Loading...
HomeMy WebLinkAboutX2021-0558 - MiscI n 3Ub NUP U lIn I JIM TEST 8a BALANCE TEST AND BALANCE REPORT PROJECT: AERIE / OFFLINE BY AERIE LOCATION: 363 NEWPORT CENTER DRIVE, NEWPORT BEACH, CA 92660 REPORT DATE: MARCH 1 S, 2022 CONTRACTOR: AC ALL STAR ARCHITECT: ENGINEER: CORTLAND MOROAN Y V KULKARNI �I JAMES CONBOV CERTIFICATION 3504 -IV. 3l3V22 Val James Conboy Supenoi Tes(nnO Babnce TABB Supervisor 191099607E MuO 31, 2023 e..uma. aaiospozz 861 E LEADORA AVENUE, GLENDORA CA 91741 TEL: 626.771.1012 SITE: WWW.SUPERIORTAB.COM EMAIL: SUPERIORTAB@GMAIL.COM INSTRUMENTATION: DIGITAL MANOMETER FLowHooD TACHOMETER DIGITAL VOLT -AMP METER ROTATING VANE ANEMOMETER THERMOMETER DESCRIPTION OF TERMS: SHORTRIDGE ADM-B6OC SHORTRIDGE DIGITAL FLOWHOOD EXTECH 461 B91 FLUKE 322 EXTECH AN31 ❑ FLUKE 5211 AK- FREE AREA OF REGISTER, IN SQUARE FEET ATM- ATMOSPHERIC PRESSURE CD- CEILING DIFFUSER, SUPPLY CE- CEILING REGISTER, EXHAUST CFM- CUBIC FEET PER MINUTE OR- CEILING REGISTER, RETURN DD- DIRECT DRIVE MOTOR FH- READINGS TAKEN WITH FLOWHOOD, NO AK FACTOR FLA- FULL LOAD, AMPERAGE FPM- FEET PER MINUTE FR- FLOOR REGISTER, SUPPLY FRR- FLOOR REGISTER, RETURN GPM- GALLONS PER MINUTE HP- HORSE POWER LD- LINEAR DIFFUSER, SUPPLY LR- LINEAR REGISTER, RETURN N/A- NOT AVAILABLE OR NOT APPLICABLE NL- NOT LISTED NVL- NO VALID LOCATION OSA- OUTSIDE AIR PSIG- POUNDS PER SQUARE INCH, READ BY GAUGE PSP- PERFORATED SUPPLY PLENUM RPM- REVOLUTIONS PER MINUTE SF- SERVICE FACTOR, AMPERAGE SP- STATIC PRESSURE, IN INCHES OF WATER SWE- SIDE -WALL REGISTER, EXHAUST SWR- SIDE -WALL REGISTER, RETURN SWS- SIDE -WALL REGISTER, SUPPLY TP- THERMALLY PROTECTED, AMPERAGE RELATED RATING VEL- VELOCITY (FEET PER MINUTE) AP- DIFFERENTIAL PRESSURE (INCHES OF WATER OR PSI) I UPERIOR Y O TEST & BALANCE Fan Test Report Project: Aerie / Offline by Aerie - Newport Beach 363 Newport Center Drive, Newport Beach, CA 92660 RTU-2 Location / Area Served Roof I Sales Area Roof I Sales Area Manufacturer / Model Carrier I SDHCQDOMfiSAOAOGO Cartier I SOMM08MMMAGG0 Serial Number 23191330437 2319P30436 Motor Make Marathon Marathon Motor HP / RPM / Frame 2.9 1670 56HZ 2.9 1670 56HZ Volts / Phase / Hertz 208 3 60 208 3 60 F.L. Amps / S.F. 6.7 1.15 6.7 1.15 Motor Sheave Diam./Bore VL44 x 5/8" VL44 x 6/8" Fan Sheave Diam./Bore AFD74 x 1" AFD74 x 1" Belt Size / # of Belts A48 1 A48 1 Sheave Closed % 30% 20% Sheaves Center to Center 16118" 161/2" TEST DATA DESIGN ACTUAL DESIGN % DESIGN I ACTUAL DESIGN % DESIGN ACTUAL DESIGN % Total Fan Airflow 3500 NVL 3500 NVL Total Outlet Airflow 3575 3443 96% 3425 3427 100% Return Airflow 2760 2619 950/6 2610 2590 99% Minimum Outside Air 815 824 101% 815 837 103% S.P. Supply /Return. 0.24"/0.52" r 0.24 /0.51" ' External S.P. 1.00" 0.76" 1.00" 0.75 Total S. P. Fan Speed (RPM) 851 - - 836 Voltaae 208 20212011200 .. 208 202/202/201 NOTES: 1 �PRIO Y O TEST Be BALANCE Air Distribution Test Report Project: Aerie / Offline by Aerie - Newport Beach 363 Newport Center Drive, Newport Beach, CA 92660 SYSTEM NAME / AREA SERVED OUTLET DESIGN PRELIMINARY FINAL % of DESIGN Note # # TYPE SIZE AK VEL FLOW VEL FLOW VEL FLOW RTU-1 Sales Area 1 CD 18" Round FH - 275 - 255 93% Sales Area 2 CD 18" Round FH - 275 - 302 110% Sales Area 3 CD 18" Round FH - 275 - 296 1 108% Sales Area 4 CD 18" Round FH - 275 - 276 100% Sales Area 5 CD 18" Round FH 275 - 261 95% Sales Area 6 CD 18" Round FH - 275 - 254 92% Sales Area 7 CD 18" Round FH 275 - 273 99% Sales Area 8 CD 18" Round FH 275 - 259 94% Sales Area 9 CD 18" Round FH - 275 - 252 92% Sales Area 10 CD 18" Round FH - 275 - 263 96% Sales Area 11 CD 18" Round FH I - 275 - 247 90% Stockroom 12 CD 24" x 24' FH - 200 - 181 91% Fitting Rooms 13 CD 18" Round FH - 175 - 158 90% Fitting Rooms 14 CD 18" Round FH - 175 - 166 95% 3575 3443 96% Outside Air OSA Intake 35" x 18.5" 4.50 181 815 223 1004 183 824 1 101% NOTES: Notes correspond to Note # above. 1 2 3 4 2 UPERIOR Jr\I\\O TEST e< BALANCE Air Distribution Test Report Project: Aerie / Offline by Aerie - Newport Beach 363 Newport Center Drive, Newport Beach, CA 92660 SYSTEM NAME / AREA SERVED OUTLET DESIGN PRELIMINARY FINAL % of DESIGN Note # # TYPE SIZE AK VEL FLOW VEL FLOW VEL FLOW RTU-2 Sales Area 1 CD 18" Round FH - 275 - 296 108% Sales Area 2 CD 18" Round FH - 275 - 272 99% Sales Area 3 CD 18" Round FH - 275 - 253 92% Sales Area 4 CD 18" Round FH - 275 - 263 96% Sales Area 5 1 CD 18" Round FH - 275 - 277 101% Sales Area 6 CD 18"Round FH - 275 - 251 91% Sales Area 7 CD 22" Round FH - 600 - 586 98% Stockroom 8 CD 24"x24" FH - 500 - 541 108% Fitting Rooms 9 CD 18" Round FH - 300 - 320 107% Fitting Rooms 10 CD 18" Round FH - 300 - 286 95% Break Area 11 CD 24" x 24" FH - 75 - 82 109% 3425 3427 100% Outside Air OSA Intake 35" x 18.5' 4.50 181 815 142 639 186 837 1 103% EF-1 Restroom 1 CE 9" x 11" FH 85 - 87 102% NOTES: Notes correspond to Note # above. 1 2 3 4 3 4 0 COMPLIES Enforcement Agency Use: Checked by/Date SHUT-OFF LIGHTING CONTROL ACCEPTANCE DOCUMENT Intent: This document is used to demonstrate compliance with acceptance requirements in §130.4(a)4 and Reference Nonresidential Appendix NA7.6.2 for shut-off lighting controls. Attach additional sets of pages 1 through 2, as required, for all controls that must be tested. Indicate all types of shut-off controls tested for this project: f Automatic time switch lighting controls (Sections A-1 and B-1 of this document should be completed) 17 Occupant sensing lighting controls (including occupant sensors, partial -ON occupant sensors, partial -OFF occupant sensors, and/or vacancy sensors) (Sections A-2 and B-2 of this document should be completed) A-1. Automatic Time Switch Lighting Control Construction Inspection (NA7.6.2.4) r a. Automatic time switch controls are programmed with acceptable weekday, weekend, and holiday (if applicable) schedules. (NA7.6.2.4(a), §110.9(b)SAii, §130.1(c)lA, §130.1(c)4) Iw b. Document for the owner weekday, weekend, and holidays schedules, as well as all set-up and preference program settings. (NA7.6.2.4(b)) W c. The correct time and date are properly set in the time switch. (NA7.6.2.4(c)) r d. The battery backup (if applicable) is installed and energized. (NA7.6.2.4(d), §110.9(b)l) Iw e. Override time limit is no more than 2 hours. (NA7.6.2.4(e), §110.9(b)SAi, §130.1(c)3B) OR The automatic time switch control's override time is exempt from the 2-hour limit. (EXCEPTION to §130.1(c)3B) W f. Override switches remote from area with controlled luminaires have annunciator lights. (NA7.6.2.4(f), §130.1(c)3A, §130.1(a)) OR The manual override switch is exempt from being in the same enclosed area with the lighting it controls. (EXCEPTION 1 to §130.1(a)2) Construction Inspection Compliance(rJ Complies)'; Does Not Comply CAL *' TP CaIlfornid'Advanced aphting Cantiolsrr2fntng Program CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance This is page 1 of 5 B-1. Automatic Time Switch Lighting Control Functional Testing (NA7.6.2.5) Confirm compliance (Y - yes / N - no) for the control being tested. Building: aerie Floor: 1 Room: Back of House Control: Automatic Time Switch Step 1: Simulate Occupied Condition. (NA7.6.2.5(a)) W a. All lights can be turned on and off by their respective area control switch. (NA7.6.2.5(a)l) F b. The switch only operates lighting in the enclosed space (ceiling -height partitioned area) in which the switch is located. (NA7.6.2.5(a)2, §130.1(c)1C) r c. For the area controlled by an automatic time switch control with a time override located in and for the area, the lighting can be turned on manually by initiating the time override. The lighting is configured to remain on for no more than 2 hours, unless the area is exempt from the 2-hour time override limit. (NA7.6.2.5(a)3, §110.9(b)lAi, §130.1(c)3B, EXCEPTION to §1301(c)3B) r d. For the area controlled by an automatic time switch control with an automatic holiday shut-off feature, the lighting in the area can be turned off automatically by initiating the holiday shut-off. (NA7.6.2.5(a)4, §110.9(b)lAii, §130.1(c)4) OR The automatic time switch control is exempt from incorporating an automatic holiday shut-off feature. (EXCEPTION to §130.1(c)4) r e. For the area controlled by an automatic time switch control with manual -on mode configured, the lighting in the area can be turned on manually when it is manually activated. (NA7.6.2.5(a)5, §130.1(c)IE) OR The automatic time switch control does not include or utilize a manual -on mode. (§130.1(c)IE) Step 2: Simulate unoccupied condition. (NA7.6.2.5(b)) r a. All non-exempt lighting turns off in accordance with the programmed time switch schedules. (NA7.6.2.5(b)1, §130.1(c)lA) r b. Manual override switch allows only the lights in the enclosed space (ceiling height partitioned) where the override switch is located to turn on or remain on until the next scheduled shut off occurs. (NA7.6.2.5(b)2, §130.1(c)1C, §130.1(c)3) Functional Testing Compliance: Does Not Comply i CALGoTP Calltamtsivilanoi-Wimm CaMitllshelningPmg2m`I I CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Tllis is page 2 of cEIZT1[TTc_1TE OF ACCEPTA.NCF cA-1il-oz _� L�•_hvas comrw Project Name:Auie Ne�cpart Beach Evfarcemeat Aaeacv: CrfY OF NERTORT BEACH JJPe Number 2021-0338 Project Ad&r w: 363 Na .A Cemx Dnce City: Newport Beach Zip Coda: 92633 A-2. Occupant Sensing Lighting Control Construction Inspection (NA7.6.2.2)) W a. Occupant sensors have been located to minimize false signals. (NA7.6.2.2(a)) r17 b. Occupant sensors are located no closer than four (4) feet from any HVAC diffuser. (NA7.6.2.2(b)) r c. Passive infrared sensor pattern does not enter into adjacent zones. (NA7.6.2.2(c)) r d. Occupant sensors do not encounter any obstructions that could adversely affect desired performance. (NA7.6.2.2(d)) W e. Ultrasonic occupant sensors do not emit audible sound. (NA7.6.2.2(e), §110.9(b)681i) Construction Inspection Compliance: M Complies(, Does Not Comply B-2. Occupant Sensing Lighting Control Functional Testing (NA7.6.2.3) Confirm compliance (Y - yes / N - no) for the control being tested. Building: aerie Floor: 1 Room: Stock Rm Control: Occ Sensors IV Control is representative of sample. (NA7.6.2.3) If sampling method is used, attach a page listing untested controls in sample. Step 1: Simulate an unoccupied condition. (NA7.6.2.3(a)) ra a. Lights controlled by occupant sensing control turn off or partially off, if applicable, within a maximum of 20 minutes from start of an unoccupied condition. (NA7.6.2.3(a)1, §110.9(b)4A) In the partial off state, partial -OFF occupant sensors automatically reduce lighting power by at least 50% (§130.1(c)6A-C, §130.1(c)7A), OR: • For metal halide or high pressure sodium lighting in warehouses, automatically reduce lighting power by at least 40% (EXCEPTION 2to §130.1(c)6A). • In aisle ways and open areas in warehouses in which the installed lighting power is 80% or less of the value allowed under the Area Category Method, automatically reduce lighting power by at least 40% (EXCEPTION 1 to §130.1(c)6A). • In corridors and stairwells in which the installed lighting power is 80% or less of the value allowed under the Area Category Method, automatically reduce lighting power by at least 40% (EXCEPTION to §130. 1(c)7A). Occupant sensing controls in parking garages, parking areas, and loading and unloading areas have at least one control step between 20 to 50% of design lighting power (§130.1(c)7B). OR Occupant sensing controls for metal halide luminaires with a lamp plus ballast mean system efficacy of 75 lumens per watt in parking garages, parking areas, and loading and unloading areas have at least one control step between 20 to 50% of design lighting power (EXCEPTION to §130.1(c)7B). r b. The occupant sensing control does not trigger p g gger a false "on" from movement in an area adjacent to the controlled space or from HVAC operation. (NA7.6.2.3(a)2) W c. Signal sensitivity is adequate to achieve desired control. (NA7.6.2.3(a)3) For library book stacks or warehouse aisles, activity beyond the stack or aisle shall not activate the lighting in the stack or aisle. (§130.1(c)6A, §130.1(c)6B) Step 2: Simulate an occupied condition. (NA7.6.2.3(b)) r a. Status indicator or annunciator operates correctly. (NA7.6.2.3(b)Y, §110.9(b)4C) b. Immediately upon an occupied condition (NA7.6.2.3(b)2): • Lights controlled by an occupant sensor or a partial -OFF occupant sensor turn on; OR: • A vacancy sensor indicates a space is "occupied" and lights may be turned on manually; OR: • The first stage of a partial -ON occupant sensor automatically activates between 50 to 700/c of the lighting. (§130.1(c)SA)OR: After the first stage occurs for partial -ON occupant sensors, manual switches allow an occupant to activate the alternate set of lights, activate 100% of the lighting power, and manually deactivate all of the lights. Functional Testing Compliance: �, TF' CaliPomiAduanced ldph11 Hng r Coi hilaatningRmli am CA BH ld n Energy Efficiency Standards - 2019 Nonresidential Compliance Thus is page 3 of 5 OF M Compliesr, Does Not Comply Celltom1am-li edLighdn@ I �iTr CaMrors7afrinAt9!dA�m CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance This is page 4 of 5 CERTIF gkTE�OFACCEP XNCE NRCA-LTI-02-A Loup, Comral PrajM Yame: derie Newport Beach E@brcement Agency: CITY OF Nn?oRT BEACH Permit Number 1021-0558 ProjMAddce u: 363 Nenmort Center Dtnx City: Newport Beach Zip Cade: 92658 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT I certify that this Certificate of Acceptance documentation is accurate and complete. Documentation Author Company Name Harry Stallmach Adec, Inc Name Address City/State/Zlp 2545 W. 237ih Street, Suite M Torrance, CA 90505 Phone CEA/ATT Certification (330)_ 0-6399 Identification (if TC-AS13033 applicable) Author Signature Date of Signature: 03/17/2022 FIELD TECHNICIAN'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided an this Certificate of Acceptance is true and correct. 2. I am the person who performed the acceptance verification reported on this Certificate of Acceptance (Field Technician). 3. The construction or installation identified on this Certificate of Acceptance complies .vith the applicable acceptance requirements Indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NA]. 4. I have confirmed that the Certificate(s) of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and signed by the responsible builder/installer and has been posted or made available with the building permits) issued for the building. Field Technician Name Harry Stallmach Company Name Adec, Inc Address: City/State/Zip 2545 W. 237th Street, Suite M Torrance, CA 90505 Phone ATT Certification (310)540-6399 Identification TC-A813033 Positio wi Company CEO Field Technician Signature Date of Signature: 03/17/2022 RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this Certificate of Acceptance. 2. I am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction or Installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement (responsible acceptance person). 3. The information provided on this Certificate of Acceptance substantiates that the construction or installation identified on this Certificate of Acceptance complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference Nonresidential Appendix NA7. 4. I have confirmed that the Certificates) of installation for the construction or installation identified on this Certificate of Acceptance has been completed and is posted or made available with the building permits) issued for the building. 5. I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certifcate of Acceptance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Acceptance Harry Stallmach Company Name Adec, [nc Person Name Address: City/State/Zip 2545 W. 237th Street, Suite M Torrance, CA 90505 Phone CSLB License (310)540-6399 640304 Position with C pony CEO Responsible Acceptance Person Signature (Title} //A/O Date of Signature: 03/17/2022 TPIIeliforRia<ABvenced LtgMtng egnfr5ta7 lntng,Rrligram " ' CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance This is page 5 of 5