Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutExhibit 5 - Exhibit 5 - 4-9-08 Fluor ReportExhibit No. 5
Fluor report dated April 9, 2008
S-(
THIS PAGE
LEFT BLANK
INTENTIONALLY
BLANK
s.
City of Newport Beach
FLUOR,
Hoag Hospital Cogeneration Facility
Cooling Tower Plume Mitigation
Option 3A - Air Cooled Heat Exchanger (ACHE)
Design/ Implementation Report
PROJECT NO.: 0OA3YZ
This document has been revised as indicated below. Please replace all pages of this document and destroy the superseded copies.
Rev.
Date
Description
By
Chk'd
Approval
Disc
Lead
Fluor City of
Newport
Beach
0
09Apr08
Final Report
FN
N1W
FN
FN .c
Rl Entire Document Issued this
Revision
Remarks:
❑ Revised Pages Only Issued
this Revision
Revised Page Nos.
r-3
City of Newport Beach
Hoag Memorial Hospital Presbyterian
Project No. OOA3YZ
Design/ Implementation Report
Table of Contents
FLUOR,
DATE 07Apr08
PAGE 2 OF 7
Rev A
1.0 INTRODUCTION ......................................................................................................................................... 3
1.1 PURPOSE OF PRE -SCHEMATIC DESIGN........................................................................................... 3
1.2 SCOPE OF PRE -SCHEMATIC DESIGN................................................................................................4
2.0 COOLING TOWER RETROFIT- OPTION 3A PRE -SCHEMATIC DESIGN.............................................4
ExistingSystem Description..............................................................................................................................4
2.1 PROPOSED SYSTEM............................................................................................................................4
2.2 VALUE ENGINEERING ITEMS................................................................................................................ 6
3.0 APPENDICES: ............................................................................................................................................ 7
A Construction budget estimates........................................................................................................... 7
B. Basis of Design Narrative.................................................................................................................... 7
C. Drawings and sketches....................................................................................................................... 7
D. Cooling Tower Manufacturer (Marley) —ACHE sizing and performance analysis ............................... 7
E. NCWD and Air2Aif hybrid tower systems..........................................................................:................ 7
F. Sound attenuating louver..................................................................................................................... 7
G. Trending Data and plume observation photos for 18 events in January and February 2008 — Report
date March 5, 2008 (update of the February 21, 2008 report)........................................................................ 7
H. Plume mitigation measure summary — Syska Hennessy, April 9, 2008 ............................................. 7
City of Newport Beach_ Hoag Hospital_optlon implementation review—Rev Oa_4_09_08.doc
s•y
City of Newport Beach
Hoag Memorial Hospital Presbyterian
Project No. OOA3YZ
Design! Implementation Report
1.0 INTRODUCTION
FLUOR®
DATE 07AprO8
PAGE 3 OF 7
Rev A
Fluor Enterprises, Inc. was requested by Newport Beach City Planning Department to provide a pre -
schematic design and budget estimate for tower plume abatement system, option 3A as it was
described in Fluor's study repot "Plume Mitigation Review" issued on 19MarO8 (refer to paragraph 2.1
for option 3A scope description).
Hoag's engineer (Syska Hennessy Group) and Fluor were assigned the task of providing engineering
services for a pre -schematic design and preparation of a Rough Order of Magnitude (ROM)
construction budget estimate for option 3A On 03Mar08, a phone conference was held to kick off the
pre -schematic design effort. Subsequent to the telephone conference, the team met on 31 Mar08 at
Hoag Hospital for a site visit, face to face discussion of the basis of design narrative and the criterion
and Hoag's requirement for the budget estimate. Note that during the meeting, although not in the
scope of work, the issues of heat plume and two (passive and fan assisted) solutions were discussed
but the team agreed to postpone further investigation of these issues to a future date.
In the first week of April 2008, the design team was asked about SPX Cooling Technologies new
wet/dry package tower and Ai12Air plume abating system and their applicability to Hoag Hospital's
cooling tower retrofit project for mitigation of water vapor plume. Our assessment of these new
systems by SPX is as follows:
Air2Air technology:
AI2Air technology application to Hoag Hospital's existing towers, due to seismic and structural issues,
is not feasible. The existing cooling towers would need to be replaced making OPTION 3-1 a better
choice. (See Appendix E)
NCWD (wet/dry) package tower system
NCWD (wet/dry) package tower application for Hoag Hospital is an option similar to OPTION 3-1
(installing new towers with plume mitigation system) which was discussed in Fluor's previous study
repot "Plume Mitigation Review" dated 19MarO8. The advantage of a NCWD tower is that they are
factory fabricated and assembled package units, fairly small (24' H X 22' L X 14' W), and cheaper than
a field erected tower. (See Appendix E)
Utilization of field erected towers with integrated plume mitigation system (option 3-1) is recognized as
the most effective solution. However its estimated construction budget was highest of all options ($9.3
MM) that were reviewed. Although a budget estimate for NCWD tower system has not been prepared,
it is our belief that this system installation would not be much cheaper than the previously discussed
hybrid system in OPTION 3-1.
1.1 PURPOSE OF PRE -SCHEMATIC DESIGN
The purpose of the pre -schematic design is to provide adequate information to the estimators enabling
them to provide a Rough Order of Magnitude (ROM) construction budget estimate (+1-30%) for the
City of Newport Beach_ Hoag Hospital option implementation review—Rev Oa_4_09_08.doc
5--S'
City of Newport Beach
Hoag Memorial Hospital Presbyterian
Project No. OOA3YZ
Design/ Implementation Report
FLUOR.
DATE 07Apr08
PAGE 4 OF 7
Rev A
implementation and construction of option 3A. The budget estimates have been prepared by three
firms (McCarthy, Syska Hennessy and Fluor). (See Appendix A)
1.2 SCOPE OF PRE -SCHEMATIC DESIGN
The scope of the pre -schematic design is to:
• Provide pre -schematic Basis of Design (See Appendix B)
• Provide preliminary selection and sizing of equipment (See Appendix D)
• Provide an equipment arrangement/Layout (See Appendix C)
• Determine space requirement for equipment installation (See Appendix C)
• Determine efficacy of the system
• Provide Rough order of Magnitude (ROM) budget estimate (+/-30%) associated with
implementation of the design option 3A (See Appendix A)
2.0 COOLING TOWER RETROFIT -OPTION 3APRESCHEMATIC DESIGN
Existing System Description
The existing coding tower system consists of a Marley (SPX Cooling Technologies) Class 400,4 -cell
mechanical, FRP field erected, counter flow cooling tower and the associated pumping system for
delivering cooling tower water (Condenser Water) to remove heat from engine lube oil cooler, engine
intercoolers, electric chiller and absorption units. The warm condenser water return passes through
the cooling towers, rejecting the heat to atmosphere. This heat removal is accomplished mostly by
water evaporation, which at times, due to atmospheric conditions such as high relative humility and
low temperature, forms a thick water vapor plume.
2.1 PROPOSED SYSTEM
Proposed design option 3A provides solution to the aesthetic issues associated with formation of the
vapor plume as described in this section. This option entails design/modification to mechanical,
automation, structural and architectural systems and has an impact on the cost and operation of
cogeneration plant. Refer to Appendix A for affected trades and ROM construction budget estimate.
Proposed System Design and Operation
Option 3A system consists of a side stream air to water heat exchanger (HX) with three HX sections
and six VFD driven fans, two VFD driven condenser water pumps and associated controls.
This system is designed to remove most of the heat load from the cooling tower by rejecting the heat
using an Air Cooled Heat Exchanger (ACHE). The ACHE is sized to fit within the proposed mechanical
yard (50'X 40') area located next to the existing cooling towers (See Appendix DD).
The ACHE is piped to the existing tower piping system in series so that the condenser water is first
passed through the ACHE, removing approximately 65% of the overall heat load. Then condenser
water through cooling tower rejects the remaining 35% of the heat load through cooling tower. The
reduction of heat load on the wet cooling tower reduces water evaporation/condensation as well as the
City of Newport Beach_ Hoag Hospital_option implementation review—Rev Oa_4_09_08.doc
S•b
City of Newport Beach
Hoag Memorial Hospital Presbyterian
Project No. 0OA3YZ
Design! Implementation Report
FLUOR®
DATE 07AprO8
PAGE 6 OF 7
Rev A
tower discharge air temperature. Discharge air temperature and relative humidity results in substantial
reduction in the plume formation.
Note that originally this option also intended to incorporate outside air intake openings with motorized
dampers in the fan section of each cooling tower cell. However, due to structural issues of the existing
towers and the potential for costly structural upgrades, this design feature was deleted from the scope
of work with minimal effect on the proposed design performance.
This design also requires revision and changes to the Building Management System (BMS) in both
programming and hardware. The BMS new control points are associated with the new heat exchanger,
pumping system controls, the new weather station and methane sensors. The condenser water
supply temperature will be reset per design conditions in the basis of design narrative and the ambient
temperature/relative humidity information from weather station will be used to energize or de -energize
the plume abatement system.
Energy efficiencyfconsumption
All engineered solution requires some form of energy to produce useful work In providing engineering
solution, the first step is to define the need and/or the problem and then the engineer using the best
available technology provides an energy efficient solution - such as an energy efficient air conditioning
system for cooling of an office or hospital building.
The solution proposed for plume abatement, OPTION 3A, also will require additional energy in form of
electricity to run the VFD driven fans and the pumps. A well though sequence of operation and post
installation fine tuning of the system is a must in order to minimize energy consumption. (See
Appendix H)
Sound and noise issues
A detail sound study of this system has not yet been performed. However in the,pre-schematic design
of this project, we have assumed and priced installation of sound attenuating louvers at the ACHE
outside air intake (See Appendix E for sound attenuating louver).
Impact ongoing operation
Based on conversation with Hoag's representative and engineers, it is possible to interrupt condenser
water system during winter time and/or yearly maintenance shut down to install the new pipes and
valves without any adverse effect on the ongoing operations. Note that if required, there are both
temporary tower and chiller system that could be rented for longer shut down and/or emergency
backup.
System efficacy and performance
Marley's analysis of the data and sizing of the equipment indicates that the ACHE as designed is
capable of reducing the quantity and occurrences of plume by more than 50% over a wide range of
ambient conditions, when operating at winter load of 12,600 gpm/8 degree F range. This load is 100%
of the winter system capacity. The ACHE manufacturer also indicates that during current winter
operation of approx. 9,000 gpm 18 degree F range, the ACHE will take the full load and there would be
absolutely no chance of plume formation.
City of Newport Beach_ Hoag Hospital option implementation review_Rev Oa_4_09_08.doc
City of Newport Beach
Hoag Memorial Hospital Presbyterian
Project No. 00A3YZ
Design/ Implementation Report
Construction Budget Estimate (Rough Order of Magnitude)
FLUOR®
DATE 07Apr08
PAGE 6 OF 7
Rev A
McCarthy, Syska & Hennessy and Fluor prepared three separate ROM construction budget estimates.
All estimators adhered to the following criteria, requested by Hoag Hospital representative, to prepare
their estimates. (See Appendix A)
1. Alternate Add cost to cover additional sound attenuation and roof above ACHE $1.00 MM
2. Landscape allowance $75 K
3. Site electrical work (Southern California Edison) — XFMR installation $250K
4. Permitting fees (City, OHSPD, Calif. Coastal Commission...) 5% of total const cost
5. Escalation
6. General Conditions
7. A/E Fees
8. Soft cost ( Hoag's PM)
9. Contingency
10. Fee/Insurance/Bond
80/o/year (1.5 years)
9-12 months
10%
2%
5%
$0.714 MM
Comparing the three ROM budget estimates, excluding the allowance for sound mitigation, they are
$5.1 MM (Fluor), $5.8 MM (Syska) and $6.7 MM (McCarthy). (See Appendix A)
Note that until a sound study is done, it would be difficult to say what the cost associated with sound
mitigation would be. Note that McCarty has an allowance of $0.56 MM for sound mitigation (Altemate
Add) compared to Fluor and Syska assumption of $1 MM. Due to uncertainty and large variance in
sound mitigation budgets, these cost are shown below the line and are not included in the above ROM
budget costs.
To obtain a more accurate estimate, 60-90% design documents are required.
2.2 VALUE ENGINEERING ITEMS
There are equipment and systems that could be deleted or numbers be reduced as the design
progresses forward.
These items are as follows:
1. Reduce number of VFDs for ACHE from six to two
2. Revise number of control points associated with items in line "1"
3. Delete Stainless Steel support for ACHE
City of Newport Beach_ Hoag Hospital_ option implementation review—Rev Oa_4_09_08.doc
S.81
City of Newport Beach
Hoag Memorial Hospital Presbyterian
Project No. 00A3YZ
Design/ Implementation Report
3.0 APPENDICES:
A Construction budget estimates
B. Basis of Design Narrative
C. Drawings and sketches
FLUOR,
DATE 07Apr08
PAGE 7OF7
Rev A
D. Cooling Tower Manufacturer (Marley) —ACHE sizing and performance analysis
E. NCWD and Ai2Air hybrid tower systems
F. Sound attenuating louver
G. Trending Data and plume observation photos for 18 events in January and February 2008 —
Report date March 5, 2008 (update of the February 21, 2008 report)
H. Plume mitigation measure summary — Syska Hennessy, April 9, 2008
City of Newport Beach_ Hoag Hospital_ option implementation review—Rev Oa_4_0g_08.doc
s•9
City of Newport Beach
Hoag Memorial Hospital Presbyterian
Project No. OOA3YZ
Design/ Implementation Report
Appendix A
Construction Budget Estimates
• Fluor Enterprises, Inc.
• Syska & Hennessey Group
• McCarthy
A- Appendices City of Newport Beach—Budget Est Rev0 4AprO8.doc
FLUOR.
DATE 8AprO8
Rev 0
5-10
Hoag Memorial Hospital Presbyterian
Cogen Building Cooling Tower Plume Mitigation
Option 3A - Air Cooled Heat Exchanger
Originator: CS
FLUOR
'ROM- Master Planning
4/2/2008
Approvers: MS 8 FN
Rev.'1 (419108)
DESCRIPTIONS
SCOPE -TASKS
QT
UM
I Manhours
Unil To.,
Labor$
Rate Cost
Material$
I Unit Pdce Cast
Subcontract$
Unit Rate I Cost
Engr Equip $
I Unit Prise I Cost
Total$
Unit I Cost
CONCRETE
Concrete work.
300
EY'
:5
1500
$110.00
$165;000 $
150
$45,000
3.
- so
$ -
$0.
$0.00
$210.000
F0m1Wefk
1
LOT
750
750
$110.00
$82,500 $
7;500
$7,500
$.
- $0
$ -
$0
$0.00
$90,000
Methene, Membrane
1
LOT
10
10
$110.00
$1;100 $
100.000
$900,000
$
- so
$ -
$0
'$0100
$101,100
Grading and Excavation
166
CY
.0.25
42
$110:00
$4,565 $
50
$8;300
$
- $0
$ -
$0
.$0.00
$12,B65
Survey Area
2
MEN
4
8
$110.00
$880 S
-
$0
$
- $0
$ -
$0
50.00
5880
Install Erosion Barder
330
LF
0.05'
17
$110.00
$1,815 $
2
$660
$
- '$0
$ -
$0
$0.00
$2,475
Front. End Loader, Diesel 170 HP, articulated, 3V2'yd
1
WK Rental
0
$0:00
so S
1,500
Si.500
$
- $0
$ -
$0
'$0.00
$1,500
bucket Case 821
103CONGRETErw Tutel
-
F 1 ++ +v
+i.i lr,
255 860? .--Z
„
..
STRUCTURAL/A RCHITECTU RAL
Rebar
12
TON
20
240
$110.00
$26,400 S
1,000
$12,000
S
- SO
S -
$0.
.$0.00
$38,400.
Wall Louvers
1
LS
60
60
$110.00
$6,600 S
104',000
$104,000
$
- $0
$ -
$0.
'$0.00
$110,600
33000�ST„n.'?t,,.,,gt�?116000�IIIj[t.+-;p,�O;U�I�1uijk�u'pr;,-,Oa
1rp
�t�.,11,P+S149-000:
MECHANICAL EQUIPMENT
.Air Cooled Heat Exchanger
1
EA
300
300
$125.00
$37,500 S
-
$0
$
- $0
$ 856,900
$856;900
$0:00
$894,400
Walkways and Ladders
1
LS
100
900
$125.00
$12(500 $
-
s0
S
- $0
$ 12,000
$12,000
$0:00
$24,500
Condenser Water Booster Pumping System
2
EA
20
40
$125.00
$5,000 $
-
$0
S
- $0
S. 25,000
$59.000
$0.00
$55,000
'RigginglCrane
1
LS
40
40
$125.00
$5,000 $
50,000
.$50,000
S
- $0
$ -
so
$0.00
$55,000
VFD 150 HP
2
EA.
50
'100.0
$115.00
$1.1,500 S
20;000
$40,000
S
- $0
S -
'$0
$20,000
$51,500
VFD 40 HP
6
EA
24
144.0
$115.00
$16,560 $
axo
$Si,000
'S
- $0
'S -
so
$8,500
$67,560
40 MECNANICALEgIIIPMENT Total;'lj, ],, i.1�i[_u„ ;,
is �f,;;5340�,4r 724.O�ipg7300�1�'�8808D
r 71 7e,50p�;4{4+iW,0�,ayi;1:'00�_�I„t.ji4�ijRB�,�..__ry�°918�900�I$78500
ye;r$174719803
„e....�....._.___. .._a._ ..
y„il
PIPING
24" Condenser Water Pipe STD.
400
LF
0.8
320.0
$115.00
$36,860 $
62
$24,800
S
- $0
I$ -
'S0
$0.00
$61,600
20" Condenser Water Pipe STD
40
LF
0.8'
32.0
5115.00
$3;680 $
41.00
$1.640
$
- $0
$ -
$0
$0.00
$5,320
18" Condenser Water Pipe STD
150
LF
0.7
105.0
$115.00
S12,075 $
36.00'
$5,400
$
- $0
$ -
'so
$0:00
$17,475
14" Condenser Water Pipe STD'
70
LF
0.6'
42.0
$115.00
:$4,830 $
27.00.
$1,800
$
- $0
$ -
$0
$0.00
$6;720
24" Couplings
30
EA
9
270
$115.00
31050 $.
-
$0
S
- $0
$ -
$0
$0.00
$31,050
20" Couplings
8'
EA
7.9
63.2
$115.00
7268 $
-
$0
$
- $0
$' -
$0
$0.00
$7,268'
18- Coupling.
10
EA
7.1
71
$115.00
8165 $
-
$0.
$
- $0
$' -
$0
$0.00
$8;165
14" Couplings
8
FA
4
32
5115.00
3660 $
-
$0
s
- $0
$' -
so
$0.00
$3,680
24" ELL 90 STD
6
EA
1B
108
$i15.00
12420 $
600.00
$3,600.
$
- $0
$ -
$0
$0.00
$16;020
24" Flange 150 RF
10
EA
9
90
$115.00
10350 $
450.00
$4.500
S
- $0
$ -
'so
$0.00
$14,850
24 X 20 reducer ECC
1
EA
16.9
16.9
5715.00
9943.5 $
800.00
$Boo
$
- $0
It -
$0
$0.00
$2,744.
20 X 14 reducer ECC
1
EA
13.7
13.7
$115,00
1575.5 $
1,350.00
$1,350
$
- so
$, -
$0
$0.00
$2,926
24' Tee STD
2
EA
12
24
$115.00
2760. $
1.950.00
$3,900
$
- $0
$ -
$0
$0.00
$6,660
24" Control Valve
3
EA
25
75
$115.00
6625 $
9,000.00
$27,000.
$
- $0
$ -
$0
$0.00
$35,625.
14" Manuel Valve
6
EA
12.5
75
$115.00
8625 S'
2,350.00
$14,100
$
- $0
$ -
$0
$0.00
$22,725
Pipe Support
12
EA
14
468.0
$115.00
$19;320 $
150
$1,800
$
- 50
$. -
$0
'$0.00
$21,120
Plumbing
1
LS
0
0.0
$0.00
$0 '$
50,000
$50,000
$
- SO
$ -
$0
50.00
$50,000
(Storm Water Drainage, Trench Drain, Tle-ins)
53Y PIP1_NG xmTotal uS?eb='9'a,��b20L€a.:jil�. ;Pii+.', y� II�1'.I�1;1u7520��"TL_i 506�.y,,.,,�.�.,,: {v: b,1773 id.1!j1: aaafl512"j1140780I3._...:,,.N� 111;1,MOT uffO B�Ii+�Y�.:,�a•'_,%s"'�e0�{�;ji�!,�1.0,Rr-..'IL''.74 a`�.5,3139471.
Haag Memorial Hospital Presbyterian -
Cogen Building Coaling Tower Plume Mitigation
Option 3A . Air Cooled Heat Exchanger
Originator: CS
�b
ROM -.Master Planning
412/2008
Approvers: MS & FN
Rev. 1 (419108)
$81,312
DESCRIPTIONS I
SCOPE -TASKS
CITY
I UM
Marthare
Unit Total
Labor$
Rate Cast
Material $
Unit Price Cost
Subcontract
Uni[ Rate Cost
Engr Equip '$
Unit Price Cost
Total $
Unit Cast
ecce i eoeAL
Bulk Material and Equipment Freight (of material and 5 %
_
$81,312
equipment cost)
Sof. Coal (Hoag's PM) 2 %
:Single -ended Main Switchboard 1
FA 8
8.0 $115100
$920
$. 20,000
$20,000
$
- $0 $ -
'$0
$20;000
$20,920
Grounding System 1
LS O4.
64.0 $115.00
$7.360
$ 10;000
$10,000
'$
- $0 $ -
so
$10,000
$17,360
PVC U1G Conduit 1
LS 16
16.0 $115.00
$1.840
$5.60
$6.
$'
-. $0 $ -
$0
$6
$1,846
Name 12 Pull Box 424x3 1
EA 26
26.0 $115.00
$2,990
$1.631.25
$1,631
$
- $0 $
so
$1,631
$4,621
Wre and Cable 3.300
LF OA8
264 $115.00
$30,360
$3.10
$10,230
$
- $0 $ -
i$0
$3
$40,590
Light Fixtures 12
EA 4
48.0 $115.00
$5,520
$250.00
$3,000
S
- $0 $ -
so
$250
$8,520
Receptacles and Switches 6
EA 4
24.0 $115.00
$2,760
$40.00
$240
$
- $0 $ -
$0
$40
$3,000
%FMR Transformer 45KVA 480-120V 1
EA 20
20.0 $115,00
$2.300
$2,500
$2,500
$
- $0 $ -
I$0
$2,500
$4,800
Distribution Panel Board 3R w/mainbreker I
EA 8
8.0 $115.00
$920
$1,200
$1.200
$
- $0 5 -
so
$1,200
$2,920
Site Electrical Work 1
LS 0
0.0 $0.00
$0
$ -
30
$ 2500,,,000 $250,000 S -
'$0
$250,000
$250,000
fiO ELEGTRICALajary Total 2.v60� �+2,a ;? �';
54970
_1 ''T ^� g,,.;,48807� � 250000�i�µIWW�.J'. i.?�}D'U�B
;? ?tE353-777.
�`t-478x,,
.,y;;j1
INSTRUMENTATION
'Direct Digital Control (DDC) 30
EA 2
60.0 $100.00
$6,000
$ 3,000
$90,000
S
- $0 S. -
50
$0.00
$96,000
Methane Sensors. 3
LS 8
24.0 $100.00
$2,400
$ 2,600
$7,600
$
- $0 S -
So
$0.00
$10,200
AO'INSTRUMENTATION'"'y Tafals 1 3. il',npn Py"
�.."?m 9,40U�'s:y®,
f�.vt
�iFt00�.$ij;l�+ 7062001_.
......:u:.�...�r,100��,,.,.:ue4',Df"�
:
t.`ry."t`�li)i�}7-97800�!3-[j!.t'.,...
uY.ss,:i,00�'15.�u�tii,Lr�f�
ni5„a1x',`�,"s.?'
MM
E9,12�"g$
414970a
INDIRECT COST (OTHER COST)
Bulk Material and Equipment Freight (of material and 5 %
$81,312
equipment cost)
Sof. Coal (Hoag's PM) 2 %
$49,794
Escalation (an direct field labor and material) free first 8 %
$108,417
yr, 8% second yr, 4%half of the third year
Permit cost(OSHPD. City. CCG_ (5% of total 5 %
$124,485
construction cost) )
ArchitecturaVEngineering Fees (10%) 10 %
$248.970
Landscape 9 LS
$.
75;000 $75,000 $75,000
General Conditions 9 months 9 MONTH
$100.000
$900,000
g
TOTAL-IIJDIRECT„COST;'.,..',d!?$PedH�i��l1f).trC:v.I``�r_......::�_t00�_lwL.TS
y$�900.000
�t y� inn
$4,07718B,3,
Contingency 5% 5 %
$203,BB4
.��" '�4..:.':.�li:
..Flaw
,• ,.s, -,a. " ">aa''LSi�'T-£E�..za,4a©'
.$,,.w'- stcon noan- +elln sr, ^ '-
w `
TO$A��Includingcontingend�lF,aeI1n90Sance78ud'd�,
Allowance for Stainless Steel support for ACHE $. 125,000.00
P n -.1,7_0",,,, x1.n.�-w:n�la lti Haumw * :."m,,+l,neamns> arc c:G�en 3v j
"1 1G ARDI,TOTA4�ilq 'u igg koMingencylFeel,InsurarceSBontllta'{ $talntes teee�''IaupPnrf�hartlwa[e[for Ir„CoolpdWeet c an90 �, I.5 -W
'1
1
Hoag Memorial Hospital Presbyterian
Cogen Building Cooling Tower Plume Mitigation
Option 3A - Air Cooled Heat Exchanger
Originator:. CS
FLUOR
ROM—Master Planning
412/20D0
Approvers: MS & FN
Rev. 1. (419108)
DESCRIPTIONS
SCOPE -TASKS.
OTY
I UM
I Manhours
Unit To[el
tabor$
Rale Cos[
Material
Unit Price I Cost
Subcontract$
Unit Rale I Cast
Engr Equip$
I Unit Price I Cost
Tota l$
I Unit I Cost
r Adds (Allowance; if sound miHigation Is
then a. concrete enclosior with roof and
Senuator devices might be required:
Roof enclosure
Inlet/oullet sound affeneuator
'Fire sprinkler system
TOTAL
oe(wlow,oerRosasf±Ecowsrrtucnoncosr=-';:1
aura
]iSKA I IENNESS
•
CIknC'
Prol.'£t t f
MEF,
E G l vkL F( ,,445
BootEstldwA tl�1.N
Pnc wwYCNgMtd By
om:.'Hrii
-r LhL. tltti
H..g trfgmhl HoaQrW:P EyMrM E.
CogE BUIIdhy C IlrpiaxwPo.01dBoghn y
30.`MM Cad iHea4EicAwB -''�_a"�n
M tc ),
peo,1p cund IM i i1
Mi'+'� 3$u'g { I- 2i5
so -17,4
,,r}tx it r t yI
` ' eTi k. L" � ,4 ni.:, it v /'S4 f
jr
..
.,� `Fi
L
'.
%
I{.°
Mahal
lamr
E'w,rrwnl
Tom
INm No. asarlm
peacrl Ion puantl
Unh
6w1
ace,
.11
Cast
f CMI
GrudmO-d vroiion cirn.1 F
LS
5 40.900
2. Stewasy
M. N.Wollen.11.nce 1
LS
'S 200A00
MCliwepurol
C -c iee new f., ecce. vett alloxan[. 1
LS
$ Zmem
A-usal louvers all—ece 1
L6
S'. imam
Tweetlava u 1
is
5 Addeo
A"A'"'A -un".f
LG
5. 15.000
Pipe..-BeMnrzW-allowanm.. 'T
LS
5 25000
3 LaMaape
Ir.,A.n.,t.w f
LS
5'. 7,,500
See pareina I
Ls
5 6o,oa0
A Mswon,
C.Mna.ee uns,lorl, denno wnsweston l
Ls
s 20,Ooo
Fowdat on memlxme and senilrq eWem +
Ls
s s0,00o
Delesaw, sula. slows f.
Ls
'.5 40mo
5 Meonandol
Ni Caged Heal E..Mr,w I
EA
StwlesSteel AEmM1menl Henwvwa Moxa.. I
LS
5 .5 an
5 211;250
S 50,Oo0
5 1.1'£250
SiAniss 4nl S.,uO Sywan Add Allvxance 1
LS
5 15.400
$
E. -
3. 15,000
vv,gNw,wwo m 1
LS
5 11;900
5 11.900
E. -
5 23,600
150 HP Cars—Wawa Pump 0
EA
5 WX0
5 15.00
5
S. '30,000
W"MEMA N. Bypass 1
LS
5 100.000
5 30,000
$: 130000
Red,
21 mntlmar-cora soppy. 5eh A0: Nd 250
LF
S 311
S 121
S -
$ IDZeia
1@'conde --in,-„;San 40, Ma 100
LF
S 225
5 a.
$ �
S 31,100
'"'elbow 5
EA
5 3',335
S 10
5 -
5N.S00
19 nw— 20
LS
5 1] 54
5 109
5 -
5 372 60
,4lee A
EA
5 3.270
S 205
5
5 13.929
1H'lee 10
EA
E 1.495
S 149
5 -
5 16,434
Nec. pigs, albs..¢ (van;chin; f4l.d.) 1
LS
S Mon
Sw.w. n.9sn d4feenr 2'
EA
S10.350
5 S6
S
5 30,573
ButlpAy raNm 21". 55 [nm '4.
EA
E 10,724
S f63
5
5 43,516
awdwdyv Ne 10": 55 tun e.
EA.
E 6,490
S 137
5
S 53,075
CliteRvaNe 2.
EA
S ],791
S 799
S -
5 17,161
Bray Aduakrs 3
EA
5 1,725
S 575
S -
S 6.0.
Flm newer i
LS
5 3.400.
S 315
5' -
5 3.795
Tawuu wrc lMlawo 'e
EA
S 175
S 17
S -
S L536
P,.,.,. lndw.. 2.
EA
{ '.SO
S 14
S
E 146
Fl- cw,pn, (.
EA
S 259
{ 67
5
5 1.421
EIeLMwI
SCE Normal Paver Sem- Pll.na 1
LS
5 250.4"
BU 6S S,A Weer Nlavanm 1
LS
5 'made
Grandin9 syscre 1
LS
E 5.000
P—n
LS
S Beac
Lipson'ayes. w6wt24ing. 1
LS
S" Wand
P.,sondwson and wndulh t
LS
5' 20.000
Pluuww,
.-dw, eewerMsaina6e system aCnwance 1
LS
5 15.000
OIIM2kr edl.m Mo se I
LS
E 2,000
Wag, cwm well eyewash Callon 1
L6
E 5,000
Conrtds
WDI/0-6"wo 48
EA
S 96,000
..Men,erwalc1 temp l/0-2 polms 2
EA
$ -4,000
Weaihn slw.n VO-2 instals D
EA
$ 4.000
Fl ox anuol valve -:3 laina*a9u' 9'
EA
S'. 18am
Neu— deteeion anti alarm 2'
EA
5'. 4,000
Arbu ecw
Penuche Auld NTeinate' 1
LS
S 1,003,000
Inkl air menuesom AM'lJkr
EPMusl Ni wlenuawn,
Flie praktionsystem
Cetlud 3%bndosurer
'Subtotal
{ 3.176.470
12 Nordin General Loudwons
1832.WG
CongMW ConsU itlon Contingency Q 5% But
S 151,823
Escalation 1.5 yews @6%lymr
S 361176
Hong PM Cos” 2%Sswoud
S'. 63,520
OSHPD?umlung Fees ". of 5rrbbW
S 150023.
AS Fees®f0%S.woodS
317.04T
Cenuae¢ Fensa..enunsoA.Ma
S T14.6o0
OPTION TOTAL (Nets 1)
s' 5.00.000
SuhINN MAwust.1 Add
S 4176,470
13Monfi Gmeml Cmdltlans
S 032000
C,,.., Construct— Conan" MY 0 M 5u
5 300,621
Bwounu nl.5ymr. Q y%".S
5011T6
Hoeg PM Costs ®2%Subtcbl
S 63,52.
GSHPOIP-ndid.g F¢a 05%.I SuNMal
{' 2086"
ArE Fees a Is%.Sualwal
i At7,6rt7
Cwft... FeaOnsur:-ensnds
5 714000
OPTION TOTAL IN. 1)
5 7140AW
Notes:
111 Spies H nosey Group's opinionbfpebah, consussimn cossA bases wu ea''maleources suOu as News Can, admaling
Guide,. I penence.ma duWcquipnenlaol nDYe lolM gela4le nature a11a68r.minaleM puipment pnong and
onferesaantla Atlas .-engin--tntlion no., 5yulm do. nut .,,wed, se lmplMy -ward wrep,.wl the.—ra,
Gael
se Ow eelimwed to tie lb.... l cost .1 .—sucew.
5.1
Hoag Energy Plant Cooling Tower Plume Reduction
Mechanical Work ROM
Air Cooled Heat Exchanger
Heat Exchanger
$923,370
Pumps & Hook -Up
$50,000
VFDa
$735,000
Flow Control Valves
$75,000
24" Condenser Water Piping
$780.000
Piping Rack & Supports
$700,000
Rigging
$50,000
Controls
$250,000
Electrical Work
$750,000
Duct Bank
Power & Feeders
Lighting, Conduit & Branch
Distribution Panel
Plumbing (Storm Water Drainage, Trench Drain, rwbns)
$50,00D
Subcontractor Contingency @ 5%
$98,768
Subcontractor Mark-Up @ 75%
$58,908
Total Subs
$2,778,384
Other Cost
Building Addition (5071417) C $45D/sf (Open Root)
$900,000
Louvers
$100,000
Methane Barder
$100,000
SCE Transformer
$250,000
Landscape
$75,000
Generol Conditions (9 months @ $100,000/monih)
$900,000
Sub Total
$4,443,384
A & E Cost @ 10%
$444,338
OSHPD Pemdlis @ 5%
$222,169
Escalation @ 8%Iyr (7.5 years)
$533,206
Contingency @ 5%
$222,169
Soft Cost (Hoag) Q2%
$88,868
FeeAnsurante/Bond
$714,496
Total ROM $6,666,630
Mote, From the information that has been sham and our experience as a Contractor
we have attempted to provide a "Rough Order of Magnitude' Budget for the "Plume
Reduction" of the existing coding towers at Hoag that serve the Energy Plant This
budget is not to be used or considered as an actuate cost of work or an offer to
provide services.
Alternate to provide roof on addition.
2,000 sf roof
$200,000
Sprinkler System
$20,000
Sound Traps for Louvers
$300,000
Added HP on Heat Exchanger Fan Motors
$72,000
Additional Power Requirements
$70,000
Roof Drain System
$15,000
Total $857,000
City of Newport Beach
Hoag Memorial Hospital Presbyterian
Project No. 0QA3YZ
Design/ Implementation Report
Appendix B
Basis of Design Narrative
B - Appendices City of Newport Beach—BOD RevO 8APRO8.doc
FLUOR,
DATE 8AprO8
S. 1 (P
Hoag Memorial Hospital Presbyterian Syska Project No. HOG06007
Cooling Tower Plume Mitigation Measure 3A DRAFT Issue for Review— March 18, 2008
BASIS OF DESIGN
TABLE OF CONTENTS
Section Page
1.0 GENERAL DESIGN CRITERIA
2.0 BASIS OF DESIGN — CIVIUSTRUCTURALIARCHITECTURAL
3.0 BASIS OF DESING —MECHANICAL
4.0 BASIS OF DESIGN — ELECTRICAL
5.0 BASIS OF DESIGN— INSTRUMENTATION AND CONTROLS
6.0 BASIS OF DESIGN —RELATED DOCUMENTS
SYSKA HENNESSY GROUP Page 1
9.17
Hoag Memorial Hospital Presbyterian
Cooling Tower Plume Mitigation Measure 3A
1.0 GENERAL DESIGN CRITERIA
1.1 Design Philosophy
Syska Project No. HOG06007
DRAFT Issue for Review — March 18, 2008
BASIS OF DESIGN
1.1.1 The design requirements contained in the document describe the minimum
acceptable standards for the Lower Campus (LC) Cogen Plant Cooling Tower
Plume Mitigation Measure 3A - Air Cooled Heat Exchanger Project as a whole
and for certain individual components.
1.1.2 The design life of the system will be a minimum of thirty (30) years assuming
normal operating and maintenance practices, including replacement of
equipment components as recommended by the manufacturers.
1.1.3 The design philosophy applicable to this project will emphasize the goal of
attaining high factors of reliability, availability and maintainability, consistent with,
or exceeding industry standards. Examples of factors contributing to this goal
include application of the following:
• Spare terminals and distribution points will be provided for future use.
• Provisions to isolate equipment for repair without affecting system or overall
plant operation.
• Standardization of equipment specified throughout the site to the extent
practical.
• Monitoring provisions for bearing of major auxiliaries to give pre -warning of
incipient problems.
Alarm management system.
• Fail-safe controls.
• Facility layout and lifting and handling equipment design.
1.2 System Design — Basis of Operation
1.2.1 System Design — Basis of Operation
1.2.1.1 The proposed air cooled heat exchanger system will be operated
automatically during conditions of low ambient air temperature and high
ambient relative humidity to mitigate the existing LC Cooling Tower
plume condition.
1.2.1.2 At present Cooling Tower loading conditions, the air cooled heat
exchanger system is estimated to fully mitigate the existing cooling tower
plume when operated in series with the existing Cooling Tower.
1.2.1.3 At anticipated future Cooling Tower loading conditions, the air cooled
heat exchanger system is estimated to mitigate the future plume
conditions better than 50% when operating in series with the existing
Cooling Tower.
SYSKA HENNESSY GROUP
Page 2
e
Hoag Memorial Hospital Presbyterian Syska Project No. HOG06007
Cooling Tower Plume Mitigation Measure 3A DRAFT Issue for Review— March 18, 2008
BASIS OF DESIGN
1.3
1.4
1.2.2 Cooling Tower Design Conditions
A. Cooling Tower:
B. Percent Tower Loading:
C. Operating Period:
D. Condenser Water Supply Temperature:
E. Condenser Water Return Temperature:
F. Condenser Water Range:
G. Condenser Water Flow:
H. Cells in Operation:
I. Cell Fan Speed:
1.2.3 Ambient Design Conditions
MARLEY 4 -cell F433A
Counterflow Cooling Tower
75%
Winter months
78°F
86°F
8°F
12,600 GPM
four
As required to maintain set point
0 —100% speed
A. Dry Bulb Temperature: 50°F
B. Percent Relative Humidity Range: 11-88% RH
C. Wind Speed: 4 MPH
System General Arrangement
Utility Tie -Ins and Interfaces
1.4.1 The following tie-in and interface points with the existing Cogen Plant and site
utility systems are included within the scope:
utility
Tie -In Location Remarks
Mechanical, Plumbin
3 and Fire Protection
1. Condenser water
Existing condenser water
Interconnect size(s) TBD
return header upstream of
towers — two locations
2. City Water
Cogen Plant
Equipment wash down.
Connection point to be
determined.
3. Water treatment
Existing system
4. Stormwater
TBD
Provide new stormwater
drainage and retention
system for displaced
swale
SYSKA HENNESSY GROUP
Page 3
5.11
Hoag Memorial Hospital Presbyterian
Cooling Tower Plume Mitigation Measure 3A
fz7
W
Syska Project No. HOG06007
DRAFT Issue for Review — March 18, 2008
BASIS OF DESIGN
5. Sanitary Sewer
Site location TBD
Provide new floor drains,
oil/water separator, etc.
in enclosure
6. Methane
For enclosure
Provide gas abatement
system, membrane,
sensing and alarm
system, vents, boot
plates, etc.
7. Fire Protection
Existing Cogen Plant
Wet sprinkler system —
head location to be
determined.
8. Irrigation
TBD
In support of
landscaping
Electrical
1. 15 kV
New 15 kV SCE pad mounted
Distribution
transformer and 480V new
(underground)
outdoor switchgear
Environmental/Design Considerations
1.5.1 Noise Emissions
A. To comply with local ordinances. Sound power level not to exceed 55 dBA
weighted average at site property line.
1.5.2 Soil Erosion and Sedimentation Control Plan
A. Required. Plan to be determined.
Technical Assumptions and Clarifications
1.6.1 The following technical assumptions and clarifications apply to the basis of
design:
A. Project assumes a continuous, uninterrupted flow of work during regular work
hours. All system shutdowns will be minimized and may be required during
off -hours. All system shutdowns to facilities utility interconnection, startup
and commissioning to be scripted by Contractor, submitted and approved by
Hoag 72 -hours in advance of shutdown.
B. There shall be free and clear access to the project site at all times.
C. Marley air cooled heat exchanger as the basis of design.
D. Oil/water separation will be required for new drains.
E. Final enclosure dimensions and height to be determined.
SYSKA HENNESSY GROUP
Page 4
5. Zo
Hoag Memorial Hospital Presbyterian Syska Project No. HOG06007
Cooling Tower Plume Mitigation Measure 3A DRAFT Issue for Review— March 18, 2008
BASIS OF DESIGN
F. Compliance with OSHPD Testing, Inspection and Observation Program
required.
G. OSHPD deferred approvals as follows by Contractors (as applicable):
1. Fire alarm
2. Enclosure lowers and seismic anchorage
3. Seismic bracing by ISAT
1.7 Codes and Standards
1.7.1 Applicable Codes and Regulations for OSHPD:
• 2007 California Building Standards Administrative Code (Part 1, Title 24,
CCR)
• 2007 California Building Code (2005 and 2007 California Amendments)
• 2007 California Electrical Code
• 2007 California Mechanical Code
• 2007 California Plumbing Code
• 2007 California Fire Code
1.7.2 Federal Regulations, Standards and Specifications:
• Occupational Safety and Health Act (OSHA)
• Environmental Protection Agency (EPA)
1.7.3 Local Municipality — Codes and Regulations
1.7.4 Coastal Commission — Codes and Regulations
1.7.5 Southern California Edison (SCE) Requirements
1.7.6 American Concrete Institute (ACI)
1.7.7 American National Standards Institute (ANSI)
1.7.8 American Society of Mechanical Engineers (ASME)
1.7.9 American Society for Testing and Materials (ASTM)
1.7.10 American Welding Society (AWS)
1.7.11 Illuminating Engineers Society (IES)
1.7.12 Instrument Society of America (ISA)
1.7.13 Manufacturers Standardization Society of the Valve and Fitting Industry (MSS)
1.7.14 National Electrical Manufacturers Association (NEMA)
SYSKA HENNESSY GROUP
Page 5
5.2f
Hoag Memorial Hospital Presbyterian
Cooling Tower Plume Mitigation Measure 3A
Syska Project No. HOG06007
DRAFT Issue for Review — March 18, 2008
BASIS OF DESIGN
1.7.15 National Fire Protection Association (NFPA)
1.7.16 Underwriter Laboratories (UL)
SYSKA HENNESSY GROUP
Page 6
E. 22
Hoag Memorial Hospital Presbyterian Syska Project No. HOG06007
Cooling Tower Plume Mitigation Measure 3A DRAFT Issue for Review — March 18, 2008
BASIS OF DESIGN
2.0 BASIS OF DESIGN — CIVILISTRUCTURALIARCHITECTURAL (C(S(A)
2.1 Construction Type
2.1.1 Type 1
2.2 Occupancy Group
2.2.1 H-3
2.3 Description of Use
2.3.1 General Acute Care Hospital Building — Cogen Building Addition
2.4 Sprinklers
2.4.1 Fully sprinklered if enclosed
2.5 Project Square Footage
2.5.1 Addition: 50 feet length, 40 feet width, 24 feet height — 2,000 SF
2.6 Project Description
2.6.1 Construction of a new Cogen Building Addition to house equipment associated
with mitigating the Cogen Building Cooling Tower plume.
2.7 Type of Approval to be Issued by OSHPD
2.7.1 Full
2.8 Site Conditions
2.8.1 Geotechnical
2.8.1.1 The underlying conditions of the soil will be verified during the design
phase geotechnical investigation. The soil bearing capacity will be
determined using geotechnical investigation, and Geotechnical Engineer
recommendations will be used to design the foundation, equipment pads
and other support locations.
2.8.2 Land Grading and Surfacing
2.8.2.1 Ground surface cover to be determined.
2.8.2.2 Exterior finish grade to be determined.
2.8.2.3 Pavement and aggregate base to be determined.
2.8.3 Utilities
SYSKA HENNESSY GROUP
Page 7
5. 2 3
Hoag Memorial Hospital Presbyterian Syska Project No. HOG06007
Cooling Tower Plume Mitigation Measure 3A DRAFT Issue for Review— March 18, 2008
BASIS OF DESIGN
2.8.3.1 Potable water will be extended from the existing Cogen Building.
2.8.3.2 Sanitary sewer service will be extended from the site. Floor drains shall
pass through a drain pit and oil interceptor.
2.8.3.3 Stormwater sewer service will be extended from the site.
2.8.3.4 SCE normal power service will be extended from the site.
2.9 Reinforced Concrete
2.9.1 Requirements to be determined.
2.10 Structural Steel and Miscellaneous Steel
2.10.1 Requirements to be determined.
2.11 Design Loads
2.11.1 Dead, live, wind and seismic load requirements to be determined.
2.12 Separation of Structures
2.12.1 Requirements to be determined.
2.13 Foundation Requirements
2.13.1 Requirements to be determined.
2.14 Architectural Design Criteria
2.14.1 The architectural design of the building addition will be designed to comply with
City of Newport noise limitation requirements.
2.14.2 Walkways
2.14.2.1 Minimum of T-6" wide for general and maintenance use.
Minimum headroom clearance of 7'-0" or more.
2.14.3 Stair and Platform
2.14.3.1
2.14.4 Roofing
2.14.4.1
2.14.5 Siding
2:14.5.1
SYSKA HENNESSY GROUP
Requirements to be determined.
Requirements to be determined.
Requirements to be determined.
Page 8
S.Zq
Hoag Memorial Hospital Presbyterian Syska Project No. HOG06007
Cooling Tower Plume Mitigation Measure 3A DRAFT Issue for Review— March 18, 2008
BASIS OF DESIGN
2.14.6 Finishing .
2.14.6.1 Requirements to be determined.
2.15 Landscape Design Criteria
2.15.1 To be determined. Provide landscape planting and irrigation consistent with Hoag
campus standards.
2.16 Permitting
2.16.1 Plan check and permitting will be required from:
• OSHPD
• City of Newport Beach Planning Department
• City of Newport Beach Building Department
• City of Newport Beach Fire Department
• City of Newport Beach Public Works Department
• California Coastal Commission
• Compliance with City of Newport Beach Environmental Impact Report
Measures
SYSKA HENNESSY GROUP
Page 9
5.Z5
Hoag Memorial Hospital Presbyterian
Cooling Tower Plume Mitigation Measure 3A
Syska Project No. HOG06007
DRAFT Issue for Review— March 18, 2008
BASIS OF DESIGN
3.0 BASIS OF DESIGN — MECHANICAL
3.1 Introduction
3.1.1 The mechanical system for the building addition will be designed based on the
criteria presented herein. Scope will include complete design, engineering,
procurement, permitting, construction, OSHPD testing, inspection and
observation, and commissioning, based on the design criteria.
3.1.2 Specific design capacities, ratings, arrangement of equipment, etc., as described
herein and as shown on related documents, will be considered representative,
and may be modified based on prudent and responsible, application of the design
criteria as the design is developed.
3.2 Major Mechanical Equipment
3.2.1 Silencers
3.2.1.1 Provide air inlet acoustical wall louvers in perimeter walls.
3.2.1.2. Provide 85% minimum efficiency air inlet filters and water barrier for
perimeter wall louvers. Frame to be stainless steel. Filter size to be
determined.
3.2.1.3 Provide air inlet sound attenuators and baffles — size to be determined.
3.2.1.4 Provide exhaust sound baffles — size to be determined.
3.2.2 Air Cooled Heat Exchanger
3.22.1 Provide SPX/Marley horizontal mechanical forced draft air cooled heat
exchanger rated to cool 12,600 GPM of condenser water from 78°F to
86°F at 50°F ambient dry bulb temperature. Air cooled heat exchanger to
be equipped with six (6) 40 HP, 480V, forced draft fans. Fan motors to
be premium efficiency, invertor rated. Provide variable frequency drives
for fans in NEMA 3X weather tight, air conditioned, enclosures.
3.2.2.2 Provide structural support frame and bracing system for air cooled heat
exchanger. Support frame, bracing system, and field -erected air cooled
heat exchanger components will need to comply with 2007 California
Building Standards Administrative Code (Part 1, Title 24, CCR) and
required OSHPD approval prior to erection.
3.2.2.3 Reference Section 6.0 — Related Documents for preliminary equipment
selection.
3.2.3 Condenser Water Booster Pumping System
3.2.3.1 Provide two (2) new condenser water booster pumps sized for parallel
operation to support the air cooled heat exchanger system. Provide
space for future N+1 spare condenser water booster pump.
SYSKA HENNESSY GROUP
Page 10
5.260
Hoag Memorial Hospital Presbyterian
Cooling Tower Plume Mitigation Measure 3A
Syska Project No. HOG06007
DRAFT Issue for Review — March 18, 2008
BASIS OF DESIGN
3.2.3.2 Condenser water booster pumps to be split case horizontal pumps, each
rated at 6,300 GPM, 60 feet head, 70% minimum efficiency, 480V, 150
HP each. Pumps to be located within air cooled heat exchanger
enclosure, under the heat exchanger. Pump motors to be premium
efficiency, invertor rated. Provide variable frequency drives for pumps in
NEMA 3X weather tight, air conditioned, enclosures.
3.2.3.3 FLOWSERVE industrial grade pump selection as basis of design.
3.3 Condenser Water Distribution System
3.3.1 Provide mechanical makeup.water fill system.
3.3.2 Provide mechanical drainage system.
3.3.3 Provide mechanical expansion tank system.
3.3.4 Provide pressure relief valves as required from heat exchanger condenser water
piping system to existing cooling tower basin.
3.3.5 Modify cooling tower basin water level control settings to accommodate
additional condenser water system overflow volume in event of system drain
down.
3.3.6 Provide system vents at high points and drains at low points.
3.3.7 Slope all piping to provide proper drainage.
3.4 Water Treatment System
3.4.1 Existing Cogen Plant water treatment system will be utilized.
3.4.2 Existing treatment program to be adjusted to accommodate increase in
condenser water system volume.
3.5 Plumbing System
3.5.1 Enclosure and floor drains will be included in the foundation design to a covered
sump. Sump to be equipped with an oil/water separator.
3.5.2 Provide perimeter daylight drains for the enclosure to accommodate stormwater
drainage.
3.5.3 Provide roof drains as required for the building addition.
3.6 Fire Protection System
3.6.1 To consist of extension of existing Cogen Building wet sprinkler system.
3.7 Methane System
SYSKA HENNESSY GROUP
Page 11
S, -z-7
Hoag Memorial Hospital Presbyterian
Cooling Tower Plume Mitigation Measure 3A
3.8
3.9
Syska Project No. HOG06007
DRAFT Issue for Review—March 18, 2008
BASIS OF DESIGN
3.7.1 Provide methane gas abatement system Including:
• Foundation membrane.
• Gas electronic sensing and alarm system.
• Planter vents
• Trench seals
Piping
3.8.1 The piping interfaces are described in Section 1.0 - of this document Pipe sizes
are shown on Related Documents.
3.8.2 Schedule of pipe and fitting materials:
Valves and Strainers
3.9.1 Reference P&ID's for valve and strainer sizes and locations.
3.9.2 Valves on condenser water services shall be as shown as follows:
CONDENSER WATER SERVICE
Pipe Material
For Type of
Fitting
Pressure Rating
Service
Weight
Joints
Material
psi swp. or
Isolation
Full Port
'/:'-2"
Bronzerreflon
Wei ht
Condenserwater
Steel
Screwed
Malleable
150
2" and under
Schedule 40
Iron
locking
Condenserwater
Steel
Welded
Steel
Schedule 40
2-112" to 10"
Schedule 40
Condenserwater
Steel Standard
Welded
Steel
Standard Weight
12" and above
Weight
Cold water
Copper
Soldered
Wrought
125
Type L
Copper
Full Port
%%2"
Vents
Galvanized Steel
Screwed
Malleable
150
2 pc.
Schedule 40
Iron
Valves and Strainers
3.9.1 Reference P&ID's for valve and strainer sizes and locations.
3.9.2 Valves on condenser water services shall be as shown as follows:
CONDENSER WATER SERVICE
Maximum 150°F and 150 psig ('/1'-12" N125 psig (14"-24")
Specialty
Application
T
Type
Size
BodylSeat
Bo /frim
Connection
Minimum
Ratan "'
Ball Valve
Isolation
Full Port
'/:'-2"
Bronzerreflon
Sweat
400 psig WOG
(with
3 -pc.
locking
handle)
and
Modulation
Full Port
%%2"
BronzeJieflon
Threaded
400 psig WOG
2 pc.
Globe
ATC
Control Valve
%%2"
BronzelMetal
Threaded
400 psig WOG
Valve
Modulation
Butterfly
Ilsolation
I General
21/."-12"
Ductile
Threaded
175 psig CWP
Valve
and
Service
Iron1EPDM
Lug
150 psig bi-
Modulation
directional
shutoff
150 pelt; dead
SYSKA HENNESSY GROUP
Page 12
Hoag Memorial Hospital Presbyterian
Cooling Tower Plume Mitigation Measure 3A
151111]
3.11
Syska Project No. HOG06007
DRAFT Issue for Review— March 18, 2008
BASIS OF DESIGN
Insulation and Lagging
3.10.1 As required.
Pipe and Valve Labeling
3.11.1 Per Hoag Memorial Hospital Presbyterian Standards.
SYSKA HENNESSY GROUP
Page 13
E. 29
end service
General
14"-24"
Ductile
Threaded
150 psig CWP
Service
Iron1EPOM
Lug
150 psig bi-
directional
shutoff
150 psig dead
end service
Plug Value
Manual
Non-
3"-12"
Steel/Iron
Flanged
Class 125
IFIalancing
1 lubricated
Check
Pumps
Silent
V"-2'
Bronze/Bronze
Threaded
200 psig WOG
Valve
Sllenl Globe
2V"-24'
IranBronze
Flanged
Class 125
Piping
Y-Paaem
Y"-2"
Bronze/Bronze
Threaded
200 psig WOG
Swing
2V"-24"
Iron/Bronze
Flanged
Class 125
Strainer
Control
Y -Type
1/2'-2"
Bronze/Stainles
Threaded
200 psig WOG
Valves and
s (1/16" dia.)
Flow
Meters
21/2'4"
Iron/Stainless
Flanged
Class 125
(1/16" dia.)
5"-24"
lmn/Stainless
Flanged
Class 125
(116" dia.)
Pump
In -Line
V"-2"
Bronze/Stainles
Threaded
200 psig WOG
Suction
Y -Type
s
1/16" dia.
21/2"4"
Iron/Stainless
Flanged
Class 125
(3116" dia.)'
5"-24"
Iron/Stainless
Flanged
Class 125
(Y.." dia.)'
Angle Suction
Ddfuser End
2"-12"
Iron/Stainless
Flanged
Class 125
Suction Pumps
(3/16" dia.)'
Start Up
Strainer= 16
Mesh Bronze
1. These are minimum ratings for ASTM A126, Class B and ASTM 8-61 and 62. For higher
pressures and temperatures, adjust these values to include static head plus 1.1 times pressure
relief valve setting plus pump shutoff head pressure. For actual matdmum allowable valve and
strainer ratings, refer to "Pressure -Temperature Ratings - Non Shock" tables and "Adjusted
Pressure Ratings' for copper tube, soldered end valves [and strainers].
2. SWP=Steam Woridng Pressure CWP=Cold Water Working Pressure
WSP=Woridng Steam Pressure WOG=Water, Oil or Gas
3. Class=ANSI Standard.
Insulation and Lagging
3.10.1 As required.
Pipe and Valve Labeling
3.11.1 Per Hoag Memorial Hospital Presbyterian Standards.
SYSKA HENNESSY GROUP
Page 13
E. 29
Hoag Memorial Hospital Presbyterian
Cooling Tower Plume Mitigation Measure 3A
3.12 Pipe Painting
Syska Project No. HOG06007
DRAFT Issue for Review— March 18, 2008
BASIS OF DESIGN
3.12.1 Per Hoag Memorial Hospital Presbyterian Standards.
SYSKA HENNESSY GROUP
Page 14
5.36
Hoag Memorial Hospital Presbyterian
Cooling Tower Plume Mitigation Measure 3A
Syska Project No. HOG06007
DRAFT Issue for Review— March 18, 2008
BASIS OF DESIGN
4.0 BASIS OF DESIGN — ELECTRCIAL
4.1 Introduction
4.1.1 The electrical system for the building addition will be designed based on the
criteria presented herein. Scope will include completer design, engineering,
procurement, permitting, construction, OSHPD testing, inspection and
observation, and commissioning, based on the design criteria.
4.1.2 Specific design capacities, ratings, arrangement of equipment, etc., as described
herein and as shown on related documents, will be considered representative,
and may be modified based on prudent and responsible application of the design
criteria as the design is developed.
4.2 480V Power Distribution
4.2.1 New mechanical equipment will be served with electrical power from SCE
provided transformer located at the service yard. This project will provide feeder
trenching, conduits, and transformer pad while SCE will provide the service
transformer and 15 kV feeder.
4.2.2 Electrical equipment will distribute power to loads as follows:
480V, 3 phase, 3 wire Motors 1/2 HP and larger
208Y/120V, 3 phase, 4 wire - Receptacles,
lights, motors under 1/2 HP
and small equipment
4.2.3 480Y/277 volt, three phase, four wire power from the service transformer will be
supplied via concrete encased underground feeder to a single -ended main
switchboard.
4.2.4 The main switchboard will feed 480V motors via VFDs and dry type 480-
208Y/120 volt transformer located adjacent to the main switchboard. This
transformer will feed 208Y/120 volt panelboard for local lights and receptacles.
4.2.5 Local 120V maintenance receptacles will be installed within 25 feet of
mechanical equipment.
4.3 Lighting System
4.3.1 The lighting system will be designed to provide minimum luminance values for
the various areas as follows:
• Maintenance Areas — 40 FC
• Walkways, Stairways and Platforms — 20 FC
• Outdoor Area/Enclosure Surroundings — 2 FC
SYSKA HENNESSY GROUP
Page 15
5.31
Hoag Memorial Hospital Presbyterian
Cooling Tower Plume Mitigation Measure 3A
4.3.2 Lighting Fixtures
Syska Project No. HOG06007
DRAFT Issue for Review— March 18, 2008
BASIS OF DESIGN
A. Enclosure emergency lighting system shall be provided from battery packs.
B. For enclosure interior and exterior lighting, wall -mounted type fixtures with
metal halide lamps, integral ballasts and photocells will be used.
C. Single/double face emergency exist signs will be provided at all suitable
locations.
D. All lighting fixtures to be UL listed for wet location.
4.4 Grounding System
4.4.1 Grounding system will be designed in accordance with CEC article 250.
4.4.2 System resistance to ground will be 5.0 ohms or less. System ground resistance
will be tested at the main service entrance to ground by means of a three point
"fall -of -potential" testing method.
4.4.3 All conduit terminations at switchboard, panelboards, cabinets and gutters will
have grounding bushings with bonding jumpers interconnecting all conduits and
panelboards, gutters etc.
4.4.4 Grounding system will extend from service transformer to the branch circuit load
or device. Grounding electrode system will include, structural steel and concrete
encased electrode (UFER) ground.
4.4.5 A code sized unbroken bond leader will connect switchboard ground bar to Xo
terminal of the local transformer.
4.5 Power and Control Cable
4.5.1 All conductors will be copper.
4.5.2 Minimum conductor size will be #12 AWG. Minimum neutral size for all shared
circuits will be #10 AWG.
4.5.3 Homeruns will be limited to (6) eight current caring conductors.
4.5.4 Circuits of different panels or different voltages will not be installed in the same
conduit.
4.6 Fire Alarm System
4.6.1 The fire alarm system extension will include alarm -initiating and alarm -sensing
devices, conduits, wires, fittings and all accessories required to provide a
complete operation sy;tem extension, meeting the applicable requirements of
NFPA.
SYSKA HENNESSY GROUP
Page 16
5.32
Hoag Memorial Hospital Presbyterian
Cooling Tower Plume Mitigation Measure 3A
Syska Project No. HOG06007
DRAFT Issue for Review — March 18, 2008
BASIS OF DESIGN
4.6.2 The fire alarm system will be installed and wired in strict accordance with the
manufacturer's recommendations and in co-ordination with overall facility
interface requirements.
SYSKA HENNESSY GROUP
Page 17
5.3 3
Hoag Memorial Hospital Presbyterian Syska Project No. HOG06007
Cooling Tower Plume Mitigation Measure 3A DRAFT Issue for Review — March 18, 2008
BASIS OF DESIGN
5.0 BASIS OF DESIGN — INSTRUMENTATION AND CONTROLS
5.1 Furnish and install complete expansion of the existing Energy Management System
(EMS) by NALAR Controls. Fumish and install all software, hardware, and power wiring
required to expand the existing NALAR control system from the Cogen Building such that
it will accomplish the control sequences (to be determined) and accommodate the control
points as shown on the Drawings.
5.2 Direct Digital Control (DDC) components shall be capable of proportional -integral -
derivative (PID) control.
5.3 Sequences shall include automatic and hand motor starter operation.
5.4 Indication and status shall be via the existing front-end Workstations 1, 2, and 3 video
terminals through the existing Hoag WAN.
5.5 All equipment controlled by the control system shall be capable of manual operation
through HOA switches in motor starters.
SYSKA HENNESSY GROUP
Page 18
5-.3q
Hoag Memorial Hospital Presbyterian
Cooling Tower Plume Mitigation Measure 3A
Syska Project No. HOG06007
DRAFT Issue for Review— March 18, 2008
BASIS OF DESIGN
6.0 BASIS OF DESIGN — RELATED DOCUMENTS
Drawing M1.3
Drawing M1.4
Drawing E1.1
SYSKA HENNESSY GROUP
Mechanical Plan View Drawing
Mechanical Single Line Diagram
Electrical Single Line Diagram
Page 19
5.35
-
y P
MECHANICAL FIRST FLOOR
PLAN - COOLING TOWER.
M-1:2
��r�rmOw�aa®w
'HOAG MEMORIAL
HOSPITAL
<c
'PRESBYTERIAN
:
F
w
'
co
P; NI
kv..+
p'��
SYSCC F�II1f.RY
rr r j
1
t
L' z
m. �^
®_
mm
_
0
.
-
y P
MECHANICAL FIRST FLOOR
PLAN - COOLING TOWER.
M-1:2
W
J
MET WHO:
rp ..
�� ue.o mrmu
HOAGMEMORW
HCSPRAL
PRES13"ERIAH.
SYSYw N0VN854T
ELECTRICAL
SINGLE LME
VApl1 HOSG MEMORIAL
nWyRl©�IApI
HOSPITAL
PRESBYTERIAN
r wr SISYAl6HI1°SSY
m i6
0
wb 7m^a'
;VA ».
k a
a4 A
k
4.u.» LPrvEfl CNAPU5CWl1_NG i%YEP
PL
E EMIT10K 110N
_ OWPiIGNUDONCE
» w MECHANICAL
SINGLE SINE
MECHANICAL SINGLE LINE
�1 1
' a
(� M-1.4
City of Newport Beach
Hoag Memorial Hospital Presbyterian
Project No. 00A3YZ
Design/ Implementation Report
Appendix C
Drawing and Sketches
C -Appendices City of Newport Beach_RevO 3_19_08.doc
FLUOR,
DATE 8Apr08
Rev 0
5.39
4 �
1
k-A"o
�� •4/Zk
Br lr cxx•o
eu.ou"wnorm ma s�a�.s exe�r xo.
POC*Z
,..._ — r
°p�`t L3p�6'a
Ey 6
�Is
_1.
1 �rstsu�,
iTY e � w�R
+
are FFX (gCHE-t)85ok
4.,td -r * 2.K
'
2 Two ftvAPS 63aoGpM@6o�{t5UNP6aZ*4K '
P�PQ (ne iMSNte��NA ) ,
14'
E iZ) %so Hr 4Fb,. $or
6) io )ir YFDe ter fxtie-1 '
N
W
JUAHOAG MEMORIAL
HOSPITAL
PRESBYTERIAN
[ { t ( m,rnaw .x yYSKA1�YNfl61'
^ � � l'JU LJ ll e •-
0
lww
Po
LOWENCAMPNSCOWNGT0 R
'PLUNEMrtIGMIW
oPTIONMCGNCEPT.
Lim w.r
m••✓- MECHANICAL
SAGLELINE
NECHANICAL.3INGLE UNE
��� M-1.4
City of Newport Beach
Hoag Memorial Hospital Presbyterian
Project No. OOA3YZ
Design/ Implementation Report
Appendix D
FLUOR®
DATE 08Apr08
Rev 0
Cooling Tower Manufacturer (Marley)
• ACHE Performance analysis and selection criteria with
reference Psychometric chart and Event 2 Trending Data
• ACHE equipment selection and budget price
D Appendices City of Newport Beach_5PX pert analysis and equipmt budget prim 8Apr08.doc
S. Ll q
Design Parameter for ACHE selection and condenser water
cooling load handling by Tower vs. ACHE
Design Parameters:
Winter Desiqn Conditions:
Flow Rate = 12,600 gpm
HWT=86F
CWT =78F
DBT = 50 F
ACHE Desitin (2/3 heat rejection):
Flow Rate = 12,600 gpm
HWT=86F
CWT = 80.6 F
Range = 5.4 F
# Bays = 3
Fans / Bay = 2
Motor Size = 40 hp
Total Power = 235 hp (max)
# tube rows = 8
# tube passes = 2
Dimensions = 40 it x 40 ft
Cooling Tower Desiqn (1/3 heat rejection):
Flow Rate = 12,600 gpm
HWT=80.6F
CWT = 78F* (assuming a 45F WBT / 68% RH)
Fan Speed = 10-25% (extrapolated approximation).
4 Cells in Operation (other operating configurations are also possible)
Results:
By diverting 2/3 of the heat load to the ACHE, the reduced heat load on the cooling tower will
prevent the formation of plume during most of the anticipated Winter design conditions. If we
utilize the resulting ACHE/CT configuration and approximate the results during the ambient
conditions that correspond with the attached Plume Event Condition #2 (i.e. DBT=49.8F /
RH=83%) and compare the results with the "cooling tower only" operation, it will provide a good
indication of the benefit achieved.
The attached psychometric chart shows two lines ("AB" is the CT/ACHE operation and "AC' is
the cooling tower only operation). Line AB indicates the psychometric path of the exit air from the
cooling tower as it leaves the fan stack at B and shows how much it crosses the saturation curve
while reaching the ambient condition at A. Likewise, line AC indicates the psychometric path of
the exit air from the cooling tower as it leaves the fan stack at point C and crosses the saturation
curve while reaching the ambient condHion at A. Note that line AB (with ACHE operation)
crosses into the saturation area to a much lesser extent and it should be noted that this is at a
higher flow rate of 12,600 gpm instead of 7,800 gpm used for line AC and a higher overall range
of 8F instead of 6.5 used for line AC (i.e. Line AB with ACHE operation actually reflects the
operation with over twice the heat load as what is present during Event 2 that is represented by
Line AC).
5 • q,5
Furthermore, the ACHE is designed such that it would be able to reject the full heat load (without
the cooling tower in operation) when the heat rejection is approximately less than 40000 MBH at
ambient temperature less than or equal to 50 deg. F. This corresponds to the winter heat load of
the currently installed equipment.
Summary:
Adding the above described ACHE wilt reduce the quantity and occurrences of plume by more
than 50% over a wide range of ambient conditions when operating at the future winter load of
12,600 gpm & 8F range. During current Winter Operation of approx. 9,000 gpm / 8F range, the
ACHE will take the full load and there would be absolutely no chance of plume.
, y(o
Fm
t �11rl�l�Jy, lr��.
rSYL;It?Jirl�tt?IL LrlrJt!t
Coel�� 'T.ry wA
RC 81 ,mac
ENTHALPY IM -M PER W NNS MY NR
so
�a
J q V
Lai Comutting + Englh�erinq + Technolbgy + Construdidh
e"� 2
.DELL OPERATIPM
CIO
A'
TREND DATA.
PATE: Ja,nuaty -101,"2,008
TME;: E
TeI)MIlpl-, e -l', r- a -fu re,,.
"deg: -F
Rel.Humidity:;'83*0
kH
Winclipeed,
2 etiph
-000ir + ktan
"sw
izest, rjurapop.,
ConS1 tifateK'Retui
W-WaW'S - Up
Heat Fte�ectibri -
RIO Ot coo0ty
'30,minutes;
Temp
: 0616g:.F.
Temp. 79.-6 86A
7-,'S -2 3 -: G P M,
26,,400'MBH
-49.0/6
SPX
Page 1 of 5
Date: March 28, 2008 MCT Ref. N--. ` 1821R1
E -Mali?
To: Hoag Hospital Fax Ns:
Attention:: From: Rajesh Gupta
Subject: Budget quote for Air Cooled Heat Exchanger
Dear Sir,
As per your recent request, SPX cooling technologies is pleased to provide its
budgetary quotation for an Air Cooled Heat Exchanger propose our standard
technical and commercial scope.
We trust that the provided information supports the your immediate needs and we
look forward to speaking with you to see if our design selection and price in line
with expectations and to further assist in the development effort. Please feel free
to call if you have any questions regarding our proposal.
Sincerely,
SPX cooling technologies
Rajesh Gupta
Application Engineer— Dry Cooling
Rqfesh.gupta@spx.com
Q✓k CYilbL�W1-GCF5FlSiA�dif ^ztk[
wp'$' i9E3a aHk:
�9;_twp �&4rt. YA�3ry f�2Cs
TEL 819 _.864 ',. 9490
VAX;813 884 7495
1
5. y9
ACHE DESIGN CONDITION
Fluid.
Water
Total Fluid Flow:
GPM
12,600
Inlet Temperature
°F
93
Outlet Temperature .
F
66.5
'Design he duty:,
MM Btu/hr
41.0
Inlet Air Dry Bulb Temperature:
°F
50
Tube side pressure drop
psi
13.5
Site. ,Elevation =
ft
100
ACHE DESIGN SELECTION: .
Number of Bays/cells per unit
3
Plot Arrangement
Unit Length:
it
40'-0"
Unit Width:
it
41'-0'
Drive Equipment
Number of Drive motor
6
Fan Diameter (Forced Draft):
it
12
Motor Size
HP
40
Sound Pressure Level 0400'
d6(A)
56
from ACHE Perimeter
Total Design Fan Power @ Fan
HP
240
sheft (all Fans Full)
SP)(
SCOPE OF SUPPLY FOR ACHE
• Forced draft design, horizontal finned tube bundles
• Modular design of Tube Bundle
• Galvanize carbon steel plenum, fan rings, fan guards, support
structures
• Zinc metal spraying of Header boxes as per specification
•. Single- Speed, 1.15 service factor, IP 55 Electric Motors with
space heater
• V -Belt Drives
• Mechanical equipment to be coated with manufacturers'
standard coating
• Hydrostatic Test on Tube Bundle per ASME Section VIII, Div.
• Vibration cut off switch for each fan to trip the motor in case of
excessive vibration
• The tubes will be SA249 Gr 304 welded stainless steel, 1.0"
diameter with 0.04" minimum wall thickness. The fin type will
be an L type fin. The Carbon Steel header boxes will be
fabricated from SA -516-70 and supplied with carbon steel
plugs. The tube -to -tube sheet joints will be roller expanded.
Vis!
SIX
Price- FOB Tulsa OK USA
Description
Air Cooled Heat Exchangers
(3 bays, 3 bundles, 6 fans per
unit) Ex Works FOB Tulsa OK.
Optional price adder for one end
walkways and 2 -ladders.
Unit price qty Total Price
USD USD
$845,000 1 $845,000
$11,900 1 $ 11,900
Terms: SPX Terms & Conditions (Available upon request)
Price Basis: Budget +/- 10%
Quotation Validity: 30 days
Material Delivery: Within 32-36 weeks from Approval of Basic Engineering
Documents
Payment: Down Payment and Progress Payments based on engineering
and material deliverables, net 30 days, essentially as follows:
• 15% Upon Submittal of Basic Engineering Documents (GA, FL)
• 35% Upon Receipt of Tube and Fin Materials at Shop
• 60% Payments against bill of lading
5.52
1
k'
W
W -a yY
f i A
8
W -Y I lfb I J
b 000
b END VIEW b A
0
000
7X.. x x 1, 1
r ar 1
V
b
o-
,f�
PRELIMINARY
FOR BID PURPOSE ONLY
SECTION A -A
anxeonw, ..
a aura
a m mmm �uT �
I I
City of Newport Beach
Hoag Memorial Hospital Presbyterian
Project No. 00A3YZ
Design/ Implementation Report
Appendix E
SPX Cooling Technologies (Marley)
• NCWD and Air2Air hybrid tower system
• ACHE air to water heat exchanger
E -Appendices City of Newport Beach_SPX-NCWD_A2A_ACHE.doc
FLUOR,
DATE 8Apr08
Rev 0
5.5q
Plume Abatement and
Water Conservation Solutions
l We're pulling the plug on the plume.. /
+� y
For decades, cooling towers' cold -weather condensation plumes have
been a major problem. At best, they're unsightly; at worst, they impair
visibility and waste water. Which make them a particular worry around
airports and other environmentally sensitive areas.
At SPX Cooling Technologies, we've made it our mission to eradicate
as much of the plume as possible — while conserving significant
amounts of water along the way.
And we've succeeded.
t Two Ways to Tame the Plume
For years, SPX's coil based hybrid cooling towers have
been a highly popular choice. Now, our NCWD tower
represents our most advanced application of this
technology. SPX's hybrid technology adds a heated
dry air stream to our coil system, keeping the plume
undersaturated. even upon mixture with the ambient air.
Therefore; visible plume is practically eliminated.
Another option is our new Air2Air" technology, which
comes at plume abatement from a slightly different, but
similarly effective, angle. Air2Air uses heat exchanger
packs to radically reduce condensation and keep the
plume in check.
Both solutions can also conserve substantial amounts
of water. And no matter which solution you choose.
you'll be helping to make "plume history" — by helping
to make the plume, well... history.
5'.56
NCWD:
Assembled on Our Site,
Not Yours
The new Marley8 NCWD package cooling
towers are configured for applications of 500
tons or greater — yet, remarkably, are factory
assembled. This significantly broadens the
usability of wet/dry towers from "critical
applications only" to more mainstream projects
and installations.
By combining direct contact (evaporative)
and indirect contact (dry) heat exchangers
in a parallel arrangement, the NCWD's
crossflow system can result in water savings
as high as 20%' versus conventional cooling
towers — while markedly limiting visible plume.
In addition, the NCWD line offers:
• Energy-efficient operation
• Lower maintenance requirements
• Cost-effective installation
• For those using chemical water treatment,
less blowdown and thus less chemicals
'Davendent on system gating c diarns and
local weather conditom .
Air2Air:
Saving Water,
A Lot of Water
Our new, patented Air2Air system uses a series of
PVC heat exchanger packs in the tower plenum to
condense moisture before it escapes. The result:
A substantial reduction in plume emission.
But there's more good news. Air2Air can reduce
your cooling tower's water consumption by up
to 30% annually`, making it the obvious choice
anywhere that water conservation is a prime
concern. And Air2Air can be used on either new
or existing towers.
Because Air2Air is a fully integrated system,
it's more reliable than exclusively coil -based
systems, which means:
Simpler hydraulics for simpler operation
• Fewer moving parts, requiring
less maintenance
• No freezing worries
For a personalized economic payback analysis of
the impact Air2Air can have on your planned or
existing facility, and to sign up for updates on new
Air2Air installations, visit www.spxcooling.com/a2a.
If you're concerned with reducing visible plume or saving water, let
SPX Cooling Technologies show you how to make our solution, your solution.
Visit for all the details.
,.S7
SPX Cooling Technologies is a world -leading full -line cooling
tower and air-cooled condenser manufacturer. The company
provides the highest -quality evaporative cooling towers,
air-cooled condensers, fluid coolers and evaporative condensers
under the Marley, Recold and Balcke brand names.
��yVILDI,yC
O
G
f` _n
a' fMBF.P M1
® Cooling Technologies
906:4e I Hamon Dry Cooling I M.*
7491 W129 Street
averta..d Park, KS USA 66213
.1913 664 7499
spxcoolinq 31cLspx.Coll
vvww.aplowoling.eom
In me merest of techwiagical progress,
a8 products are subject to dasgn andjor
matanal clsange without notice.
ISM SPX Coaling Tachnmiogies, me
Prinwd:n LISA I Clear04
,.58
1, N fier i §Of
i t FLIPP
i t.}I'M
id
l:ua. �j4
u
��y', �
tn
�
*tx,L •x.,"' }s3 'FM1@ Si S �'' rpt i- '- 3
WU
'q _ a
5.5111
Q2,
R
zal
_..A—.
1, N fier i §Of
i t FLIPP
i t.}I'M
id
l:ua. �j4
u
��y', �
tn
�
*tx,L •x.,"' }s3 'FM1@ Si S �'' rpt i- '- 3
WU
'q _ a
5.5111
AirFin HEAT EXCHANGERS
-----------------
AIRFIN OBJECTIVES ADVANCED RESEARCH
AirFin Heat Exchangers have been designed, AND TECHNOLOGY
manufactured, and supplied worldwide for AirFin benefits from the advanced research
over 40 years. Our satisfied customers include facility at SPX Cooling Technologies in
the chemical, petrochemical, oil and gas,
process, and porter generation industries.
SPX Cooling Technologies' AirFin heat transfer
engineering team works with a set of concise
objectives
• Commitment to the customer to provide
the most advanced technology available
• Promote innovative Value engineering
designs"
• Custom designs with optimized heat
transfer surface and pressure drop
• Laxer fan power consumption and lower
fan noise criteria
• Overall guaranteed performance
Competitive cost, reduced operating and
maintenance cost thereby providing a
simple, clear choice for all your heat
exchanger needs
WORLDWIDE MANUFACTURING
CAPABILITIES
AirFin derives maximum advantage from its
international manufacturing and service
organization. As a result of this worldwide
sourcing, customers derive economic benefits
from advanced product design and cost
optimization.
SPX Cooling Technologies offers prod.
ucts manufactured at our own facilities
in Germany, South Africa and China.
Additionally, our alliance partners in North
America, South America and other
countries provide a 'competitive edge and
a unique flexibility in meeting our clients'
requirements.
Germany. Ongoing, aggressive research and
development assures the division's position
as a market leader in technology. The primary
marketing objective is to identify new markets
and opportunities for which creative solutions
and advanced technologies can be applied.
At AirFin, our mission is to provide our
customers with the finest quality heat transfer
equipment in the industry. Our objective is to
be your worldwide, preferred partner.
QUALITY ASSURANCE AND
QUALITY CONTROL
Quality Assurance and Quality Control
programs are certified to ISO 9001, TUV.
and others. The testing and verification
process is rigorous, while our certified
inspection programs meet or exceed industry
standards. Testing includes hydrostatic,
pneumatic, and/or submerged underwater
leak testing, as well as nondestructive and
specific testing per project specifications.
In addition, all materials are inspected upon
receipt, in -process, and at final assembly
stage. Additionally, AirFin quality programs
include third -party independent inspections
when necessary.
Fabrication facdiN at Zhangliakcu, Peoples Republic of China
XCtiANGER S THE FIN -TUBE BUNDLE.
AiPFIN DESIGNS AND CUSTOM -BUILDS
.; F.SF, ENSURING',S"TRfCTADHERFN,-,:
�UALiTY STANDARDS AND
1 1CATI0NS.
Petrochemical application
465 MWCCCP plant, El Dorado Energy. Nevada
5.106
GE frame 7EA gas turbine closed coaling wafer
module with pump skid
HeidTranster Hesea,�h c.
OUR MISSION IS TO PRaVi DE
CUSTOMERS WITH THE FINEST
QUALITY HEAT TRANSFER
EQUIPMENT IN THE INDUSTRY.
OUR OBJECTIVE IS TD BE YCt;R
WORLDWIDE, PREFERRED
PARTNER.
Oil and gas application
INNOVATIVE TECHNOLOGY
HEAT EXCHANGERS
SPX Cooling Technologies has Over
40 years of experience in the design
and manufacturing of air-cooled heat
exchangers. Our thermal designs are
based on SPX Cooling Technologies' pro.
prietary computer programs, and are, as
standard procedure, verified to the latest
version of widely accepted HTRI thermal
design software.
The AirFin air-cooled heat exchanger is
designed and manufactured as a forced
draft or induced draft type. Each tube
bundle is constructed, tested, and stamped
in strict accordance with the following rigid
standards
• ASME Section VIII, Division I, with
'U" stamp
• API 661, when applicable (recommended
design practice for Refinery Application)
• TEMA, when applicable
• Additional world standards: DIN, British,
AS, AD-Merkblatt, REGELS
• Chinese standards: 313-150, BR1, GB/
T15386, JB 4730
Project planning and Implementation
processes utilize ultramodern computer
software for engineering, design and
manufacturing.
AirFin designs can be completely shop -
assembled, or pre -assembled in modular
pieces for easy onsite field erection,
the choice contingent upon optimum
transportation cost benefit to the customer.
For export projects, to ensure that your
shipment arrives in perfect condition, we
offer seaworthy packing, with nitrogen fill
for longterm storage.
yield erecter` modules
Process industry application
Completely factory assembled modules
5.0
FINNED TUBES, HEADERS, AND DESIGNS
FINNED TUBES
Finned tubes are available in
several configurations, including
"L" footed
• Extruded
• Embedded (G -fin)
• Elliptical — Galvanized
FIN MATERIAL IS AVAILABLE IN
• Aluminum
• Copper
• Hot -dipped galvanized steel
TUBE MATERIAL IS AVAILABLE
IN THE FOLLOWING METALS
AND ALLOYS
• Carbon steel
• Stainless steel
• Duplex stainless steel
• Copper
• Copper nickel
• Titanium
•Inconel/Incoloy
• Hastalloy and other exotic alloys
Bolted cover type header
HEADER TYPES CAN BE DESIGNED
IN MULTIPLE CONFIGURATIONS,
INCLUDING
t
Bolted cover
header
i
1
Bonnet head- Manifold head -
DESIGN CONFIGURATIONS
• Forced draft
• Individual draft
• Horizontal
• Vertical
• A -frame
DESIGN PRESSURES INCLUDE
• Full vacuum
• Up to 300 bar (4,500 psi)
"L' tooted Extruded Embedded(G-
fin)
Process air cooler and "A.Frame' condenser
in a chemical plant
5.(2
Galvanizing workshop
Q=UALITY ,
WELDING. PROCESSES
AirFin uses state-of-the-art welding
processes, including
• S.A.W. multi -pass
• G.T.A.W. manual and automatic
• G.M.A.W.
•. F.C.A.W.
• Manual or automatic tube.to-tube.
sheet seal welding, or strength
welding (when required)
MACHINING CAPABILITY, QUALITY
CONTROL, AND TESTING
-Use of high -tolerance, computer
controlled (CNC) machining, centers
• All materials are inspected upon
receipt, in process, and at final
assembly stage
• Testing includes hydrostatic,
pneumatic and/or submerged
.underwater
• Nondestructive and other testing
per project specifications
• Quality programs include third,
party independent inspections,
when required
BENEFITS OF=AIRRN
HEAT EXCHANGERS'
• Value engineered, optimized design
• Hot -dipped galvanized structure
• Mechanical equipment and fan run -
tested in -shop for factory assem _
bled units
• Thermal, hydraulic, vibration, and
mechanical guarantee
Welding of a plug;type header
5.G3
/ Full Service Local Representation /
The Global Network of Dry Cooling
Belgium
SPX Cooling Technologies Belgium
Twin House, Rue Neerveld 107
B - 1200 Brussels, Belgium
Phone: +32 (0)2 761 61 11
Fax: +32 (0)2 761 61 86
infobeBcts.spx.com
www.spxcooling.com
France
SPX Cooling Technologies France
3, promenade de Is Bonnette
F - 92238 Gennevilliers, France
Phone: +33 (0)1 47 99 60 40
Fax: +33 (0)1 47 99 60 50
infofr@cts.spx.com
www.spxcooling.com
China
SPX Cooling Technologies Co. Ltd.
B-701, Guomen Building, No 1
Zuojiazhuang, Chaoyang District
100028 Beijing, China
Phone: +86 10 6462 1188
Fax: +86 10 6461 9162
infocn®cts.spx.com
www.spxcooling.com
Germany
SPX Cooling Technologies GmbH
Ernst -Dietrich -Platz 2
D - 40882 Ratingen, Germany
Phone: +49 (0)2102 1669 0
Fax: +49 (0)2102 1669 215
infode®cts.spx.com
www.spxcooling.com
Italy
SPX Cooling Technologies Italia SpA
Via Raffaello Sanzio 2 (Corpo A)
1- 21013 Gallarate (Va), Italy
Phone: +39 0331 2484 11
Fax: +39 0331 2484 12
infoit®cts.spx.com
www.spxcooling.com
United States of America
SPX Cooling Technologies, Inc.
1200 U.S. Highway 22 East
Bridgewater, N.J. 08807, USA
Phone: +1 908 450 8008
Fax: +1 908 450 8050
infousa@ct.spx.com
www.spxcooling.com
United Kingdom
SPX Cooling Technologies
Gregory's Bank,
UK - Worcester. WR3 8AB,
Phone: +44 (0) 1905 720 241
Fax: +44 (0) 1905 720 201
infouk®cst.spx.com
www.spxcooling.com
SPX Cooling Technologies
Bakke I Homon Dry Cooling I Marley
5-(4
City of Newport Beach
Hoag Memorial Hospital Presbyterian
Project No.00A3YZ
Design/ Implementation Report
Appendix F
Sound Attenuating Louver
F -Appendices City of Newport Beach_ SAD_08.doc
DATE 8Apr08
Rev 0
5.&5
RUSK/N"
3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955
ACL1245AF STATIONARY ACOUSTICAL LOUVER
FORMED STEEL
STANDARD CONSTRUCTION
FRAME
12' (305) deep, 16 gage (1.6) galvanized
steel channel.
BLADES
18 gage (1.3) airfoil shaped galvanized
steel exterior surface, with 22 gage (.9)
perforated steel interior surface that cov-
ers insulation. Blades positioned at 45•
angle and spaced approximately 12" (305)
center to center.
ACOUSTICAL INSULATION
Ruskatherm blanket.
SCREEN
r/i mesh x 19 gage (13 x 1.1) galvanized
bird screen in removable frame. Screen
adds approximately +h' (13) to louver depth.
FINISH
Mill.
MINIMUM SIZE
12'w x 24"h (305 x 610).
APPROXIMATE SHIPPING WEIGHT
10 lbs. per sq. ft. (48.8 kg/m').
MAXIMUM FACTORY ASSEMBLY SIZE
Shall be 64 sq. ft. (6m'). Maximum single
section size shall be 48" x 96' (1219 x
2438). Louvers larger than the maximum
single section size will require field assem-
bly of smaller sections.
FRAME CONSTRUCTION
3
A'
A-
FCB r —
Varies
Standard Integral Flange
12'
(305)
Dimensions in parenthesis ( ) indicate millimeters.
FEATURES
The ACLI245AF offers:
• 23% Free Area.
• Insulated blades which provide effective
sound attenuation and weather protection.
• Published performance ratings based on
testing in accordance with AMCA Publication
511.
• Architecturally pleasing appearance.
VARIATIONS
Variations to the basic design of this louver are
available at additional cost. They include:
• Extended sill.
• Front or rear security bars.
• Fitter racks.
• Installation angles.
• A variety of bird and insect screens.
• Selection of finishes: prime coat, baked
enamel (modified fluoropolymer), epoxy,
Peadedize, Kynar, clear and color anodize.
(Anodize finish available only on aluminum
construction. Some variation in anodize
color consistency is possible.)
• Formed aluminum frame with .100' (2.5)
nominal wall thickness and .080' (2) blade
with .040' (1) perforated aluminum interior
surface.
Octave Band
Frequency (Hz)
Free Field Nolse
Reduction (db)
Ruskatherm
Blanket
2/125
13
3/250
13
4/500
14
5/1000
20
6/2000
20
7/4000
20
8/8000
23
To calculate Transmission Loss (db), subtract
6 db from Free Field Noise Reduction (db).
'Units furnished 1/: (6) smaller than given opening dimensions.
SIZE
TAG CITY. FRAME VARIATIONS
A• -WIDE B' -HIGH
PROJECT LOCATION
ARCHJENGR. CONTRACTOR
REPRESENTATIVE DATE
Spec ACL12<5AF89NReIacea ACLIMAF898 ALL STATED SPECIFICA17ONS ARE SUBJECT To CHANGE wrTNOUT NOTICE OR OBLIGATION ORuslrn Company Januan•1998
5• &
SUGGESTED SPECIFICATION
Furnish and install louvers as hereinafter specified where shown on
plans or as described in schedules. Louvers shall be stationary
acoustical type contained within a 12" (305) frame. Louver compo-
nents (heads, jambs, sills, blades, and mullions) shall be factory
assembled by the lower manufacturer. Louver sizes too large for
shipping shall be built up by the contractor from factory assembled
louver sections to provide overall sizes required. Louver design
shall incorporate structural supports required to withstand a wind -
load of 20 In. per sq. ft. (.96kPa) (equivalent of a 90 mph wind
1145 KPH] wind - specifier may substitute any loading required).
PERFORMANCE DATA
AMCA Standard 500 provides a reasonable basis for testing and
rating louvers. Testing to AMCA 500 is performed under a certain
set of laboratory conditions. This does not guarantee that other
conditions will not occur in the actual environment where lowers
must operate.
.30
(3.23)
25
(2 69)
Q
20
f2.151
U.
O C
15
E E
r
m
m 0
(1.06)
MI
O
.05
(54)
Louvers shall be Ruskin Model ACL124SAF constmction as fol-
lows:
Frame: 16 gage (1.6) galvanized steel channel.
Blades: 18 gage (1.3) galvanized steel exterior surface, 22 gage
(.9) perforated steel interior surface that covers insula-
tion. Blades are positioned at 45° angle and spaced
approximately 12' (305) center to center.
Screen: 1/2" mesh x 19 gage (13 x 1.1) galvanized steel in remov-
able frame.
Finish: Select finish specification from RuskinNalspar Finishes
Brochure.
Published lower performance data bearing the AMCA Certified
Ratings Seal for Air Performance and Water Penetration must be
submitted for approval prior to fabrication and must demonstrate
pressure drop equal to or less than the Ruskin model specified.
The louver system should be designed with a reasonable safety
factor for louver performance. To ensure protection from water
carry-over, design with a performance level somewhat below maxi-
mum desired pressure drop and .01 oz./sq. h. of water penetration.
WATER PENETRATION
Test size 48" wide x 48" high (1219 x 1219)
Beginning point of water penetration at .01 ozJsq. ft. is 1126 fpm (343 m/min).
Ruskin Manufacturing Com-
pany certifies that the louver
shown herein is licensed to
bear the AMCA Seal. The
ratings shown are based on
tests and procedures per-
formed in accordance with
AMCA Standard 511 and
comply with the requirements
of the AMCA Certified Rat-
ings Program. AMCA Carti-
tied Ratings Seal applies to
air performance ratings and
water penetration ratings
only.
1000 1100 1200 1300
(305) (335) (366) (396)
Free Area Velocity in feet (meters) per minute
Standard air.075 Hatit'(1.2 kg/m')
5.("7
FREE AREA GUIDE
Free Area Guide shows free area in fN and m' for various sizes of ACL1245AF
Width - Inches and Meters
1.00 X2469)
90 (224.01)
.80 1189.12)
.70 1174231
.60 049.36
.501124.451
.40199.581
m
Q.. 20174.611
Ch
3 20(49781
of
d
t
u
c
c 10(24M)
a 44A4 18.81 �z244;
C
M(1742)
Y A6(14.93)
1�q .0411245)
p 44(998)
8
CL mt7471
v
N42(4.981
-01(2.49)
PRESSURE DROP
INTAKE
Air Velocity in feet (meters) per minute through Free Area
Ratings do not include
the effect of a bird
screen.
5. CDs"
12
/8
24
30
36
42
48
54
60
66
72
78
84
90
96
0.30
0.46
0.61
0.76
0.91
1.07
1.22
1.37
1.52
1.68
1.63
1.98
2.13
2.29
2.44
18
0.59
0.99
1.38
1.78
2.17
2.57
2.96
3.36
3.75
4.15
494
4.94
5.33
5.73
6.12
0.46
0.06
0.09
0.13
0.17
0.20
024
028
0.31
0.35
0.39
0.42
0.46
0.50
0.53
0.57
24
0.40
0.56
0.93
1.19
1.46
1.72
1.99
225
2.62
2.78
3.05
3.31
358
3.84
4.11
0.61
0.04
0.06
0.09
0.11
0.14
0.16
0.18
0.21
0.23
0.26
026
0.31
0.33
0.35
0.38
30
0.72
120
1.68
2.16
2.65
3.13
3.61
4.09
457
&05
5.53
6.01
SAS
6.97
7A6
0.76
0.07
0.11
0.16
0.20
0.25
029
0.34
0.38
0.42
0.47
0.51
am
0.60
0.65
0.69
36
057
0.95
133
1.71
2.09
2.47
2.85
3.27
3.61
3.99
4.38
4.76
5.14
5.52
5.90
0.91
0.05
0.09
0.12
0.16
0.19
0.23
0.27
0.30
0.34
0.37
0.41
OA4
0.48
0.51
0.55
42
0.89
1.49
2.06
2.68
327
396
4A6
595
SAS
624
6.84
7.43
8.03
8.62
922
1.07
0.08
0.14
0.19
0.25
0.30
0.36
0.41
0.47
0.53
0.58
0.64
0.89
0.75
0.80
OAS
48
0.74
123
1.73
232
2.71
320
3.70
4.19
4.68
&18
6.67
6.16
6.65
7.15
7.64
122
0.07
L 0.11
L 0.16
0.21
0.25
0.30
1 0.34
0.39
0.44
0.48
0.53
0.57
0.62
0.661
0.71
54
1.06
1.77
2,48
3.19
330
4.51
522
6.03
&74
7.45
LIS
8.87
9.58
1029
11.00
1.37
0.10
0.16
023
0.30
0.36
0.43
0.49
0.56
0.63
0.69
0.761
0.82
0.89
0.96
1.02
60
0.91
152
2.13
2.74
3.35
3.95
456
5.17
5.78
639
7.00
7.60
821
892
9.43
1.52
0.08
0.14
0.20
0.25
0.31
0.37
0.42
0.48
0.54
0.59
0.65
0.71
0.76
0.82
0.88
66
123
2.06
2.99
3.70
452
5.35
6.17
6.99
7.81
8.64
9.46
1028
11.10
11.93
12.75
1.68
0.11
0.19
0.27
0.34
0.42
0.50
0.57
0.65
0.73
0.80
0.88
0.96
1.03
1.11
1.19
72
1.09
1.80
2.52
3.24
3.96
4.68
5.41
6.13
6.85
7.57
839
9.01
9.73
10A5
11.17
1.83
0.10
0.17
0.23
1 0.30
0.37
0.44
0.50
0.57
0.64
0.70
0.77
0.84
0.91
0.97
1.04
78
1.41
234
328
422
6.15
6.09
7.03
7.99
&90
9.64
10.77
11.71
12.65
1358
14.52
1.98
0.13
0.22
0.30
0.39
0.48
0.57
0.65
0.74
O.B3
0.91
1.00
1.09
1.18
126
1.35
84
125
2.09
2.93
3.76
4.60
5.44
627
7.11
7.94
8.78
9.62
10.45
1129
12.13
12.96
2.13
1 0.12
1 0.19
0.27
0.35
0.43
0.51
0.58
0.66
0.74
0.82
0.89
097
1.05
1.13
1.21
90
1.58
263
3.68
4.73
5.79
6.84
7.89
&94
9.99
11.04
12.10
13.15
1420
1535
1630
2.29
0.15
0.24
0.34
0.44
0.54
0.64
0.73
0.83
0.93
1.03
1.12
1.22
1.32
1.42
1.52
96
1.42
237
332
127
522
6.17
7.12
&O6
9.01
9.96
10.91
11.86
1281
13.76
14.71
2.44
0.13
0.22
0.31
0.40
0.49
0.57
0.66
0.75
0.84
0.93
1.01
1.10
1.19
1.28
1.37
1.00 X2469)
90 (224.01)
.80 1189.12)
.70 1174231
.60 049.36
.501124.451
.40199.581
m
Q.. 20174.611
Ch
3 20(49781
of
d
t
u
c
c 10(24M)
a 44A4 18.81 �z244;
C
M(1742)
Y A6(14.93)
1�q .0411245)
p 44(998)
8
CL mt7471
v
N42(4.981
-01(2.49)
PRESSURE DROP
INTAKE
Air Velocity in feet (meters) per minute through Free Area
Ratings do not include
the effect of a bird
screen.
5. CDs"
TYPICAL INSTALLATION DETAILS
CMU
Caulk
(by other
Louver
Extendec
SIII
Masonry
Wall
Caulk
(by other
Lauver
Corrugate
Metal
Drip C
Insulation
Loi
Extenoe
SIII
Metal Panel
Wall
Wood Flange
Installation Mount
3800 Gr. Greaves Rd.
RUSK/N`� sw»S�
w:
Flang
Fram
Louver
Anchor
(by others)
Accessories at additional cost.
5.G9
City of Newport Beach
Hoag Memorial Hospital Presbyterian
Project No. 0OA3YZ
Design/ Implementation Report
Appendix G
DATE 8AprO8
Rev 0
Trending Data and plume observation photos for 18 events in
January and February 2008 — Report date February 21, 2008
(Update)
G -Appendices City of Newport 8each_Trending Data and photos_RevO 8Apr08.doc
5.70
5. 7l
£p
F4
1
pg
6U
u
¢°u
iry
_
Z
s
s
eI
a
si
sass
ss
s
ss
---
s
¢xssss�samssaaa:
ossssss
Psm-
sass
ese
-
ss
=s�se
8
-
8
8
i
8
-
21
-
$ s
-
i
o` o
o`
a`
o' o`
o`
o`
o°o`
i
1
6
0
6
`o €
'0
6
`0 8
0 6
c 6
0
6
0`
6
8 6
0$
0
8
8 8
0 6
to
8
`0 6
'01 8
`a e
0
8
8
8
6
-
0 0
6
6 6
6 6
E
8 5
6
6
a`I o`
6
8 8
6
0`
6 6
6
0`
0
0
0` o`
0`
m` o`
6
6
6 0`
6 6
0` 8
6
8
8
0`
8 8
8
8
8
6
8 0`
6 8
0`
o`
o o`
6 a`
8 8
-
-sa
s
s
saes
3
�
s
e
SS
m
5. 7l
a
SYSKA if,,„ :.NE? S)'
G"Ou.
Consulting + [ngineerinq + Technology + Con�truction
I
t!
-D �Qopu,m,e--n-'iLowerQampus,,,Cooling�to\A/�br4oXhau�st,co:n'�d.ens.
events and eff6otofig a$utos at' nme
Roord E e- e
v OtW atherDO sr
Outdo-ortem1per-pture
I -
Relative humidi
Windi,speed and direction
Record Eyont To wer Load
— Condenser water supply and
— Condenser water flow
— Fan speed
Isolation-, v'alve- position -
Heat reject
Percent. capacity
return temperature
I e
Consulting + Lngineering + Technology + Construction
SYSKA I It"'N'NE-SSY
*Hoop
Abstract.
Ogf-aph T e
Ph� ot OW'r Rhaust Condition Event
Three" photo angles
Location., I On',grade parking lot
Location
2*
Hillside
property
libe,
narthwest-torner tower enclosure
Location
3.
Hillside
property
line;
northeast corner C-pgen Plant
Location..2
j
74,i ......
E; Consuking + Engineering + Tcchnology + ConstructiOn
GROUP
Mitigation Moasures.:
Threetellr to r pe,
p " ration v4r'suiE06,ur ore r operation=
- we
Const0twoather conditions
- Constantcooling touter load
Condenserwater reset
- 5 deg. Average condenser waiter supply temp. reset
No load 'shift to Upper Campus
6=S�V� Ht IW��WV �W.
Ul
4
a
Sl,x-\ I tv.,mm'ss),
ofloop
3.. CELL,OPERATION
Consulting + Engineering + Technology + Contiuctlon
4 -CELL OPERATION
TRIE.N.D. DATA
• DATE: Jarivary%2008
TIME7, 7-308:16AM
VVEAT—HER,,CONDITIPNS,,
Temperature
: 62.4 deg, P
Rel Humi,dit:'V,:, 86% RH
Wiqd,,oeedt CWm
NIA
. AVERAGE TOWEkCOAD:
-, Test,Duraiion
46'thinUtes
Coad. Water S:Up *Temp�:r
7,5:5 deg. F
bqd.-`W rF
8-38600M:
Heit n--
m, 45.0, , M6H
, Pir.ceptotipacity,-,
61%
om,Fka He tiasomp, lie.
5
rig
3 CELL OPERATION
Consultirig + Engirteering, 4, Technology + ConStrLlCtion
:4 CELL OPERATION
I
9® S a 3
• PATEf January 10,;2008
f-21ME:- 7,15 —7:46 AM
Ternoriture,! 49';e deg, F
R6,1; m y,. 8A. kH
Win'&SO 2 mph
?Wind Di SW
AVERAGE :T,.0W,ER-,L
Tett!Duraffbil-,',
301mihutes
Gond.. Water -Retumlemp:
86 deg.;F
Cond. -',WkWt-jSup'ft Temp,
791 dog; F
ddrid'. WAMKFIOW
7t23"GPM,
Hwd Rojet ' tfib
26,400, MBH
Por!�,OntCapacity:
49%
R
rim
4y% -)KA I it NIN, FIN -SI,
4000P
3,CELL OPERATION
FeCftary 21, 2m&
CIQ
Consulting, + Erigioeerfng + technology + Construction
4 CELLOPERATION
TREND QATA-
•
DATE: January 10, 2008
• TIME: 7:00 — 7:30 AM:
• WEATHER -CONDITIONS:
Temperature* 61.4 deg. F
Rei: Humiditv..-'w 510 RH
Wind ;O Direction: Sw
n.
Te -40 minutes
Return T -=06g,'f
r
Conti. VMfaterf Supply Temp: 75 de6l, F
abridlwater-Flow. 7,257 GPM
Neat Refection;_ 25,400 MBH
Percent Capacity:
02W26"na He w"Yontp, [to.
Consulting + Pngfnci�rjng + Teclinology,+ Construttion
SYSK,\ I It: NNEsSYll
3 DELL OPERATION 4 CELL'OPERATION. TREND DATA
0 DATE- 4,arivary 16;1009
TIME: 7*1r6-7-,45,,AM
0i
WEATHER -CONDITIONS
- t6mperkuev,; 49JAeg. F
- 'R MR% RH
7-Uifind Speed:Jllmioh
Wind Dir, 4#qhNE
AVERAGETOWERLOAD -
TestDuration:;;.3
0 minutes
Cond;:}iYaterrn, T mp
;deg; F
c on er",
6,3,6a G PM
-: Heat Rejection:
22;300 MBF!
Percent C. ity:
0,',ac
460
021126}¢N3 Ht rresyGtnip,f�c. �
SYSKA I I 1-,NfNEvS'SY
anoup
Event 5
3 CELL OPERATION
Consulting + bigineering + Technology + Constructi6r)
4 DELL OPERATION
TRENP,PATA
DATE.' January -I,—;2008
TIME: 7:00 — 7:30 AM
urr�pe�lr. 55.7 tim F
I .
Rei: Humidity-'*' "10%AH
lfliind:Speedi '4 -mph
WindVr. i.'Q"n"--,.,'ENE
AVERAGE .TOWER ILOAD:
TeStVuratiow-
-ketun
C er u
Gond. WIter Flow*
Pleic"erit-CfaO , acity:
.30 minutes
816 deg. F
75 den. F-
22poo: MBH
40%-
OR%
W-1
LN
51`5 1:.1 I 11 N, -N, l'-% s '5
eRoup
3 -CELL OPERATION'
Consulting + Engineering + Terhnology + Construction -- ----
4 CELL OPERATION
TREND DATA
• DATE: January 2.2,2008
• TIME: 8:00 -8130 AM
YVI:RTHt:K.UVNUIIlVrWb,Temperature d
'.
F.
deg: 6g. F
R_
'e. Hu'llftildft-n I 'RH
V
Wirid n --S5
I I
AYERAit T6WEFt LOAD-.
G-J. F,
T6sfburabon!
'30 minutes
66,nodl.Wdor Return u
t., m Temp:
82 6 deg. F
Cl
75,deg, F
-6 4er
c n&W -..'FloW:
6,,2W6PM
I I
H6itR'6jedtlbo,,
19,-900-,MBH-
peeeofitca a ity
40%
10
Constilfing + Engineering + Technology + r"o,astruction
Yq kA I I S
3 CELL OPERATION
4 CELL OPERATION
0011- -1---- ftDmw ' 21.2W
TREND DATA
• DATE,: January 23,2008
TIME:, 7-:00 -m7:30,AM
WEATHER G 00 b`ITIQN S'_1
oigUfbi: 49.8. deg. F
R81. Humidity:`' 79°Jo RH
7-,
--Wih d'Soed': 7 mph
Wind,.Directions ti ESE
., _.-
e
LeSX Wuraponi,
tond.Waterketun
c ond.v
bond.Water"Fl-low',
Watkoheection:
Porcpnitl;-apacity.'
'30 minutes
Temp: 81.6 deg, F
Temp: '76deg. F
5,644 GPM
18,000.MBH
;36%
ONE
LN
SYS" I
6KOUP
Event 8
3 CELL OPERATION
Cqnsultincl + Enoineering + Technology + Construction
4 CELL.OPERATION
TREND DATA
• DATEf Jqnuary 24; 2008:
TIME;
WE
HER CQNDif108S�.
Temperature:- emipkitueo-.- 482 deg, F
RI.0 'HUiiifdfty:. 84-0/6, RH
-
7- Wirtd:S§eed& 11 Mph
e
Gond. IWater - R
e-1tu1i
Cdhd. Water .
SUPO
C06& -Water" Flow
Heat Rejerction.
P.OrcOnf-;Opacity
r
I 02IM26)cra IIA tbUSVGMPU*.
.30.,mihUtes
Temp:, -9.1 dog: F
Temp: 75 deg. F
7,214 GPM
21,600 MBH
45,0/6
1.2
V
undo,
Consulting + Engineering + I'Lchzloliogy + Cotistrulftion
3CELL OPERATION 4 CEILLOPERATION TREND DATA
January 29,- 2008
YVWH -'IC
ER Qd..NbiT' PkS:+
Tir'r!-p'e`rafue6:. 6624eg. F
Rel; HUffildfly:. 620/6 RH
1 7 mphnd,
Wind Plr'f,"qtkdh'-,SSW
AVERAGE --TQWE-�R-LOAD
-
Test uration, '30 minutes
— Concl.'Water Return Temp: 84 deg: F
—
Cond. ,Water 'Sup'
Supply Temp: 78 deg; F
Cond.-Water 'F'10- Wl' 8,768;
GPM
Heat Rej ktibfv 263001'MBH
:
PericentiQ'Oadip-...
U
Sl SKA I I1NN4,'lSSY
anoup
3 CELL OPERATION
ConsulLing + Enginciering + Technology + t-.onstruction
,4, CELL. OPERATION
Fednafy27; 2m$
TREND DATA,
• DATE,'. Janory30;.2008
• TIME:: T.-30 — 0:00 AM
TVO*ratbW'
49`.17409: F
.1.
Rel HUmIdii ,
lko-RH
„tpeedi.
,2--rhph
-Wind :Dii b -�
n.
redfi '
- NE
AVERAGE 'TOWER .-LOAD:
— Test Duration:
30 minutes
— Cond., iiter Return Temp.
83 deg. -F
Cond.-.--W46rtuppjy Temp',
78 deg. F
ond'., #k -T o
8;500'GPM,
H'6tR'qje On�-'!
4l;60,0 -MBH
percenv 0
'Adity,
47/6
0=2 SWn He 77 W -q GMIP':40.
14
Consulting + bigineering, + Technology + Construction
SYSKA I ll"-lN-Nli:SSY
13 'C.ELL OPERATTIPIS! 4. CELL OPERA11ON TREND PATA.
DATE: Janua,ry,3.1,.2008
7,1
TIME: 6-8:00AM
I - -
WEATHER ddNbIt-6.Nt-,
Temperature: 48A dog. F
kU HU'- Midliv.'� 660/o RH
Wir(&'.S,-' d�' 2 mph
peoA;
%*d.:bl'rettjt'oin''NNW,
AVERAGE TOWER ,116AD.
Test Duration:. 45 minutes
C'qr4.V'a'ter Return Temp: 84-.6r deg.; F
L " i 14" ' '�
'C6i-,i,��'.,-tit6tt7SUp'oiyTemp, 78:5 &-ai F
t6!i&WAkFI,6w- 9,425 GPM'
Heat R"ecSn., je [o, 28,278 MBH
Percent r.,Q 659
OQ 15
V=S-VSNa me lk USOM go. bo.
adeuk
Event 12
3..GELL OPER ,qN
c�
J
�� � IYbrlaFp�1.22�i8
Consulting + Engin(�erie i + Technology + Construction
41, ELLOPERATION;
e
_'%REND LATA,
DATE,Fekiruary 5,,2008
TIME 7:15 — 7:45 RM
Tamperaturei'
49Z deg. F
— Rel. El arrddity
44°!o RH
— VUin&Speed.':
5 mph
Wind Gijrection>
NNE
Heat F2e�ecti. on
ParcentrCapacty
QMNS�pKa Ht kiessyGmlp; lie.
30' m inutes
85 d!pq. F
191d'eg: F
%t83. GPM
26350 MBH
W%
v�.
C19
OR
Wom
Lai
SYSKA I EI NP',, SY
a,1aus
Event 13
3 CELL APERATION
Fe011ary21.2CG$
Consulting + Engineering + Technology + Corlstructi r)
4 CELL'OPERATIQN,
1
TREND DATA.,
• DATE,: FOr"U ry 6; 2008'
TIME.' 7.00;' -7:45 -AM
WE
ATHER',CG1hiDlTiON3>
Temperature'- 47A deg. F
Re Humidity 709/6 RH
Wind„$peed: 1 mph
Wind f3irecEiori S
AVERAGE TOW, ER�L'QAD:
i,es� uurat�vn;;
— Goad .Water Retui
'co
— c0h,-lfUater,F[aw
Heat ReJectton:
F?,erceret Capadiity
o2D2S�aka tle elassgGiasp: (w.
45” minutes
Temp: 80,deg .F
Temp.. 7,W -deg: -F`
-8;803;GPM.
24,200WBH
47%
17
I
S)',',K,\/A
EISSY
OAOUV
Event 1.4
4,CELLOPERAMPN
Consulting + Engineering + I'echnology + CoilstruCtion
*CELUOPERATION.
TRgNps T.
DATE: Februa,ry7,2008
TIME, 7:00 — 7M AM
WPAT-HER't,61\61TI,
L 1 1.
mper'�Iu r'e: 4*57 de� F
Re[Mumidi�n6/o . RH
7 -mph
W.in,,q-lpire,dtlo.m -,W.,Sw
AVERAG I E t#SR LOAD:
30 minutes
eturn-Temv 815 deg. F
Upoly., Ternp: 77.5 deg. F
In
my
LFA
sv��N I lit'NNIS.S),
QPoGUn
Event 15
3,rPELL-OPERATION'
ConsUltiho +,Ergineering + Technology + ConstrucUon
A CELL OPERATION
TREND DATA
• DATE F6kiruft 12;2008,
• TIME T*30 — 8,00 AM
"i
WEATHE'RiC6ND"[TIONS'::
ye- mperku r -e-- 652 deg. F
— ROLHumidity. 949/,DRH
— Wir&SP'eed: 1 mph
— Win -dT �Di're N
, qUon
P.Or'doorc4adit"w
36minuies
Temp: _86 'deg:'F
Temp' 771 F
.6
,8,004 GPM
>t 4\ lfl;;NNIl.SSY
GAOQ*
4 -CELL OPERATION
1, ,
Cop5ujtj,jg + Engineerit,,q Technology + Construction
4 CELL OPERATION,
TRENIJ DATA
• DAT-E;lF6bVuaiy 14,;2008
• TIME: 7:15_-=7:46 Am,
WEA T HER':QQNDI'TIQNS-.
Temperature; 62.7. deg. F
Rel -HUfbidityo,. 56%. RH
W.16d,!§ d mph
Wind NE
. AVEFZAdET0WER'-.LOkD
T0tLD4ratiqn:'-
30 minutes
C'on&: Water Return Temp:
86.5 deg. F
Cond-Water-SupPIV. Temp:
78 deg:F
7
Conoi:Water l'FI , ow
-8j2 11 GPM
'
Heat Rejiictfibrf-
34;900MBH-
T , —
Percent
68%
1 20
0=26VO He I �klssvlo 1p. Im.
mozam
EA
SYSKA Ingoun
Ev"ent. 177
3,GELL OPERATION
Consulting + Enqino&ihg 4- Tpthnology + Construction
4 CELLOPERATION,
TREND DATA.
DATE: February
TIME.
7A5 — TAB,Am
WEATHER "CONDITIONS, -."
Tifter, fc, 64S deg, F
Rel. Humidity: , 54% RH
WJnd-,'Sp'*e,,d.: 13.lmph
VVir-W. Direction ENE
Test Duraiiow, :30 minutes
C'ond,,later 'Return Temp: .86 deg> F
Cond.v pk. op01YTemp-1-'TT.6 deg , F
-9ol GPM
Heig-R-qjpq 10
"ri, 133�'7W MBH
P#e Capacity: 66%
29
V3
f
rN Consulting + 5ogineerMg,+ Technology + Construction
GROUP
EVent TO
3 CELL.OPERATIPM
4 CELLOPERATION,
4
TREND DATA
RATE: Ftbrwkry 21,, 2008
TIME: 7,3Q'— 8:00 AM
D , I , tftt.
EA
f— Tirnperaturw: 54,2,cleg. F
k6LHLffiildi*72% RH
Wind Speed 7 -mph
WindE.
Test
30.mfilutes
-Gond ,UUater-Ak6rwremp:
9
77:deg. F
d -VV`
aiter Flow
9,021 'IjPM
Heat Refection::
31.,600'MBH
Rif nrVp*oj*Itv:
'61%
22
City of Newport Beach
Hoag Memorial Hospital Presbyterian
Project No. 0OA3YZ
Design/ Implementation Report
Appendix H
Rev 0
Plume Mitigation Measure Summary —Syska Hennessy, April 9,
2008
H - Appendices City of Newport Beach_Syska Plm Milg Summary 9Apr08.doc
5.99
�me�o
S: c, I;taltirg + Er_(ineer na. 4- lechnoloc)y 4 ons rf =:i1Y' - -
Cooling Tower Plume Mitigation Measure.Surnmary
� T_ J_
-.-:r3:.Hu 3�
�Measurer�S!
�
.>IyT2 fx�a�ii
�..Descnpflon�)���Apprhz
'�
�I Ilfk w
�
1�- fn,vs�^tu*Ar'
�i1i�IlTim�ell�ne,fo 'ii
� � 1rT� I
nv 1n 2ih -
fgOPi�nof,
ip }�
n aillt{9f �"'
n Apptox�
i•4f,3:„v u f
ImplaG lox
Lam, ^�' Inufa "� .
�Appflo��}.j �
5,�,=,T 5i f ' �'r t f 7 �,' "y�.vl.""`�
^I`'i �, -M. ��1-Cons h�#;��, nt ;
� t� 3 '•titin
>�Ihri,�4.
rr<
s;y v},;� iii
>r� -.
.,
�* '^�-:
�
- i i
p y��
,�. �
�-
k
1
Modify Cooling
10-15%
Immediate
$0.
None
Incremental'
$12,000
• Increase in electrical demand,
Tower Operation,
Increase
- (note 3);
consumption and costs..
"
• Hospital "carbon footprint" increased.
Emissions Increased by :approxi:
> 67,500'ilblyear Carbon Dioxide
'- 2
Cooling Tower
15-20% _''
2009 -
$0.5 million
None
Incrementah
$24,000/yr
• Iriterruption oUutility services to Hospital.
Basin Pump
(note 7)
Increase
(note 4)`
• Increase:in electrical.' demand,
System
consumption and costs.
• Hospital "carbon footprind' increased.
Emissions Increased. by approx.:
.
> 135,0001blyearCarbon Dioxide
3
New Tower with
>70%
'Wnter2010
$7.9-9.3
Tower
Incremental
$843001yr
• Interruption of utility services to Hospital.
Plume Mitigation
(note7)million
height
Increase
(note 5) -
• increasetl boiler emissions from Plant,,
System
Increased
• Increase In electrical and natural gas.
by 10'd.
-
demand;: consumption and costs.
• Hospital"carbon footprint" increased.
- -
Emissions increased, by approx.:
> 160;000 Iblyr Carbon Dioxide
>.500'-Iblyear Nitrous Oxide
3A
Air Cooled Heat
>'50%
Winter 2010
$5.8-7.2
None
Incremental
$62,5001yr
• Interruption of utility services to Hospital.
Exchanger
(note 7)
(million
-
Increase.
(note;6)
• Electrical energy. input
System
required to modify for plume mitigation
•.Hospital "carbon footprint" increased.
Emissionsincreased. by approx.:
-
> 111,000 Ib/yr Carbon Dloxlde
ApNI%2003'
1 Z
—. ib2CO2:eYska Y,enaeSsy GrcvP. Inc r -.__ I,.
I i
RU
4i slux I ll"-\. ?ti s5Y
..doom.
Cr,, surItir:g •H I:r_iirw. r rtes .i, I echno Ic gy + 4;cin5} i atit>•.
Cooling Tower Plume Mitigation Measure Summary
Table Notes:
1. Includes design. OSHPD plan check (permitting), Coastal. Commission review and construction,
2. Syska's opinion of probable construction cost is based upon traditional sources, actual experience, or an actual equipment
quote. Due to the volatile nature of labor, material and equipment pricing and unforeseeable factors affecting the construction
industry, Syska does not expressly or implicitly warrantr or represent the accuracy- of the estimated cost to be the actual cost
of construction.
3. Approx. annual increase in electrical consumption cost due to measure implementation — equivalent to power use of 40
residential homeslvear.
4. Approx. annual increase in electrical consumption cost due to measure implementation equivalent to power use of 80
residential homes/year.
5. Approx. annual increase in natural gas and electrical consumption and cost due measure implementation— equivalent to
power use of 300 residential homes/year.
6. Approx. annual increase in electrical consumption and cost"due measure implementation — eguivalent.to power use of 222
residential homeslvear:
7. Assumes concurrent implementation of Measure/Option 1,.
April a, 20015
02002 Syaka:Hannessy Group,, 1.s
I
Engine -r ny r- Technology + Cr rn5tn i -icy
SYS KA k IENNF. SSY
6 i1 Cal C r
ptin it pled eat Ean Sustem
® Reduce the condenser water return temperature to operating towers by
p it cooled heat
rejectingcondenser water heat to the atmosphere viva a
exchanger system_
• Used in conjunction with modified' operational sequences outlined under
Option 1.
® Scope of Work:
- New air cooledheat exchanger system and fan(s) - located on grade
- Side steam condenser water pumping piping system
- Instrumentation and controls
- Building penetrations
- Structural pad and foundation
- Screening walls/enclosure for heat exchanger, -
- Normal power system feeders
_ .-..............
amu a. xoo6 !
--- 0 2002 $ySY.G Henressy Groap, In,..
I
Ci.,- :+,a#ir3 r- Frqine-r ny + Technology a.
cenar
tion 3A ®it Coolied HeatCool Exchanger System
Awn19,
-
en'haey�R .-v... V
�� �RH:�ClGtFJrA'
"r4u
a�
R
S
1 ; tiewr
uaw.
Awkr
fi
,{3
,i3
IF!
I'
{ in
{'
Awn19,
-
en'haey�R .-v... V
�� �RH:�ClGtFJrA'
"r4u
e A"^iY 1"C
1 ; tiewr
uaw.
Awkr
fi
M42 I a
S c Rir + Er_�inc.=r ns -I- `C r: ,nal[ -j + %' )r - n - i, - -- _--
evc�4
Option 3 it Cooled Heat Exchanger System
G
a e I k
a T
f.w t'Y"' - -_ h
�°'m+
4 �!ry 4 �* haw 1 i 9 a r ➢ `tizg� i:, E it -. _x
WE";j
W I VC.`�
3 ��}e;ss
:i
t
LN C..,;,rj%ulfirg -i- Er.jinm,,r no + lechriology + Cofishrk,thw-
caauo
Option 3A - 'Air Cooled Heat Exchanger System
April
C,^r,}. Itir9 + l r=aific, f,r n c.i- "I c (.f;no Ir qy .i- C r)ris,:rk ..i.:"
euauo
-
pion 33A ® it pled eatr s
— Greater then 50% reduction in cooling tower water plume density,
height and length when used is combination with Option 1.
• Cons
— $5.8 — 7.2 million estimated construction cost
— OSHPD plan check and permitting required,
— Air cooled heat exchanger system located outside of cooling tower
enclosure — new screened yard required
— New electrical service required
— Condenser water service curtailment interruption of Hospital
Operation during construction
— Energy inefficient — increases. Hospital's "carbon footprint'
— Increases the sound -power level (noise) at property line.
mlb3, 2309
0200SYSY.0 Henressl GmnP:)nc. � ,. •.,'-•-.. •..
W