Loading...
HomeMy WebLinkAboutF2018-0342 - Permits1850 Samhoree R4 Fool e- o3Lfa FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the thne ofsystem acceptance and approval. It shall be permitted to modify this form as needed to provide a more complete and/or clear record. Insert N/A in all unused lines. Attach additional sheets, data, or calculations as necessary to provide a complete record. 1. PROPERTY INFORMATION Name of property: BIG CANYON MAINTENANCE FACILAITY Address: 1850 JAMBOREE ROAD NEWPORT BEACH, CA 92660 Description of property: OFFICENVAREHOUSE lAil Occupancy type: B,S-1 Name of property representative: SLATER BUILDERS Address: 3100 PULLMAN STREET SUITE B, COSTA MESA, CA 92626 Phone: 714-434-4884 Fax: E-mail: Authority having jurisdiction over this property: NEWPORT BEACH FIRE DEPARTEMENT Phone: (949) 644-3106 Fax: E-mail: . 2. INSTALLATION, SERVICE, AND TESTING CONTRACTOR INFORMATION Installation contractor for this equipment: INTEC NETWORK SOLUTIONS, INC. Address: 15131 TRITON LANE SUITE 111 HUNTINGTON BEACH, CA 82649 License or certification number: 916986 C -10/C-7 Phone: .714-475 6675 Fax: E-mail: ALARMS@INTECSOCAL.COM Service organization for this equipment: INTEC NETWORKSOLUTIONS, INC. Address: 15131 TRITON LANE SUITE 111 HUNTINGTON BEACH, CA 92649 License or certification number: 916986 C -10/C-7 Phone: 714-475-6675 Fax: E-mail: ALARMS@INTECSOCAL.COM A contract for test and inspection in accordance with NFPA standards is in effect as of 3/1/2018 Contracted testing company: INTEC NETWORK SOLUTIONS, INC. Address: 15131 TRITON LANE SUITE 111 HUNTINGTON BEACH CA 92649 Phone: 714-475-6675 Fax: E-mail: ALARMS@INTECSOCAL.COM Contract expires: 5/1/2019 Contract number: 11035 Frequency of routine inspections: BIANNUAL 3. DESCRIPTION OF SYSTEM OR SERVICE El Fire alarm system (nonvoiee) ❑ Fire alarm with in -building fire emergency voice alarm communication system (EVACS) ❑ Mass notification system (MNS) ❑ Combination system, with the following components: ❑ Fire alarm ❑ EVACS ❑ MNS ❑ Two-way, in -building, emergency communication system ❑ Other (specify): NFPA 72, Fig. 10.18.2.1.1 (p. 1 of 12) Copyright 0 2009 National Fire protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 3. DESCRIPTION OF SYSTEM OR SERVICE (continued) NFPA 72 edition: 2016 Additional description of system(s): 3.1 Control Unit Manufacturer:. SILENT KNIGHT Model number: 6700 3.2 Mass Notification System ® This system does not incorporate an MNS 3.2.1 System Type: ❑ In -building MNS—combination ❑ In -building MNS—stand-alone ❑ Wide -area MNS ❑ Distributed recipient MNS ❑ Other (specify): 3.2.2 System Features: ❑ Combination fire alarm/MNS ❑ MNS autonomous control unit ❑ Wide -area NINS to regional national alerting interface ❑ Local operating console (LOC) ❑ Direct recipient MNS (DAMNS) ❑ Wide -area MNS to DRMNS interface ❑ Wide -area MNS to high-power speaker array (HPSA) interface ❑ In -building MNS to wide -area MNS interface ❑ Other (specify): 3.3 System Documentation ® An owner's manual, a copy of the manufacturer's instructions, a written sequence of operation, and a copy of the numbered record drawings are stored on site. Location: IN DOCUMENT BOX NEXT TO FACP 3.4 System Software ® This system does not have alterable site-specific software. Operating system (executive) software revision level: Site-specific software revision date: Revision completed by: ❑ A copy of the site-specific software is stored on site. Location: 3.5 Off -Premises Signal Transmission ❑ This system does nothave off -premises transmission. Name of organization receiving alarm signals with phone numbers: Alarm: CRITICOM MONITORING SERVICES Phone: 800-331-5165 Supervisory: CRITICOM MONITORING SERVICES Phone: 800-331-5165 Trouble: CRITICOM MONITORING SERVICES Phone: 800-331.5165 Entity to which alarms are retransmitted: NEWPORT BEACH FIRE Phone: 714-780-0981 Method of retransmission: CELLULAR If Chapter 26, specify the means of transmission from the protected premises to the supervising station: If Chapter 27, specify the type of auxiliary alarm system: ❑ Local energy ❑ Shunt ❑ Wired ❑ Wireless NFPA 72, Fig. 10.18.2.1.1 (p. 2 of 12) Copyright ®2009 National Fire Protection Association. This farm may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 4. CIRCUITS AND PATHWAYS 4.1 Signaling Line Pathways 4.1.1 Pathways Class Designations and Survivability Pathways class: Class B Survivability level: 0 Quantity: 1 (See NFPA 72, Sections 12.3 and 12.4) 4.1.2 Pathways Utilizing Two or More Media Quantity: _._ Description: 4.1.3 Device Power Pathways ❑ No separate power pathways from the signaling line pathway ❑ Power pathways are separate but of the same pathway classification as the signaling line pathway ❑ Power pathways are separate and different classification from the signaling line pathway 4.1.4 Isolation Modules Quantity: 4.2 Alarm Initiating Device Pathways 4.2.1 Pathways Class Designations and Survivability Pathways class: Survivability level: Quantity: (See NFPA 72, Sections 12.3 and 12.4) 4.2.2 Pathways Utilizing Two or More Media Quantity: _._. _ Description: 4.2.3 Device Power Pathways ® No separate power pathways from the initiating device pathway ❑ Power pathways are separate but of the same pathway classification as the initiating device pathway ❑ Power pathways are separate and different classification from the initiating device pathway 4.3 Non -Voice Audible System Pathways 4.3.1 Pathways Class Designations and Survivability Pathways class: Class B Survivability level: 0 _.. (See NFPA 72, Sections 12.3 and 12.4) 4.3.2 Pathways Utilizing Two or More Media Quantity: .. Description: Quantity: 2 4.3.3 Appliance Power Pathways ® No separate power pathways from the notification appliance pathway ❑ Power pathways are separate but of the same pathway classification as the notification appliance pathway ❑ Power pathways are separate and different classification from the notification appliance pathway NFPA 72, Fig. 10.18.2.1.1 (p. 3 of 12) Copyright 0 2009 National Fire Protection Association. This form may be copied for individual use other then for resale. It may not be copied for commercial sale or distribution. 5. ALARM INITIATING DEVICES 5.1 Manual Initiating Devices 5.1.1 Manual Fire Alarm Boxes ❑ This system does not have manual fire alarm boxes. Type and number of devices: Addressable: 1 Conventional: Coded: Transmitter: Other (specify): 5.1.2 Other Alarm Boxes ® This system does not have other alarm boxes. Description: Type and number of devices: Addressable: Conventional: Coded: Transmitter: Other (specify): 5.2 Automatic Initiating Devices 5.2.1 Smoke Detectors ❑ This system does not have smoke detectors. Type and number of devices: Addressable: 2 Conventional: Other (specify): Type of coverage: ❑ Complete area ® Partial area ❑ Nonrequired partial area Other (specify): Type of smoke detector sensing technology: ❑ Ionization ® Photoelectric ❑ Multicriteria ❑ Aspirating ❑ Beam Other (specify): 5.2.2 Duct Smoke Detectors ® This system does not have alarm -causing duct smoke detectors. Type and number of devices: Addressable: Conventional: Other (specify): Type of coverage: Type of smoke detector sensing technology: ❑ Ionization ❑ Photoelectric ❑ Aspirating ❑ Beam 5.2.3 Radiant Energy (Flame) Detectors ® This system does not have radiant energy detectors. Type and number of devices: Addressable: Conventional: Other (specify): Type of coverage: 5.2.4 Gas Detectors ® This system does not have gas detectors. Type of detector(s): Number of devices: Addressable: Conventional: Type of coverage: 5.2.5 Heat Detectors ❑ This system does not have heat detectors. Type and number of devices: Addressable: 3 Conventional: Type of coverage: ❑ Complete area ® Partial area ❑ Nonrequired partial area ❑ Linear ❑ Spot Type of heat detector sensing technology: ❑ Fixed temperature ® Rate -of -rise ❑ Rate compensated NFPA 72, Fig. 10.18.2.1.1 (p. 4 of 12) Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 5. ALARM INITIATING DEVICES (continued) 5.2.6 Addressable Monitoring Modules ❑ This system does not have monitoring modules. Number of devices: 3 ❑ This. system does not have sprinkler supervisory devices. 5.2.7 Waterflow Alarm Devices ❑ This system does not have waterflow alarm devices. Type and number of devices: Addressable: Conventional: 2 Coded: Transmitter: 5.2.8 Alarm Verification ® This system does not incorporate alarm verification. Number of devices subject to alarm verification: Alarmverification set for seconds 5.2.9 Presignal ® This. system does not incorporate pre -signal. Number of devices subject to presignal: Describe presignal functions: 5.2.10 Positive Alarm Sequence (PAS) ®This system does not incorporate PAS. Describe PAS: 6.3 Duct Smoke Detectors (DSDs) 5.2.11 Other Initiating Devices M This system does not have other initiating devices. Describe: Other (specify): 6. SUPERVISORY SIGNAL -INITIATING DEVICES 6.1 Sprinkler System Supervisory Devices ❑ This. system does not have sprinkler supervisory devices. Type and number of devices: Addressable: Conventional: 3 Coded: Transmitter: . Other (specify): 6.2 Fire Pump Description and Supervisory Devices M This system does not have a fire pump. Type fire pump: ❑ Electric pump ❑ Engine Type and number of devices: Addressable: Conventional: Coded: Transmitter: _ Other (specify):. 6.2.1 Fire Pump Functions Supervised ❑ Power ❑ Running ❑ Phase reversal ❑ Selector switch not in auto ❑ Engine or control panel trouble ❑ Low fuel Other (specify): 6.3 Duct Smoke Detectors (DSDs) ❑ This system does not have DSDs causing supervisory signals. Type and number of devices: Addressable: Conventional: 1 Other (specify): Type of coverage: Type of smoke detector sensing technology: ❑ Ionization ®.Photoelectric ❑ Aspirating E-] Beam 6.4 Other Supervisory Devices ❑ This system does not have other supervisory devices. Describe: NFPA 72, Fig. 10.18.2.1.1 (p. 5 of 12) Copyright 0 2009 National Fire protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 7. MONITORED SYSTEMS 7.1 Engine -Driven Generator 7.1.1 Generator Functions Supervised ❑ Engine or control panel trouble ❑ Generator running ❑ Other (specify): ® This system does not have a generator ❑ Selector switch not in auto ❑ Low fuel 7.2 Special Hazard Suppression Systems ® This system does not monitor special hazard systems. Description of special hazard system(s): 7.3 Other Monitoring Systems ®This system does not monitor other systems. Description of special hazard system(s): 8. ANNUNCIATORS 8.1 Location and Description of Annunciators Location 1: ON FACU IN MAIN ELECTICAL ROOM Location 2: Location 3: ❑ This. system does. not have annunciators. 9. ALARM NOTIFICATION APPLIANCES 9.1 In -Building Fire Emergency Voice Alarm Communication System ® This system does not have an EVACS. Number of single voice alarm channels: Number of multiple voice alarm channels: Number of speakers: Number of speaker circuits: Location of amplification and sound -processing equipment: Location of paging microphone stations: Location 1: Location 2: Location 3: 9.2 Nonvoice Notification Appliances ❑ This system does not have nonvoice notification appliances. Horns: 1 With visible: 1 Bells: With visible: Chimes: With visible: Visible only: Other (describe): 9.3 Notification Appliance Power Extender Panels Quantity: Locations: ® This system does not have power extender panels. NFPA 72, Fig. 10.18.2.1.1 (p. 6 of 12) Copyright 0 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 10. MASS NOTIFICATION CONTROLS, APPLIANCES, AND CIRCUITS ® This system does not have an MNS 10.1 MNS Local Operating Consoles Location 1: Location 2: Location 3: 10.2 High -Power Speaker Arrays Number of HPSA speaker initiation zones: Location 1: Location 2: Location 3: 10.3 Mass Notification Devices Combination fire alartri visible appliances: MNS-only visible appliances: Textual signs _.. Other (describe): Supervision class: 10.3.1 Special Hazard Notification ❑ This system does not have special suppression predischarge notification. ❑ MNS systems DO NOT override notification appliances required to provide special suppression predischarge notification. 11. TWO-WAY EMERGENCY COMMUNICATION SYSTEMS 11.1 Telephone System ® This system does not have a two-way telephone system. Number of telephonejacks installed: Number of warden stations installed: Number of telephone handsets stored on site: Type of telephone system installed: ❑ Electrically powered ❑ Sound powered 11.2 Two -Way Radio Communications Enhancement System ® This system does not have a two-way radio communications enhancement system. Percentage of area covered by two-way radio service: Critical areas: _ % General building areas: % Amplification component locations: ------------ Inbound signal strength: ,. _ dBm Outbound signal strength: _ dBm Donor antenna isolation is: _. dB above the signal booster gain Radio frequencies covered: Radio system monitor panel location: NFPA 72, Fig. 10.18.2.1.1 (p. 7 of 12) Copyright 0 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 11. TWO-WAY EMERGENCY COMMUNICATION SYSTEMS (continued) 11.3 Area of Refuge (Area of Rescue Assistance) Emergency Communications Systems ® This system does not have an area of refuge (area of rescue assistance) emergency communications system. Number of stations: Location of central control point: Days and hours when central control point is attended: Location of alternate control point: Days and hours when alternate control point is attended: 11.4 Elevator Emergency. Communications Systems N This system does not have an elevator emergency communications system. Number of elevators with stations: _ _.. Location of central control point: Days and hours when central control point is attended: Location of alternate control point: Days and hours when alternate control point is attended: 11.5 Other Two -Way Communication Systems Describe: 12. CONTROL FUNCTIONS This system activates the following control fuctions: ❑ Hold -open door releasing devices ❑ Smoke management ❑ HVAC shutdown ❑ F/S dampers ❑ Door unlocking ❑ Elevator recall ❑ Fuel source shutdown ❑ Extinguishing agent release ❑ Elevator shunt trip ❑ Mass notification system override of fire alarm notification appliances Other (specify): 12.1 Addressable Control Modules ® This system does not have control modules. Number of devices: Other (specify): 13. SYSTEM POWER 13.1 Control Unit 13.1.1 Primary Power Input voltage of control panel: 120VAC _ _ Control panel amps: 20 Overcurrent protection: Type: p Amps: Location (of primary supply panel board): Panel: Circuit: `3 Disconnecting means location: Breaker 13.1.2 Engine -Driven Generator ® This system does not have a generator. Location of generator: Location of fuel storage: _ _ .Type of fuel: NFPA 72, Fig. 10.18.2.1.1 (p. 8 of '12) Copyright 02009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 13. SYSTEM POWER (continued) 13.1.3 Uninterruptible Power System E This system does not have a UPS. Equipment powered by a UPS system: Location of UPS system: Calculated capacity of UPS batteries to drive the system components connected to it: In standby mode (hours): In alarm mode (minutes): 13.1.4 Batteries Location: In Panel.. _ _ Type: Gell Cell _ _ _ Nominal voltage: 12VDC Amp/hour rating: 7 _ Calculated capacity of batteries to drive the system: In standby mode (hours): 24 _ _ In alarm mode (minutes): 5 E Batteries are marked with date of manufacture ® Battery calculations are attached 13.2 In -Building Fire Emergency Voice Alarm Communication System or Mass Notification System E This system does not have an EVACS or MNS system. 13.2.1 Primary Power Input voltage of EVACS or MNS panel: EVACS. or MNS panel amps: Overcurrentprotection: Type: _ Amps: Location (of primary supply panel board): Disconnecting means location: 13.2.2 Engine -Driven Generator ❑ This system does not have a generator. Location of generator: Location of fuel storage: _. Type of fuel: 13.2.3 Uninterruptible Power System ❑ This system does not have a UPS. Equipment powered by a UPS system: Location of UPS system: Calculated capacity of UPS batteries to drive the system components connected to it: In standby mode (hours): _ In alarm mode (minutes): _ 13.2.4 Batteries Location: _ _ Type: Nominal voltage: _ Amp/hour rating: Calculated capacity of batteries to drive the system: In standby mode (hours): In alarm mode (minutes): ,. ❑ Batteries are marked with date of manufacture ❑ Battery calculations are attached NFPA 72, Fig. 10.18.2.1.1 (p. 9 of 12) Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 13. SYSTEM POWER (continued) 13.3 Notification Appliance Power Extender Panels ® This system does not have power extender panels. 13.3.1 Primary Power Input voltage of power extender panel(s): Power extender panel amps: Overcurrent protection: Type: Amps: Location (of primary supply panel board): Disconnecting means location: 13.3.2 Engine -Driven Generator ® This system does not have agenerator. Location of generator: Location of fuel storage: Type of fuel: 13.3.3 Uninterruptible Power System ® This system does not have a UPS. Equipment powered by a UPS system: Location of UPS system: Calculated capacity of UPS batteries to drive the system components connected to it: In standby mode (hours): In alarm mode (minutes): 13.3.4 Batteries Location: Type: Nominal voltage: Amp/hour rating: Calculated capacity of batteries to drive the system: In standby mode (hours): In alarm mode (minutes): ❑ Batteries are marked with date of manufacture ❑ Battery calculations are attached 14. RECORD OF SYSTEM INSTALLATION Fill out after all installation is complete and wiring has been checked for opens, shorts, ground faults, and improper branching, but before conducting operational acceptance tests. This is a: ® New system ❑ Modification to an existing system Permit number: The system has been installed in accordance with the following requirements: (Note any or all that apply.) ® NFPA 72, Edition: 2016 ® NFPA 70, National Electrical Code, Article 760, Edition: 2016 ® Manufacturer's published instructions Other (specify): System deviations from referenced NFPA standards: Signed: ,. ed name: ERIK PETERSON __. _ Date: 5/21/2019 Organization: Intec Network Solutions Title: President Phone: 714-580-6980 NFPA 72, Fig. 10.18.2.1.1 (p. 10 of 12) Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 15. RECORD OF SYSTEM OPERATIONAL ACCEPTANCE TEST ® New system All operational features and f tnctions of this system were tested by, or in the presence of, the signer shown below, on the date shown below, and were found to be operating -properly in accordance with the requirements for the following: ❑ Modifications to an existing system All newly modified operational features and functions of the system were tested by, or in the presence of, the signer shown below, on the date. shown below, and were found to be operating properly in accordance with the requirements ofthe following: ® NFPA 72, Edition: 2016 ® NFPA 70, National Electrical Code, Article 760, Edition: 2016 ® Manufacturer's published instructions Other (specify): ® Individual device. testing documentation [Inspection and Testing Form (Figure 14.6.2.4) is attached] Signed: Printed name: ERIK PETERSON Date: 5/21/2019 Organization: NTEC NETWORK Title: PRESIDENT Phone: 714.580-6980 SOLUITIONS, INC 16. CERTIFICATIONS AND APPROVALS 16.1 System Installation Contractor: This system, as specified herein, has been installed and tested according to all NFPA standards cited herein.. Signed: Printed name: ERIK PETERSON Date: 5/21/2019 Organization: INTEC NETWORK Title: PRESIDENT Phone: 714-580-6980 SOLUTIONS, INC 16.2 System Service Contractor: The undersigned has a service contract for this system in effect as of the date shown below. Signed/- �_ Printed name: ERIK PETERSON - _ Date: 5/21/2019 Organization: INTEC NETWORK Title: PRESIDENT Phone: 714-580-6980 SOLUTIONS, INC.. 16.3 Supervising Station: This system, as specified herein, will be monitored according to all NFPA standards cited herein. Signed: N/A Printed name: N/A Date: Organization: CritiLink Title: N/A Phone: 800-331-5165 NFPA 72, Fig. 10.18.2.1.1 (p. 11 of 12) Copyright 0 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 16. CERTIFICATIONS AND APPROVALS (continued) 16.4 Property or Owner Representative: I accept this system as having been installed and tested to itsspecifications and all NFPA standards cited herein.. Signedy. .. �_. Printed naihe`.�" `" a�►L'd.. Date: V '3 d—I— 1 �t Organization: S�_Ir r_J... _.. Title: S.t�,J. U..,V„Phone: ��`/--�3-3/-.Lb 16.5 Authority Having Jurisdiction: I have witnessed a satisfactory acceptance test of this system and find it to be installed and operating properly in accordance with its approved plans and specifications, with its approved sequence of operations, and with all NFPA standards cited herein. Signed: N. Kkowks Printedname: NAj>jNe M'012Z�SDate: s -30-(q.. Organization: NEWPORT BEACH FIRE _ Title: l NSr'l:c-hot Phone: (9`+CA) (o`(4 -310J NFPA 72, Fig. 10.18.2.1.1 (p. 12 of 12) Copyright © 2009 National Fire Protection Association. This farm may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.