HomeMy WebLinkAboutW_5325_SIRWD STANDARD WATER NOTES: A. THE WATER SYSTEM IS TO BE INSTALLED BY THE DEVELOPER. ALL WATER SYSTEM WORK SHALL CONFORM TO THE DISTRICT'S "PROCEDURAL GUIDELINES AND GENERAL DESIGN REQUIREMENTS" AND" CONSTRUCTION MANUAL", AS LAST REVISED. B. THE DISTRICT ENGINEERING OFFICE SHALL BE CALLED FOR INSPECTION FOUR(4) WORKING DAYS BEFORE START OF WORK AT (949) 453-5615. C. A PRE-CONSTRUCTION CONFERENCE OF REPRESENTATIVES FROM AFFECTED AGENCIES AND THE CONTRACTOR SHALL BE HELD ON THE JOB .SITE 48-HOURS PR[OR TO START OF WORK. D. THE WATER SYSTEM IS TO BE STAKED BY THE DEVELOPER'S ENGINEER AT A MINIMUM 50-FOOT STATIONING IF THERE ARE NO EXISTING CURBS. E. ANY WATER SERVICE FOUND TO BE WITHIN A DRIVEWAY OR SIDEWALK SHALL BE R&\'.IOVED COMPLETELY AND REINSTALLED AT THE PROPER LOCATION AT NO COST TO THE DISTRICT. F. ALL MAIN LINE VAL YES SHALL BE MAINTAINED SO AS TO BE ACCESSIBLE DURING TRACT DEVELOPMENT, AND ALL VAL VE STEM TOPS HA YING OVER 48-INCHES OF COVER WILL REQUIRE AN EXTENSION AS PER ORA WING W-23. G. IN RESIDENTIAL STREETS, TIIE TOP OF THE PIPE, 10--INCHES AND SMALLER, SHALL BE A MINIMUM OF 42-INCHES BELOW THE FINISHED STREET SURFACE AND 48-INCHES BELOW FINISHED STREET SURF ACDE ON ALL PRIMARY AND SECONDARY STREETS. H. ALL FIRE HYDRANTS SHALL BE SET WITH THE BOTTOM FLANGE 4-INCHES ABOVE THE CONCRETE PAD OR SIDEWALK WITHOUT THE USE OF SPOOLS AND SHALL BE LOCATED A MINIMUM OF 3 FEET FROM THE ECR OR BCR AT INTERSECTIONS. I. ALL WATER MAINS 6-INCHES THROUGH 12-INC!IES SHALL BE CLASS 200, A WW A C-900 PVC, UNLESS OTHERWISE NOTED. J. NO TAPS OR OTHER CONNECTIONS SHALL BE MADE TO EXISTING DISTRICT WATER MAINS PRIOR TO CONDUCTING AN APPROVED PRF~5SURE TEST ON THE NEW WATER DISTRIBUTION SYSTEM. TAPPING SLEEVES SHALL BE PRESSURE TESTED IN AN APPROVED MANNER IN THE FIELD, IN THE PRESENCE OF THE DISTRICT INSPECTOR, PRIOR TO TAPPING THE MAINLINE. TAPPING OF THE MAIN LINE SHALL NOT PROCEED UNLESS A DISTRICT INSPECTOR IS PREESNT. K. WHERE METERS AND METER BOXES ARE LOCATED WITHIN SLOPES, THE ANGLE METER STOPS SHALL BE SO LOCATED THAT THE METERS AND BOXES WILL BE PARALLEL AND FLUSH, RESPECTIVELY, WITH THE FINISHED SURFACE. L. NO METER IS TO BE PLACED WITHIN ANY SIDEWALK OR DRIVEWAY AREA. M. CURBS SHALL BE INSCRIBED WITH A "W' INDICATING LOCATIONS OF ALL DOMESTIC WATER SERVICES BY MEANS OF A 4" GRINDER. N. INDIVIDUAL PRESSURE REGULATORS ARE TO BE REQUIRED BY THE UNIFORM PLUMBING CODE IF AVERAGE STATIC PRESSURE IS 80 PSI OR MORE. 0. CURBS SHALL BE INSCRIBED WITH TIE DOWNS FOR ALL VAL VE LOCATIONS BY MEANS OF A 4" GRINDER. P. THE CONTRACTOR SHALL EXPOSE ALL JOIN POINTS TO THE EXISTING RECLAIMED WATER SYSTEM FOR VERIFICATION OF HORIZONTAL AND VERTICAL LOCATION BEFORE CONSTRUCTION. Q. FINAL INSPECTION FOR WATERLINE MUST INCLUDE WATER SAMPLES THAT WILL BE TESTED FOR CONDUCTIVITY, TURBIDITY, AND ODOR. THE TURBIDITY MUST BE LESS THAN 2.5 NTU AND THE ODOR MUST BE LESS THAN 1.0 TON, NOT TO INCLUDE CHLORINE ODOR, TO BE ACCEPTABLE. R. THE CONTRACTOR WORKING ON IRWD WATERLINES MUST HA VE A C-34 LICENSE OR A CLASS A GENERAL CONTRAC..'TORS LICENSE. S. CON'IRACTOR SHALL OBTAIN AND SHOW PROOF OF A DEWATERING PERMfl' FROM THE STATE OF CALIFORNIA, REGIONAL WATER QUALITY CONTORL BOARD PRIOR TO THE START OF CONSTRUCTION. IRWD CONSTRUCTION NOTES : QUANTITIES: CONSTRUCT NEW I" SERVICE CONNECTION TO EXIST. 6" PVC PIPE IN ACCORDANCE--I EA. WITHIRWD STANDARDS W-1 & W-3 AND DIRECTIONFROMTIIB IRWDINSPECTOR. INSTALL NEW I" DOMESTIC WATER METER PER IRWD STA.."!DARD W-1. -------! EA. REMOVE CORP. STOP AND INSTALL BRASS PLUG AT MAIN AND ABANDON EXISTING --1 EA. l" SERVICE IN ACCORDANCE WITH IRWD STANDARDS. REMOVE EXIST. WATER METER AND RETURN TO IRWD ------------! EA. SAW-CUT STREET, BACKFILL AND REPAVE WATER SERVICE TRENCH PER CITY----! EA. OF NEWPORT BEACH STANDARD 105-L CYPRESS STREET ~====~~~J=.-.c==<i"===-===1=~5~NT<39~•~~•1~5~Ep=====--=~~=,=~===~===~==.c==-==.c=~~~~-~--+ Q --~XIST. 8" VCP_SEWER MAIN ON C.L. Q -t _,,rEXIST. 2" GAS MAIN ----------------G------t---G----~c-t---0----+---+---+----~------- 1 ~EXIST. 6" ACP WATER MAIN (PER IRWD AS-BUILT NO. 1064) ______ _,, ____ ----------~---,---:a.-i---'lf•-...,_-----+-_,..1--1--------::,,,:=EX:-::'.IST. CURB &~G~U~T=TE~R:---w-- ~,:;,---...... -t-~--1~=-=-::-'---s~-------.------ E-< ~"' z P.L. ISil ,j ~~ ,j 0.. ~e: 0.. co .L. 0 + ~ "' '°1 "' ~ C\ll ~I C\l ;t, "' R/w (\J I. C\l 2. 20362 S.W. CYPRESS ST. 20352 S.W. CYPRESS ST. 20342 S.W. CYPRESS ST. • ~ • u NOTICE TO CONTRACTORS: 1-------------1 PURSUANT TO ASSEMBLY BILL 3019, NO EXCAVATION PERMIT rs LEGEND: DIG ALERT CALL TOLL FREE 1-800-422-4133 AT LEAST TWO DAYS BEFORE YOD DIG UNDERGROUND SERVICE ALERT OF SOUTHERN CALIFOR.c'\!IA VALID UNLESS THE FOLLOWING IS PERFORMED: 1. UNDERGROUND SERVICE ALERT HAS BEEN CONTACTED AND HASPR.OVIDEDINQUIRYI.0.# _______ ~ 2. 11-JB UNDERSIGNED AGREES TO CONTACT AND OBT AlN AN INQUIRY 1.D. # FROM UNDERGROUND SERVICE ALERT (I-800--422-4133) AT LEAST TWO (2) WORKING DAYS PRJOR TO TIIE COMMENCEMENT OF EXCAVATION. S1GNED:. J. WM ----WATER METER FHA ----FIRE HYDRANT FDC ----FIRE DETECTOR CHECK EM --·-ELECTRIC METER TB ----TELEPHONE BOX DWY. ---DRIVEWAY A.C. -ASPHALT WV ----WATER VALVE PfV ----POST INDICATOR VALVE D£SIGNED: CH£CK£D: PJD :r o------J1f ---STREET LIGHT ~ ----SEWER MANHOLE (D ----TELEPHONE MANHOLE -'i;f--·-· LJG!IT ON WALL ' /RY/NE RANCH WATER DISTRICT Irvine, Calil f.1 8iim.J IIIVINIIWICII Jl'l'III Dlffiltt IRVINE RANCH WATER DISTRICT '"""""'"' OF DOMESTIC WATER ,..,..,_... ,,,.,.....,_ ----==""'-"'-=-----------r,_..,,..., SUl'ElMm) fl'f ~' :1J &:!' «/p,---/. REllfEltEV BY/7 .. l:M I ~ z ...... ,_;j I C) 0 -0 C\l + C\l O') ~ > i---. ~ 0 0 ~ ~ :::i= u ~ 0 • ~ • u PREPARED BY: DUCA-McCOY, INC. 3840 E. COAST HWY. CORONA DEL MAR, CA 92625 (949) 675-4487 PREP~~ER THE~SIONOF: VICINITY MAP N.T.S. E T MESA DRIVE • .. .,_: IJ PROJECT LOCATION N.T.S. 20' o· 20· 40' I I I I I GRAPHIC SCALE: 1 " =20' RCE# 24668 EXP. 12-31-09 DATE:t ·2.3,~ PETE DUCA IRWD CODE #5206 20352 CYPRESS STREET WATER METER RELOCATION PLAN PROJECT NUMBER _§..?..Q§ __ LEHN RESIDENCE 20352 CYPRESS STREET SANTA ANA HEIGHTS, CA SHEET 1 OF 1