Contractor's Material and Test Certificate for Underground Piping
Procedure: Upon completion of work, inspection and tests shall be made by the contractors representative and witnessed by
an owner's representative. All defects shall be corrected and system left in service before contractor's personnel finally leave
the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners,
and contractor. It is understood the owner's representative's signature in no way prejudices any claim against contractor for
faulty material, poor workmanship, or failure to comply with approving authority's requirements or local ordinances.
Property Name: "Ocean 48"
Property Address: 151 Newport Center Dr., Newport Beach, CA 92660
Date: 5/23/2024
Accepted by Approving Authorities (Names): Newport Beach Fire Department
Address: 100 Civic Center Drive, Bay 2B, Newport Beach, CA 92660
Installation conforms to accepted plans: ■ Yes No
Plans
Equipment use is approved: ■ Yes No
If no, explain deviations:
Has person in charge of fire equipment been instructed as to a Yes
No
location of control valves and care and maintenance?:
If no, explain:
Instructions
Have copies of the following been left on the premises?:
1. System components instructions Yes ■ No
2. Care and maintenance instructions Yes ■ No
3. NFPA 25 Yes ■I No
Location of
Syste
Supplies Buildings:ew
p151 Nort Center Dr.
m
Pipe Types and Class:
Type Joint:
C-900 P.V.C, Class 150, Stainless Steel Solid Sweep where Pipe passes underfooting. "Tyton"
Slip joint, Ductile Iron, UL Listed.
Pipe conforms to NFPA 24 & NBFD standard
■ Yes No
Underground
Fittings conform to NFPA 24 & NBFD standard
■ Yes No
Pipes and
Joints
If no, explain:
Joint needing anchorage clamped, strapped, or blocked in
■ Yes No
accordance with NewD & NFPA 24 standard
If no, explain:
Test Descriotion:
Flushing
Flow the required rate until water is clear as indicted by no collection of foreign material in burlap bags as outlets such
as hydrants and blow -offs. Flush at flows not less than 390 GPM (1476 Umin) for a 4" pipe, 880 GPM (3331 Umin) for
a 6" pipe, 1560 GPM (5905 L/min) for an 8" pipe, 2440 GPM (9235 Umin) for a 10" pipe, and 3520 GPM (13323 L/min)
for a 12" pipe. When supply cannot produce stipulated flow rates, obtain maximum available.
Hydrostatic
Hydrostatic tests shall be made at not less than 200 psi (13.8 bars) for two hours or 50 psi (3.4 bars) above static
pressure in excess of 150 psi 10.3 bars for two hours.
Leakage
New pipe laid with rubber gasket joints shall, if the workmanship is satisfactory, have little or no leakage at the joints.
The amount of leakage at the joints shall not exceed 2 gts/hr (1.89 Uhr) per 100 joints irrespective of pipe diameter.
The leakage shall be distributed overall joints. If such leakage occurs at a few joints, the installation shall be
considered unsatisfactory and necessary repairs made. The amount of allowable leakage specified above may be
increased by 1 fl oz per inch valve diameter/hr (30 mU25mm/h) for each metal seated valve isolating the test section. If
dry barrel hydrants are tested with the main valve open so the hydrants are under pressure, an additional 5 oz/min (150
mUmin) leakage is permitted for each hydrant.
piping flushed according to
standard by ■ Yes No
Flushing
DCFlreTestsin:
7Newundergroundground
g flow was obtained? ❑� public water ❑ tank or reservoir ❑fire pump
hat type of opening?
Hydrostatic
All new underground piping hydrostatically tested at 2DD psi for 2 hours
Test
Joints covered ■ Yes I No
Leakage
Total amount of leakage measured D gallons for 2 hours
Test
Allowable leakage .5 gallons for 2 hours
Number installed: D Type and make:
Hydrants
All operate satisfactorily: Yes IND
Water control valves left wide open ■ Yes No
Control
If no, state reason:
Valves
Hose thread of Fire Department connections and hydrants interchangeable with those of Fire Department
answering alarm ■ Yes I No
Date left in service
Remarks
System was required to always be in service during Tenant Improvement.
Name of Installing Contractor:
DC Fire Protection
Test
For Property Owner (signed) TITLE DATE
Witnessed
By
F� prinkler o ractor (signed) TITLE DATE
Owner 5/23/2024
Additional Explanation and Notes: