Loading...
HomeMy WebLinkAboutX2019-3729 - Miscb I A I e yr UHLIrUNNIA 21459 Necupori COOS+ VT AIR ECONOMIZER CONTROLS ACCEPTANCE X.2014- 37.24 CLC-NRCA-MCH-05-A fRevisod nvtet t,HLVUKNIA t,NtKUT UUIVIIWN5b1UIN CERTIFICATE OF ACCEPTANCE NRCA-MCH-05-A Air Economizer Controls Acceptance (Page 1 of 3) . Project Name: - TIC NEWPORT COAST Enforcement Agency: CITY OF NEWPORT BEACH Perm1tNmnber: 2570-2019 Project Address -.City: ' - 21159 NEWPORT COAST DR IRVINE Zip Code: 92657 System Name or Identification/rag: SOKCOA06A2A6/1619C78699 System Location or Area Same& MAIN AREA Note: Submit one Certificate ofAcceptancefor each system that must Enforcement AgencyUse: Checked' by/Date demonstrate compliance. A. Construction Inspection 1.. :Supporting documentation needed to perform test includes: a. 2016 Building Energy Efficiency Standards Nonresidential Compliance Manual (NAZ5.4 Air Economizer Controls Acceptance At -A- b. 2016 Building Energy Efficiency Standards. 2. Instrumentation to perform test includes: a. Hand-held temperature probe Calibration Date: 3/17/19 (must be within last year) b. Device capable of calculating enthalpy (i.e. psychrometer) - Calibration Date: 3/17/19 (must be within last year) c. 1.2 k Ohm Resistor ( when specified by the manufacturer) 3•. ;Installation; (all of the following boxes should be checked) ❑ - Economizer high limit shutoff control complies with Table 140.4-B found in the 2016 Building Energy Efficiency Standards Section 140.4(e)3. ❑ Economizer reliability features are present per 2016 Building Energy Efficiency Standards Section 140.4(e)4: - a. 5 -year manufacturer warranty of economizer assembly b. Provide a product specification sheet proving capability of at least 60,000 actuations c. Provide a product specification sheet proving compliance with AMCA Standard 500-D damper leakage at 10 cfm/ftz at 250 Pascals (1.0 in w.g). A product specification sheet showing the manufacturer's results after following the testing procedures of AMCA Standard 500-D. A product specification sheet showing the economizer outside air and return air damper leakage rates have been certified to the Energy Commission in accordance with Section 110. d. If the high limit setpoint is fixed dry-bulb or fixed enthalpy + fixed dry-bulb then the control shall have an adjustable setpoint e. Outdoor air, return air, mixed air, and supply air sensors shall be calibrated as follows: i. Dry-bulb and wet -bulb temperatures accurate to ±27 over the range of 40°F to 80°F ii. Enthalpy accurate to ±3 Btu/Ib over the range of 20 Btu/Ib to 36 Btu/Ib iii. Relative humidity (RH) accurate to±5%over the range of 20% to 80% RH f. Check that the sensor performance curve(s) is provided by the factory and sensor output values measured during sensor calibration are plotted on the performance curve(s). g. Sensors used for high limit control shall be located to prevent false readings, including but not limited to being properly shielded from direct sunlight. ❑ Unitary systems with an economizer have control systems, including two-stage or electronic thermostats, that cycle compressors off when economizers can provide partial cooling. ❑ System has return fan speed control, relief dampers, or dedicated relief fans to prevent building over pressurization in full economizer mode. ❑ .For systems with DDC controls, sensor used for economizer lockout has been factory or field calibrated.. ❑ For systems with non -DDC controls, manufacturer's startup and testing procedures have been applied. cA building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016 J IAI t Ur UALIPUKNIA AIR ECONOMIZER CONTROLS ACCEPTANCE > CEC-NRCA-MCH-05-A (Revised 01/16) CERTIFICATE OF ACCEPTANCE v NRCA,MCH-05-A Air Economizer Controls Acceptance (Page 2 of 3) Project Name: TIC NEWPORT COAST Enforcement Agency: CITY OF NEWPORT BEACH Permit Number: 2570-2019 Project Address: 21159 NEWPORT COAST DR City: IRVINE Zip Code: 92657 System Name or Identification/rag: SOKCOA06A2A6/1619C78699 System Location.,Area Served: MAIN AREA B. Functional Testing IResults Is the economizer listed in the CEC equipment certification directory? (if yes, proceed to Section D.) Yes 0 No 0 Step 1: Disable demand control ventilation systems (if applicable) Step 2: Enable the economizer and simulate a cooling demand large enough to drive the economizer fully open. Verify the following: a. , Economizer damper modulates 100% open. Yes Q No 0 b• Return air damper modulates 100% closed. Yes 0 No 0 - C. ,: For systems that meet the criteria of 2016 Building Energy Efficiency Standards Section 140.4(e)1, verify that the economizer remains 100% open with the use of mechanical cooling. This occurs when the cooling demand can no longer be met by the economizer alone. Yes 0 No 0 Ell. All applicable fans and dampers operate as intended to maintain building pressure. Yes p No 0 e, The unit heating is disabled (if applicable). - Yes 0 No O.NA 0. Step 3: Disable the economizer and simulate a cooling demand. Verify the following: a• Economizer damper closes to its minimum position. Yes. Q No 0 b• - Allapplicable fans and dampers operate as intended to maintain building pressure. Yes 0 No 0 c• The unit heating is disabled (if applicable). iYes C) No 0 NA 0 Step 4: If the unit is equipped with heating, simulate a heating demand and enable the economizer. Verify the following: a. Economizer damper closes to its minimum position. IYes (j) No 0 NA 0 b-.. - Return air damper opens. Yes No NA 0 Step 5: Turn off the unit and verify the following: EEconomizer damper closes completely. Yes Q No 0 Step 6: System returned to initial operating conditions Yes 0 No 0 C. Testing Results PASS. / FAIL .Step 2: Simulatecooling load and enable the economizer (all answers are Y and/or NA). 0 0 Step 3: Simulate cooling load and disable the economizer (all answers are Y and/or NA). 0 0 Step 4: Simulateheating demand and enable the economizer (all answers are Y and/or NA). 0 Step 5: Turn off the unit (all answers are Y). E 0 D. Evaluation R PASS: All Construction Inspection responses are complete and all Testing Results responses are "Pass" or the economizer is listed in the CEC equipment cerification directory. Notes: CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016 JI A I It Lir GALII-V NNIA AIR ECONOMIZER CONTROLS ACCEPTANCE CEC-NBCA-MCH-05-A (Revised 01/16) rni ianannn anicary rnnnnniccinnr CERTIFICATE OF ACCEPTANCE - NRCA-MCH-05-A .Air Economizer Controls Acceptance (Page 3 of 3) Project Name: TIC NEWPORT COAST Enforcement Agency: CITY OF NEWPORT BEACH Permit Number: 2570-2019 Project Address:' - 21159 NEWPORT COAST DR City; IRVINE Zip Code: 92657 System Name or Identification/Tag: 50KCQA06A2A6/1619C78699 system Location or Area Sewed; MAIN AREA DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1; 1 certify that this Certificate of Acceptance documentation is accurate and complete. Documentation Author Name: JOSEJASSO Documentation Author Signature: Documentation Author Company Name: - - M3 MECHANICAL / - Date Signed: l. ,a ATT Certification Identification v Address: 600A W TAFT AVE City/State/Zip: ORANGE, CA 92865 Phone: 714-628-1308 FIELD TECHNICIAN'S DECLARATION STATEMENT - I certify the. following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Acceptance is true and correct. 2. 1 am the person who performed the acceptance verification reported on this Certificate of Acceptance (Field Technician). - 3. The construction or installation identified on this Certificate of Acceptance complies with the applicable acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance 'requirements and procedures specified in Reference Nonresidential Appendix NAT 4. 1 have confirmed that the Certificate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and signed by the responsible builder/installer and has been posted or made available with the building permit(s) issued for the building. Field Technician Name: RICK MOLNAR Field Technician Signature: - Field Technician Company Name: M3 MECHANICAL Position with Company (Title): SR. TECHNICIAN Address: 600A W TAFT AVE ATT Certification Identification (if applicable):Q61 O City/State/Zip:ORANGE, CA 92865 Phone: 714-628-1305 Date signed: q ry RESPONSIBLE PERSON'S DECLARATION STATEMENT 'I certify the following under penalty of perjury, under the laws of the State of California: -1 1. am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the - information provided on this Certificate of Acceptance. 2. I am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction or installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement (responsible acceptance person). 3. The information provided on this Certificate of Acceptance substantiates that the construction or installation identified on this Certificate of Acceptance complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NAT 4, I have confirmed that the Certificate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and is posted or made available with the building permit(s) issued for the building. 5. 1 will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that signed copy of this Certificate of Acceptance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Acceptance Person Name: TONY MOLNAR Responsible Acceptance Person Signature: Responsible Acceptance Person Company Name: - M3 MECHANICAL Position with Company (Title): PRESIDENT Address: 600A W TAFT AVE CSLB License: 786760 City/State/Zip: ORANGE, CA 92867 Phone: 714-628-1308 Date signed: CA Building Efficiency Standards - 2016 Nonresidential Compliance January 2015. FAULT DETECTION AND DIAGNOSTICS FOR PACKAGED DIRECT EXPANSION UNITS CEC-NRCA-MCH-12-A Revised 08/16 CALIFORNIA ENERGY COMMISSION . r. CERTIFICATE OF ACCEPTANCE NRCA-MCH-12-A Fault Detection and Diagnostics (FDD) for Packaged Direct Expansion Units (Page 1 of 2) Project Name: TIC NEWPORT COAST Enforcement Agency: CITY OF NEWPORT BEACH Permit Number. 9 2570-2019 Project Address: - .21159 NEWPORT COAST DR City: IRVINE - Zip Code: 92657 System Name or ldentifration/rag: 50KCQA06A2A6/1619C78699 system wcation orArea served: MAIN AREA Note: Submit one Certificate of Acceptance for each system that must Enforcement Agency Use: Checked by/Date demonstrate compliance. A. Construction Inspection 1, Prior to functional testing, verify and document: - The Fault Detection and Diagnostics (FDD) hardware is installed on the unit. ❑ The FDD system is certified to the California Energy Commission. ❑ 2. The following air temperature sensors are permanently installed: ❑ Outside Air Sensor ❑ Supply Air Sensor ❑ .Return Air Sensor (Applicable for differential economizer operation only) ❑ B. Functional Testing Air Temperature Sensor Failure/Fault Step 1: Verify the FDD system indicates normal operation. - ❑ Step 2: Disconnect outside air temperature sensor from unit controller. Verify the FDD system reports a fault. ❑ Step 3: Connect outside air temperature sensor tounit controller. Verify the FDD system indicates normal operation. ❑ Excess Outside Air Step 1:_ Coordinate this test with NRCA-MCH-02-A (NA 7.5.1 Outdoor Air), if NRCA-MCH-02-A indicates "pass" then verify the FDD - indicated normal operation. 11system Economizer Operation Step 1:. Coordinate this test with NRCA-MCH-05-A (NA 7.5.4 Air Economizer Controls). Simulate failure by immobilizing the outdoor air economizer damper according to the manufacturer's instructions. Verify the FDD system reports a fault. 11 Step 2: Successfully complete and pass NRCA-MCH-05-A and verify the FDD system reports normal operation. ❑ C. Testing Results PASS / FAit Test passes if all boxes are checked under Functional Testing. Q D. Evaluation ❑� PASS: All Construction Inspection responses are complete and Testing Results is "Pass". Notes: - CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance August 2016 FAULT DETECTION AND DIAGNOSTICS FOR PACKAGED DIRECT EXPANSION UNITSe Fault Detection and Diagnostics (FDD) for Packaged Direct Expansion Units (Page 2 of 2) CFC -NBCA -MCH -12-A !Revised nails) IAi mnou A EMERCv nnaaaniemnni Enforcement Agency: CITY OF NEWPORT BEACH CERTIFICATE OF ACCEPTANCE NRCA-MCH-12-A Fault Detection and Diagnostics (FDD) for Packaged Direct Expansion Units (Page 2 of 2) Project Name: :TIC NEWPORT COAST Enforcement Agency: CITY OF NEWPORT BEACH Permit Number: 2570-2019 Project Address: - - 21159 NEWPORT COAST DR City: IRVINE Zip Cade: - 92657 System Name or Identification/ rag: '. SOKCQA06A2A6/1619C78699 System Location or Area Served: MAIN AREA DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1.- L certify that this Certificate of Acceptance documentation is accurate and complete. Documentation Author Name: JOSEIASSO Documentation Author Signature: Documentation Author Company Name: - M3 MECHANICAL Date Signed: k(Id3 /I ATT Certification Identification lit appucablei: Address: 600A W TAFT AVE City/State/Zip: ORANGE, CA 92865 Phone: 714-628-1308 FIELD TECHNICIAN'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. - The information provided on this Certificate of Acceptance is true and correct. 2.'. `I am the person who performed the acceptance verification reported on this Certificate of Acceptance (Field Technician). B. The construction or installation identified on this Certificate of Acceptance complies with the applicable acceptance requirements indicated in the plans andspecificationsapproved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NAT 4.. (have confirmed that the Certificate(s) of Installation forthe construction or installation identified on this Certificate of Acceptance. has -. been completed . and signed by the responsible builder/installer and has been posted or made available with the building permits) issued for the building. Field Technician Name: RICK MOLNAR Field Technician Signature: 0111ar .Field Technician Company Name: M3 MECHANICAL Position with Company (Title): SR. TECHNICIAN Address(, 600A W TAFT AVE ATT Certification Identification (if applicable): —116760 / O City/State/Zip: ORANGE, CA 92865 Phone: 714-628-1308 Date Signed: (� las�/y, - RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this Certificate of Acceptance. 2. -1 am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction or installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement (responsible acceptance person). 3.. The information provided on this Certificate of Acceptance substantiates that the construction or installation identified on this Certificate of Acceptance complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NA T 4: 1.}lave confirmed that the Certificate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and is posted or made available with the building permit(s) issued for the building. 5. 1 will ensure that a completed, signed copy of this Certificate of Acceptance shall be pasted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder provides to the building. owner at occupancy. Responsible Acceptance Person Name: TONY MOLNAR Responsible Acceptance Person Signature: M Responsible Acceptance Person Company Name: M3. MECHANICAL Position with Company (Title): PRESIDENT ..Address: 600A W TAFT AVE CSLB License: 786760 City/State/Zi ORANGE, CA 92867 Phone: 714-628-1308 Date Signed: CA Buildir Energy Efficiency Standards - 2016 Nonresidential Compliance August 2016 J I H It Ur UHLII'URIVIH CONSTANT VOLUME, SINGLE ZONE, UNITARY (PACKAGED AND SPLIT) A701 CONDITIONER AND HEAT PUMP SYSTEMS CEC-NRCA-MCH-03-A Revised 07/76 - CALIFORNIA EN "O lull MMISSION CERTIFICATE OF ACCEPTANCE NRCA-MCH-03-A Constant Volume, Single Zone, Unitary (Packaged and Split) Air Conditioner and Heat Pump Systems Page 1 of 3 Project Name: TIC NEWPORT COAST Enforcemen[Agenry: CITY OF NEWPORT BEACH Permit Number: 2570-2019 Project Address: 21159 NEWPORT COAST DR City: IRVINE Zip Code: 92657 System Name or Identigcatkm/Tag: 50KCQA06A2A6/1619C78699 System Location or Area Serves: MAIN AREA Note: Submit one Certificate ofAcceptancefor each system that must Enforcement Agency Use: Checked by/Date demonstrate compliance. A. Construction Inspection 1. Supporting documentation needed to perform test includes, but not limited to: a. 2016 Building Energy Efficiency Standards Nonresidential Compliance Manual (NA7.5.2 Constant Volume, Single -zone, Unitary Air Conditioner and Heat Pumps Systems Acceptance At -A -Glance). b. 2016 Building Energy Efficiency Standards Manual 2. Instrumentation to perform test may include: a. Temperature Meter b. Amp Meter 3. Installation (check if applies): ❑ Thermostat is located within the space -conditioning zone that is served by the HVAC system. 4. Programming (check all those that apply): ❑ Thermostat meets the temperature adjustment and dead band requirements of 2016 Building Energy Efficiency Standards Manual Section 120.2(b). Minimum heating setpoint: 68 OF. Maximum cooling setpoint 72 OF. Deadband: 2 OF. ❑ Occupied, unoccupied, and holiday schedules have been programmed per the schedule provided. ❑ Pre -occupancy purge has been programmed to meet the requirements of 2016 Building Energy Efficiency Standards Manual Section 120.1(c)2. 1. Check method used to determine pre -occupancy purge: ❑ Lesser of: conditioned floor area times ventilation rate from 2016 Building Energy Efficiency Standards TABLE. 120.1-A or 15cfm per person times the expected number of occupants. ❑ 3 complete air changes. Notes: Standards -2016 Nonresidential Compliance July 2016 b] H I t Ur UHLWUKN IH CONSTANT VOLUME, SINGLE ZONE, UNITARY (PACKAGED AND SPLIT) Alit CONDITIONER AND HEAT PUMP SYSTEMS re no^ a C^rprvrnba^aCen^ CERTIFICATE OF ACCEPTANCE NRCA-MCH-03-A "Constant Volume, Single Zone, Unitary (Packaged and Split) Air Conditioner and Heat Pump Systems Page 2 of 3 Project Name: TIC NEWPORT COAST Enforcement Agency: CITY OF NEWPORT BEACH Permit Number 2570-2019 Project Address: -21159 NEWPORT COAST DR City: IRVINE Zipcode: 92657 System Na me or ldentifw[ion/rag: 50KCQA06A2A6/1619C78699 System Location or Area Served: MAIN AREA B. Functional Testing Requirements I operating Modes Step 1: Disable economizer control and demand -controlled ventilation (if applicable) to prevent unexpected interactions. -. Occupied Mode - 5 Step 2: Heating load during occupied condition 3 Step 3: No-load during occupied condition '. Step 4: Cooling load during occupied condition Unoccupied Mode Step 5: No-load during unoccupied condition Step 6: Heating load during unoccupied condition Step 7: Cooling load during unoccupied condition Step 8: Manual override P P 8 7 6 5 4. ''3 2f Step 2 - 8: Check and verify the following for each simulation mode required a. Supply fan operates continually { {'-+ Ej;; b. -Supply fan turns off fk1t ?;ii• is;!lI� ✓ i Ih�F� Jih���;I;i C. Supply fan cycles on and off t/ t/ �33 j4 i � l j liiti Xjwl d. System reverts to "occupied" mode to satisfy any condition ✓ ii ;n ' ' I,Is ( System turns off when manual override time period expires ✓!t�i431( ,)iii Ijg��!�'fli�iti lliSj{l Gwt".i.i� 5a ;�:tl�ihhe. f. Gas-fired furnace, heat pump, or electric heater stages on Ijf l g. No heating is provided by the unitCi.. ✓j� ✓ ✓ ✓:" - h. - No cooling is provided by the unit lIP�III; t/ V/ i. Compressor stages on ✓ ({3 ik,lit. �} ✓ $laagq rl{:n{. ,✓ j. Outside air damper is open to minimum position ✓ ✓ £! i ✓ ✓ k. Outside air damper closes completely� � , ri ii ;)J1� WIN Step 9: System returned to initial operating conditions after all tests have been completed: Yes No Q C. Testing Results 8 7 6 5 4 3 2 Indicate if Passed (P), Failed (F), or N/A (X), fill in appropriate letter P P P P I P I P I P' D. Evaluation PASS: All Construction Inspection responses are complete and all applicable Testing Results responses are "Pass" (P). CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance July 2016 a i A It Ur UAurUKNIA Constant Volume, Single Zone, Unitary (Packaged and Split) Air Conditioner and Heat Pump Systems Page 3 of 3 CONSTANT VOLUME, SINGLE ZONE, UNITARY (PACKAGED AND SPLIT) Enforcement Agency: CIN OF NEWPORT BEACH AIR CONDITIONER AND HEAT PUMP SYSTEMS ellCEC NRCA-MCH-03-A Revised 07/16 CALIFORNIA ENERGY COMMISSION Zip Code: 92657 System Name or Identification/rag: SOKCQA06A2A6/1619C78699 System Location cr Area Served: MAIN AREA I certify the following under penalty of perjury, underthe laws of the State of California: 1, The information provided on this Certificate of Acceptance is true and correct. - 2. 1 am the person who performed the acceptance verification reported on this Certificate of Acceptance (Field Technician). . CERTIFICATE OF ACCEPTANCE NRCA-MCH-03-A Constant Volume, Single Zone, Unitary (Packaged and Split) Air Conditioner and Heat Pump Systems Page 3 of 3 Prajaet Name: TIC NEWPORT COAST - Enforcement Agency: CIN OF NEWPORT BEACH Permit Number: 2570-2019 Project Address: .21159 NEWPORT COAST DR City: IRVINE Zip Code: 92657 System Name or Identification/rag: SOKCQA06A2A6/1619C78699 System Location cr Area Served: MAIN AREA DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that this Certificate of Acceptance documentation is accurate and complete. Documentation Author Name: JOSE JASSO Documentation Author Signature: Documentation Author Company Name: M3 MECHANICAL Date Signed: ATT Certification Identifica.._:.,r .. Ae): Address: 600A W TAFT AVE City/State/Zip: ORANGE, CA 92865 Phone: 714-628-1308 FIELD TECHNICIAN'S DECLARATION STATEMENT I certify the following under penalty of perjury, underthe laws of the State of California: 1, The information provided on this Certificate of Acceptance is true and correct. - 2. 1 am the person who performed the acceptance verification reported on this Certificate of Acceptance (Field Technician). . 3.' The construction or installation identified on this Certificate of Acceptance complies with the applicable acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance -requirements and procedures specified in Reference Nonresidential Appendix NA7. 4. 1 have confirmed that the Certificate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and signed by the responsible builder/installer and has been posted or made available with the building permit(s) issued for the building. Field Technician Name: RICK MOLNAR Field Technician Signature: I of n G ir i Field Technician Company Name: M3 MECHANICAL Position with Company (Title): SR. TECHNICIAN AN Address:; 600A W TAFT AVE ATT Certification Identification (if applicable): 'I R o City/State/Zip: ORANGE, CA 92865 Phone: 714-628-1308 d11rP Date Signe; p II/�pj14 ✓' RESPONSIBLE PERSON'S DECLARATION STATEMENT. Icertify the following under penalty of perjury, under the laws of the State of California: 1. 1 am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this Certificate of Acceptance. - 2._ . I. am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the - system design,. construction or installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement (responsible acceptance person). 3. The information provided on this Certificate of Acceptance substantiates that the construction or installation identified on this Certificate of Acceptance complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, andconforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential - Appendix NA7: 4. L have confirmed that the Certificate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has beencompletedand is posted or made available with the building permit(s) issued for the building. S. I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Acceptance Person Name: TONY MOLNAR Responsible Acceptance Person Signature: -TM Responsible Acceptance Person Company Name; - M3 MECHANICAL Position with Company (Title): PRESIDENT Address: 600A W TAFT AVE CSLB License: 786760 City/State/Zip:Phone: ORANGE, CA 92867 714-628-1308 Date Signed: I CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance July 2016 J IM I tLr l.nurunrvw OUTDOOR AIR ACCEPTANCE "'EC -NBCA -MCH -02-A (Revised 07/16) rtAI IFnRNIA FNFRr Y COMMISSION CERTIFICATE OF ACCEPTANCE NRCA-MCH-02-A Outdoor Air Acceptance (Page I of 3) Pmica Name: Enforcement Agency: Permit Number: TIG NEWPORT COAST CITY OF NEWPORT BEACH 2570-2019 Project Address: City: Zip Code: ,21159 NEWPORT COAST DR IRVINE 92657 System Name or Identification/Tag: system Location or Area served: 50KCQA06A2A6/1619C78699 MAIN AREA Note: Submit one Certificate of Acceptance for each system Enforcement Agency Use: Checked by/Date that must demonstrate compliance. Intent:. Verify measured outside airflow reading is within 10% of the total required outside airflow. Required for all newly installed HVAC units: Reference MCH -03 (Column 14) or Mechanical Equipment Schedules. Note: MCH -02-A can be performed in conjunction with MCH -07-A Supply Fan VFD Acceptance (if applicable) since testing activities overlap.: 1. Supporting documentation needed to perform test includes: As-bui It and/or design documents (for example, Mecha nical Equipment Schedu les, Equipment a' Start -Up Sheets or Balancing Reports). b. 2016 Building Energy Efficiency Standards Nonresidential Compliance Manual (NA7.5.1.1 Ventilation Systems: Variable Air Systems At -A -Glance and NA7.5.I.2 Constant Volume Systems Outdoor Air Acceptance At -A -Glance). C. 2016 Building Energy Efficiency Standards. 2. Instrumentationneeded to perform test includes: a. Watch -b. Calibrated means to measure airflow (i.e. hot-wire anemometer, velocity pressure probe, etc.). i. Method and equipment used: FLOWHOOD ii. Equipment calibration date (must be within one year): 3/17/19 3. System type (check either VAV or CAV): ❑ VAV ❑ CAV a. Check if Variable Air Volume (VAV) and complete the following: i. Outside airflow is either factory calibrated or field calibrated. ❑ Check if factory calibrated and attach calibration certification. ❑ Check if field calibrated and attach calibration results. ii. Damper Control (must be checked): ❑ Dynamic damper control is being used to control outside air. (This is NOT a fixed minimum position). iii. One of the following dynamic controls is being utilized to control outside air (check method used) ❑ Outdoor Air CFM Compensation ❑ Energy Balance Method ❑ Demand Control Ventilation ❑ Return Fan Tracking ❑ Injection Fan Method ❑ Dedicated Minimum Ventilation Damper with Pressure Control ❑d Other Active Control, Describe: b. Check if Constant Air Volume (CAV) and verify the following: ❑V System is designed to provide a fixed minimum OSA when the unit is on. 4:: Method of delivering outside air to the unit (check one of the fallowing): © Outside air is ducted to the return air plenum. Confirm that outside air is ducted to within (check one of the following): © 5 ft. of the unit. ❑V 15 ft. of the unit, with the air directed substantially toward the unit. ❑,7 Return air plenum is NOT used to distribute outside air to the unit. (i.e. outside air is ducted directly to. the unit, outside air is provided independent of the unit, or economizer) 5. Pre -occupancy purge has been programmed for the 1 -hour period immediately before the building is normally occupied to provide (one of the following methods must be verified and checked): 0Theconditionedfloor area times the ventilation rate from the 2016 Building Energy Efficiency Standards TABLE 120.1-A, or 15 cfm per person times the expected number of occupants, whichever is greater. ❑✓ Complete air changes to the zone served by the air handler. CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance _- _ July 2016 J IMI LZUr t.MLItVttINIM OUTDOOR AIR ACCEPTANCE GEC-NRCA-MCH-02-A (Revised 07/16) CERTIFICATE OF ACCEPTANCE V NRCA-MCH-02-A Outdoor Air Acceptance (Page.2 of 3)' Project Name.._ - TIC NEWPORT COAST. Enforcement Agency: CITY OF NEWPORT BEACH Permit Number: - Z Step 2: Verify unit is not ineconomizermode during test (economizer disabled) 2570-2019: Project Address: 21159 NEWPORT COAST DR City: IRVINE Zip Cade: 92657 System Name or ldentifwtion/Tag: 50KCCW06A2A6/1619C78699 System Location or Area Sen d: MAIN AREA B. NA7.5.1.1 Outdoor Air Acceptance Functional Testing CAV VAV Step 1: Disable demand control ventilation (if applicable) © - Z Step 2: Verify unit is not ineconomizermode during test (economizer disabled) IZI Note: Shaded boxes do not apply for C41/systems it lli [�i}�� 1 sr= ; T',yirlliMr� s'iIA1.11.': Step 3: CAV and VAV testing at full supply airflow 1 }I�}�p SI'18TI iB1 Ti=i' �1 illi �llllljl'Iwi`Ir' i1�. n (fl,ri Adjustsupplyairto achieve design airflow or maximum airflowatfull a. cooling. Record VFD speed (Hz). ( lj'I lj]l,� Hz b. Measured outdoor airflow reading (cfm) 305 cfm cfm Required outdoor airflow (cfm) (from MCH -03, Column 14, or C. Mechanical Equipment Schedules). 300 cfm -cfm d Time for outside air damper to stabilize after full supply airflow i -achieved .'(minutes):. - lily?a min Step 4: VAV testing at reduced supply airflow CAV VAV a Adjust supply airflow to either the sum of the minimum zone airflows, full heating, or 30% of the total design airflow. Record VFD speed (Hz): 1g I Hz b. .Measured outdoor airflow reading (cfm). Itl�#aIi ;1i1i1<`i'i'�,u1I ? cfm C. Required outdoor airflow (cfm) (from MCH -03, Column 14, or Mechanical Equipment Schedules). �ll<.,=j i1t613AiRti - cfm d. Time for outside air damper to stabilize after reduced supply airflow is achieved (minutes): 1 „{, ' tl.,,,ii= min .Step 5: Return to initial conditions (check) 0✓ 0✓ C. Testing Calculations & Results Determine Percent Outside Air at full supply airflow (%OAPA) for Step 3. a. %OA,= Measured outdoor airflow reading /Required outdoor airflow.(Step3b/Step3c) 1.02 ti:. Y°OA1A is within 10% of design Outside Air. (90%5 %OA, < 110%) Yes Q No 0 Yes Q No 0 C. --Outside air damper position stabilizes within 5 minutes. (Step 3d <5 minutes)] i 'i"IS{ii;i1``I" Q No 411 ibis)' Yes 0 - Determine Percent Outside Air at reduced supply airflow (%OA,A) for Step 4. (VAV only) a....%OARA=Measured outdoor airflow reading/Required outdoor airflow reading. (Step4b/Step4c) ���`xHI �F+�it { ;hisij b. %OAgp is within 10% of design Outside Air. (90%!5 %oAgA < 110%)%)'i i,ii!{ � f�43�if i,3 Yes Q No 0 C. Outside air damper position stabilizes within 5 minutes. (Step 4d <5 minutes) kap; ill J d iIII MVI, Yes Q, No Note: The intent of this testis to ensure that 1) all air handlers provide the minimum amount of OSA and 2) VAV air handlers use dynamic controls to avoid over ventilation. - D. Evaluation 0✓ '-PASS: All Construction Inspection responses are complete and Testing Calculations & Results responses are positive. CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance July 2016 aeric ur uHururtrvw OUTDOOR AIR ACCEPTANCE rEC-NRCA-MCH-02-A (Revised 07/16) i" l /' n CERTIFICATE OF ACCEPTANCE NRCA-MCH-02-A Outdoor Air Acceptance (Page 3 of 3) -Project Name: - TIC NEWPORT COAST Enforcement Ager, CITY OF NEWPORT BEACH Permit Number: 2570-2019 Project Address: -21159 NEWPORT COAST DR City: IRVINE Zip Code: .92657 System Name or ldentifcation/Tag: SOKCQA06A2A6/1619C78699 System Location or Area Served MAIN AREA DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that thisCertificateof Acceptance documentation is accurate and complete. Documentation Author Name: JOSEJASSO Documentation Author Signature: Documentation Author Company Name: M3 MECHANICAL Date Signed: I�Id5j1y ATT Certification Identification (if applicable): Address'' 600A W TAFT AVE City/state/Zip:. ORANGE, CA 92865 Phone: 714-628-1308 FIELD TECHNICIAN'S DECLARATION STATEMENT - - I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Acceptance is true and correct. 2' , lam the person who performed the acceptance verification reported on this Certificate of Acceptance (Field Technician). 3. The construction or installation identified on this Certificate of Acceptance complies with the applicable acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NA7. 4. I have confirmed that the Certificate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and signed by the responsible builder/installer and has been posted or made available with the building permit(s) issued for the building. Field. Technician Name: RICK MOLNAR Field Technician Signature: - Field Technician Company Name:M3 MECHANICAL Position with Company(Title): SR. TECHNICIAN Address: 600A W TAFT AVE ATT Certification Identification (if applicable): -18 o City/State/Zip:ORANGE, CA 92865 ' Phone: 714-628-1308 Date Signd: 10$) i(d RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this Certificate of Acceptance. 2. 1 am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction or installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement (responsible acceptance person). 3. The information provided on this Certificate of Acceptance substantiates that the construction or installation identified on this Certificate of Acceptance complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NA7.- 4. 1 have confirmed that the Certificate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and is posted or made available with the building permit(s) issued for the building. - 5. 1 will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building -permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is. required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Acceptance Person Name: TONY MOLNAR Responsible Acceptance Person Signature: _ I ill - Responsible Acceptance Person Company Name: M3 MECHANICAL Position with Company PRESIDENT Address:. 600A W TAFT AVE CSLB License: 786760 City/state/zip: ORANGE, CA 92867 Phone: 714-628-1308 Date Signed: Energy Efficiency Standards - 2016 Nonresidential Compliance July 2016