags (e.g. AHU 1 to 10) and system description (e.g. Single Duct VAV reheat) as appropriate. Multiple units
with common requirements can be grouped together.
2. Provide references to plans (i.e. Drawing Sheet Numbers) and/or specifications (including Section name/number and
relevant paragraphs) where each requirement is specified. Enter "N/A" if the requirement is not applicable to this system.
3. The referenced plans and specifications must include all of the following information: equipment tag, equipment nominal capacity,
Title 24 minimum efficiency requirements, and actual rated equipment efficiencies. Where multiple efficiency requirements
are applicable (e.g. full and part load) include all. Where appliance standards apply (110.1), identify where equipment is required
to be listed per Title 20 1601 et seq.
4. Identify where the ventilation requirements are documented for each central HVAC system. Include references to both central unit
schedules and sequences of operation. If one or more space is naturally ventilated identify where this is documented in the
plans and specifications. Multiple zone central air systems must also provide a MCH-03-E compliance document.
5. If one or more space has demand controlled ventilation identify where it is specified including the sensor specifications and the
sequence of operation.
6. If one or more space has occupant sensor ventilation control identify where it is specified including the sensor specifications
and the sequence of operation
7. If the system is DDC identify the sequences for the system start/stop, optimal start, setback (if required) and setup (if required).
For all systems identify the specification for the thermostats and time clocks (If applicable).
8. Identify where the heating, cooling and deadband airflows are scheduled for this system. Include a reference to the specification
of the zone controls. Provide a MCH-03-E compliance document.
9. Enter N/A if there is no electric heating. If the system has electric heating indicate which exception to 140.4(g) applies.
10. If duct leakage sealing and testing is required, a MCH-04-A compliance document must be submitted.
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or
system design identified on this Certificate of Compliance (responsible designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design
or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the
California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the
information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted
to the enforcement agency for approval with this building permit application.
5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s)
issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed
signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the
building owner at occupancy.
CEC-NRCC-MCH-02-E (Revised 01/16)CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-02-E
HVAC Dry & Wet System Requirements (Page 3 of 3)
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
CEA/HERS Certification Identification (if applicable):
RESPONSIBLE PERSON'S DECLARATION STATEMENT
Project Name:Date Prepared:
Responsible Designer Name:Responsible Designer Signature:
Company:Date Signed:
Address:License:
City/State/Zip:Phone:
Documentation Author Name:Documentation Author Signature:
Signature Date:Company:
Address:
City/State/Zip:Phone:
CEC-NRCC-MCH-01-E (Revised 01/16)CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-01-E
Mechanical Systems (Page 4 of 4)
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
CEA/HERS Certification Identification (if applicable):
RESPONSIBLE PERSON'S DECLARATION STATEMENT
Project Name:Date Prepared:
Documentation Author Name:Documentation Author Signature:
Signature Date:Company:
Address:
City/State/Zip:Phone:
Responsible Designer Name:Responsible Designer Signature:
Company:Date Signed:
Address:License:
City/State/Zip:Phone:
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or
system design identified on this Certificate of Compliance (responsible designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or
system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the
California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the
information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to
the enforcement agency for approval with this building permit application.
5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s)
issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed
signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building
owner at occupancy.
STATE OF CALIFORNIA
MECHANICAL SYSTEMS
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016
STATE OF CALIFORNIA
MECHANICAL SYSTEMS
STATE OF CALIFORNIA
Mechanical Systems
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016
STATE OF CALIFORNIA
HVAC DRY & WET SYSTEM REQUIREMENTS
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016
STATE OF CALIFORNIA
HVAC SYSTEM REQUIREMENTS
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016
STATE OF CALIFORNIA
Mechanical Systems
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016
HARBOR DAY SCHOOL 08/13/2019
HARBOR DAY SCHOOL 08/13/19
CU'S 2
- -
- -
- -
FCU'S (W/
OSA)83
HARBOR DAY SCHOOL 08/13/19
FCU'S W/ OSA 83
CU'S 4
-
- -
- -
HARBOR DAY SCHOOL 04/24/20
FC/CU VRF SS 1-1/1-2 -
AC0.01, AC0.02 -
AC0.01, AC0.02 -
AC1.01, AC1.02 -
N/A -
-
AC0.01, AC0.02 -
-
N/A -
--
--
N/A -
N/A -
N/A -
AC0.05 -
N/A N/A -
N/A N/A -
N/A N/A -
N/A N/A -
N/A N/A -
HARBOR DAY SCHOOL 04/24/20
CALEB DAVIES
ACCO ENGINEERED SYSTEMS INC.
265 MCCORMICK AVE.
COSTA MESA, CA 92626 714-352-2226
04/24/20
M33701
04/24/20
ASHLEY DAVITT
ACCO ENGINEERED SYSTEMS INC.
265 MCCORMICK AVE.
COSTA MESA, CA 92626 714-352-2226
HARBOR DAY SCHOOL 04/24/20
CALEB DAVIES
ACCO ENGINEERED SYSTEMS INC.
265 MCCORMICK AVE
COSTA MESA, CA 92626 714-352-2226
04/24/20
M33701
04/24/20
ASHLEY DAVITT
ACCO ENGINEERED SYSTEMS INC.
265 MCCORMICK AVE
COSTA MESA, CA 92626 714-352-2226
N/A
N/A
N/A N/A -
-
AC0.01, AC0.02
AC0.01, AC0.02
AC1.01, AC1.02
N/A
AC0.01, AC0.02
N/A
-
-
N/A
N/A
N/A
AC0.05
N/A
N/A
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
2/
5
/
2
0
2
1
3
:
1
0
:
2
0
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC0.05
TITLE-24, MANDATORY
MEASURES, & GENERAL
NOTES
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
N/A
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
DUCT INSULATION REQUIREMENTS
(PER 2016 BUILDING ENERGY EFFICIENCY STANDARDS)
DUCT LOCATION INSULATION
R-VALUE
INSTALLED INSULATION
THICKNESS
R-8
- OUTDOORS
- SPACE BETWEEN ROOF & INSULATED CEILING
- IN VENTED ATTIC SPACES
- IN UNCONDITIONED SPACES
2"
- IN RETURN AIR PLENUM - ALL OTHER SPACES R-4.2 1"
- ENCLOSED IN DIRECTLY CONDITIONED SPACE NONE REQUIRED N/A
NOTES:
1. INSULATION THICKNESS VALUES BASED ON JOHNS MANVILLE INSULATION.
2. THE INSTALLED INSULATION THICKNESS OF DUCT LINING FOR PURPOSE OF COMPLIANCE IS
EQUIVALENT TO ITS NOMINAL THICKNESS.
3. THE INSTALLED INSULATION THICKNESS OF DUCT WRAP FOR PURPOSE OF COMPLIANCE IS
75% OF ITS NOMINAL THICKNESS.
LG 90-116 0.5 (ANY DIAM.) 130-176
0.75≤1-1/8" PIPE
1.0≥1-3/8" PIPE 40-70 0.75≤1-1/8" PIPE
1.0≥1-3/8" PIPE
MANUF.
LIQUID LINE HIGH PRESSURE VAPOR LINE LOW PRESSURE VAPOR LINE
TEMPERATURE
RANGE (°F)
INSULATION
REQUIREMENTS
(INCHES)
TEMPERATURE
RANGE (°F)
INSULATION
REQUIREMENTS
(INCHES)
TEMPERATURE
RANGE (°F)
INSULATION
REQUIREMENTS
(INCHES)
FC-A1-1 265 N/A 265 Y N/A 108 0.15 17 1 15 15 N/A 17 Y N/A N/A N/A N/A N/A N/A
FC-A1-2 1250 N/A 1250 Y N/A 429 0.50 215 14 15 210 N/A 215 Y N/A N/A N/A N/A N/A N/A
FC-A1-3 265 N/A 265 Y N/A 215 0.15 33 2 15 30 N/A 33 Y N/A N/A N/A N/A N/A N/A
FC-A1-4 285 N/A 285 Y N/A 179 0.50 90 6 15 90 N/A 90 Y N/A N/A N/A N/A N/A N/A
FC-A1-5 265 N/A 265 Y N/A 142 0.15 22 1 15 15 N/A 22 Y N/A N/A N/A N/A N/A N/A
FC-A1-6 310 N/A 480 Y N/A 617 0.15 93 6 15 90 N/A 93 Y N/A N/A N/A N/A N/A N/A
FC-A1-7 265 N/A 265 Y N/A 130 0.15 20 2 15 30 N/A 30 Y N/A N/A N/A N/A N/A N/A
FC-A1-8 265 N/A 460 Y N/A 207 0.15 31 1 15 15 N/A 31 Y N/A N/A N/A N/A N/A N/A
FC-A1-9 265 N/A 265 Y N/A 123 0.15 19 1 15 15 N/A 19 Y N/A N/A N/A N/A N/A N/A
FC-A1-10 310 N/A 265 Y N/A 123 0.38 47 4 15 60 N/A 60 Y N/A N/A N/A N/A N/A N/A
FC-A1-13 310 N/A 310 Y N/A 418 0.15 63 6 15 90 N/A 90 Y N/A N/A N/A N/A N/A N/A
FC-A1-14 265 N/A 265 Y N/A 126 0.15 19 2 15 30 N/A 30 Y N/A N/A N/A N/A N/A N/A
FC-A1-15 265 N/A 265 Y N/A 178 0.15 27 1 15 15 N/A 27 Y N/A N/A N/A N/A N/A N/A
FC-A1-16 310 N/A 285 Y N/A 227 0.50 114 8 15 120 N/A 120 Y N/A N/A N/A N/A N/A N/A
FC-A1-17 265 N/A 265 Y N/A 148 0.15 23 1 15 15 N/A 23 Y N/A N/A N/A N/A N/A N/A
FC-A1-18A 1450 N/A 1915 Y N/A 1343 0.38 511 33 15 495 N/A 511 Y N/A N/A N/A N/A N/A N/A
FC-A1-18B 1450 N/A 1735 Y N/A 892 0.38 338 23 15 345 N/A 345 Y N/A N/A N/A N/A N/A N/A
FC-A1-19 310 N/A 265 Y N/A 321 0.38 122 8 15 120 N/A 122 Y N/A N/A N/A N/A N/A N/A
FC-A1-20 390 N/A 390 Y N/A 371 0.38 141 9 15 135 N/A 141 Y N/A N/A N/A N/A N/A N/A
FC-A1-21 390 N/A 390 Y N/A 383 0.38 146 10 15 150 N/A 150 Y N/A N/A N/A N/A N/A N/A
FC-A2-1 390 N/A 565 Y N/A 351 0.38 134 9 15 135 N/A 135 Y N/A N/A N/A N/A N/A N/A
FC-A2-2 2260 N/A 1745 Y N/A 830 0.50 415 16 15 240 N/A 415 Y N/A N/A N/A N/A N/A N/A
FC-A2-3 265 N/A 265 Y N/A 117 0.15 17 1 15 15 N/A 17 Y N/A N/A N/A N/A N/A N/A
FC-A2-4 265 N/A 265 Y N/A 118 0.15 18 1 15 15 N/A 18 Y N/A N/A N/A N/A N/A N/A
FC-A2-5 265 N/A 265 Y N/A 115 0.15 17 1 15 15 N/A 17 Y N/A N/A N/A N/A N/A N/A
FC-A2-6 265 N/A 265 Y N/A 113 0.50 67 3 15 45 N/A 67 Y N/A N/A N/A N/A N/A N/A
FC-A2-7 265 N/A 265 Y N/A 142 0.15 21 1 15 15 N/A 21 Y N/A N/A N/A N/A N/A N/A
FC-A2-8 310 N/A 530 Y N/A 466 0.15 70 5 15 75 N/A 75 Y N/A N/A N/A N/A N/A N/A
FC-A2-9 265 N/A 265 Y N/A 142 0.15 21 1 15 15 N/A 21 Y N/A N/A N/A N/A N/A N/A
FC-A2-10 265 N/A 265 Y N/A 118 0.15 18 1 15 15 N/A 18 Y N/A N/A N/A N/A N/A N/A
FC-A2-11 265 N/A 265 Y N/A 101 0.15 15 1 15 15 N/A 15 Y N/A N/A N/A N/A N/A N/A
FC-A2-12 265 N/A 460 Y N/A 230 0.15 35 2 15 30 N/A 35 Y N/A N/A N/A N/A N/A N/A
FC-A2-15 1000 N/A 1320 Y N/A 800 0.38 304 20 15 300 N/A 304 Y N/A N/A N/A N/A N/A N/A
FC-B1-1 1250 N/A 1735 Y N/A 924 0.38 352 23 15 345 N/A 352 Y N/A N/A N/A N/A N/A N/A
FC-B1-3 285 N/A 480 Y N/A 130 0.38 50 4 15 60 N/A 60 Y N/A N/A N/A N/A N/A N/A
FC-B1-4 1250 N/A 1735 Y N/A 920 0.38 350 23 15 345 N/A 350 Y N/A N/A N/A N/A N/A N/A
FC-B1-5 1250 N/A 1735 Y N/A 756 0.38 288 19 15 285 N/A 288 Y N/A N/A N/A N/A N/A N/A
FC-B1-6 310 N/A 495 Y N/A 214 0.50 107 7 15 105 N/A 107 Y N/A N/A N/A N/A N/A N/A
FC-B1-7 1250 N/A 1320 Y N/A 743 0.38 282 19 15 285 N/A 285 Y N/A N/A N/A N/A N/A N/A
FC-B1-8 1250 N/A 1320 Y N/A 776 0.38 295 20 15 300 N/A 300 Y N/A N/A N/A N/A N/A N/A
FC-B1-9 310 N/A 310 Y N/A 151 0.50 75 5 15 75 N/A 75 Y N/A N/A N/A N/A N/A N/A
FC-B1-10 1000 N/A 1320 Y N/A 734 0.38 279 19 15 285 N/A 285 Y N/A N/A N/A N/A N/A N/A
FC-B1-11 1000 N/A 1320 Y N/A 736 0.38 280 19 15 285 N/A 285 Y N/A N/A N/A N/A N/A N/A
FC-B1-12 310 N/A 480 Y N/A 152 0.50 76 5 15 75 N/A 76 Y N/A N/A N/A N/A N/A N/A
FC-B1-13 1000 N/A 1320 Y N/A 766 0.38 291 20 15 300 N/A 300 Y N/A N/A N/A N/A N/A N/A
FC-B1-14 1250 N/A 1320 Y N/A 747 0.38 284 19 15 285 N/A 285 Y N/A N/A N/A N/A N/A N/A
FC-B1-15 310 N/A 310 Y N/A 197 0.50 98 7 15 105 N/A 105 Y N/A N/A N/A N/A N/A N/A
FC-B1-16 1450 N/A 1900 Y N/A 799 0.38 304 20 15 300 N/A 304 Y N/A N/A N/A N/A N/A N/A
FC-B1-17 1000 N/A 1320 Y N/A 658 0.38 251 17 15 255 N/A 255 Y N/A N/A N/A N/A N/A N/A
FC-B1-18 1450 N/A 1745 Y N/A 1,179 0.38 448 30 15 450 N/A 450 Y N/A N/A N/A N/A N/A N/A
FC-C2-2 285 N/A 265 Y N/A 208 0.15 35 6 15 90 N/A 90 Y N/A N/A N/A N/A N/A N/A
FC-C2-3 1000 N/A 1320 Y N/A 801 0.38 304 20 15 300 N/A 304 Y N/A N/A N/A N/A N/A N/A
FC-C2-4 800 N/A 1320 Y N/A 577 0.38 219 15 15 225 N/A 225 Y N/A N/A N/A N/A N/A N/A
FC-C2-5 800 N/A 1320 Y N/A 584 0.38 221 15 15 225 N/A 225 Y N/A N/A N/A N/A N/A N/A
FC-C2-6 800 N/A 1320 Y N/A 567 0.38 216 15 15 225 N/A 225 Y N/A N/A N/A N/A N/A N/A
FC-C2-7 310 N/A 495 Y N/A 268 0.15 45 7 15 105 N/A 105 Y N/A N/A N/A N/A N/A N/A
FC-C2-8 800 N/A 1320 Y N/A 582 0.38 221 15 15 225 N/A 225 Y N/A N/A N/A N/A N/A N/A
FC-C2-9 800 N/A 1320 Y N/A 558 0.38 213 14 15 210 N/A 213 Y N/A N/A N/A N/A N/A N/A
FC C2-10 390 N/A 530 Y N/A 327 0.15 50 9 15 135 N/A 135 Y N/A N/A N/A N/A N/A N/A
FC-C2-11 800 N/A 1320 Y N/A 558 0.38 213 14 15 210 N/A 213 Y N/A N/A N/A N/A N/A N/A
FC-C2-12 390 N/A 530 Y N/A 286 0.15 45 8 15 120 N/A 120 Y N/A N/A N/A N/A N/A N/A
FC-C2-13 800 N/A 1320 Y N/A 595 0.38 226 15 15 225 N/A 226 Y N/A N/A N/A N/A N/A N/A
FC-C2-14 800 N/A 1320 Y N/A 567 0.38 216 15 15 225 N/A 225 Y N/A N/A N/A N/A N/A N/A
FC-C2-15 800 N/A 1320 Y N/A 567 0.38 216 15 15 225 N/A 225 Y N/A N/A N/A N/A N/A N/A
FC-C2-16 800 N/A 1320 Y N/A 577 0.38 220 15 15 225 N/A 225 Y N/A N/A N/A N/A N/A N/A
FC-C2-17 800 N/A 1320 Y N/A 581 0.38 221 15 15 225 N/A 225 Y N/A N/A N/A N/A N/A N/A
FC-C2-18 800 N/A 1320 Y N/A 599 0.38 227 15 15 225 N/A 227 Y N/A N/A N/A N/A N/A N/A
FC-C2-19 800 N/A 1320 Y N/A 597 0.38 227 15 15 225 N/A 227 Y N/A N/A N/A N/A N/A N/A
FC-D1-1 1800 N/A 2020 Y N/A 1,194 0.50 597 34 15 510 N/A 597 Y N/A N/A N/A N/A N/A N/A
FC-D1-2 390 N/A 495 Y N/A 261 0.38 100 7 15 105 N/A 105 Y N/A N/A N/A N/A N/A N/A
FC-D1-3 1800 N/A 1745 Y N/A 1297 0.50 649 36 15 540 N/A 649 Y N/A N/A N/A N/A N/A N/A
FC-D1-4 800 N/A 1320 Y N/A 511 0.50 256 13 15 195 N/A 256 Y N/A N/A N/A N/A N/A N/A
FC-D1-5 1750 N/A 1520 Y N/A 1311 0.50 655 33 15 495 N/A 655 Y N/A N/A N/A N/A N/A N/A
FC-D1-6 265 N/A 265 Y N/A 170 0.15 26 2 15 30 N/A 30 Y N/A N/A N/A N/A N/A N/A
FC-D1-7 2260 N/A 1770 Y N/A 1,530 0.50 765 39 15 585 N/A 765 Y N/A N/A N/A N/A N/A N/A
FC-D1-8 1250 N/A 1880 Y N/A 730 0.50 365 19 15 285 N/A 390 Y N/A N/A N/A N/A N/A N/A
FC-D2-1 800 N/A 1320 Y N/A 574 0.38 220 15 15 225 N/A 225 Y N/A N/A N/A N/A N/A N/A
FC-D2-2 390 N/A 530 Y N/A 335 0.38 127 9 15 135 N/A 135 Y N/A N/A N/A N/A N/A N/A
FC-D2-3 1750 N/A 1770 Y N/A 1311 0.50 656 33 15 495 N/A 656 Y N/A N/A N/A N/A N/A N/A
FC-D2-4 390 N/A 565 Y N/A 289 0.50 145 9 15 135 N/A 145 Y N/A N/A N/A N/A N/A N/A
FC-D2-5 1750 N/A 1770 Y N/A 1,219 0.50 610 31 15 465 N/A 610 Y N/A N/A N/A N/A N/A N/A
FC-D2-6 1450 N/A 1735 Y N/A 818 0.15 125 21 15 315 N/A 315 Y N/A N/A N/A N/A N/A N/A
LVL 1 HALLWAY N/A N/A N/A N/A N/A 6915 0.15 1040 N/A N/A N/A N/A 1040 Y N/A N/A N/A N/A N/A N/A
LVL 2 HALLWAY N/A N/A N/A N/A N/A 5673 0.15 855 N/A N/A N/A N/A 855 Y N/A N/A N/A N/A N/A N/A
Notes:
2. The largest amount of primary air supplied by the terminal unit when it's operating in the cooling mode.
3. The smallest amount of primary air supplied by the terminal unit in the deadband mode.
4. The largest amount of primary air supplied by the terminal unit when it's operating in the heating mode.
5. A terminal unit can be controlled with DDC controls, or non-DDC controls. Each control category has different reheat limitations in code.
6. Transfer Air must be provided where Required Ventilation Airflow (Column 14) is greater than the Design Primary Deadband Airflow (Column 3).
8. Minimum ventilation rate per Section §120.1. Table 120.1-A.
10. Based on number of fixed seats where applicable or the greater of the expected number of occupants and 50% of the CBC occupant load for egress purposes for space without fixed seating.
14. Required Ventilation Airflow (Req'd Ventilation Airflow) is the larger of the ventilation rates calculated on an AREA BASIS or OCCUPANCY BASIS (Column 9 or 12)
15. This column identifies whether or not the Design Primary Deadband Airflow complies or not. It compares the value in column 14 to the value in column 3 and column 6.
16. Design Primary Cooling Airflow * 0.50 for DDC, Design Primary Cooling Airflow * 0.30 for Non‐DDC. If the Design Primary Cooling Airflow is less than 300 cfm, then this is not applicable.
17. Maximum of Column 14 and Column 16. If the Design Primary Cooling Airflow is 300 cfm or less, then this is not applicable.
18. This column identifies whether or not the Design Primary Reheat Airflow at the zone level, complies or not. It compares the value in column 17 to the value in column 4.
19. Design Primary Cooling Airflow * 0.20 for DDC. Not applicable for Non‐DDC zones or zones where Design Primary Cooling Airflow is 300 cfm or less.
20. Maximum of Column 14 and Column 19. Not applicable if the Design Primary Cooling Airflow is 300 cfm or less.
21. This column identifies whether or not the Design Primary Deadband Airflow at the zone level, complies or not. It compares the value in column 20 to the value in column 3.
CEC-NRCC-MCH-03-E (Revised 05/16)CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-03-E
Mechanical Ventilation & Reheat (Page 1 of 2)
ACTUAL DESIGN INFO (FROM
EQUIPMENT SCHEDULES, ETC)AREA BASIS OCCUPANCY
BASIS
ROOM
BASIS
VAV Reheated
Primary Air CFM
VAV Deadband
Primary Air CFM
01 02
Project Name:Date Prepared:
ZO
N
E
/
S
Y
S
T
E
M
/
V
A
V
BO
X
T
A
G
DE
S
I
G
N
P
R
I
M
A
R
Y
CO
O
L
I
N
G
A
I
R
F
L
O
W
(C
F
M
)
DE
S
I
G
N
P
R
I
M
A
R
Y
DE
A
D
B
A
N
D
AI
R
F
L
O
W
(
C
F
M
)
DE
S
I
G
N
P
R
I
M
A
R
Y
HE
A
T
I
N
G
A
I
R
F
L
O
W
(C
F
M
)
CO
N
T
R
O
L
T
Y
P
E
D
D
C
(Y
/
N
)
TR
A
N
S
F
E
R
A
I
R
F
L
O
W
(C
F
M
)
CO
N
D
I
T
I
O
N
E
D
A
R
E
A
(f
t
²
)
MI
N
C
F
M
P
E
R
A
R
E
A
(C
F
M
/
f
t
²
)
MI
N
C
F
M
B
Y
A
R
E
A
NU
M
B
E
R
O
F
P
E
O
P
L
E
CF
M
P
E
R
P
E
R
S
O
N
MI
N
C
F
M
B
Y
OC
C
U
P
A
N
T
MI
N
C
F
M
B
Y
R
O
O
M
CO
M
P
L
I
E
S
?
MA
X
I
M
U
M
R
E
H
E
A
T
(C
F
M
)
CO
M
P
L
I
E
S
?
PR
I
M
A
R
Y
CO
O
L
I
N
G
A
I
R
AI
R
F
L
O
W
CO
M
P
L
I
E
S
?
BA
S
E
D
D
E
S
I
G
N
PR
I
M
A
R
Y
C
O
O
L
I
N
G
AI
R
03 04 05 06 07 08 09 10 11 12 13 14 16 17 18 19 20 21
MINIMUM
15
RE
Q
'
D
V
E
N
T
AI
R
F
L
O
W
(
C
F
M
)
A. Mechanical Ventilation and Reheat
In lieu of this compliance document, the required outdoor ventilation rates and airflows may be shown on the plans or the calculations can be presented in a spreadsheet. Mechanical
Ventilation and Reheat worksheet available on the Energy commission's website at: http://www.energy.ca.gov/title24/2016standard/.
Note: In all calculations that compare a supply quantity to the REQ'D V.A. quantity, the actual percentage of outdoor air in the supply is ignored. Area in building for which
natural ventilation is used should be clearly designated. Specifications must require that building operating instructions include explanations of the natural ventilation system.
CEC-NRCC-MCH-03-E (Revised 05/16)CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-03-E
Mechanical Ventilation & Reheat (Page 2 of 2)
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
RESPONSIBLE PERSON'S DECLARATION STATEMENT
Project Name:Date Prepared:
Documentation Author Name:
Company:
Address:
City/State/Zip:
Documentation Author Signature:
Signature Date:
Phone:
Responsible Designer Name:
Company:
City/State/Zip:
Address:
Responsible Designer Signature:
Date Signed:
License:
Phone:
CEA/HERS Certification Identification (if applicable):
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or
system design identified on this Certificate of Compliance (responsible designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design
or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the
California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the
information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted
to the enforcement agency for approval with this building permit application.
5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s)
issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed
signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the
building owner at occupancy.
STATE OF CALIFORNIA
MECHANICAL VENTILATION AND REHEAT
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance May 2016
STATE OF CALIFORNIA
MECHANICAL VENTILATION AND REHEAT
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance May 2016
HARBOR DAY SCHOOL 04/24/20HARBOR DAY SCHOOL 04/24/20
CALEB DAVIES
ACCO ENGINEERED SYSTEMS INC.
265 MCCORMICK AVE.
COSTA MESA, CA 92626 714-352-2226
04/24/20
M33701
04/24/20
ASHLEY DAVITT
ACCO ENGINEERED SYSTEMS INC.
265 MCCORMICK AVE.
COSTA MESA, CA 92626 714-352-2226
VRF PIPE INSULATION REQUIREMENTS (2016)
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
2/
5
/
2
0
2
1
3
:
1
0
:
2
2
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC0.06
TITLE-24 (CONT.)
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
N/A
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
0 09/11/20 ISSUED FOR
CONSTRUCTION
CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
2/
5
/
2
0
2
1
3
:
1
0
:
2
3
P
M
C. DAVIES A. DAVITT
C. DAVIES
AC0.07
ENERGY COMPLIANCE
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
030 01/15/21 CCD-030 CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
2/
5
/
2
0
2
1
3
:
1
0
:
2
4
P
M
C. DAVIES A. DAVITT
C. DAVIES
AC0.08
ENERGY COMPLIANCE
(CONT.)
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
030 01/15/21 CCD-030 CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
2/
5
/
2
0
2
1
3
:
1
0
:
2
5
P
M
C. DAVIES A. DAVITT
C. DAVIES
AC0.09
ENERGY COMPLIANCE
(CONT.)
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
030 01/15/21 CCD-030 CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
PC
J
J
J
J
J
J
J
J
UTILITY NOTES
POWER WIRING TO EQUIPMENT BY ELECTRICIAN
CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER
SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN,
INSTALLED BY ACCO
AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED,
INSTALLED, AND WIRED BY ELECTRICIAN
DSD
ASD
CCCC
1
1
3
3
10
10
16
16
20
20
22
22
25
25
ZZ
YY
V
V
SS
NN
KK
HH
EE
BB
27
27
2
2
4
4
5
5
18
18
DD
FF
GG
AAAA
XX
DDDD
UU
QQ
C
8
8
13
13
19
19
21
21
17
17
11
11
OFFICE
124A
4TH GRADE
CLASSROOM
120
3RD GRADE
CLASSROOM
118
SMALL GROUP
119A
4TH GRADE
CLASSROOM
119
LOWER SCHOOL
SCIENCE
CLASSROOM
122
WORLD
LANGUAGE
CLASSROOM
121
CERAMICS
125A
KILN
125B
UPPER SCHOOL
ART LAB
125
1ST GRADE
CLASSROOM
112
SMALL GROUP
113
2ND GRADE
CLASSROOM
115
1ST GRADE
CLASSROOM
114
SMALL GROUP
115A
TEACHING AREA
131B
WORKROOM
131A
ELEV.
E-1-1
ELECT.
110
DATA
109
CONFERENCE
ROOM
107
ASSOCIATES
134
PSYCH.
137A
SMALL GROUP
AREA
137
2ND GRADE
CLASSROOM
116
SMALL GROUP
117A 3RD GRADE
CLASSROOM
117
LANGUAGE ARTS
SPECIALIST
137B
CUSTODIAL
136
STAIR 1
STR1-1
ELECTRICAL
163
STAFF TOILET
145
UNISEX TOILET
142
STAIR 2
STR2-1
LOBBY
100
GIRLS'
RESTROOM
140
BOYS'
RESTROOM
139
GIRLS'
RESTROOM
143
BOYS'
RESTROOM
144
WORKROOM
106
FACILITIES DIR.
105
LOWER DIR.
102
TECHNOLOGY
DIRECTOR
103
HEAD OF
SCHOOL
104
HALLWAY
161
LIBRARY
131
TINKER AREA
133
STORY TELLING
132
MATH
SPECIALIST
137C
MAKER SPACE
123
LOWER SCHOOL
ART LAB
126
OPEN OFFICE
159
HALLWAY
160
HALLWAY
162
?
?
(1,325 LBS.)
(1,325 LBS.)
(1,305 LBS.)
(1,664 LBS.)
FC
A1-1
FC
A1-3
FC
A1-4 FC
A1-5
FC
A1-7
FC
A1-8
FC
A1-9
FC
A1-10
FC
A1-11
FC
A1-12
FC
B1-4
FC
B1-1
FC
B1-2
FC
B1-5
FC
B1-7
FC
A1-13
FC
A1-14
FC
A1-16
FC
A1-17
FC
A1-15
FC
A1-19 FC
A1-18B
FC
B1-8
FC
B1-9
FC
B1-10
FC
B1-11
FC
B1-12
FC
B1-13
FC
B1-14
FC
A1-20
FC
A1-21
FC
B1-15
FC
B1-16 FC
B1-17
FC
D1-8
FC
B1-19
FC
B1-20
FC
D1-1
FC
D1-3
FC
D1-5
FC
D1-6
FC
D1-7
FC
B1-6
NURSE
101
TOILET
111A TOILET
108A
WORK ROOM
108C
STOR.
111B
KINDERGARTEN
108
KINDERGARTEN
111 STOR.
108B
TOILET
101A
TECH LAB
123A
DESIGN CENTER
124
FC
B1-3
SF
1-2
SF
1-1
SF
1-3
FC
A1-2
FC
D1-4
FC
A1-6
BS
A1
BS
A2
BS
A-3
BS
B-1
BS
A-4
BS
D-2
BS
D-1
EF
1-6
EF
1-1
EF
1-2
EF
1-5
EF
1-4
EF
1-8
(180 LBS.)
(180 LBS.)
FSD
1
FSD
1
1 SQ. FT.
TRANSFER AIR
OPN'G (TYP)
FSD
1
NORMALWEIGHT
CONCRETE PAD
BY G.C.
BS
B-2
BS
B-3
L
1
L
1
L
1
L
1
(TYP. 3)
L
1
L
1
L
1
L
1
L
1
L
1
L
1
L
1
L
1
L
1
L
1
L
1
L
1
L
1
L
1
(TYP. 3)
L
1
L
1
L
1
L
1
L
1
L
1
L
1
FC
A1-18A
ADMISSIONS DIR.
100A
TOILET
100B
STAFF TOILET
153ELECT.
146
CUSTODIAN
151
UNISEX TOILET
152
ELEV.
E-2-1
CORRIDOR
154
FIRE RISER
112A
PP
MM
12
126
6
LL
RR
TT
W
W
24
24
26
26
23
2315
15
14
14
7
7
9
9
BBBB
AA
JJ
DATA
147
L
1
FC
D1-9
L
1
L
1
L
1
FC
B1-18
NORMALWEIGHT
CONCRETE PAD
BY G.C.
CU
1
CU
A
CU
B
CU
D
CU
C
CU
2
FSD
1
FSD
1
INSTALL DUCT
EXTENSIONS ATOP
CU-A & CU-B SUCH
THAT AIR WILL
DISCHARGE AT THE
SAME ELEVATION AS
THE TOP OF THE
ADJACENT
CONCRETE WALL
(SEE DET. 3/AC5.03)
INSTALL DUCT
EXTENSIONS ATOP
CU-C & CU-D SUCH
THAT AIR WILL
DISCHARGE AT THE
SAME ELEVATION AS
THE TOP OF THE
ADJACENT
CONCRETE WALL
(SEE DET. 3/AC5.03)
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
N
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
A
B
2/
5
/
2
0
2
1
3
:
1
0
:
3
8
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC1.01
MECHANICAL LEVEL 01
FLOOR PLAN OVERALL
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
1/16" = 1'-0"
AC1.01A
AC1.01B
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
0 09/11/20 ISSUED FOR
CONSTRUCTION
CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
J
J
J
J
J
J
UTILITY NOTES
POWER WIRING TO EQUIPMENT BY ELECTRICIAN
CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER
SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN,
INSTALLED BY ACCO
AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED,
INSTALLED, AND WIRED BY ELECTRICIAN
DSD
ASD
1
1
3
3
10
10
16
16
20
20
SS
NN
K
HH
EE
BB
2
2
4
4
5
5
18
18
DD
FF
GG
QQ
C
8
8
13
13
19
19
17
17
11
11
1ST GRADE
CLASSROOM
112
SMALL GROUP
113
2ND GRADE
CLASSROOM
115
1ST GRADE
CLASSROOM
114
SMALL GROUP
115A
ELEV.
E-1-1
ELECT.
110
DATA
109
CONFERENCE
ROOM
107
ASSOCIATES
134
PSYCH.
137A
SMALL GROUP
AREA
137
2ND GRADE
CLASSROOM
116
3RD GRADE
CLASSROOM
117
LANGUAGE ARTS
SPECIALIST
137B
CUSTODIAL
136
STAIR 1
STR1-1
ELECTRICAL
163
STAFF TOILET
145
UNISEX TOILET
142
LOBBY
100
GIRLS'
RESTROOM
143
BOYS'
RESTROOM
144
WORKROOM
106
FACILITIES DIR.
105
LOWER DIR.
102
TECHNOLOGY
DIRECTOR
103
HEAD OF
SCHOOL
104
LIBRARY
131
TINKER AREA
133
STORY TELLING
132
MATH
SPECIALIST
137C
OPEN OFFICE
159
HALLWAY
160
FC
A1-1
FC
A1-3
FC
A1-4
FC
A1-5
FC
A1-7
FC
A1-8
FC
A1-9FC
A1-10
FC
B1-1FC
B1-4
FC
B1-5
FC
B1-6
FC
A1-13
FC
A1-14
FC
A1-15
FC
A1-17
FC
A1-16
FC
B1-10
FC
B1-9
FC
A1-19
FC
A1-12
FC
A1-11
FC
B1-2
SF
1-2
SF
1-1
FC
A1-2
FC
B1-3
FSD
1
BS
A1
FC
A1-6
1 SQ. FT. TRANSFER
AIR OPENING BY G.C.
(TYP. UNLESS
OTHERWISE STATED)
EF
1-2
BS
A2
BS
B-1
FC
B1-7
FC
B1-8
FSD
1
FC
A1-18B
BS
A-3
3RD GRADE
CLASSROOM
117
NURSE
101TOILET
111A
TOILET
108A
WORK ROOM
108C
STOR.
111B
KINDERGARTEN
108
KINDERGARTEN
111
STOR.
108B
ADMISSIONS DIR.
100A
TOILET
101A
TOILET
100B
EF
1-1
12"ø OSA
8"ø
8"ø OSA
6"ø OSA
20 CFM
16"ø OSA
6"ø OSA
30 CFM
14"ø OSAFSD
1
6"ø OSA
60 CFM
8"ø OSA
110 CFM
DURATECH FLUE UP TO SECOND FLOOR.
SEE AC1.02A FOR CONTINUATION
AND TERMINATION.
8"ø EA
8"ø EA
1" U.C. DOOR
BY G.C.
1" U.C. DOOR
BY G.C.
1" U.C.
DOOR
BY G.C.
10"Ø CS1
315 CFM
(TYP. 4)
8"Ø CE1
100 CFM 10"Ø CS1
420 CFM
(TYP. 3)
FILTER BOX
12"ø SA
10"ø SA
10"ø SA
16"ø SA
8"Ø CE1
100 CFM8"Ø CE1
100 CFM
8"Ø CE1
100 CFM
1" U.C.
DOOR
BY G.C.
1" U.C.
DOOR
BY G.C.
12"ø OSA
FILTER BOX
8"Ø CE1
100 CFM8"Ø CE1
100 CFM10"Ø CE1
300 CFM
10"Ø CE1
300 CFM
10"Ø CS1
315 CFM
(TYP. 4)
10"Ø CS1
315 CFM
(TYP. 4)
12"ø SA
12"⌀RA
(TYP. 2)
FILTER
BOX
14"⌀RA
FILTER
BOX
10"ø SA
10"Ø CS1
315 CFM
(TYP. 4)
14"⌀RA
FILTER
BOX
10"ø SA
10"Ø CS1
200 CFM
(TYP. 4)
12"⌀RA
FILTER
BOX
12"ø OSA
560 CFM
12"ø SA
14"⌀RA
FILTER
BOX
12"Ø CS1
365 CFM
(TYP. 4)
14"⌀RA
FILTER BOX
FC
A1-18A
CR1
CR1
CR1
CR1
CR1
CR1
CT2
CT2
16"Ø CT1
CT1
16"ø
CR1
(TYP. 2)
16"Ø CT1
16"Ø CT1
16"Ø CT1
16"Ø CT1
16"Ø CT1
16"Ø CT1 12"Ø CT1
CR1
10"Ø CS1
315 CFM
(TYP. 4)
6"ø OSA
35 CFM
14"ø OSA
SWG1
12"X6"
215 CFM EA
PP
MM
12
126
6
L
L
RR
15
15
14
14
7
7
9
9
AA
JJ
10X10 SOUND
BOOT (1" L)
(TYP. 2, SEE
DET. 8/AC5.03)
FSD
1
6"Ø CS1
60 CFM
6"ø OSA 6"ø OSA
6"ø 6"ø
8"ø OSA
6"ø
12"ø OSA
6"ø
10"ø OSA
270 CFM
8"ø EA
8"ø EA
48"x14"
12"Ø RA
(TYP. 2)
10"ø
10"ø
10"ø SA
14"Ø RA 12"ø OSA
6"Ø CS1
60 CFM
6"ø OSA
14"Ø RA
48"x14"
12"Ø SA
TAP
(TYP. 2)
10"ø SA 10"ø SA
EXHAUST FAN TO HAVE
GYPSUM ENCLOSURE
BY G.C.
10"ø SA10"ø SA
16"Ø SA
10"ø OSA 16"Ø CT1
8"ø EA
8"ø EA12"ø EA
8"ø EA
14"ø EA
8"Ø CS1
110 CFM 12"ø EA
48"x14"
10"ø SA
10"ø SA
12"Ø SA TAP
(TYP. 2)
10"ø OSA
10"ø OSA
12"Ø SA TAP
(TYP. 2)
10"ø SA
48"x14"
6"Ø CS1
75 CFM
6"ø OSA
10"ø SA
12"Ø SA TAP
(TYP. 2)
48"x14"
10"ø OSA
12"ø OSA
12"ø OSA
8"Ø CS1
125 CFM
8"ø OSA
20"x8" SA
14"ø SA
12"ø SA
48"x14"
12"x8" SA
20"x8" SA
12"ø
12"ø OSA
6"Ø CS1
90 CFM
8"Ø CS1
120 CFM
16"ø OSA
8"ø OSA
16"x16" SWG2
36"X19" BLDG.
RELIEF LOUVER
W/ BAROMETRIC
B.D.D.
(TYP. 2, VIF
DIMENSIONS).
29-1/8"X19" BLDG.
RELIEF LOUVER W/
BAROMETRIC B.D.D.
(VIF DIMENSIONS).
FILTER BOX
FILTER BOX
20 CFM
OSA
35 CFM
OSA
700 CFM OSA
6"Ø CS1
95 CFM 30 CFM
OSA
25 CFM
OSA
FILTER BOX
6"Ø CS1
90 CFM
415 CFM OSA410 CFM OSA
370 CFM OSA
370 CFM
OSA
370 CFM
OSA
310 CFM
OSA
25 CFM
OSA
.6"ø
1145
CFM
OSA
6"ø30 CFM
OSA
46" x 18"
LOUVER
36" x 18"
LOUVER
46" x 18"
LOUVER
36" x 18"
LOUVER
46" x 18"
LOUVER
46" x 18"
LOUVER
46" x 18"
LOUVER
36" x 18"
LOUVER
36" x 18"
LOUVER
36" x 18"
LOUVER
36" x 18"
LOUVER
36" x 18"
LOUVER
1 SQ. FT.
TRANSFER AIR
OPN'G IN SOFFIT
ABOVE CEILING
BY G.C.
1 SQ. FT.
TRANSFER AIR
OPN'G IN SOFFIT
ABOVE CEILING
BY G.C.
10"Ø CR1
10"Ø CR1
10"Ø CR1
10"Ø CR1
10"Ø CR1
10"Ø CR1
10"Ø CR1
10"Ø CR110"Ø CR1
10"Ø CR1
10"Ø CR1
10"Ø CR1
10"Ø CR1
10"Ø CR1
ACOUSTICAL WRAP
BY OTHERS.
2
ACOUSTICAL
WRAP BY
OTHERS.
2
ACOUSTICAL
WRAP BY
OTHERS.
2
ACOUSTICAL WRAP
BY OTHERS.
2
2
2
2
2
10X10 SOUND
BOOT (1" L)
(TYP. 6, SEE
DET. 9/AC5.03)
2
2
2
2
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
N
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
A
B
2/
5
/
2
0
2
1
3
:
1
0
:
4
0
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC1.01A
MECHANICAL LEVEL 01
FLOOR PLAN NORTH
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
1/8" = 1'-0"
AC1.01A
AC1.01B
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
0 09/11/20 ISSUED FOR
CONSTRUCTION
CD
013 11/23/20 CCD-013 CD
017 11/30/20 CCD-017 DN
1 01/22/21 CITY PERMIT
AMENDMENT
CD
2 xx/xx ACOUSTICAL CHANGES DN
PC
J
J
UTILITY NOTES
POWER WIRING TO EQUIPMENT BY ELECTRICIAN
CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER
SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN,
INSTALLED BY ACCO
AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED,
INSTALLED, AND WIRED BY ELECTRICIAN
DSD
ASD
CCCC
1
1
3
3
10
10
16
16
20
20
22
22
25
25
ZZ
YY
VV
SS
27
27
2
2
4
4
5
5
18
18
AAAA
XX
DDDD
UU
8
8
13
13
19
19
21
21
17
17
11
11
OFFICE
124A
4TH GRADE
CLASSROOM
120
3RD GRADE
CLASSROOM
118
SMALL GROUP
119A
4TH GRADE
CLASSROOM
119
LOWER SCHOOL
SCIENCE
CLASSROOM
122
WORLD
LANGUAGE
CLASSROOM
121
CERAMICS
125A
KILN
125B
UPPER SCHOOL
ART LAB
125
TEACHING AREA
131B
WORKROOM
131A
SMALL GROUP
117A
3RD GRADE
CLASSROOM
117
STAIR 2
STR2-1
GIRLS'
RESTROOM
140
BOYS'
RESTROOM
139
HALLWAY
161
LIBRARY
131
TINKER AREA
133
MAKER SPACE
123
LOWER SCHOOL
ART LAB
126
HALLWAY
162
FC
B1-11
FC
B1-12
FC
B1-13
FC
B1-15
FC
B1-17
FC
A1-18B
FC
A1-20
FC
A1-21
FC
D1-8
FC
D1-1
FC
B1-20
FC
B1-19
FC
D1-3
FC
D1-5
FC
D1-6
FC
D1-7
SF
1-3
BS
D-2
EF
1-6
FC
D1-4BS
D-1
EF
1-8
BS
A-4
FC
B1-14
FC
B1-16 EF
1-4
EF
1-5
8"ø OSA
8"ø OSA
8"ø OSA
14"ø EA
EXHAUST FAN TO
HAVE GYPSUM
ENCLOSURE BY G.C.
8"ø OSA
14"ø EA 20"ø
EXHAUST FAN TO
HAVE GYPSUM
ENCLOSURE BY G.C.
TECH LAB
123A
DESIGN CENTER
124
1" U.C. DOOR
BY G.C.
BS
B-3
BS
B-2
10"ø SA
10"Ø CS1
365 CFM
(TYP. 4)14"⌀RA
FILTER BOX
12"ø SA
10"ø SA
10"Ø CS1
365 CFM
(TYP. 4)
FILTER BOX
10"ø OSA
12"⌀
RA
10
"
ø
S
A
10
"
ø
S
A
10"Ø CS1
200 CFM
(TYP. 4)
22"x22" CE1
1220 CFM
16"Ø
12"⌀OSA
FILTER BOX
12"⌀OSA
FILTER BOX
12"⌀OSA
FILTER BOX
12"X8" SWG1
355 CFM
(TYP. 2)
14"Ø CE2
960 CFM
(TYP. 2)
12"Ø CS1
365 CFM
(TYP. 4)
10"Ø CS1
200 CFM
(TYP. 4)
10"ø SA
10"Ø CS1
315 CFM
(TYP. 4)
FILTER BOX
12"⌀RA
FILTER BOX
12"⌀RA
FILTER BOX
12"⌀RA
(TYP. 2)
10"ø SA
12"ø SA
10"ø SA 10"Ø CS1
200 CFM
(TYP. 4)
12"ø SA
10"ø SA
10"ø SA
10"Ø CS1
290 CFM
(TYP. 6)
14"⌀RA
FILTER BOX
14"ø OSA
10"Ø CS1
320 CFM
(TYP. 6)
10"ø SA
14"⌀RA
FILTER
BOX
12"⌀RA
(TYP. 2)
FILTER BOX
10"ø OSA
CR1
(TYP. 2)CR1
CR1
CS1
CR1 CR1
CR1
CR1 CR1
CR1
CT2CT1
CT1
CT2
16"ø
12"x12" SWG2
12"x12" SWG2
12"x12" SWG2
12"x12" SWG2
AC1.01AAC1.01B
AC1.01A
10"Ø CE1
300 CFM
10"Ø CE1
300 CFM
16"Ø CT2
16"Ø CT1
16"Ø CT1
16"Ø CT1
16"Ø CT1
16"Ø CT1
6"⌀OSA
30 CFM
STAFF TOILET
153
ELECT.
146
CUSTODIAN
151
ELEV.
E-2-1
CORRIDOR
154
FSD
1
FSD
1
8"ø EA
8"Ø CE1
100 CFM
8"Ø CE1
100 CFM
SWG1
10"X4"
140 CFM
8"Ø CS1
195 CFM
(TYP. 4)
12"x10" SWG1
280 CFM
(TYP. 8)
12
126
6
TT
WW
24
24
26
26
23
2315
15
14
14
7
7
9
9
BBBB
DATA
147
FC
D1-9
12"ø EA
SKUTT
"ENVIROVENT 2"
DOWNDRAFT KILN
VENT W/ WALL
MOUNTED BLOWER
(TYP. 3, SEE DET.
1/AC5.01)
SKUTT ELECTRIC
KILN (TYP. 3)
PROVIDED AND
INSTALLED BY
OTHERS
FILTER BOX
10"x6" SWG3
30 CFM
10"x6"
SWG2
48"x13"
FILTER BOX
14"⌀RA
12"ø OSA
12"x12" OSA
10"ø OSA12"ø SA 12"ø SA
12"x8" SA12"x8" SA
12"ø SA12"ø SA
20"x8" SA
20"x8" SA
10"ø SA
10"ø SA
48"x14"
48"x16"
14"Ø SA
EF
1-3
48"x14"
48"x16"
10"ø SA
10"ø OSA
12"ø OSA
10"ø OSA
10"ø OSA
EXHAUST FAN TO
HAVE GYPSUM
ENCLOSURE BY G.C.
36"X19" BLDG.
RELIEF LOUVER W/
BAROMETRIC B.D.D.
(TYP. 2, VIF
DIMENSIONS).
12"Ø SA TAP
12"Ø SA
TAP
12"Ø SA
TAP
10"ø SA
14"Ø SA TAP
14"Ø SA TAP
12"Ø SA
TAP
(TYP. 2)
48"x14"
16"Ø CT1
FC
B1-18
12"⌀RA
(TYP. 2)
10"ø SA
48"x14"
12"Ø SA
TAP
12"⌀RA
16"ø
12"ø SA
B.D.D. (TYP. 3)
12"⌀OSA
10"Ø SA TAP
(TYP. 2)
8"ø SA
6"ø OSA
8"ø SA
48"x14"
48"x14"
12"ø SA
10"ø SA
10"ø SA
12"Ø SA
TAP
10"ø SA48"x14"
12"ø SA 10"ø SA
12"Ø SA
TAP
8"ø EA
UNISEX TOILET
152
16"ø
14"ø EA
8"ø
12"ø EA 10"ø EA
8"ø EA8"ø EA
8"Ø CS1
150 CFM
35-1/4"X19" BLDG.
RELIEF LOUVER W/
BAROMETRIC B.D.D.
(VIF DIMENSIONS).
FILTER BOX
10"ø OSA
310 CFM
OSA
310 CFM
OSA
370 CFM
OSA
8"Ø CS1
105 CFM
395 CFM
OSA
310 CFM
OSA
450 CFM
OSA
400 CFM
OSA
765 CFM
OSA
655 CFM OSA
310 CFM
OSA
705 CFM
OSA
135 CFM OSA665 CFM
OSA
8"Ø CS1
145 CFM
560 CFM
OSA
405 CFM
OSA
12"X12" OPENING IN
SOFFIT FOR FLEX
DUCT TRANSFER AIR
CR1
46" x 18"
LOUVER
46" x 18"
LOUVER
46" x 18"
LOUVER
46" x 18"
LOUVER
46" x 18"
LOUVER
46" x 18"
LOUVER
46" x 18"
LOUVER
46" x 18"
LOUVER
46" x 18"
LOUVER
46" x 18"
LOUVER
46" x 18"
LOUVER
46" x 18"
LOUVER
46" x 18"
LOUVER
46" x 18"
LOUVER
46" x 18"
LOUVER46" x 18"
LOUVER
46" x 18"
LOUVER
36" x 18"
LOUVER
46" x 18"
LOUVER
46" x 18"
LOUVER
36" x 18"
LOUVER
12"⌀RA
22"x12" EA
10"Ø CR1
10"Ø CR1
10"Ø CR1 10"Ø CR1
10"Ø CR1
12"x12" SWG2
16"Ø CT2
12"x12" SWG2
6"ø OSA
8"ø OSA
105 CFM
14"ø EA
L
1
12"⌀RA (TYP. 2)
L
1
18"x10" SWG1
440 CFM
(TYP. 4)
14"ø SA
20"x14"
FILTER BOX
14"ø OSA
12"X10" SWG1
380 CFM
(TYP. 2)
12"x12" SWG2
12"X12" SOUND
BOOT (1"L) SEE
DET. 8/AC5.03
20"ø SA 16"ø
2
16"ø 12"ø
ACOUSTICAL WRAP
BY OTHERS.
2
ACOUSTICAL WRAP
BY OTHERS.
2
ACOUSTICAL WRAP
BY OTHERS.
2
SHEET NOTES
1. INSTALLATION OF ELECTRIC KILNS (BY OTHERS) SHALL COMPLY WITH
CLEARANCES AS NOTED BY CMC 932.5.1: KILNS SHALL BE LOCATED NOT
LESS THAN 18 INCHES FROM A NON-COMBUSTIBLE WALL SURFACE, AND 3
FEET FROM A COMBUSTIBLE WALL SURFACE. IN NO CASE SHALL THE
CLEARANCE ON THE CONTROL SIDE OF THE KILN BE REDUCED TO LESS
THAN 30 INCHES.
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
N
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
A
B
2/
5
/
2
0
2
1
3
:
1
0
:
4
6
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC1.01B
MECHANICAL LEVEL 01
FLOOR PLAN SOUTH
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
1/8" = 1'-0"
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
0 09/11/20 ISSUED FOR
CONSTRUCTION
CD
013 11/23/20 CCD-013 CD
018 12/07/20 CCD-018 DN
016 12/09/20 CCD-016 DN
1 01/22/21 CITY PERMIT
AMENDMENT
CD
2 xx/xx ACOUSTICAL CHANGES DN
RE
F
.
R
E
F
.
DW
RE
F
.
DW
REF.
PC
PC
PC
PC
J
UTILITY NOTES
POWER WIRING TO EQUIPMENT BY ELECTRICIAN
CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER
SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN,
INSTALLED BY ACCO
AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED,
INSTALLED, AND WIRED BY ELECTRICIAN
DSD
ASD
CCCC
1
1
3
3
10
10
16
16
20
20
22
22
25
25
ZZ
YY
V
V
SS
NN
KK
HH
EE
BB
27
27
2
2
4
4
5
5
18
18
DD
FF
GG
AAAA
XX
DDDD
UU
QQ
C
8
8
13
13
19
19
21
21
17
17
11
11
UPPER SCHOOL
SCIENCE LAB
230
PREP ROOM
229A
UPPER SCHOOL
SCIENCE LAB
229
WORKROOM
228
6TH -8TH
CLASSROOM
226
6TH -8TH
CLASSROOM
224
READING ROOM
231
STAIR 2
STR-2-2
6TH -8TH
CLASSROOM
220
6TH -8TH
CLASSROOM
216
6TH -8TH
CLASSROOM
214
STAFF
WORKROOM
208
SYSTEMS ADMIN.
209
UNASSIGNED
210
6TH -8TH
CLASSROOM
219
6TH -8TH
CLASSROOM
217
COLAB
218
COLAB
249
STORAGE
248
ELEV.
E-1-2
CUSTODIAL
242
STAFF TOILET
244
UNISEX TOILET
247
DATA
240
ELECT
241
STAIR 1
STR-1-2
COLAB
211A
5TH GRADE
CLASSROOM
211
STAFF LOUNGE
207
UNASSIGNED
204
UPPER
DIRECTOR
203DEVELOPMENT
DIRECTOR
202
COMMUNICATIONS
DIR.
201
5TH GRADE
CLASSROOM
212
BOYS'
RESTROOM
245
GIRLS'
RESTROOM
246
HALLWAY
250
ROOF DECK
253
GIRLS'
RESTROOM
238
BOYS'
RESTROOM
237
6TH -8TH
CLASSROOM
221
6TH -8TH
CLASSROOM
223
6TH -8TH
CLASSROOM
222
6TH -8TH
CLASSROOM
215
6TH -8TH
CLASSROOM
225
6TH -8TH
CLASSROOM
227
6TH -8TH
CLASSROOM
213
COLAB
254
ROOF DECK
254
OPEN OFFICE
252
HALLWAY
251
HALLWAY
255
FC
A2-5
FC
A2-7
FC
A2-9
FC
A2-12
FC
A2-11
FC
A2-10
FC
A2-4
FC
A2-3
FC
A2-13
FC
A2-14
FC
C2-2
FC
C2-5
FC
C2-4
FC
C2-6
FC
C2-8
FC
C2-9
FC
C2-10
FC
C2-11
FC
C2-13
FC
C2-14
FC
C2-15
FC
C2-16
FC
C2-17
FC
C2-18
FC
C2-19
FC
D2-1
FC
D2-2
FC
D2-3
FC
D2-5
FC
D2-6
FC
C2-20
FC
C2-21
FC
C2-12
FC
C2-7
FC
D2-4
BUSINESS
OFFICE
205
HUMAN
RESOURCES DIR.
206
MOTHER'S ROOM
207A
FC
A2-1
FC
A2-8
SF
2-3
SF
2-1
SF
2-2
FC
A2-6
BS
D-4
SF
2-4EF
2-3
EF
2-4
EF
2-2
FC
C2-3
FC
A2-15
BS
C-4
BS
D-3
BS
C-3
BS
C-2
BS
C-1
BS
A-6
BS
A-5
EF
2-1
FSD
1
FSD
1
ELECT
233 CUSTODIAL
235
ELEV.
E-2-2 UNISEX TOILET
239
STAFF TOILET
236
PP
MM
12
126
6
LL
RR
TT
W
W
24
24
26
26
23
2315
15
14
14
7
7
9
9
BBBB
AA
JJ
FC
A2-2
ELEV. MACHINE
ROOM
243
L
1
L
1
L
1
FSD
1
L
1
(TYP. 3)
(TYP. 3)
L
1
FSD
1
FSD
1
DATA
233B
ELEV. MACH.
ROOM
234
SS
1-2
FSD
1
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
N
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
A
B
2/
5
/
2
0
2
1
3
:
1
1
:
0
2
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC1.02
MECHANICAL LEVEL 02
FLOOR PLAN OVERALL
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
1/16" = 1'-0"
AC1.02A
AC1.02B
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
0 09/11/20 ISSUED FOR
CONSTRUCTION
CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
RE
F
.
R
E
F
.
DW
REF.
PC
PC
UTILITY NOTES
POWER WIRING TO EQUIPMENT BY ELECTRICIAN
CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER
SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN,
INSTALLED BY ACCO
AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED,
INSTALLED, AND WIRED BY ELECTRICIAN
DSD
ASD
1
1
3
3
10
10
16
16
20
20
SS
NN
K
HH
EE
BB
2
2
4
4
5
5
18
18
DD
FF
GG
QQ
C
8
8
13
13
19
19
17
17
11
11
6TH -8TH
CLASSROOM
216
6TH -8TH
CLASSROOM
214
STAFF
WORKROOM
208
SYSTEMS ADMIN.
209
UNASSIGNED
210
6TH -8TH
CLASSROOM
217
COLAB
218
COLAB
249
STORAGE
248
ELEV.
E-1-2
CUSTODIAL
242
STAFF TOILET
244
UNISEX TOILET
247
DATA
240
ELECT
241
STAIR 1
STR-1-2
COLAB
211A
5TH GRADE
CLASSROOM
211
STAFF LOUNGE
207
UNASSIGNED
204
UPPER
DIRECTOR
203
DEVELOPMENT
DIRECTOR
202
COMMUNICATIONS
DIR.
201
5TH GRADE
CLASSROOM
212
BOYS'
RESTROOM
245
GIRLS'
RESTROOM
246
ROOF DECK
253
6TH -8TH
CLASSROOM
215
6TH -8TH
CLASSROOM
213
OPEN OFFICE
252
HALLWAY
251
FC
A2-15
FC
C2-2
FC
A2-3 FC
A2-4
FC
A2-5
FC
A2-7
FC
A2-9
FC
A2-12
FC
A2-11
FC
A2-10
FC
A2-14
FC
A2-13
FC
C2-7
FC
C2-5
FC
C2-4
FC
C2-6
FC
C2-8
FC
C2-10
FC
C2-3
SF
2-1
SF
2-2
SF
2-3
FC
A2-6
FC
A2-1
BS
C-1
EF
2-1
FSD
1
FC
A2-8
BS
A-5
BS
A-6
BS
C-2
FC
C2-9
36"X19" BLDG. RELIEF
LOUVER W/
BAROMETRIC B.D.D.
(TYP. 2, VIF
DIMENSIONS).
1 SQ. FT. TRANSFER AIR
WALL OPENING BY G.C.
(TYP. UNLESS OTHERWISE
NOTED)
12"ø OSA
8"ø OSA
10"ø OSA
6"ø OSA
14"ø OSA
8"ø OSA
8"ø EA
12"ø EA
12"ø EA
EXHAUST FAN TO HAVE
GYPSUM ENCLOSURE BY G.C.1" U.C. DOOR
BY G.C.
12"ø OSA
415 CFM
12"Ø CS1
435 CFM
(TYP. 4)
8"Ø CE1
100 CFM8"Ø CE1
100 CFM10"Ø CE1
300 CFM
10"Ø CE1
300 CFM
10"Ø CS1
200 CFM
(TYP. 4)
FILTER BOX
12"⌀RA
FILTER BOX
10"ø SA8"Ø CS1
200 CFM
(TYP. 4)
10"⌀RA
(TYP. 2)
FILTER BOX
8"Ø CS1
200 CFM
(TYP. 4)
FILTER BOX
10"⌀RA
(TYP. 2)
FILTER BOX
10"⌀RA
(TYP. 2)
FILTER BOX
10"⌀RA
(TYP. 2)
FILTER BOX
8"Ø CS1
200 CFM
(TYP. 4)
10"ø SA
8"Ø CS1
200 CFM
(TYP. 4)
8"Ø CS1
200 CFM
(TYP. 4)
CR1CR1
CR1
CR1
CR1
CR1
CR1
CR1
16"Ø CT2
16"Ø CT2
16"Ø CT1
16"Ø CT1
16"Ø CT1
16"Ø CT1
16"Ø CT1 16"Ø CT1
CR1
CR1
(TYP. 2)
16"Ø CT1
16"Ø CT1
6"⌀OSA
15 CFM
BUSINESS
OFFICE
205
HUMAN
RESOURCES DIR.
206
MOTHER'S ROOM
207A
DURATECH FLUE UP THROUGH ROOF
WITH CHIMNEY CAP. TO BE MIN. 1'-0"
ABOVE ROOF PENETRATION AND MIN.
1'-8" FROM PARAPET. MAINTAIN 2'-0"
SPACING BETWEEN FLUE
DISCHARGES.
SEE DETAIL 10 ON AC5.02 FOR SECTION
VIEW.
12"Ø RA
(TYP. 2)
8"ø SA
(TYP. 4)
6"ø OSA 10"ø OSA
SWG1
12"X6"
150 CFM
PP
MM
12
126
6
L
L
RR
15
15
14
14
7
7
9
9
AA
JJ
10"⌀OSA
310 CFM
10"⌀OSA
310 CFM
10"⌀OSA
310 CFM
10"⌀OSA
310 CFM
10"⌀OSA
310 CFM
10"Ø OSA UP
TO ROOF
255 CFM OSA
10"Ø UP
TO ROOF
195 CFM
OSA
ELEV. MACHINE
ROOM
243
10X10 SOUND BOOT (1" L)
(TYP. 6, SEE DET. 9/AC5.03)
FSD
1
6"⌀OSA
20 CFM 6"⌀OSA
35 CFM
6"⌀OSA
25 CFM
6"⌀OSA
25 CFM
14"ø OSA
FC
A2-2
6"ø OSA
CR1
6"⌀OSA
20 CFM
14"Ø RA
14"Ø RA
CR1
14"ø SA
14"Ø
SA TAP
12"ø OSA
44"x16"
6"⌀OSA
20 CFM
10"ø OSA
10"ø OSA
8"Ø CS1
135 CFM
6"ø OSA
6"Ø CS1
70 CFM
10"ø SA
48"x14"12"Ø SA
10"Ø SA
48"x14"
6"⌀OSA
20 CFM
12"⌀RA
10"Ø SA10"Ø SA
10"ø OSA
12"ø SA
48"x12"
10"ø SA
10"Ø SA
TAP
8"Ø SA
(TYP. 4)
10"Ø SA
TAP
(TYP. 2)
48"x14"
10"ø OSA
16"Ø EA
48"x14"
10"Ø SA
TAP
(TYP. 2)
10"ø SA
8"Ø SA
(TYP. 4)
8"Ø SA
(TYP. 4)
8"Ø SA
(TYP. 4)
6"Ø CS1
135 CFM
6"ø OSA
8"Ø CS1
105 CFM
8"ø EA
SS
1-1
10"Ø SA
TAP
(TYP. 2)
SWG2
16"X16"
29-1/8"X19" BLDG.
RELIEF LOUVER W/
BAROMETRIC B.D.D.
(VIF DIMENSIONS).
10"Ø CS1
200 CFM
(TYP. 4)
FILTER BOX
FILTER BOX
FILTER BOX
FILTER
BOX
8"Ø CS1
125 CFM 925 CFM OSA
6"⌀OSA
20 CFM
310 CFM
OSA
310 CFM
OSA
8"Ø CS1
90 CFM
8"ø OSA
36" x 18"
LOUVER
46" x 18"
LOUVER
46" x 18"
LOUVER
10"Ø CR1
10"Ø CR1
10"Ø CR1
10"Ø CR1
10"Ø CR1
10"Ø CR1
10"Ø CR110"Ø CR110"Ø CR1
10"Ø CR1
10"Ø CR1
10"Ø CR1
10"Ø CR1
16"Ø CT1
16"Ø CT1
ACOUSTICAL WRAP
BY OTHERS.
2
ACOUSTICAL WRAP
BY OTHERS.
2
2
2
2
2
2
2
FSD
1
FSD
1
FSD
1
2
2
10X10 SOUND
BOOT (1" L)
(TYP. 5, SEE
DET. 8/AC5.03)
2
2
16"Ø CT1
2
2
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
N
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
A
B
2/
5
/
2
0
2
1
3
:
1
1
:
0
7
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC1.02A
MECHANICAL LEVEL 02
FLOOR PLAN NORTH
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
1/8" = 1'-0"
AC1.02A
AC1.02B
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
0 09/11/20 ISSUED FOR
CONSTRUCTION
CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
2 xx/xx ACOUSTICAL CHANGES DN
RE
F
.
DW
PC
PC
J
UTILITY NOTES
POWER WIRING TO EQUIPMENT BY ELECTRICIAN
CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER
SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN,
INSTALLED BY ACCO
AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED,
INSTALLED, AND WIRED BY ELECTRICIAN
DSD
ASD
CCCC
1
1
3
3
10
10
16
16
20
20
22
22
25
25
ZZ
YY
VV
SS
27
27
2
2
4
4
5
5
18
18
AAAA
XX
DDDD
UU
8
8
13
13
19
19
21
21
17
17
11
11
UPPER SCHOOL
SCIENCE LAB
230
PREP ROOM
229A
UPPER SCHOOL
SCIENCE LAB
229
WORKROOM
228
6TH -8TH
CLASSROOM
226
6TH -8TH
CLASSROOM
224
READING ROOM
231
STAIR 2
STR-2-2
6TH -8TH
CLASSROOM
220
6TH -8TH
CLASSROOM
219
COLAB
218
HALLWAY
250
ROOF DECK
253
GIRLS'
RESTROOM
238
BOYS'
RESTROOM
237
6TH -8TH
CLASSROOM
221
6TH -8TH
CLASSROOM
223
6TH -8TH
CLASSROOM
222
6TH -8TH
CLASSROOM
225
6TH -8TH
CLASSROOM
227
COLAB
254
ROOF DECK
254
HALLWAY
255
FC
C2-13
FC
C2-14
FC
C2-15
FC
C2-16
FC
C2-17
FC
C2-18
FC
C2-19 FC
D2-1
FC
D2-2
FC
D2-4
FC
D2-6
FC
C2-21
FC
C2-20
FC
C2-12
BS
C-3
BS
C-4
EF
2-2
BS
D-4
FC
D2-3 FC
D2-5
EF
2-4
SF
2-4
EF
2-3
BS
D-3
FC
C2-11
36"X19" BLDG.
RELIEF LOUVER W/
BAROMETRIC B.D.D.
(TYP. 2, VIF
DIMENSIONS).
1 SQ. FT. TRANSFER AIR
WALL OPENING
(TYP. UNLESS
OTHERWISE NOTED)
FSD
1
6"ø OSA
EXHAUST FAN TO
HAVE GYPSUM
ENCLOSURE BY G.C.
10"ø EA
EXHAUST FAN TO
HAVE GYPSUM
ENCLOSURE BY G.C.
EXHAUST FAN TO
HAVE GYPSUM
ENCLOSURE BY G.C.
1" U.C. DOOR
BY G.C.
8"Ø CE1
100 CFM
10"Ø CE1
300 CFM
10"Ø CE1
300 CFM
22"x22" CE2
1290 CFM
22"x22" CE2
1290 CFM
8"Ø CS1
200 CFM
(TYP. 4)
FILTER BOX
10"⌀RA
(TYP. 2)
FILTER BOX
10"⌀RA
(TYP. 2)
10"ø SA
8"Ø CS1
200 CFM
(TYP. 4)
8"Ø CS1
200 CFM
(TYP. 4)
FILTER BOX
10"⌀RA
(TYP. 2)
8"Ø CS1
200 CFM
(TYP. 4)
FILTER BOX
10"⌀RA
(TYP. 2)
8"Ø CS1
200 CFM
(TYP. 4)
FILTER BOX
10"⌀RA
(TYP. 2)
8"Ø CS1
200 CFM
(TYP. 4)
FILTER BOX
10"⌀RA (TYP. 2)
8"Ø CS1
200 CFM
(TYP. 4)
FILTER
BOX
10"⌀RA
(TYP. 2)
FILTER
BOX
10"⌀RA
(TYP. 2)
8"Ø CS1
200 CFM
(TYP. 4)
FILTER
BOX
10"⌀RA
(TYP. 2)
12"ø SA
12"Ø CS1
365 CFM
(TYP. 4)
FILTER BOX
12"⌀RA (TYP. 2)
8"Ø CS1
295 CFM
(TYP. 6)
8"ø SA
8"ø SA
FILTER BOX
12"⌀RA
(TYP. 2)
8"ø SA
8"Ø CS1
295 CFM
(TYP. 6)
FILTER BOX
12"⌀RA
(TYP. 2)
CR1
CR1
CR1
CR1
CR1
CR1 CR1 CR1
CR1
CR1
CR1 CR1
CT1
CT1
CT1
CT1
16"ø
16"ø
10"Ø CT1
16"Ø CT116"Ø CT1
16"Ø CT1
16"Ø CT1
16"Ø CT1
5 SQ. FT. TRANSFER AIR
WALL OPENING BY G.C.
AC1.02A
AC1.02B
ELECT
233
ELEV.
E-2-2
STAFF TOILET
236
SWG1
16"X4"
140 CFM10"ø EA
FSD
1
FSD
1
8"Ø CE1
100 CFM
12"ø EA
10"ø SA
10"ø SA
10"ø SA
8"ø SA 8"ø SA
8"ø SA
10"ø SA
8"Ø CS1
200 CFM
(TYP. 4)
8"ø SA 12"ø SA8"ø SA 12"ø SA
12
126
6
TT
WW
24
24
26
26
23
2315
15
14
14
7
7
9
9
BBBB
10"⌀OSA
310 CFM
10"⌀OSA
310 CFM
10"⌀OSA
310 CFM
10"⌀OSA
310 CFM
10"⌀OSA
310 CFM
10"⌀OSA
310 CFM
10"⌀OSA
230 CFM
10"⌀OSA
230 CFM
10"⌀OSA
225 CFM
10"⌀OSA 350 CFM
18"⌀UP
16"⌀OSA
660 CFM
16"⌀OSA
610 CFM
16"⌀UP
DATA
233B
ELEV. MACH.
ROOM
234
UNISEX TOILET
239
CUSTODIAL
235
8"ø SA
(TYP. 4)
10"Ø SA TAP
(TYP. 2)
48"x14"
8"ø SA
(TYP. 4)
48"x14"
48"x14"
8"Ø SA
(TYP. 4)
10"Ø SA
TAP
10"Ø SA
16"Ø SA
8"ø SA
CR1
(TYP. 2)
10"Ø SA
16"Ø SA
48"x12"
8"ø SA
(TYP. 4)
10"⌀SA
TAP
(TYP. 2)
48"x12"48"x12"48"x12"
8"ø SA
(TYP. 4)
10"⌀SA
TAP
(TYP. 2)10"⌀SA
TAP
(TYP. 2)
8"ø SA
(TYP. 4)
6"Ø CS1
120 CFM
10"⌀SA
TAP
(TYP. 2)
8"ø SA
(TYP. 4)
48"x16"
8"ø SA
12"Ø SA TAP
8"ø SA
12"ø SA
10"⌀UP TO ROOF
270 CFM OSA
8"Ø CS1
135 CFM 12"⌀SA TAP
8"ø SA
18"ø SA
14"ø SA
12"ø SA
10"ø
16"⌀UP
SS
1-2
35-1/4"X19" BLDG.
RELIEF LOUVER
W/ BAROMETRIC
B.D.D.
(VIF DIMENSIONS).
FILTER BOX
FSD
1
8"Ø CS1
135 CFM
14"x6"10"x6"
10"Ø CR1
10"Ø CR1
10"Ø CR1
ACOUSTICAL
WRAP BY OTHERS.
2
ACOUSTICAL
WRAP BY
OTHERS.
2
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
N
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
A
B
2/
5
/
2
0
2
1
3
:
1
1
:
1
2
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC1.02B
MECHANICAL LEVEL 02
FLOOR PLAN SOUTH
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
1/8" = 1'-0"
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
0 09/11/20 ISSUED FOR
CONSTRUCTION
CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
2 xx/xx ACOUSTICAL CHANGES DN
CCCC
1
1
3
3
10
10
16
16
20
20
22
22
25
25
ZZ
YY
V
V
SS
NN
KK
HH
EE
BB
27
27
2
2
4
4
5
5
18
18
DD
FF
GG
AAAA
XX
DDDD
UU
QQ
C
8
8
13
13
19
19
21
21
17
17
11
11
PP
MM
12
126
6
LL
RR
TT
W
W
24
24
26
26
23
2315
15
14
14
7
7
9
9
BBBB
AA
JJ
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
GV
2
GV
1
GV
2
GV
1
GV
3
GV
1
GV
1
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
N
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
A
B
1/16" = 1'-0"
2/
5
/
2
0
2
1
3
:
1
1
:
1
4
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC1.03
MECHANICAL ROOF FLOOR
PLAN OVERALL
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
AC1.03A
AC1.03B
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
1
1
3
3
10
10
16
16
20
20
SS
NN
K
HH
EE
BB
2
2
4
4
5
5
18
18
DD
FF
GG
QQ
C
8
8
13
13
19
19
17
17
11
11
PP
MM
12
126
6
L
L
RR
15
15
14
14
7
7
9
9
AA
JJ
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
MIN. 10'-0" FROM EXHAUST
OR VENT (TYP. 2)
MIN. 10'-0" FROM EXHAUST
OR VENT
MIN. 10'-0" FROM EXHAUST
OR VENT
MIN. 10'-0" FROM EXHAUST
OR VENT (TYP. 3)
GV
1
300 CFM OSA
195 CFM OSA 950 CFM EA
300 CFM OSA
MIN. 10'-0" FROM OSA
INTAKE
300 CFM OSA
300 CFM OSA
300 CFM OSA
300 CFM OSA
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
N
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
A
B
1/8" = 1'-0"
2/
5
/
2
0
2
1
3
:
1
1
:
1
7
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC1.03A
MECHANICAL ROOF FLOOR
PLAN NORTH
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
AC1.03A
AC1.03B
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
CCCC
1
1
3
3
10
10
16
16
20
20
22
22
25
25
ZZ
YY
VV
SS
27
27
2
2
4
4
5
5
18
18
AAAA
XX
DDDD
UU
8
8
13
13
19
19
21
21
17
17
11
11 12
126
6
TT
WW
24
24
26
26
23
2315
15
14
14
7
7
9
9
BBBB
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
GV
3
GV
2
GV
1
GV
1
GV
2
MIN. 10'-0" FROM OSA
INTAKE
MIN. 10'-0" FROM
EXHAUST OR VENT
MIN. 10'-0" FROM
OSA INTAKE
MIN. 10'-0" FROM
EXHAUST OR VENTMIN. 10'-0" FROM
EXHAUST OR VENT
MIN. 10'-0" FROM
EXHAUST OR VENT
MIN. 10'-0" FROM
EXHAUST OR VENT
MIN. 10'-0" FROM
EXHAUST OR VENT
MIN. 10'-0" FROM
EXHAUST OR VENT
300 CFM OSA
300 CFM OSA
300 CFM OSA
300 CFM OSA
300 CFM OSA
GV
1
1035 CFM EA
MIN. 10'-0" FROM
OSA INTAKE
300 CFM OSA 230 CFM OSA 230 CFM OSA 225 CFM OSA
330 CFM OSA
1,290 CFM EA
GV
3
270 CFM OSA660 CFM OSA
610 CFM OSA
1,290 CFM EA
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
N
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
A
B
1/8" = 1'-0"
2/
5
/
2
0
2
1
3
:
1
1
:
1
9
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC1.03B
MECHANICAL ROOF FLOOR
PLAN SOUTH
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
AC1.03A
AC1.03B
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
J
J
J
J
J
J
J
J
CCCC
1
1
3
3
10
10
16
16
20
20
22
22
25
25
ZZ
YY
V
V
SS
NN
KK
HH
EE
BB
27
27
2
2
4
4
5
5
18
18
DD
FF
GG
AAAA
XX
DDDD
UU
QQ
C
8
8
13
13
19
19
21
21
17
17
11
11
OFFICE
124A
4TH GRADE
CLASSROOM
120
3RD GRADE
CLASSROOM
118
SMALL GROUP
119A
4TH GRADE
CLASSROOM
119
LOWER SCHOOL
SCIENCE
CLASSROOM
122
WORLD
LANGUAGE
CLASSROOM
121
CERAMICS
125A
KILN
125B
UPPER SCHOOL
ART LAB
125
1ST GRADE
CLASSROOM
112
SMALL GROUP
113
2ND GRADE
CLASSROOM
115
1ST GRADE
CLASSROOM
114
SMALL GROUP
115A
TEACHING AREA
131B
WORKROOM
131A
ELEV.
E-1-1
ELECT.
110
DATA
109
CONFERENCE
ROOM
107
ASSOCIATES
134
PSYCH.
137A
SMALL GROUP
AREA
137
2ND GRADE
CLASSROOM
116
SMALL GROUP
117A
3RD GRADE
CLASSROOM
117
LANGUAGE ARTS
SPECIALIST
137B
CUSTODIAL
136
STAIR 1
STR1-1
NURSE
101
ELECTRICAL
163
STAFF TOILET
145
UNISEX TOILET
142
STAIR 2
STR2-1
LOBBY
100
GIRLS'
RESTROOM
140
BOYS'
RESTROOM
139
GIRLS'
RESTROOM
143
BOYS'
RESTROOM
144
WORKROOM
106
FACILITIES DIR.
105
HEAD OF
SCHOOL
104
HALLWAY
161
LIBRARY
131
TINKER AREA
133
STORY TELLING
132
MATH
SPECIALIST
137C
MAKER SPACE
123
LOWER SCHOOL
ART LAB
126
OPEN OFFICE
159HALLWAY
160
HALLWAY
162
?
?
FC
B1-2
FC
A1-1
FC
A1-5
FC
A1-7
FC
A1-4
FC
B1-1
FC
B1-5
FC
B1-6
FC
B1-7
FC
A1-12
FC
A1-11
FC
A1-10
FC
A1-9
FC
A1-8
FC
A1-14
FC
A1-13
FC
A1-16
FC
A1-17
FC
A1-15
FC
A1-19 FC
A1-18B
FC
B1-9
FC
B1-8
FC
B1-10
FC
B1-11
FC
B1-12
FC
B1-13
FC
B1-14
FC
A1-20
FC
A1-21
FC
B1-19
FC
B1-20
FC
D1-1
FC
D1-3
FC
D1-8
FC
D1-7
FC
B1-17FC
B1-16
FC
B1-15
FC
D1-5
FC
B1-4
FC
A1-3
SF
1-1
BS
A1
BS
A-3
BS
A-4
SF
1-2
BS
B-1
BS
B-2
BS
B-3
FC
D1-4
BS
D-2 BS
D-1
FC
A1-6
FC
A1-2
NORMALWEIGHT
CONCRETE PAD
BY G.C. SEE
DETAIL 5/AC5.02
14"X46" PAD
OPENING
6" PVC
MIN. 12" U.G.
12" PVC
MIN. 12" U.G.
(TYP. 2)
14"X46" PAD
OPENING
6" PVC
MIN. 12" U.G.
12" PVC
MIN. 12" U.G.
(TYP. 2)
EF
1-5
EF
1-6
EF
1-8
EF
1-4
EF
1-2
EF
1-1
NORMALWEIGHT
CONCRETE PAD BY G.C.
SEE DETAIL 5/AC5.02
FC
A1-18A
TOILET
111A
TOILET
108A
WORK ROOM
108C
STOR.
111B
KINDERGARTEN
108
KINDERGARTEN
111
STOR.
108B
ADMISSIONS DIR.
100A
TOILET
101A
TECH LAB
123A
DESIGN CENTER
124
TOILET
100B
LOWER DIR.
102
CUSTODIAN
151
UNISEX TOILET
152
STAFF TOILET
153
PP
MM
12
126
6
LL
RR
TT
W
W
24
24
26
26
23
2315
15
14
14
7
7
9
9
BBBB
AA
JJ
TECHNOLOGY
DIRECTOR
103
BS
A2
FC
B1-3
FC
B1-18
ELECT.
146
DATA
147
FC
D1-6
FC
D1-9
EF
1-3
CU
1
CU
A
CU
B
(180 LBS.)
(1,325 LBS.)
(1,325 LBS.)
(1,664 LBS.)
CU
2
(180 LBS.)
CU
D
CU
C
(1,305 LBS.)
SF
1-3
UTILITY NOTES
POWER WIRING TO EQUIPMENT BY ELECTRICIAN
CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER
SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN,
INSTALLED BY ACCO
AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED,
INSTALLED, AND WIRED BY ELECTRICIAN
DSD
ASD
SHEET NOTES
1. FOR VRF PIPING FROM CONDENSING UNITS TO HEAT RECOVERY UNITS:
L -LIQUID
HV -HIGH VAPOR
LV -LOW VAPOR
2. FOR VRF PIPING FROM HEAT RECOVERY UNITS TO FAN COILS:
L -LIQUID
V -VAPOR
3. MIN. 20" OF STRAIGHT PIPE INTO FAN COIL UNITS
4. REFER TO SHEETS AC6.01 & AC6.02 FOR VRF PIPING DIAGRAMS.
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
N
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
A
B
2/
5
/
2
0
2
1
3
:
1
1
:
2
9
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC2.01
MECHANICAL PIPING
LEVEL 01 FLOOR PLAN
OVERALL
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
1/16" = 1'-0"
AC2.01A
AC2.01B
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
0 09/11/20 ISSUED FOR
CONSTRUCTION
CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
J
J
J
J
J
J
1
1
3
3
10
10
16
16
20
20
SS
NN
K
HH
EE
BB
2
2
4
4
5
5
18
18
DD
FF
GG
QQ
C
8
8
13
13
19
19
17
17
11
11
1ST GRADE
CLASSROOM
112
SMALL GROUP
113
2ND GRADE
CLASSROOM
115
1ST GRADE
CLASSROOM
114
SMALL GROUP
115A
ELEV.
E-1-1
ELECT.
110
DATA
109
CONFERENCE
ROOM
107
ASSOCIATES
134
PSYCH.
137A
SMALL GROUP
AREA
137
2ND GRADE
CLASSROOM
116
LANGUAGE ARTS
SPECIALIST
137B
CUSTODIAL
136
STAIR 1
STR1-1
ELECTRICAL
163
STAFF TOILET
145
UNISEX TOILET
142
LOBBY
100
GIRLS'
RESTROOM
143
BOYS'
RESTROOM
144
WORKROOM
106
FACILITIES DIR.
105
LOWER DIR.
102
TECHNOLOGY
DIRECTOR
103
HEAD OF
SCHOOL
104
LIBRARY
131
TINKER AREA
133
STORY TELLING
132
MATH
SPECIALIST
137C
OPEN OFFICE
159
HALLWAY
160
FC
A1-1
FC
A1-3
FC
A1-4
FC
A1-5
FC
A1-7
FC
A1-8
FC
A1-9
FC
A1-10
FC
A1-11
FC
A1-12
FC
B1-1
FC
B1-4
FC
B1-2
FC
B1-5
FC
B1-6
FC
B1-7
FC
A1-15
FC
A1-14
FC
A1-13
FC
A1-16
FC
A1-17
FC
B1-8
FC
B1-9
FC
B1-10
FC
A1-19
NURSE
101
TOILET
111A
TOILET
108A
WORK ROOM
108C
STOR.
111B
KINDERGARTEN
108
KINDERGARTEN
111
STOR.
108B
ADMISSIONS DIR.
100ATOILET
101A
TOILET
100B
FC
A1-2
EF
1-1
SF
1-1
FC
A1-6
EF
1-2
BS
A2
BS
A1
SF
1-2
FC
A1-18B
BS
A-3
BS
B-1
FC
B1-3
FC
A1-18A
PP
MM
12
126
6
L
L
RR
15
15
14
14
7
7
9
9
AA
JJ
VRF PIPING
UP TO 2ND
FLOOR
VRF PIPING
UP TO 2ND
FLOOR
MAINTAIN MINIMUM
45'-0" EQUIVALENT
PIPE LENGTH
BETWEEN BRANCH
SELECTOR BOX A-3
& ANY ASSOCIATED
FAN COIL UNIT
MAINTAIN MINIMUM 45'-0" EQUIVALENT
PIPE LENGTH BETWEEN BRANCH
SELECTOR BOX A-3 & ANY ASSOCIATED
FAN COIL UNIT
MAINTAIN MINIMUM
45'-0" EQUIVALENT
PIPE LENGTH
BETWEEN BRANCH
SELECTOR BOX A-3
& ANY ASSOCIATED
FAN COIL UNIT
UTILITY NOTES
POWER WIRING TO EQUIPMENT BY ELECTRICIAN
CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER
SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN,
INSTALLED BY ACCO
AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED,
INSTALLED, AND WIRED BY ELECTRICIAN
DSD
ASD
SHEET NOTES
1. FOR VRF PIPING FROM CONDENSING UNITS TO HEAT RECOVERY UNITS:
L -LIQUID
HV -HIGH VAPOR
LV -LOW VAPOR
2. FOR VRF PIPING FROM HEAT RECOVERY UNITS TO FAN COILS:
L -LIQUID
V -VAPOR
3. MIN. 20" OF STRAIGHT PIPE INTO FAN COIL UNITS
4. REFER TO SHEETS AC6.01 & AC6.02 FOR VRF PIPING DIAGRAMS.
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
N
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
A
B
2/
5
/
2
0
2
1
3
:
1
1
:
3
5
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC2.01A
MECHANICAL PIPING
LEVEL 01 FLOOR PLAN
NORTH
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
1/8" = 1'-0"
AC2.01A
AC2.01B
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
0 09/11/20 ISSUED FOR
CONSTRUCTION
CD
017 11/30/20 CCD-017 DN
1 01/22/21 CITY PERMIT
AMENDMENT
CD
J
J
CCCC
1
1
3
3
10
10
16
16
20
20
22
22
25
25
ZZ
YY
VV
SS
27
27
2
2
4
4
5
5
18
18
AAAA
XX
DDDD
UU
8
8
13
13
19
19
21
21
17
17
11
11
OFFICE
124A
?
?
4TH GRADE
CLASSROOM
120
3RD GRADE
CLASSROOM
118
SMALL GROUP
119A
4TH GRADE
CLASSROOM
119
LOWER SCHOOL
SCIENCE
CLASSROOM
122
WORLD
LANGUAGE
CLASSROOM
121
CERAMICS
125A
KILN
125B
UPPER SCHOOL
ART LAB
125
TEACHING AREA
131B
WORKROOM
131A
SMALL GROUP
117A
3RD GRADE
CLASSROOM
117
STAIR 2
STR2-1
GIRLS'
RESTROOM
140
BOYS'
RESTROOM
139
HALLWAY
161
LIBRARY
131
TINKER AREA
133
MAKER SPACE
123
LOWER SCHOOL
ART LAB
126
HALLWAY
162
?
?
FC
B1-11FC
B1-12
FC
B1-13
FC
B1-15
FC
B1-16
FC
B1-17
FC
B1-19
FC
B1-20
FC
A1-20
FC
A1-21
FC
A1-18B
FC
A1-19
FC
D1-1
FC
D1-3
FC
D1-6
FC
D1-7
FC
D1-8
FC
D1-5
BS
B-2
FC
B1-13 BS
A-4
FC
B1-14
BS
B-3
BS
D-2
BS
D-1
EF
1-8
EF
1-6
FC
D1-4
EF
1-5
EF
1-4
TECH LAB
123A
DESIGN CENTER
124
STAFF TOILET
153ELECT.
146
CUSTODIAN
151
UNISEX TOILET
152
ELEV.
E-2-1
CORRIDOR
154
12
126
6
TT
WW
24
24
26
26
23
2315
15
14
14
7
7
9
9
BBBB
VRF PIPING
UP TO 2ND
FLOOR
VRF PIPING
UP TO 2ND
FLOOR
FC
D1-9
FC
B1-18
DATA
147
EF
1-3
SF
1-3
UTILITY NOTES
POWER WIRING TO EQUIPMENT BY ELECTRICIAN
CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER
SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN,
INSTALLED BY ACCO
AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED,
INSTALLED, AND WIRED BY ELECTRICIAN
DSD
ASD
SHEET NOTES
1. FOR VRF PIPING FROM CONDENSING UNITS TO HEAT RECOVERY UNITS:
L -LIQUID
HV -HIGH VAPOR
LV -LOW VAPOR
2. FOR VRF PIPING FROM HEAT RECOVERY UNITS TO FAN COILS:
L -LIQUID
V -VAPOR
3. MIN. 20" OF STRAIGHT PIPE INTO FAN COIL UNITS
4. REFER TO SHEETS AC6.01 & AC6.02 FOR VRF PIPING DIAGRAMS.
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
N
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
A
B
2/
5
/
2
0
2
1
3
:
1
1
:
4
0
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC2.01B
MECHANICAL PIPING
LEVEL 01 FLOOR PLAN
SOUTH
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
1/8" = 1'-0"
AC2.01A
AC2.01B
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
018 12/07/20 CCD-018 DN
1 01/22/21 CITY PERMIT
AMENDMENT
CD
DW
DW
TD TDTDTDTDTDTD
TDTDTDTDTDTDTDTDTDTDTDTD
TD TD TD
TD
TD
J
CCCC
1
1
3
3
10
10
16
16
20
20
22
22
25
25
ZZ
YY
V
V
SS
NN
KK
HH
EE
BB
27
27
2
2
4
4
5
5
18
18
DD
FF
GG
AAAA
XX
DDDD
UU
QQ
C
8
8
13
13
19
19
21
21
17
17
11
11
UPPER SCHOOL
SCIENCE LAB
230PREP ROOM
229A
UPPER SCHOOL
SCIENCE LAB
229
WORKROOM
228
6TH -8TH
CLASSROOM
226
6TH -8TH
CLASSROOM
224
READING ROOM
231
STAIR 2
STR-2-2
6TH -8TH
CLASSROOM
220
6TH -8TH
CLASSROOM
216
6TH -8TH
CLASSROOM
214
STAFF
WORKROOM
208
6TH -8TH
CLASSROOM
219
6TH -8TH
CLASSROOM
217
COLAB
218
COLAB
249
STORAGE
248
ELEV.
E-1-2
CUSTODIAL
242
STAFF TOILET
244
UNISEX TOILET
247
DATA
240
ELECT
241
STAIR 1
STR-1-2
COLAB
211A
5TH GRADE
CLASSROOM
211
STAFF LOUNGE
207
UNASSIGNED
204
UPPER
DIRECTOR
203
DEVELOPMENT
DIRECTOR
202
COMMUNICATIONS
DIR.
201
5TH GRADE
CLASSROOM
212
BOYS'
RESTROOM
245
GIRLS'
RESTROOM
246
HALLWAY
250
ROOF DECK
253
GIRLS'
RESTROOM
238
BOYS'
RESTROOM
237
6TH -8TH
CLASSROOM
221
6TH -8TH
CLASSROOM
223
6TH -8TH
CLASSROOM
222
6TH -8TH
CLASSROOM
215
6TH -8TH
CLASSROOM
225
6TH -8TH
CLASSROOM
227
6TH -8TH
CLASSROOM
213
COLAB
254
ROOF DECK
254
OPEN OFFICE
252
HALLWAY
251
HALLWAY
255
FC
A2-3
FC
A2-4
FC
A2-5
FC
A2-7
FC
A2-14
FC
A2-13
FC
C2-2
FC
A2-15
FC
C2-3
FC
A2-10
FC
A2-11
FC
A2-12
FC
A2-9
FC
C2-7
FC
C2-4
FC
C2-5
FC
C2-6
FC
C2-8
FC
C2-9
FC
C2-10
FC
C2-11
FC
C2-12
FC
C2-14
FC
C2-13
FC
C2-15
FC
C2-16
FC
C2-17
FC
C2-18
FC
C2-19
FC
C2-20
FC
C2-21
FC
D2-1
FC
D2-2
FC
D2-3
FC
D2-5
FC
D2-4
FC
D2-6
SF
2-1
SF
2-2
SF
2-3
SF
2-4
FC
A2-1
FC
A2-6
FC
A2-8
BS
A-5
BS
A-6
BS
D-4
BS
C-1
BS
C-2
BS
C-3 BS
C-4
BS
D-3
EF
2-1
EF
2-2
EF
2-3
EF
2-4
ELECT
233 CUSTODIAL
235
ELEV.
E-2-2
SYSTEMS ADMIN.
209
UNASSIGNED
210
UNISEX TOILET
239
STAFF TOILET
236
BUSINESS
OFFICE
205
HUMAN
RESOURCES DIR.
206
MOTHER'S ROOM
207A
ELEV. MACHINE
ROOM
243
PP
MM
12
126
6
LL
RR
TT
W
W
24
24
26
26
23
2315
15
14
14
7
7
9
9
BBBB
AA
JJ
FC
A2-2
DATA
233B
ELEV. MACH.
ROOM
234
SS
1-2
SS
1-1
UTILITY NOTES
POWER WIRING TO EQUIPMENT BY ELECTRICIAN
CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER
SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN,
INSTALLED BY ACCO
AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED,
INSTALLED, AND WIRED BY ELECTRICIAN
DSD
ASD
SHEET NOTES
1. FOR VRF PIPING FROM CONDENSING UNITS TO HEAT RECOVERY UNITS:
L -LIQUID
HV -HIGH VAPOR
LV -LOW VAPOR
2. FOR VRF PIPING FROM HEAT RECOVERY UNITS TO FAN COILS:
L -LIQUID
V -VAPOR
3. MIN. 20" OF STRAIGHT PIPE INTO FAN COIL UNITS
4. REFER TO SHEETS AC6.01 & AC6.02 FOR VRF PIPING DIAGRAMS.
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
N
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
A
B
2/
5
/
2
0
2
1
3
:
1
1
:
4
9
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC2.02
MECHANICAL PIPING
LEVEL 02 FLOOR PLAN
OVERALL
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
1/16" = 1'-0"
AC2.02A
AC2.02B
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
DW
1
1
3
3
10
10
16
16
20
20
SS
NN
K
HH
EE
BB
2
2
4
4
5
5
18
18
DD
FF
GG
QQ
C
8
8
13
13
19
19
17
17
11
11
6TH -8TH
CLASSROOM
216
6TH -8TH
CLASSROOM
214
STAFF
WORKROOM
208
SYSTEMS ADMIN.
209
UNASSIGNED
210
6TH -8TH
CLASSROOM
219
6TH -8TH
CLASSROOM
217
COLAB
218
COLAB
249
STORAGE
248
ELEV.
E-1-2
CUSTODIAL
242
STAFF TOILET
244
UNISEX TOILET
247
DATA
240
ELECT
241
STAIR 1
STR-1-2
COLAB
211A
5TH GRADE
CLASSROOM
211
STAFF LOUNGE
207
UNASSIGNED
204
UPPER
DIRECTOR
203
DEVELOPMENT
DIRECTOR
202
COMMUNICATIONS
DIR.
201
5TH GRADE
CLASSROOM
212
BOYS'
RESTROOM
245
GIRLS'
RESTROOM
246
HALLWAY
250
ROOF DECK
253
6TH -8TH
CLASSROOM
215
6TH -8TH
CLASSROOM
213
COLAB
254
OPEN OFFICE
252
HALLWAY
251
FC
A2-15
FC
A2-3
FC
A2-4
FC
A2-5
FC
A2-7
FC
A2-9
FC
A2-14
FC
A2-13
FC
C2-2
FC
C2-3
FC
C2-4
FC
C2-5
FC
C2-7
FC
C2-6
FC
C2-8
FC
C2-10
FC
A2-10
FC
A2-11
FC
A2-12
SF
2-1
BS
A-5
BS
A-6
EF
2-1
SF
2-2
SF
2-3
BS
C-2
FC
C2-9
BS
C-1
FC
A2-1
FC
A2-6
FC
A2-8
MATCH LINE
SEE SHEET -AC2.02B
BUSINESS
OFFICE
205
MOTHER'S ROOM
207A
HUMAN
RESOURCES DIR.
206
ELEV. MACHINE
ROOM
243
PP
MM
12
126
6
L
L
RR
15
15
14
14
7
7
9
9
AA
JJ
VRF PIPING DN
TO 1ST FLOOR
FC
A2-2
SS
1-1
VRF PIPING
DN TO 1ST
FLOOR
UTILITY NOTES
POWER WIRING TO EQUIPMENT BY ELECTRICIAN
CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER
SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN,
INSTALLED BY ACCO
AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED,
INSTALLED, AND WIRED BY ELECTRICIAN
DSD
ASD
SHEET NOTES
1. FOR VRF PIPING FROM CONDENSING UNITS TO HEAT RECOVERY UNITS:
L -LIQUID
HV -HIGH VAPOR
LV -LOW VAPOR
2. FOR VRF PIPING FROM HEAT RECOVERY UNITS TO FAN COILS:
L -LIQUID
V -VAPOR
3. MIN. 20" OF STRAIGHT PIPE INTO FAN COIL UNITS
4. REFER TO SHEETS AC6.01 & AC6.02 FOR VRF PIPING DIAGRAMS.
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
N
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
A
B
2/
5
/
2
0
2
1
3
:
1
1
:
5
5
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC2.02A
MECHANICAL PIPING
LEVEL 02 FLOOR PLAN
NORTH
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
1/8" = 1'-0"
AC2.02A
AC2.02B
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
DW
J
CCCC
1
1
3
3
10
10
16
16
20
20
22
22
25
25
ZZ
YY
VV
SS
27
27
2
2
4
4
5
5
18
18
AAAA
XX
DDDD
UU
8
8
13
13
19
19
21
21
17
17
11
11
UPPER SCHOOL
SCIENCE LAB
230
PREP ROOM
229A
UPPER SCHOOL
SCIENCE LAB
229
WORKROOM
228
6TH -8TH
CLASSROOM
226
6TH -8TH
CLASSROOM
224
READING ROOM
231
STAIR 2
STR-2-2
6TH -8TH
CLASSROOM
220
6TH -8TH
CLASSROOM
219
COLAB
218
HALLWAY
250
ROOF DECK
253
GIRLS'
RESTROOM
238
BOYS'
RESTROOM
237
6TH -8TH
CLASSROOM
221
6TH -8TH
CLASSROOM
223
6TH -8TH
CLASSROOM
222
6TH -8TH
CLASSROOM
225
6TH -8TH
CLASSROOM
227
COLAB
254
ROOF DECK
254
HALLWAY
255
FC
C2-11
FC
C2-13
FC
C2-12
FC
C2-14
FC
C2-15
FC
C2-20
FC
D2-6
FC
D2-2
FC
D2-1
FC
C2-19
FC
C2-18
FC
C2-17FC
C2-16
FC
D2-3
FC
D2-4
FC
D2-5
BS
C-3
BS
C-4
EF
2-2
EF
2-3
EF
2-4
BS
D-4
BS
D-3
ELECT
233
CUSTODIAL
235
ELEV.
E-2-2
UNISEX TOILET
239
STAFF TOILET
236
12
126
6
TT
WW
24
24
26
26
23
2315
15
14
14
7
7
9
9
BBBB
VRF PIPING
DN TO 1ST
FLOOR
VRF PIPING DN
TO 1ST FLOOR
ELEV. MACH.
ROOM
234DATA
233B
FC
C2-21
SS
1-2
SF
2-4
UTILITY NOTES
POWER WIRING TO EQUIPMENT BY ELECTRICIAN
CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER
SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN,
INSTALLED BY ACCO
AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED,
INSTALLED, AND WIRED BY ELECTRICIAN
DSD
ASD
SHEET NOTES
1. FOR VRF PIPING FROM CONDENSING UNITS TO HEAT RECOVERY UNITS:
L -LIQUID
HV -HIGH VAPOR
LV -LOW VAPOR
2. FOR VRF PIPING FROM HEAT RECOVERY UNITS TO FAN COILS:
L -LIQUID
V -VAPOR
3. MIN. 20" OF STRAIGHT PIPE INTO FAN COIL UNITS
4. REFER TO SHEETS AC6.01 & AC6.02 FOR VRF PIPING DIAGRAMS.
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
N
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
A
B
2/
5
/
2
0
2
1
3
:
1
2
:
0
0
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC2.02B
MECHANICAL PIPING
LEVEL 02 FLOOR PLAN
SOUTH
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
1/8" = 1'-0"
AC2.02A
AC2.02B
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
2/
5
/
2
0
2
1
3
:
1
2
:
0
0
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC4.01
MECHANICAL ENLARGED
PLANS
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
1/4" = 1'-0"
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
016 12/09/20 CCD-016 DN
1 01/22/21 CITY PERMIT
AMENDMENT
CD
MAX 12"
HEIGHT
1" MINIMUM
(CPC 801.2)
SS
-
FC
-
91011
5678
4 3 2 1
RECTANGULAR DUCT ROUND DUCT
CONDENSATE TRAP DETAIL
CONCEALED REFRIG. PIPING HANGING DETAILEXPOSED REFRIG. PIPING HANGING DETAILDUCT HANGING DETAILDIFFUSER HANGING DETAIL
INLINE EXHAUST FAN HANGING DETAIL WALL MOUNTED FAN COIL DETAIL HANGING VRF FAN COIL ATTACHMENT DETAIL CONDENSING UNIT MOUNTING DETAIL
FOR DUCTS
OVER 20"
DEEP ONLY
#10 TEK
SCREW
(TYP.)
FOR DUCTS
OVER 12"
DEEP ONLY
#10 TEK SCREW
(TYP.)
SEE DETAIL
9 FOR
UPPER
ATTACHMENTS
1/2" MIN.
1" MAX.
OFFSET
SAND-LIGHTWEIGHT OR NORMAL
WEIGHT CONCRETE (MIN. f'c =
3000 PSI) OVER MIN. 20ga METAL
DECK
UNISTRUT SPREADER
HANGER ROD
ROD COUPLER
1"-18 GA
DUCT
STRAP
(TYP.)
1"-18 GA
DUCT
STRAP
(TYP.)
1"-18 GA
DUCT
STRAP
(TYP.)
SHOT PIN (TYP.)
**THE FOLLOWING UPPER ATTACHMENTS ARE OPTIONS
FOR DIFFERENT LOWER ATTACHMENTS. FOR THE LOWER
ATTACHMENT DETAILS, PLEASE SEE THE HANGING DETAILS
FOR THE DIFFERENT PIECES OF EQUIPMENT
1-1/4" RADIUS MIN.
1"-18 GA
DUCT
STRAP
(TYP.)
ROD INSERTS
SHEET METAL
CURL INSERTS
HANGER RODHANGER ROD
SHOT PIN (TYP.)
1" MAX.
OFFSET
UNISTRUT SPREADER
HANGER ROD
ROD COUPLER
2ND FLOOR
1"-18 GA
DUCT
STRAP
(TYP.)
HANGER ROD
1"-18 GA
DUCT
STRAP
(TYP.)
#10 TEK SCREW
(TYP.)
1"-18 GA
DUCT
STRAP
(TYP.)
1-1/4" RADIUS MIN.
#10 TEK SCREW
(TYP.)
SHEET METAL CURL
INSERTS
1"-18 GA
DUCT
STRAP
(TYP.)
#10 TEK SCREW
(TYP.)#10 TEK SCREW
(TYP.)
1ST FLOOR
NOTE:
SUPPORTING HANGERS AND ANCHOR BOLTS FOR MECHANICAL EQUIPMENT WILL
BE DESIGNED BY ACCO'S STRUCTURAL ENGINEER PER SMACNA GUIDELINES.
ANCHOR BOLT SEE
SEISMIC SUPPORT
PACKAGE (TYPICAL)
MANUF. HANGER
BRACKET WITH
RUBBER
GROMETS.
(TYPICAL OF 4)
3/8"Ø THREADED
ROD (TYP. OF 4)
ATTACHMENT TO
STRUCTURE. SEE
DETAIL 9 FOR
UPPER
ATTACHMENT
OPTIONS
CABLE WITH 1-1/2"
SLACK, AT EACH
CORNER, AT 45°
ANGLEFC
#
CONDENSATE DRAIN PIPING
TAG MIN. DIAMETER (IN.) MIN. H-VALUE (IN.)
ALL FC'S 3/4 1.50
NEGATIVE
PRESSURE
CHAMBER
VENT
H"
DRAW THRU SYSTEM
H - MAXIMUM ANTICIPATED PRESSURE DIFFERENTIAL BETWEEN ATMOSPHERE AND CHAMBER HOUSING DRAIN PAN.
ADD 50% SAFETY FACTOR FOR "H" CALCULATION.
3/4 INCH
1 INCH
1 1/4 INCH
1 1/2 INCH
2 INCH
EQUIPMENT CAPACITY IN TONS
OF REFRIGERATION
MINIMUM
CONDENSATE
PIPE DIAMETER
UP TO 20
OVER 21 TO 40
OVER 41 TO 90
OVER 91 TO 125
OVER 126 TO 250
H"
UP TO 20
OVER 21 TO 40
OVER 41 TO 90
OVER 91 TO 125
OVER 126 TO 250
EQUIPMENT CAPACITY IN TONS
OF REFRIGERATION
PER 2016 CALIFORNIA PLUMBING CODE
(FOR DRAIN LINES (INDIRECT WASTE) FROM
EQUIPMENT TO APPROVED RECEPTOR)
(CPC 814.3)
PER 2016 CALIFORNIA MECHANICAL CODE
(FOR CONDENSATE PIPE LINES FROM
EQUIPMENT TO APPROVED RECEPTACLE)
(CMC 310.3)
NOTES:
PER 2016 CALIFORNIA MECHANICAL CODE 1109.9, PIPING AND FITTINGS WHICH CONVEY BRINE, REFRIGERANT OR
COOLANTS WHICH DURING NORMAL OPERATION COULD REACH A SURFACE TEMPERATURE BELOW THE DEW POINT OF
THE SURROUNDING AIR AND THAT ARE LOCATED IN SPACES OR AREAS WHERE CONDENSATION COULD CAUSE A
HAZARD TO THE BUILDING OCCUPANTS OR DAMAGE TO THE STRUCTURE OR ELECTRICAL OR OTHER EQUIPMENT SHALL
BE PROTECTED TO PREVENT SUCH DAMAGE.
** PER 2016 CALIFORNIA PLUMBING CODE 703.2, SANITARY DRAINAGE PIPING SHALL BE SIZED TO ALLOW FOR TWO (2)
FIXTURE UNITS FOR EACH GALLON PER MINUTE OF FLOW.
PITCH TO OPEN DRAIN 1/4"
PER FOOT RECOMMENDED,
1/8" PER FOOT MINIMUM
(CPC 814.1)
(CMC 310.3)
FLOOD-LEVEL
RIM OF
RECEPTOR
(CPC 810.4)
**
INSULATED REFER. LINES
TOLCO OR BLINE FELTED J-HANGER
3/8" ALL-THREAD
SEE DETAIL 9 FOR UPPER
ATTACHMENT TO
SURFACE ABOVE
TO STRUCTURE ABOVE.
SEE DETAIL 9 FOR OTHER
UPPER ATTACHMENT
OPTIONS.
#12 GA. WIRE OR
1" WIDE HANGER STRAP
FLEXIBLE ROUND
DUCT
ROUND TO SQUARE
METAL CAP, AS REQUIRED
OBD @ AIR REGISTER
ONLY AS REQUIRED
CEILING
#10 TEK SCREW
VOLUME DAMPER WHERE
SHOWN ON PLANS
#10 TEK SCREW
CEILING DIFFUSER
SHEET METAL DRAW
BAND AROUND FLEX.
UL APPROVED TAPE
OR DUCT SEALER
REFRIGERANT PIPING
B-LINE ROOF SUPPORT
"FLOATING" WITH ADJUSTABLE
HEIGHT ALL THREAD ROD OR
EQUAL.UNI-STRUT
PIPE CLAMP
ASSEMBLY OR
EQUAL.
CONCRETE
PAD BY G.C.
EXPANSION
ANCHORS BY
ACCO
NORMALWEIGHT CONCRETE PAD BY G.C.
CU
A NEOPRENE VIB.
ISO
CU
B
DUPLEX
RECEPTACLE BY
ELECTRICAL
CONTRACTOR
CEILING
EXTERNAL
CONDENSATE PUMP
BY PLUMBING
CONTRACTOR
DISCONNECT BY
ELECTRICAL
CONTRACTOR POWER BY
ELECTRICAL
CONTRACTOR
FINISHED FLOOR
EXPOSED PIPING
RACKED ON WALL
(TYP)
REFRIGERANT
PIPING
POWER
BY
ELECTRICAL
CONTRACTOR
CONDENSATE
DRAIN
NOTE: MOUNT INSTALLATION PLATE
LEVEL WITH A MINIMUM OF FOUR (4) #10
x 2 TEK SCREWS LANDING TEK SCREWS
IN A MINIMUM OF TWO STUDS.
STUD BY G.C.
(TYP.)
MOUNTING
BRACKET
PROVIDED WITH
UNIT. FASTEN TO
STUDS
INSULATED REFER.
LINES
TOLCO OR BLINE
FELTED J-HANGER
3/8" ALL-THREAD
FOR UPPER
ATTACHMENT DETAIL
SEE 9
CU
C
CU
D
CU
1
CU
2
UPPER ATTACHMENTS DETAILREFRIGERANT PIPING MOUNTING DETAIL
AIRCRAFT CABLE FOR
LATERAL BRACING
TYPICAL @ 45° ANGLE
TO STRUCTURE ABOVE.
SEE DETAIL 9 FOR OTHER
UPPER ATTACHMENT
OPTIONS.
EF
1-8
3"
MAX.
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
2/
5
/
2
0
2
1
3
:
1
2
:
0
1
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC5.01
MECHANICAL DETAILS
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
N/A
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
14"X46 OPENING IN
NORMALWEIGHT CONCRETE
PAD FOR REFRIGERANT
PIPING TO GO
UNDERGROUND. LOCATION
PER PLANS. MIN 6" EDGE
DISTANCE. VRF PIPING TO BE
ENCLOSED IN 12" PVC. SPLIT
SYSTEM PIPING TO BE
ENCLOSED IN 6" PVC.
6" EDGE DISTANCE TO
BE CONFIRMED BY
STRUCTURAL DRAWINGS
PAD THICKNESS PER
STRUCTURAL DRAWINGS
TRANSFER AIR
OPENING (TYP. 1 SQ. FT.
UNLESS OTHERWISE
STATED
SHEET METAL CAN
FLEX (TYP. 16"Ø)
24"X24" CT1 LAY-IN
GRILLE
VRF LINES ENCASED
IN 12" PVC LINES
SPLIT SYSTEM LINES
ENCASED
IN 6" PVC LINES
HARDSCAPE
CHIMNEY CAP
(TYP.)
PARAPET
TOP OF
CHIMNEY CAP
TO BE BELOW
TOP OF
PARAPET LINE
1/4"
(MIN.)
1"
MIN.
33'-7"
7'-6"
6"
6"
3'-10"
1'-2"
6" MIN.
6" MIN.
12" MIN.
6" MIN.6" MIN.
1' - 0"
20"20"2'-0"
910
34
78
2 1
56
DUST COLTR MOUNTING DETAIL (NOT USED)HALLWAY TRANSFER AIR DETAILREFRIGERANT TRENCH DETAILFIREPLACE FLUE TERMINATION DETAIL
DUST COLTR. EQUIP. ATTCH DETAIL (NOT USED)DUST COLTR. DUCT ATTCH DETAIL (NOT USED)CONDENSING UNIT PAD DETAIL
FIRE SMOKE DAMPER DETAIL
OPTIONAL
FIRESTAT OR
END SWITCHES
AUXILIARY
OPERATING JACK
SHAFT
OPENING TO BE
FRAMED AND
SHEETROCKED BY
G.C. (WITH
REQUIRED
CLEARANCE)
PFMA OR
CONVENTIONAL
MOUNTING
ANGLES
S JOINT/DUCTMATE,
SLEEVE TO DUCT
BREAKAWAY
CONNECTION
PFMA OR
1-1/2"x1-1/2"
STEEL ANGLE
NO EXPANSION
GAP REQUIRED,
TYPICAL OF ALL
SIDES
#10 TEK SCREWS
MAX. 12" O.C.
MOUNTING
ANGLES TO
OVERLAP WALL A
MINIMUM OF 1"
ON ALL 4 SIDES
CEILING
AIRFLOW DIRECTION
T-BAR
CLG
RATED WALL
T-BAR CLG
RATED WALL
T-BAR CLG
AD
ONE SIDE MOUNTING ANGLE
INSTALLATION FASTENED
DIRECTLY TO METAL STUD
ONE SIDE MOUNTING ANGLE
INSTALLATION FASTENED
DIRECTLY TO WALL
FSD IN DUCT
ALTERNATE UL LISTED MOUNTING
DETAILS
UL 555 AND UL 555S LISTED, CLASS II FSD
SEE FLOOR PLANS FOR LOCATION AND SIZE OF DAMPER
CONSISTENT WITH SMACNA'S "FIRE DAMPER & HEAT STOP GUIDE"
S JOINT/DUCTMATE,
SLEEVE TO DUCT
BREAKAWAY
CONNECTION
DAMPER
ACTUATOR
SLEEVE
EXTENDED MIN.
3" EACH SIDE OF
PARTITION
SUPPLY OR
RETURN DUCT
WHERE OCCURSAIRFOIL BLADES
[MODEL#]
18x18 CEILING ACCESS
PANEL (FIRE RATED WHERE
REQ'D)
FOR ACTUATOR AND
DAMPER ACCESS
FIRE/SMOKE
DAMPER DUCT
ACCESS
FIRE RATED WALL
MOUNTING
ANGLES
FASTENED TO
SLEEVE BY #10
TEK SCREWS
6-8" O.C.
MOUNTING
ANGLES TO
OVERLAP WALL A
MINIMUM OF 1"
ON ALL 4 SIDES
CONTROL LINKAGE
DAMPER
CBC 717.3.3.2:
Smoke dampers shall be closed by actuation of a smoke detector installed in accordance with the Fire Code and one of the
following applicable methods:
1. Where a damper is installed within a duct, a smoke detector shall be installed in the duct within 5 feet (1524 mm) of the damper
with no air outlets or inlets between the detector and the damper. The detector shall be listed for the air velocity, temperature and
humidity anticipated at the point where it is installed.
2. Where a damper is installed within an unducted opening in a wall, a spot-type detector listed for releasing service shall be
installed within 5 feet (1524 mm) horizontally of the damper.
3. Where a damper is installed in a ceiling, a spot-type detector listed for releasing service shall be installed on the ceiling within 5
feet (1524 mm) of the damper.
4. Where a damper is installed in a corridor wall or ceiling, the damper may be controlled by a smoke-detection system installed in
the corridor.
5. When a total-coverage smoke-detection system is provided within all areas served by an HVAC system, dampers may be
controlled by the smoke-detection system.
INSTALL FSD SUCH
THAT DAMPER
BLADES ARE IN THE
RATED WALL
ASSEMBLY WHEN
CLOSED
NOTE: WHERE INSTALLATION
DETAIL AND MANUFACTURER'S
INSTALLATION INSTRUCTIONS
CONFLICT, MFR'RS
INSTRUCTIONS SHALL PREVAIL.
DUCTMATE WITH PLASTIC
CLEATS PER MFR'RS
INSTRUCTIONS
MOUNTING
ANGLES TO
OVERLAP WALL A
MINIMUM OF 1" ON
ALL 4 SIDES
#10 TEK SCREWS
MAX. 12" O.C.
SCREWS 1/2"
LONGER THAN
SHEETROCK
DEPTH
FSD IN WALL
NOTE: SMOKE DETECTORS FOR FIRE/SMOKE DAMPERS TO
BE FURNISHED BY FIRE LIFE SAFETY CONTRACTOR AND
WIRED BY ELECTRICIAN. SEE ABOVE FOR APPROVED
LOCATIONS FOR SMOKE DETECTORS PER CBC 717.3.3.2.
SA/RA DUCT
PROVIDE SHUTDOWN OF HVAC SYSTEM
SERVING SMOKE DAMPERS OR COMBINATION
SMOKE-FIRE DAMPERS WHEN AUTOMATIC
ACTIVATION OF DAMPER OCCURS.
PIPE PENETRATION THRU FIRE-RATED WALL DETAIL
DUST COLLECTOR DETAIL (NOT USED)
CEILING
CLASSROOMHALLWAY
DECK
SAND OR
SANDY LOAM
UNDISTURBED
GRADE
NOTE: SEE FIRE
STOPPING DETAILS ON
A9.06, A9.07 AND A9.08.
A
DSD
E E
PENDANT AREA
SMOKE
DETECTOR
LOCATED IN
PLENUM, WITHIN
5' OF FSDOR
TOTAL COVERAGE
SMOKE DETECTION
SYSTEM
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
2/
5
/
2
0
2
1
3
:
1
2
:
0
2
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC5.02
MECHANICAL DETAIL
(CONT.)
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
N/A
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
016 12/09/20 CCD-016 DN
1 01/22/21 CITY PERMIT
AMENDMENT
CD
B.D.D.
1" FIBERGLASS DUCT LINING
OPEN BOTH ENDS ONLY
SHEET METAL
ACCOUSTICAL SEALANT
RETURN AIR BOOT ABOVE
CEILING
4" DUCT
SKUTT ENVIROLINK
SHALL BE INSTALLED
FOR AUTOMATED
INTERLOCK
BETWEEN KILN &
DOWNDRAFT
VENTING SYSTEM
SKUTT
ENVIROVENT 2
PLENUM CUP &
CUP STAND
SKUTT
ENVIROVENT 2
BLOWER W/
MOTOR
KILN CONTROL
PANEL
ACCOUSTICAL SEALANT
RETURN AIR BOOT ABOVE
CEILING
1" FIBERGLASS DUCT LINING
OPEN BOTH ENDS ONLY
SHEET METAL
ELBOW CAN BE IN
ANY PLANE.
PREFERRED
ORIENTATION IS UP.
89
567-
4 3 2 1
TYP "L" AIR RETURN RELIEF BOOT
HEAT RECOVERY UNIT HANGING DETAILGRAVITY VENTILATOR DETAILREF. PIPE THERMAL EXPANSION DETAIL-
INLINE EXHAUST / SUPPLY FAN DETAIL REFRIGERANT WALL PIPING DETAIL GRAVITY VENTILATOR MOUNTING DETAIL KILN DOWNDRAFT EXHAUST VENT
SKUTT
KM/KMT-1027-3
ELECTRIC KILN
1ST FLOOR
SUPPLEMENTAL STRUCTURE
AS REQUIRED PER
STRUCTURAL
BY G.C.
O.S.A. DUCT DOWN TO FAN
COIL RETURN PLENUM
MANUF'R ROOF CURB FURNISHED BY
ACCO
WOOD NAILER
(TYP.)
TEK SCREW
(TYP.)
ROOFING
BY G.C.
WITH SCREEN HAVING NOT LESS
THAN 1/4-INCH OPENINGS AND NOT
MORE THAN 1/2-INCH OPENINGS
12" EA
CONCRETE WALL
TO STRUCTURE ABOVE.
SEE DETAIL 9/AC5.01 FOR
OTHER UPPER
ATTACHMENT OPTIONS.
EF
1-1
EF
1-2
EF
1-3
EF
1-4
EF
1-5
EF
1-6
EF
1-7
EF
2-1
EF
2-2
EF
2-3
EF
2-4
SF
1-1
SF
1-2
SF
1-3
SF
2-1
SF
2-2
SF
2-3
SF
2-4
SPRING HANGERS OR
NEOPRENE PAD
NOTE:
SUPPORTING HANGERS AND ANCHOR BOLTS FOR MECHANICAL EQUIPMENT WILL
BE DESIGNED BY ACCO'S STRUCTURAL ENGINEER PER SMACNA GUIDELINES.
MANUF. HANGER
BRACKET WITH
RUBBER
GROMETS.
(TYPICAL OF 4)
3/8"Ø THREADED
ROD (TYP. OF 4)
ATTACHMENT TO
STRUCTURE. SEE
DETAIL 9 FOR
UPPER
ATTACHMENT
OPTIONS
BS
#
NEOPRENE PAD
GRAVITY VENTILATOR
VRF FAN COIL RETURN
PLENUM
SEE DETAIL 2 FOR GRAVITY
VENTILATOR MOUNTING
DETAIL
CONDENSING UNIT
(TYP.)
B.D.D.
18" FLEX CONNECTOR ON
HIGH PRESSURE VAPOR
LINE FOR THERMAL
EXPANSION. FINAL LENGTH
TO BE CONFIRMED BY
ENGINEERING.
PVC PIPE
REFRIGERANT LINES
INSIDE PVC PIPING,
UNDERGROUND
KILN PLACEMENT NOTES (INSTALLED BY OTHERS):
1. THE SIDES AND TOPS OF KILNS SHALL BE LOCATED NOTE LESS THAN 18 INCHES FROM A NON-COMBUSTIBLE WALL SURFACE
AND 3 FEET FROM A COMBUSTIBLE WALL SURFACE. [CMC 932.5.1]
2. KILNS SHALL BE INSTALLED ON NONCOMBUSTIBLE FLOORING CONSISTING OF NOT LESS THAN 2 INCHES OF SOLID MASONRY OR
CONCRETE EXTENDING NOT LESS THAN 12 INCHES BEYOND THE BASE OR SUPPORTING MEMBERS OF THE KILN. [CMC 932.5.1]
3. IN NO CASE SHALL THE CLEARANCE ON THE GAS OR ELECTRICAL CONTROL SIDE OF A KILN BE REDUCED TO LESS THAN 30
INCHES. [CMC 932.5.1]
INSTALL DUCT EXTENSION ATOP
CONDENSING UNIT SUCH THAT AIR
DISCHARGES AT THE SAME LEVEL
AS THE TOP OF THE ADJACENT
CONCRETE WALL
DUCT
EXTENSION
SEE PLANS FOR SIZES
TYP "U" AIR RETURN RELIEF BOOT
SLOPE PIPE TO MAINTAIN
12" FROM TOP OF PIPE
TO TOP OF
LANDSCAPING.
W
W
2W
2W
2W
W
3W, MIN
2W
2
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
2/
5
/
2
0
2
1
3
:
2
8
:
0
7
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC5.03
MECHANICAL DETAIL
(CONT.)
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
N/A
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
016 12/09/20 CCD-016 DN
1 01/22/21 CITY PERMIT
AMENDMENT
CD
2 xx/xx ACOUSTICAL CHANGES DN
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
2/
5
/
2
0
2
1
3
:
1
2
:
0
6
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC6.01
MECHANICAL VRF PIPING
DIAGRAM
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
N/A
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
0 09/11/20 ISSUED FOR
CONSTRUCTION
CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
2/
5
/
2
0
2
1
3
:
1
2
:
1
0
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC6.02
MECHANICAL VRF PIPING
DIAGRAMS (CONT.)
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
N/A
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
0 09/11/20 ISSUED FOR
CONSTRUCTION
CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
M
BAS
BAS
BAS
BAS
BAS
BAS
E
E
E
E
E
E
E
E
E
E
E
E
E
E
M
BAS
BAS
BAS
BAS
BAS
BAS
E
E
E
E
E
E
E
E
E
E
E
E
E
E
M
BAS
BAS
BAS
BAS
BAS
BAS
E
E
E
E
E
E
E
E
E
E
E
E
E
E
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CIRCUIT BREAKER OR
FUSED DISCONNECT
S REQUIRED
SHIELD GROUND AT CHASSIS
CEN SHIELD GROUNDS AT THE
END OF LINE MASTER CU ONLY
SHIELD WIRE TWISTED AND
TAPED TO CABLE
SODU/IDU SHIELDS
GROUND AT ALL
MASTER CU'S SINGLE OR DOUBLE POLE DRY
CONTACT INPUT RELAY (RIB RELAY)
UNGROUNDED SHIELD
CONNECTION WIRE NUT
SUPPLY AIR SMOKE DETECTOR
INSTALLED BY ACCO IN
DISCHARGE DUCTWORK. FURNISHED
AND WIRED BY ELECTRICIAN
LG PROVIDED THREE-CORE
COMMUNICATION CABLE OR
18-3 TWISTED, STRANDED,
AND UNSHIELDED CABLE.
TYPICAL ALL THERMOSTATS
18-2 SHIELDED & STRANDED
LOW VOLTAGE WIRING
18-2 SHIELDED &
STRANDED LOW
VOLTAGE WIRING
TO ADDITIONAL MASTER UNIT OR CENTRAL
CONTROLLER. CHAIN TERMINATES AT CENTRAL
CONTROLLER (REQUIRES 24 VAC POWER, 40 VA)
18-2 SHIELDED
& STRANDED LOW
VOLTAGE WIRING
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CIRCUIT BREAKER OR
FUSED DISCONNECT
S REQUIRED
SHIELD GROUND AT CHASSIS
CEN SHIELD GROUNDS AT THE
END OF LINE MASTER CU ONLY
SHIELD WIRE TWISTED AND
TAPED TO CABLE
SODU/IDU SHIELDS
GROUND AT ALL
MASTER CU'S SINGLE OR DOUBLE POLE DRY
CONTACT INPUT RELAY (RIB RELAY)
UNGROUNDED SHIELD
CONNECTION WIRE NUT
SUPPLY AIR SMOKE DETECTOR
INSTALLED BY ACCO IN
DISCHARGE DUCTWORK. FURNISHED
AND WIRED BY ELECTRICIAN
LG PROVIDED THREE-CORE
COMMUNICATION CABLE OR
18-3 TWISTED, STRANDED,
AND UNSHIELDED CABLE.
TYPICAL ALL THERMOSTATS
18-2 SHIELDED & STRANDED
LOW VOLTAGE WIRING
18-2 SHIELDED &
STRANDED LOW
VOLTAGE WIRING
TO ADDITIONAL MASTER UNIT OR CENTRAL
CONTROLLER. CHAIN TERMINATES AT CENTRAL
CONTROLLER (REQUIRES 24 VAC POWER, 40 VA)
18-2 SHIELDED
& STRANDED LOW
VOLTAGE WIRING
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CIRCUIT BREAKER OR
FUSED DISCONNECT
S REQUIRED
SHIELD GROUND AT CHASSIS
CEN SHIELD GROUNDS AT THE
END OF LINE MASTER CU ONLY
SHIELD WIRE TWISTED AND
TAPED TO CABLE
SODU/IDU SHIELDS
GROUND AT ALL
MASTER CU'S SINGLE OR DOUBLE POLE DRY
CONTACT INPUT RELAY (RIB RELAY)
UNGROUNDED SHIELD
CONNECTION WIRE NUT
SUPPLY AIR SMOKE DETECTOR
INSTALLED BY ACCO IN
DISCHARGE DUCTWORK. FURNISHED
AND WIRED BY ELECTRICIAN
LG PROVIDED THREE-CORE
COMMUNICATION CABLE OR
18-3 TWISTED, STRANDED,
AND UNSHIELDED CABLE.
TYPICAL ALL THERMOSTATS
18-2 SHIELDED & STRANDED
LOW VOLTAGE WIRING
18-2 SHIELDED &
STRANDED LOW
VOLTAGE WIRING
TO ADDITIONAL MASTER UNIT OR CENTRAL
CONTROLLER. CHAIN TERMINATES AT CENTRAL
CONTROLLER (REQUIRES 24 VAC POWER, 40 VA)
18-2 SHIELDED
& STRANDED LOW
VOLTAGE WIRING
3
2
1VRF-A POWER LOAD DIAGRAM
CENSODUIDU
A B A B A B
CENSODUIDU
A B A B A B 4 3
HEAT RECOVERY UNIT
TO NEXT FCU/HRU IN SERIES,
SEE SCHEDULE & FLOOR
PLAN FOR QUANTITIES
INDOOR UNIT INDOOR UNIT GROUNDGROUND
208V-1Ø208V-1Ø
TO FIRE ALARM PANEL
BY ELECTRICIAN
THERMOSTAT THERMOSTAT
4 3 R G Y4 3 R G Y
208V-1Ø460V-3Ø460V-3Ø
NOTE:
UNGROUNDED SHIELD MAY USE
WIRE NUT AS INDICATED ABOVE.
ALL OTHER LG VRF
COMMUNICATION WIRES MAY NOT
CONTAIN SPLICES OR WIRE NUTS.
WIRED CONTROLLER
(PROVIDED WITH UNIT)
SET THERMOSTAT @
75°F COOLING, 70°F
HEATING
WIRED CONTROLLER
(PROVIDED WITH UNIT)
SET THERMOSTAT @
75°F COOLING, 70°F
HEATING
OUTDOOR UNIT
MASTER
(LARGEST TONNAGE)
OUTDOOR UNIT
SLAVE
SHIELD
GROUND
CU
A
LG VRF CONDENSING UNIT
ON GRADE (QTY. 2 AS SHOWN)
HRU
-
LG VRF HEAT RECOVERY UNIT
SEE FLOOR PLAN FOR
LOCATION
(QTY. 6)
FCU
-
LG VRF FAN COIL
SEE FLOOR PLAN FOR FAN COILS
WHICH DO NOT NEED SMOKE
DETECTORS
FCU
-
LG VRF FAN COIL W/ DSD
SEE FLOOR PLAN FOR FAN COILS
WHICH NEED SMOKE DETECTORS
CENSODUIDU
A B A B A B
CENSODUIDU
A B A B A B 4 3
HEAT RECOVERY UNIT
TO NEXT FCU/HRU IN SERIES,
SEE SCHEDULE & FLOOR
PLAN FOR QUANTITIES
INDOOR UNIT INDOOR UNIT GROUNDGROUND
208V-1Ø208V-1Ø
TO FIRE ALARM PANEL
BY ELECTRICIAN
THERMOSTAT THERMOSTAT
4 3 R G Y4 3 R G Y
208V-1Ø460V-3Ø460V-3Ø
NOTE:
UNGROUNDED SHIELD MAY USE
WIRE NUT AS INDICATED ABOVE.
ALL OTHER LG VRF
COMMUNICATION WIRES MAY NOT
CONTAIN SPLICES OR WIRE NUTS.
WIRED CONTROLLER
(PROVIDED WITH UNIT)
SET THERMOSTAT @
75°F COOLING, 70°F
HEATING
WIRED CONTROLLER
(PROVIDED WITH UNIT)
SET THERMOSTAT @
75°F COOLING, 70°F
HEATING
OUTDOOR UNIT
MASTER
(LARGEST TONNAGE)
OUTDOOR UNIT
SLAVE
SHIELD
GROUND
CU
B
LG VRF CONDENSING UNIT
ON GRADE (QTY. 2 AS SHOWN)
HRU
-
LG VRF HEAT RECOVERY UNIT
SEE FLOOR PLAN FOR
LOCATION
(QTY. 3)
FCU
-
LG VRF FAN COIL
SEE FLOOR PLAN FOR FAN COILS
WHICH DO NOT NEED SMOKE
DETECTORS
FCU
-
LG VRF FAN COIL W/ DSD
SEE FLOOR PLAN FOR FAN COILS
WHICH NEED SMOKE DETECTORS
CENSODUIDU
A B A B A B
CENSODUIDU
A B A B A B 4 3
HEAT RECOVERY UNIT
TO NEXT FCU/HRU IN SERIES,
SEE SCHEDULE & FLOOR
PLAN FOR QUANTITIES
INDOOR UNIT INDOOR UNIT GROUNDGROUND
208V-1Ø208V-1Ø
TO FIRE ALARM PANEL
BY ELECTRICIAN
THERMOSTAT THERMOSTAT
4 3 R G Y4 3 R G Y
208V-1Ø460V-3Ø460V-3Ø
NOTE:
UNGROUNDED SHIELD MAY USE
WIRE NUT AS INDICATED ABOVE.
ALL OTHER LG VRF
COMMUNICATION WIRES MAY NOT
CONTAIN SPLICES OR WIRE NUTS.
WIRED CONTROLLER
(PROVIDED WITH UNIT)
SET THERMOSTAT @
75°F COOLING, 70°F
HEATING
WIRED CONTROLLER
(PROVIDED WITH UNIT)
SET THERMOSTAT @
75°F COOLING, 70°F
HEATING
OUTDOOR UNIT
MASTER
(LARGEST TONNAGE)
OUTDOOR UNIT
SLAVE
SHIELD
GROUND
CU
C
LG VRF CONDENSING UNIT
ON GRADE (QTY. 2 AS SHOWN)
HRU
-
LG VRF HEAT RECOVERY UNIT
SEE FLOOR PLAN FOR
LOCATION
(QTY. 4)
FCU
-
LG VRF FAN COIL
SEE FLOOR PLAN FOR FAN COILS
WHICH DO NOT NEED SMOKE
DETECTORS
FCU
-
LG VRF FAN COIL W/ DSD
SEE FLOOR PLAN FOR FAN COILS
WHICH NEED SMOKE DETECTORS
VRF-B POWER LOAD DIAGRAM
VRF-C POWER LOAD DIAGRAM
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
2/
5
/
2
0
2
1
3
:
1
2
:
1
1
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC7.01
POWER LOAD DIAGRAMS
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
N/A
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
M
BAS
BAS
BAS
BAS
BAS
E
E
E
E
E
E
E
E
E
E
E
E
E
E
BAS
E
E
ELECTRICAL SHEET NOTES
8
7.
2.
1.
3.
4.
9.
WIRING AND INSTALLATION SHALL CONFORM TO ALL GOVERNING CODES.
INDICATES ITEMS FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR.
INDICATES ITEMS FURNISHED BY MECHANICAL CONTRACTOR.
ALL COPPER AND/OR ALUMINUM CONDUCTOR CONNECTIONS SHALL BE MADE AS
PRESCRIBED BY ESTABLISHED ELECTRICAL INDUSTRY AND ENGINEERING STANDARDS.
EXTREME CARE MUST BE TAKEN WHEN CONNECTIONS INVOLVE DISSIMILAR MATERIALS.
INDICATES LINE VOLTAGE WIRING BY ELECTRICAL CONTRACTOR.
INDICATES LOW VOLTAGE WIRING.
INDICATES ITEMS FURNISHED AND INSTALLED BY BUILDING AUTOMATION
SYSTEM CONTRACTOR.
10. FROM 2016 CMC, SEC. 301.4:
"EQUIPMENT REGULATED BY THIS CODE REQUIRING ELECTRICAL CONNECTIONS OF
MORE THAN 50 VOLTS SHALL HAVE A POSITIVE MEANS OF DISCONNECT ADJACENT TO
AND IN SIGHT FROM THE EQUIPMENT SERVED. A 120-VOLT RECEPTACLE SHALL BE
LOCATED WITHIN 25 FEET OF THE EQUIPMENT FOR SERVICE AND MAINTENANCE
PURPOSES. THE SERVICE RECEPTACLE NEED NOT BE LOCATED ON THE SAME LEVEL AS
THE EQUIPMENT. LOW VOLTAGE WIRING OF 50 VOLTS OR LESS WITHIN A STRUCTURE
SHALL BE INSTALLED IN A MANNER TO PREVENT PHYSICAL DAMAGE." ELECTRICAL
WIRING, CONTROLS, AND CONNECTIONS TO EQUIPMENT AND APPLIANCES REGULATED
BY THIS CODE SHALL BE IN ACCORDANCE WITH NFPA 70.
5.INDICATES ITEMS FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR TO
BE ON EMERGENCY POWER.
6.INDICATES ITEMS FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR
TO BE ON UPS POWER.
E
M
BAS
EMP
UPS
M
BAS
BAS
E
E
E
E
E
BAS
BAS
BAS
E
E
E
E
E
E
BAS
M
BAS
BAS
E
E
E
E
E
BAS
M
M
E
E
E
E
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CIRCUIT BREAKER OR
FUSED DISCONNECT
S REQUIRED
SHIELD GROUND AT CHASSIS
CEN SHIELD GROUNDS AT THE
END OF LINE MASTER CU ONLY
SHIELD WIRE TWISTED AND
TAPED TO CABLE
SODU/IDU SHIELDS
GROUND AT ALL
MASTER CU'S SINGLE OR DOUBLE POLE DRY
CONTACT INPUT RELAY (RIB RELAY)
UNGROUNDED SHIELD
CONNECTION WIRE NUT
SUPPLY AIR SMOKE DETECTOR
INSTALLED BY ACCO IN
DISCHARGE DUCTWORK. FURNISHED
AND WIRED BY ELECTRICIAN
LG PROVIDED THREE-CORE
COMMUNICATION CABLE OR
18-3 TWISTED, STRANDED,
AND UNSHIELDED CABLE.
TYPICAL ALL THERMOSTATS
18-2 SHIELDED & STRANDED
LOW VOLTAGE WIRING
18-2 SHIELDED &
STRANDED LOW
VOLTAGE WIRING
18-2 SHIELDED
& STRANDED LOW
VOLTAGE WIRING
CIRCUIT BREAKER OR
FUSED DISCONNECT
S REQUIRED
TO ADDITIONAL MASTER UNIT OR CENTRAL
CONTROLLER. CHAIN TERMINATES AT CENTRAL
CONTROLLER (REQUIRES 24 VAC POWER, 40 VA)
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CURRENT SWITCH BY
CONTROLS CONTRACTOR
SPEED CONTROLLER
(PROVIDED WITH FAN)
MOUNTED AND WIRED BY
ELECTRICAL CONTRACTOR
24V WIRING
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
CURRENT SWITCH BY
CONTROLS CONTRACTOR
SPEED CONTROLLER
(PROVIDED WITH FAN)
MOUNTED AND WIRED BY
ELECTRICAL CONTRACTOR
RELAY (IF NECESSARY) WITH
24V COIL AND 120V RATED CONTACT.
CIRCUIT BREAKER OR
FUSED DISCONNECT
AS REQUIRED
DUCT OR AREA SMOKE DETECTOR BY
ELECTRICIAN. NORMALLY CLOSED CONTACT
FROM LOCAL SMOKE DETECTOR.
BREAK ON ALARM TO CLOSE DAMPER.
DEVICE & CONTROL BY ELEC CONTRACTOR
NORMALLY CLOSED CONTACT
TO ASSOCIATED AC UNIT/FAN FOR
AC UNIT/FAN SHUT DOWN.
SEE NOTE 3.
BY FLS CONTRACTOR.
SIGNAL FROM AC UNIT/FAN.
NORMALLY OPEN RELAY FOR FSD
OPEN/CLOSE DURING NORMAL OPERATION.
CLOSE WHEN SIGNAL IS RECEIVED FROM AC
UNIT/FAN TO OPEN DAMPER.
DEVICE & CONTROL BY FLS CONT'R.
(NOT REQUIRED IF DUCT OR AREA
SMOKE DETECTOR DOES NOT
HAVE MINIMUM FLOW REQUIREMENT
PER CODE 2016 CBC 717.3.3.2.1)
LOCAL DISCONNECT SWITCH
BY ELECTRICIAN
120VAC, SPRING RETURN
DAMPER ACTUATOR
(PROVIDED WITH DAMPER ASSEMBLY)
6789
2345
1
SPLIT SYSTEM POWER LOAD
FIRE SMOKE DAMPER POWER LOAD ELECTRICAL SHEET NOTESEXHAUST FAN POWER LOAD
VRF-D POWER LOAD DIAGRAM
CENSODU IDU
A B A B A B
CENSODU IDU
A B A B A B 4 3
HEAT RECOVERY UNIT
TO NEXT FCU/HRU IN SERIES,
SEE SCHEDULE & FLOOR
PLAN FOR QUANTITIES
INDOOR UNIT INDOOR UNIT GROUNDGROUND
208V-1Ø208V-1Ø
TO FIRE ALARM PANEL
BY ELECTRICIAN
THERMOSTAT THERMOSTAT
4 3 R G Y43 R G Y
208V-1Ø460V-3Ø460V-3Ø
NOTE:
UNGROUNDED SHIELD MAY USE
WIRE NUT AS INDICATED ABOVE.
ALL OTHER LG VRF
COMMUNICATION WIRES MAY NOT
CONTAIN SPLICES OR WIRE NUTS.
WIRED CONTROLLER
(PROVIDED WITH UNIT)
SET THERMOSTAT @
75°F COOLING, 70°F
HEATING
WIRED CONTROLLER
(PROVIDED WITH UNIT)
SET THERMOSTAT @
75°F COOLING, 70°F
HEATING
OUTDOOR UNIT
MASTER
(LARGEST TONNAGE)
OUTDOOR UNIT
SLAVE
SHIELD
GROUND
CENSODU IDU
A B A B A B
460V-3Ø
OUTDOOR UNIT
SLAVE
SHIELD
GROUND
FCU
-
LG VRF FAN COIL
SEE FLOOR PLAN FOR FAN COILS
WHICH DO NOT NEED SMOKE
DETECTORS
FCU
-
LG VRF FAN COIL W/ DSD
SEE FLOOR PLAN FOR FAN COILS
WHICH NEED SMOKE DETECTORS
HRU
-
LG VRF HEAT RECOVERY UNIT
SEE FLOOR PLAN FOR LOCATION
(QTY. 4)
CU
D
LG VRF CONDENSING UNIT
ROOF (QTY. 3 AS SHOWN)
EF
2-2
EXHAUST FAN
IN-LINE
115V-1Ø
MOTOR
STATUS
START/STOP
GROUND
EF
2-3
EF
1-1
MOUNT ON
WALL IN ZONE
ROOM AT 48"
A.F.F.
THERMOSTAT
R
G
W1
W2
Y
Y2
C
O
INDOOR UNIT
208V-1Ø
OUTDOOR UNIT
208V-1Ø
GROUND
BAS INTEGRATION THROUGH
COMMUNICATION LINK
COMMUNICATION INTEGRATION
GROUND
SUPPLY FAN POWER LOAD
DUST COLTR POWER LOAD (NOT USED)
2-4
OSA SUPPLY FAN
IN-LINE
115V-1Ø
MOTOR
STATUS
START/STOP
GROUND
2-32-2
1-31-2
SF
1-1
2-1
SF SF
SFSFSFSF
120V-1Ø
FSD OPEN/CLOSE NOTES:
1. ALL ASSOCIATED FIRE/SMOKE DAMPERS
SHALL OPEN WHENEVER A SIGNAL IS
RECEIVED FROM THE TIMECLOCK/FAN RUN
SIGNAL.
2. ALL ASSOCIATED FIRE/SMOKE DAMPERS
SHALL CLOSE WHENEVER A SIGNAL FROM
THE TIMECLOCK/FAN PROOF RUN SIGNAL IS
REMOVED.
3. THE AC UNIT/FAN AND ALL ASSOCIATED
FIRE/SMOKE DAMPERS SHALL SHUT DOWN
WHENEVER:
·AN ALARM IS RECEIVED FROM THE AC
UNIT/FAN SUPPLY AIR SMOKE
DETECTOR.
·AN ALARM IS RECEIVED FROM ANY OF
THE LOCAL SMOKE DETECTORS AT ANY
OF THE FIRE/SMOKE DAMPERS.
FSD
1
FIRE SMOKE DAMPER
SEE PLANS FOR LOCATION
2-4
EF
2-1
EF EF
1-6
EF
1-3
EF
1-2
EF
1-4
EF
1-5
EF
1-8
--
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
2/
5
/
2
0
2
1
3
:
1
2
:
1
2
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC7.02
POWER LOAD DIAGRAMS
(CONT.)
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
N/A
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
0 09/11/20 ISSUED FOR
CONSTRUCTION
CD
016 12/09/20 CCD-016 DN
1 01/22/21 CITY PERMIT
AMENDMENT
CD
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
2/
5
/
2
0
2
1
3
:
1
2
:
1
6
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC7.03
SEQUENCE OF OPERATIONS
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
N/A
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
0 09/11/20 ISSUED FOR
CONSTRUCTION
CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
CC
1 3 10
10
16
16
20
20
22 25
25
Z
Y
V
S
N
K
H
E
B
27
27
2 4 5
18
D
F
G
AA
X
DD
U
Q
C
8
8
13
13
19
19
21
21
17
17
11
11
P
M
12
6
L
R
T
W
24 26
23
23
14
14
7 9
J
23.5
15
15
CCCC
1
1
3
3
10
10
16
16
20
20
22
22
25
25
ZZ
YY
V
V
SS
NN
KK
HH
EE
BB
27
27
2
2
4
4
5
5
18
18
DD
FF
GG
AAAA
XX
DDDD
UU
QQ
C
8
8
13
13
19
19
21
21
17
17
11
11
OFFICE
124A
4TH GRADE
CLASSROOM
120
3RD GRADE
CLASSROOM
118
SMALL GROUP
119A
4TH GRADE
CLASSROOM
119
LOWER SCHOOL
SCIENCE
CLASSROOM
122
WORLD
LANGUAGE
CLASSROOM
121
CERAMICS
125A
KILN
125B
UPPER SCHOOL
ART LAB
125
1ST GRADE
CLASSROOM
112
SMALL GROUP
113
2ND GRADE
CLASSROOM
115
1ST GRADE
CLASSROOM
114
SMALL GROUP
115A
TEACHING AREA
131B
WORKROOM
131A
ELEV.
E-1-1
ELECT.
110 DATA
109
CONFERENCE
ROOM
107
ASSOCIATES
134
PSYCH.
137A
SMALL GROUP
AREA
137
2ND GRADE
CLASSROOM
116
SMALL GROUP
117A
3RD GRADE
CLASSROOM
117
LANGUAGE ARTS
SPECIALIST
137B
CUSTODIAL
136
STAIR 1
STR1-1
ELECTRICAL
163
STAFF TOILET
145
UNISEX TOILET
142
STAIR 2
STR2-1
LOBBY
100
GIRLS'
RESTROOM
140
BOYS'
RESTROOM
139
GIRLS'
RESTROOM
143
BOYS'
RESTROOM
144
WORKROOM
106
FACILITIES DIR.
105
LOWER DIR.
102
TECHNOLOGY
DIRECTOR
103
HEAD OF
SCHOOL
104
HALLWAY
161
LIBRARY
131
TINKER AREA
133
STORY TELLING
132
MATH
SPECIALIST
137C
MAKER SPACE
123
LOWER SCHOOL
ART LAB
126
OPEN OFFICE
159
HALLWAY
160
HALLWAY
162
?
?
FC B1-5
FC B1-6
FC B1-7
FC B1-8
FC B1-9
FC B1-10 FC A1-19
FC A1-17
FC A1-16
FC A1-13
FC A1-14
FCA1-15
FC B1-2
FC A1-1
FC A1-2
FC A1-4
FC A1-5
FC A1-7
FC A1-6
FC A1-8
FC A1-9FC A1-10
FC A1-11FC A1-12
FC B1-11
FC B1-12
FC B1-13
FC B1-14
FC B1-15
FC B1-16 FC B1-17 FC B1-18
FC A1-20 FC A1-21
FC D1-1
FC D1-2
FC D1-3
FC D1-4
FC D1-6
FC D1-7
FC D1-8
FC A1-18A
FC A1-18B
NURSE
101
TOILET
111A
TOILET
108A
WORK ROOM
108C
STOR.
111B
KINDERGARTEN
108
KINDERGARTEN
111
STOR.
108B
ADMISSIONS DIR.
100ATOILET
101A
TECH LAB
123A
DESIGN CENTER
124
FC A1-3FC B1-4 FC B1-1FC B1-3
FC B1-19
FC D1-5
CC
1 4 10 15
18 22 25 27
Z
20
AA
2 635
2321
11
24 26
12 179
D
G
B
C
F
H
K
M
L
N
S
P
R
T
Q
U
XY
W
V
DD
19
14 167
E
138
J
BB
23.5
TOILET
100B
STAFF TOILET
153
ELECT.
146 CUSTODIAN
151 UNISEX TOILET
152
ELEV.
E-2-1
CORRIDOR
154
FIRE RISER
112A
FC B1-20
PP
MM
12
126
6
LL
RR
TT
W
W
24
24
26
26
23
2315
15
14
14
7
7
9
9
BBBB
AA
JJ
T
T
T
T
T
T
T
T
T
T
TT
T T
T
T
T
T
TT
T
T
T
T
T T
T
T
T
$
T
T
T
T
T
T
T
T
TTT
T
T
T
T
TT
T T
T
CO2
CO2
CO2
CO2 CO2CO2CO2CO2
CO2
CO2
CO2
CO2
CO2CO2
CO2
CO2
CO2
CO2
CO2
T
FC D1-9
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
N
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
A
B
2/
5
/
2
0
2
1
3
:
1
2
:
3
1
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC9.01
MECHANICAL LEVEL 01
HVAC ZONE PLAN
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
1/16" = 1'-0"
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD
CC
1 3 10
10
16
16
20
20
22 25
25
Z
Y
V
S
N
K
H
E
B
27
27
2 4 5
18
D
F
G
AA
X
DD
U
Q
C
8
8
13
13
19
19
21
21
17
17
11
11
P
M
12
6
L
R
T
W
24 26
23
23
14
14
7 9
J
23.5
15
15
CCCC
1
1
3
3
10
10
16
16
20
20
22
22
25
25
ZZ
YY
V
V
SS
NN
KK
HH
EE
BB
27
27
2
2
4
4
5
5
18
18
DD
FF
GG
AAAA
XX
DDDD
UU
QQ
C
8
8
13
13
19
19
21
21
17
17
11
11
UPPER SCHOOL
SCIENCE LAB
230
PREP ROOM
229A
UPPER SCHOOL
SCIENCE LAB
229
WORKROOM
228
6TH -8TH
CLASSROOM
226
6TH -8TH
CLASSROOM
224
READING ROOM
231
STAIR 2
STR-2-2
6TH -8TH
CLASSROOM
220
6TH -8TH
CLASSROOM
216
6TH -8TH
CLASSROOM
214
STAFF
WORKROOM
208
SYSTEMS ADMIN.
209
UNASSIGNED
210
6TH -8TH
CLASSROOM
219
6TH -8TH
CLASSROOM
217
COLAB
218
COLAB
249
STORAGE
248
ELEV.
E-1-2
CUSTODIAL
242
STAFF TOILET
244
UNISEX TOILET
247 DATA
240ELECT
241
STAIR 1
STR-1-2
COLAB
211A
5TH GRADE
CLASSROOM
211
STAFF LOUNGE
207
UNASSIGNED
204
UPPER
DIRECTOR
203DEVELOPMENT
DIRECTOR
202
COMMUNICATIONS
DIR.
201
5TH GRADE
CLASSROOM
212
BOYS'
RESTROOM
245
GIRLS'
RESTROOM
246
HALLWAY
250
ROOF DECK
253
GIRLS'
RESTROOM
238
BOYS'
RESTROOM
237
6TH -8TH
CLASSROOM
221
6TH -8TH
CLASSROOM
223
6TH -8TH
CLASSROOM
222
6TH -8TH
CLASSROOM
215
6TH -8TH
CLASSROOM
225
6TH -8TH
CLASSROOM
227
6TH -8TH
CLASSROOM
213
COLAB
254
ROOF DECK
254
OPEN OFFICE
252
HALLWAY
251
HALLWAY
255
FC A2-1
FC A2-2
FC A2-3 FC A2-4
FC A2-6
FC A2-7FC A2-8
FC A2-9
FC A2-10 FC A2-11
FC A2-12
FC A2-13 FC A2-14
FC A2-15
FC C2-10
FC C2-9
FC C2-8
FC C2-6
FC C2-7
FC C2-5
FC C2-4
FC C2-3
FC C2-2
FC C2-11 FC C2-12
FC C2-13
FC C2-14
FC C2-15
FC C2-16
FC C2-17 FC C2-18 FC C2-19 FC D2-1 FC D2-2 FC D2-3 FC D2-4 FC D2-5
FC D2-6
BUSINESS
OFFICE
205
HUMAN
RESOURCES DIR.
206
MOTHER'S ROOM
207A
FC A2-5
CC
1 4 10 15
18 22 25 27
Z
20
AA
2 635
2321
11
24 26
12 179
D
G
B
C
F
H
K
M
L
N
S
P
R
T
Q
U
XY
W
V
DD
19
14 167
E
138
J
BB
23.5
ELECT
233
DATA
233B
CUSTODIAL
235
ELEV.
E-2-2 UNISEX TOILET
239
STAFF TOILET
236
FC C2-21
SS 1-2
PP
MM
12
126
6
LL
RR
TT
W
W
24
24
26
26
23
2315
15
14
14
7
7
9
9
BBBB
AA
JJ
SS 1-1 T
T
TT
T
TTT
T
T
T
T
TT
T
T
T
T
T
T
T
T
T
T
CO2CO2
CO2
CO2
CO2
CO2
CO2
T T
T
T
T
T
T
T
T
T T T T T
T T
T
CO2
CO2
CO2
CO2
CO2
CO2 CO2 CO2 CO2
CO2 CO2
T
ELEV. MACH.
ROOM
234
FC C2-20
T
EXP. 06/30/21
No.M33701
R
EGISTER E D P R O FESSIONA
L
E
N
G
I
N
EER
S
TATEOFCA L I F O R NIAMECHANICAL
AS H L E Y M.DAVIT
T
THE PLANS AND SPECIFICATIONS HEREIN ARE
ACCO ENGINEERED SYSTEMS, INC. ("ACCO"),
OWNED BY AND FOR THE SOLE USE OF
AND MAY NOT BE REPRODUCED OR USED BY
OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED
BY ACCO IN WRITING. ACCO CANNOT ACCEPT
ANY LIABILITY, WARRANTY, OR OBLIGATION IN
THE EVENT OF UNAUTHORIZED USE.
265 McCORMICK AVENUE
COSTA MESA, CALIFORNIA 92626
(714) 352-2226
N
Title
Project
Revisions
Scale
Drawn By
Job Number
Designed By
No.Date
of Sheets
Project Manager
Checked By
Description By
A
B
2/
5
/
2
0
2
1
3
:
1
2
:
4
6
P
M
P. ABERCROMBIE A. DAVITT
P. ABERCROMBIE
AC9.02
MECHANICAL LEVEL 02
HVAC ZONE PLAN
3443 PACIFIC VIEW DR.
CORONA DEL MAR, CA 92625
HARBOR DAY SCHOOL
R. REPP
652051
X:\
6
5
2
0
5
1
&
6
4
1
1
7
1
_
H
A
R
B
O
R
D
A
Y
S
C
H
O
O
L
\
0
0
3
-
E
-
H
V
A
C
\
R
e
v
it
(
C
e
n
t
r
a
l
M
o
d
e
l
)
/
H
D
_
P
1
_
M
_
M
D
L
_
A
C
C
O
.
r
v
t
1/16" = 1'-0"
A 08/16/19 100% DESIGN
DEVELOPMENT
PKA
B 10/25/19 1ST CITY SUBMITTAL PKA
C 02/14/20 2ND CITY SUBMITTAL HH
D 05/01/20 3RD CITY SUBMITTAL CD
1 01/22/21 CITY PERMIT
AMENDMENT
CD