HomeMy WebLinkAboutX2021-2180 - Calcs�C2o21-2180 E S I / F M E INC. STRUCTURAL ENGINEERS BUILDING DIVISION AUG 1 9 2021 Br M.K. MELICAN PATIO to be built at 1417 KEEL DRIVE, Newport Beach, CA CBC 2019 April 8, 2021 1+1 1800 E. 16th Street, Unit B, Santa Ana, CA 92701 HAWKER ]ob No. No. M147 Tel: (714) 835-2800 Fax: (714) 835-2819 Page: 2 ESI/FME INC Date: 4/8/2021 STRUCTURAL ENGINEERS Job No: M147 Client: HAWKER Project Name: MELICAN PATIO Plan No: Load Conditions Seismic Design Summary Analysis Used: Equivalent Lateral Force Procedure (12.8) S = 1.331 5 s , = 0.472 Soil Site Class = D I = 1.0 R = 6.5 F, = 1.2 F„ = 1.8 Seismic Design Catergory = D p = 1.0 D = 2.5 Roof (Psf) Floor ( sf) Comp. The Deck w/o LW Conic. 1.5" LW Con'. or 1" Gyperete 20.0 Live Loadl SMS = 1.597 SM, = 0.850 4.0 Dead Load 77-1 SDs = 1.065 So, = 0.566 Base Shear = 0.115W Sheathing 1.5 Rafter/Joists 2.5 Wind Design Summary Sprinklers 0.0 Wind Velocity = 110 M.P.H. Wind Exposure = C Ceiling Joists 0.0 Drywan 0.0 Governing Codes is./Solar PV 2.0 IBC 2018 ASCE72016 NDS 2018 TMS 4022016 10.0 Total (DL) CBC 2019 ACI318 2014 SDPWS 2015 AISC360 - 16 30.0 11 TotaHDL+LL) Proiectlnfo Solis Report Initials Date Address By: CBC Engineer of Record: DF 4/7/2021 Street 1417 KEEL DRIVE Job No: Project Engineer: Be 4/7/2021 City Newport Beach Date: Back Check: State, Zip CA, Allowable Soil Bearing Pressure 1500 psf Roof Truss Review: For Addition) Information Refer to CBC Floor Truss Review: PT Foundation Review: Structural Observation/Special Inspection Structural Observation Required: Yes Plan Check 1: Special Inspection Required: No Plan Check 2: Revisions Revision Revised Sheets Initials Date ESI/FME, Inc. - Structural Engineers (This Signature is to be a wet signature, not a copy.) Q(tOFESSI REry q O C 30407 m CMI. .� r.. FOFCAUFO Date: ESI/FME INC STRUCTURAL ENGINEERS Project Name: CODES IBC 2018 CBC 2019 ASCE7 2016 In all cases calculations will supersede this design criteria sheet TIMBER Doue Fir - Larch #11 Doue Fir - Larrh 0 Size Fe (psi) F� (psi) I Fb (psi) F„ (psi) E (psi) 2x4, 2x6, 2x8, 2x10, 2x12, 2.00E+06 Parallam 2.2(PSL) 2900 290 2.20E+06 Microllam (LVL) 1000 180 900 180 1.60E+06 2x14 1.30E+06 Glulam (24F -V4) 2400 240 1.80E+06 4x4, 4x6, 4x8, 4x10, 4x12, 1000 180 900 180 1.60E+06 4x14 6x6, 6x8, 8x8, 8x10 1200 170 750 170 1.60E+06 6x10, 6x12, 6x14, 8x12, 8x14 1350 1 170 875 1 170 1.60E+06 mat romper pe TMe m near center Page: 3 Date: 4/8/2021 Job No: M147 Client: HAWKER Plan No: Grade Fb (psi) F. (psi) I E (psi) Parallam 2.0 (PSL) 2900 290 2.00E+06 Parallam 2.2(PSL) 2900 290 2.20E+06 Microllam (LVL) 2600 285 1.90E+06 Timberstrand (LSL) 1700 425 1.30E+06 Glulam (24F -V4) 2400 240 1.80E+06 1 Drypack shall be composed of one part Portland Cement to not more than three parts sand. 2 All structural concrete Pc = 3000 psi Special Inspection Required All slab-ongrade, continous footings, pad footings f'c = 2500 psi Special Inspection Not Required All concrete shall reach minimum compressive strength at 28 days. REINFORCING STEEL 1 All reinforcing shall be. A.ST.M. A-616-40 for #4 bars and smaller, & A615-60 for#5 bars and larger. Welded wire fabric to be A.S.T.M. A-185, lap 1-1/2 spaces, 9" min. 2 Development length of Tension Bars shall be calculated per AC1318-14 Section 12.2.2 Class B Splice = 1.3x1d Splice length for 2500 psi concrete is: #4 Bars (40K) = 21", #5 Bars (60K) = 39", #6 Bars (60K) = 47" (30 dia. for compression) Masonry reinforcement shall have lapping of 48 dia. Or 2'-0". This is in all cases U.N.O. 3 All reinforcing bars shall be accurately and securely placed before pouring concrete, or grouting masonry. 4 Concrete protection for reinforcement shall be at least eaqual to the diameter of the bars. Cover for casi-in-place concrete shall be as follows, U.N.O. A. Concrete cast against & permenently exposed to earth .......... 3" B. Concrete exposed to earth or weather 5 #5 Bars .... 11/2" >_ #6 Bars ........ 2" C. Concrete no exposed to weather or in contact with ground Slabs, Walls, Joists 5 #5 Bars ...................... 3/4" Beams & Columns: Primary reinforcement, Ties, Stirups, Spirals .. 11/2" 1 Fabrication and erection of structural steel shall be in accordance with "Specification for the Design, Fabrication and Erection of Structural Steel Buildings", AISC, current edition. Steel to conform to ASTM A992. Round pipe columns shall conform to ASTM A53, Grade B. Square/Rectangular steel tubes ASTM A500, Grade B. 2 All welding shall be performed by certified welders, using the Electric Shielded Arc Process at licensed shops or otherwise approved by the Building Department. Continuous inspection is required for all field welding. 3 All Steel exposed to weather shall be hot -dip galvanized after fabrication, or other approved weatherproofing method. 4 Where finish is attached to structural steel. Provide 1/2" dia. bolt holes @ 4'-0" o.c. for attachment of nailer, U.N.O. See architectural drawings for finishes (Nelson studs 1/2" x 3" CPL may replace bolts) 1 Concrete block shall be of sizes shown on architectural drawings and/or called for in specifications and conform to ASTM C-90-09, Grade A normal weight units with max linear shrinkage of 0.06% 2 All vertical reinforcing in masonry walls not retaining earth shall be located in the center of the wall U.N.O. Retaining walls are to be as shown in details. 3 All cells with steel are to be solid grouted (except retaining walls where all cells are to be solid grouted) ESI/FME INC STRUCTURAL ENGINEERS Project Name: MELICAN PATIO CODES: IBC 2018 CBC 2019 ASCE72016 NDS 2018 SDPWS 7075 A. All beams to be supported with full bearing unless noted otherwise. Page: 4 Date: 4/8/2021 Job No: M147 Client: HAWKER Plan No: B. All isolated posts and beams to have Simpson PB's, PC's and/or BC's minimum, U.N.O. C. All bearing walls on wood floors are to be supported with double joists or solid blocking, U.N.O. D. Provide 4x or 2-2x members under sole plate nailing less than 6" o/c. E. All Simpson HTT, HDU, HDQ and CB holdowns to be fastened to 4x4 post min. U.N.O. F. All hardware is to be Simpson Strong -Tie or approved equal. Install per mfr.'s specifications. G. All shop drawings are to be reviewed by the contractor and the architect prior to submittal for engineers review. H. All exterior walls are to be secured with 1/2" diameter x 10" anchor bolts or MASA anchors @ 72" o.c., U.N.O. (Please call structural engineer for a fix.) I. All interior walls to be secured with shot pins per manufacturer's recommendations, U.N.O. Calculations govern in all cases. Recommend Simpson 0.145" dia.,3" long PDP Powder Actuated Anchors @ 24" o.c. (ICC-ESRg2138) or equal. J. All conventional framed portions of structure are to be constructed per section 2308 of the CBC 2019 or IBC 2018 U.N.O. K. All nailing is to be per table 2304.10.1 of the IBC or California Building Code, U.N.O. L. All nails to be "common", U.N.O. FOUNDATION HARDWARE LEGEND SOLE PLATE NAILING SPN16: 16d Sole Plate Nailing @ 16" O.C. SCR10: 1/4" x 41/2" SDS Screws @ 10" O.C. SPN12: 16d Sole Plate Nailing @ 12" O,C. SCR8: 1/4" x 4 1/2" SDS Screws @ 8" O.C. SPN10: 16d Sole Plate Nailing @ 30" O.C. SCR6: 1/4" x 4 1/2" SDS Screws @ 6" O.C. SPN8: 16d Sole Plate Nailing @ 8" O.C. SCR4: 1/4" x 4 1/2" SDS Screws @ 4" O.C. SPN6: 16d Sole Plate Nailing @ 6" O.C. SCR2: 1/4" x 41/2" SDS Screws @ 2" O.C. SPN4: 16d Sole Plate Nailing @ 4" O.C. (1) Simpson HDU2 per post AB32: SPN2: 15d Sole Plate Nailing @ 2" D.C. (1) Simpson HDU4 per post HDUS : FOUNDATION HARDWARE LEGEND AB72: 1/2" Dia. X 10" Anchor Bolts @ 72" O.C. or MASA Anchors @ 72" O.C. 244 : Provide a total of 244 at top 244 at bottom of footing, 3' past post AB64: 1/2" Dia. X 10" Anchor Bolts @ 64" O.C. or MASA Anchors @ 64" O.C. 344: Provide a total of 344 at top 344 at bottom of footing, 3' past post AB56: 1/2" Dia. X 10" Anchor Bolts @ 56" O.C. or MASA Anchors @ 56" O.C. 444: Provide a total of 444 at top 444 at bottom of footing, 3' past post AB48: 1/2" Dia. X 10" Anchor Bolts @ 48" O.C. or MASA Anchors @ 48" O.C. HTT4 : (1) Simpson HTT4 per post AB40: 1/2" Dia. X 10" Anchor Bolts @ 40" O.C. or MASA Anchors @ 40" O.C. HTT5 : (1) Simpson HTT5 per post HDU2: (1) Simpson HDU2 per post AB32: 1/2" Dia, X SO" Anchor Bolts @ 32" O.C. or MASA Anchors @ 32" O.C. HDU4: (1) Simpson HDU4 per post HDUS : (1) Simpson HDI per post AB24: 1/2" Dia. X 10" Anchor Bolts @ 24" O.C. or MASA Anchors @ 24" O.C. HDU8: (1) Simpson HDU8 per post HDQS : (1) Simpson HDQB per post AB16: 1/2" Dia. X 30" Anchor Bolts @ 16" O.C. or MASA Anchors @ 16" O.C. HDU31 : (1) Simpson HDU31 per post HDU14 : (1) Simpson HDU14 per post AB8: 1/2" Dia. X 10" Anchor Bolts @ 8" O.C. HD3B : (1) Simpson HD3B per post or MASA Anchors @ 8" O.C. HD19 : (1) Simpson HD19 per post ,Die: when anchor bolts are used, provide 3" sq, X.229" thick plate washer for all sill plate A.e.'s at shear walls only. ROOF FRAMING PLAN SCALE : 1/47 = 1'-d' ,vmurn mr emmx E/Yi s BOnou - N:\Fi les\M 147\M 147s-1.dwg _ Page: 5 ESI/FME INC Date: 4/8/2021 STRUCTURAL ENGINEERS Job No: M147 Client: HAWKER Project Name: MELICAN PATIO Plan No: O RIDGE Member Span= 17.0 FT DL LL RL Total (lb) X (ft) Beam Source P X P1=( + + )_ Total (plf) Design Factors: Roof = ( 14 + + P2=( + + )_ Size Factor, Cr = 0.98 Wall = ( 10 + + P3=( + + )_ Rep. Factor, Cr = No = 1 Floor = ( 14 + 40 + P4 = ( + + ) _ F„ = 265 PSI Fb = 2400 x R1 = 2352 PSI R2 DL LL RL Trib (ft) Total (plf) Design Factors: Roof = ( 30 + + 20 ) x ( 12 + ) = 360 Size Factor, Cr = 0.99 LC Cd WCd M/Cd Wall = ( 10 + + ) x ( + ) = 0 Rep. Factor, Cr = No =1 1.00 868 Ib 8620 ft -Ib Floor = ( 14 + 40 + ) x ( + ) = 0 F„ = 170 PSI Fb = 1350 x Cr x Cr =1337 PSI 16590 ft -Ib Deck = ( 14 + 40 + ) x ( + ) = 0 E = 1.60E+06 PSI D+.75LL+.75RL 1.25 1307 lb 14167 ft -Ib R1(Ib) R2(Ib) Floor Live Load Reduction Factor = 1.00 Self Weight = 16.5 b= 5.50" LC Cd V/Cd M/Cd Roof Live Load Reduction Factor =. 1.00 Total = 377 d= 13.50" D+LL 1.00 1160 lb 4931 ft -Ib MEMBER SIZE = 1 6 x 14 Aproddad = DF #1 D+RL 1.25 2560 lb 10881 ft -Ib Comments: dact,ai = 0.68 D+.75LL+.75RL 1.25 2152 ib 9147 ft -Ib R,(Ib) R2(lb) Design: 1.5 x A,,=0.44 in Stress Ratio Total ` 3200 E-32007 S', = M,a,x/Fb = 97.70 in Mmax = 10881 ft -Ib Sm,14 d = 167.06 in' 58.5% OK DL 1160 1160 A,=1.5V,a„/Fv= 22.59 int Vmax = 2560 ib A,ro li d = 74.25 int 30.4% OK LL 0 0 Aap = L/ 360 = 0.57 in A,n,,, = 0.39 in 69.2% OK RL 2040 2040 4oc = 0.14 in GLB Camber = 1.5 x 4o, = 0.21 in 2O BEAM AT FRONT P Member Span= 24.0 FT x DL LL RL Total (Ib) X (ft) Source P2 = ( 1160 + 0 + 2040 ) = 3200 12 B1 P2=( + + )_ P3=( + + )_ P4 = ( + + ) _ R1 R2 DL LL RL Trib (ft) Total (plf) Design Factors: Roof = ( 14 + + 20 ) x ( + ) = 0 Size Factor, Cr = 0.98 Wall = ( 10 + + ) x ( + ) = 0 Rep. Factor, Cr = No = 1 Floor = ( 14 + 40 + ) x ( + ) = 0 F„ = 265 PSI Fb = 2400 x CF x Cr = 2352 PSI Deck = ( 14 + 40 + ) x ( + ) = 0 E = 1.80E+06 PSI Floor Live Load Reduction Factor = 1.00 Self Weight = 24.0 b= 5.13" LC Cd WCd M/Cd Roof Live Load Reduction Factor = 1.00 Total = 24 d= 15.00" D+LL 1.00 868 Ib 8620 ft -Ib MEMBER SIZE _ ( 1 ) 5.125 x 15 Glulam 24F -V4 D+RL 1.25 1511 lb 16590 ft -Ib Comments: D+.75LL+.75RL 1.25 1307 lb 14167 ft -Ib R1(Ib) R2(Ib) Design: Stress Ratio Total 1888 I F-18-887 S,e, = M,aa,/Fb = 84.64 in Mmax = 16590 ft -Ib S,r ,,,d = 192.19 in' 44.0% OK DL 868 868 Ar 4=1.5V,aax/Fv= 8.55 Int Vmax = 1511 Ib Aproddad = 76.88 int 11.1% OK LL 0 0 4ap = L/ 360 = 0.80 in dact,ai = 0.68 in 85.4% OK RL 1020 1020 A,,=0.29 in GLB Camber= 1.5 x A,,=0.44 in Page: 6 ESI/FME INC Date: 4/8/2021 STRUCTURAL ENGINEERS Job No: M147 Client: HAWKER Project Name: MELICAN PATIO Plan No: Simply Supported Wood Beam (NDS 2018, CBC 2019, SDPWS 2015) O RAFTERS P Member Span = 12.0 FT X DL LL RL Total (lb) X (ft) Source P2=( + + )_ P3=( + + )_ P4 = ( + + ) _ Rl R2 DL LL RL Trib (ft) Total (plf) Design Factors: Roof = ( 10 + + 20 ) x ( 2 + ) = 60 Size Factor, Cr = 1.30 Wall = ( 10 + + ) x ( + ) = 0 Rep. Factor, Cr = No =1 Floor = ( 14 + 40 + ) x ( + ) = 0 F„ = 180 PSI Fb = 900 x Cr x Cr =1170 PSI Deck = ( 14 + 40 + ) x ( + ) = 0 E = 1.60E+06 PSI Floor Live Load Reduction Factor = 1.00 Self Weight = 4.3 b= 3.50" LC Cd V/Cd M/Cd Roof Live Load Reduction Factor = 1.00 Total = 64 d= 5.50" D+LL 1.00 146 lb 437 ft -Ib MEMBER SIZE _ ( 1 4 x 6 DF #2 D+RL 1.25 3091b 926 ft -Ib Comments: D+.75LL+.75RL 1.25 261 lb 782 ft -Ib R2(lb) R2(Ib) Design: Stress Ratio Total F 386 386 } Sre, = Mroa,/Fb = 9.49 in Mraaa = 926 ft -Ib Spromaea = 17.65 i0 53.8% OK DL 146 146 Aroq=1.WmrojFv= 2.57 in2 Vmax = 309 Ib A,ro,, d = 19.25 int 13.4% OK LL 0 0 A, = L/ 240 = 0.60 in Aa,",, = 0.39 in 64.4% OK RL 240 240 ADL = 0.15 in GLB Camber = 1.5 x dpi = 0.22 in 4O BEAM AT side Member Span = 17.0 FT DL LL RL P2 = ( 413 + 0 + 480 P2=( + + P3=( + + pa=( + + Total (lb) X (ft) Source 893 6 B6 DL LL RL Trib (ft) Total (plf) Design Factors: Roof = ( 10 + + 20 ) X( 7 + ) = 210 Size Factor, Cr = 0.97 Wall = ( 10 + + ) x ( + ) = 0 Rep. Factor, Cr = No =1 Floor = ( 14 + 40 + ) x ( + ) = 0 F„ = 170 PSI Fb = 1350 x Cr x Cr = 1310 PSI Deck = ( 14 + 40 + ) x ( + ) = 0 E = 1.60E+06 PSI Floor Live Load Reduction Factor = 1.00 Self Weight = 18.9 b= 5.50" LC Cd V/Cd M/Cd Roof Live Load Reduction Factor = 1.00 Total = 229 d= 15.50" D+LL 1.00 10231b 4586 ft -Ib MEMBER SIZE = 1 6 x 16 ID #1 DAL 1.2s 201916 8958 ft -lb Comments: D+.75LL+.75RL 1.25 1719 lb 7635 ft -Ib R,(Ib) R2(Ib) Design: Stress Ratio Total 3 2524 2261 `- SreQ = Mroax/Fb = 82.09 in' Mmex = 8958 ft -Ib Sprey�ded = 220.23 in3 37.3% OK DL 1023 902 Areq=1.5VmJI'v= 17.82 in Vmax = 2019 lb AproWded = 85.25 in 20.9% OK LL 0 0 Aad = L/ 360 = 0.57 in Dan„a7 = 0.21 in 36.8% OK RL 1501 1359 At, = 0.08 in GLB Camber = 1.5 x Opp, = 0.13 in ESI/FME INC STRUCTURAL ENGINEERS Project Name: Page: 7 Date: 4/8/2021 Job No: M147 Client: HAWKER Plan No: ONEW HDR AT LIVING - P Member Span= 16.0 FT X DL LL RL Trib (ft) DL LL RL Total (lb) X (ft) Source Roof = ( 16 + + 20 ) x ( 6 + ) = p1 = ( 1160 + 0 + 2040 ) = 3200 8 B1 Size Factor, CF = 1.10 P2=( + + )_ ) x ( + ) = 0 Rep. Factor, Cr = No =1 P3=( + + )_ Floor = ( 14 + 40 + R1 0 R2 Pa=( + + ) = CF x Cr = 990 PSI Deck = ( 14 + 40 + ) x ( + ) = DL LL RL Trib (ft) Total (plf) Design Factors: E = 1.60E+06 PSI Roof = ( 15 + + 20 ) x ( 7 + ) = 245 Size Factor, CF = 0.97 1.00 Self Weight = 7.2 Wall = ( 10 + + ) X( + ) = 0 Rep. Factor, Cr = No =1 M/Cd Roof Live Load Reduction Factor = Floor = ( 14 + 40 + ) x( + ) = 0 F„ = 290 PSI Fb = 2900 x Cr x Cr = 2813 PSI 1.00 Deck = ( 14 + 40 + ) x ( + ) = 0 E = 2.00E+06 PSI Cd V/Cd M/Cd Floor Live Load Reduction Factor = 1.00 Self Weight = 17.5 b= 3.50" LC Roof Live Load Reduction Factor = 1.00 Total = 263 d= 16.00" DAL 1.00 1560 Ib 8514 ft -Ib MEMBER SIZE _ ( 1 3.5 x 16 PSL 2.0 (Parallam) DAL 1.25 29601b 16858 ft -Ib R1(lb) R,(Ib) Design: D+.75LL+.75RL 1.25 2532 lb 14346 ft -Ib Comments: me Total 893 893 Sreq = Mma�✓Fb = 17.31 Stress Ratio Rme R1(Ib) Design: 5,,iftd = 49.91 in' 34.7% OK ,. DL 413 413 Total 3700 : 370Q : 5req = Mmax/Fb = 71.91 in3 M,,,x =16858 ft -Ib S,.Ided = 149.33 in' 48.2% OK DL 1560 1560 Are,=1.Wm„/Fv= 15.31 int Vmex = 2960 Ib A°roomed = 56.00 int 27.3% OK LL 0 0 A, = L/ 360 = 0.53 in OK A,ei„ t = 0.36 in 67.4°% OK RL 2140 2140 ADD = 0.15 in GLB Camber = 1.5 x ADI = 0.22 in Obm at exist patio cover Member Span = 8.0 FT DL LL RL Total (ib) X (ft) Source P �X P1=( 0 + 0 + 0 )= 0 0 P2=( + + )_ P3=( + + ) 1 - R1 R2 P4=( + + - DL LL RL Trib (ft) Total (plf) Design Factors: Roof = ( 16 + + 20 ) x ( 6 + ) = 216 Size Factor, CF = 1.10 Wall = ( 10 + + ) x ( + ) = 0 Rep. Factor, Cr = No =1 Floor = ( 14 + 40 + ) x ( + ) = 0 F„ = 180 PSI Fb = 900 x CF x Cr = 990 PSI Deck = ( 14 + 40 + ) x ( + ) = 0 E = 1.60E+06 PSI Floor Live Load Reduction Factor = 1.00 Self Weight = 7.2 b= 3.50" LC Cd V/Cd M/Cd Roof Live Load Reduction Factor = 1.00 Total = 223 d= 9.25" D+LL 1.00 413 lb 826 ft -Ib MEMBER SIZE _ ( 1 4 x 10 DF #2 DAL 1.25 7141b 1428 ft -Ib D+.75LL+.75RL 1.25 618 lb 1236 ft -Ib Comments: Stress Ratio R1(lb) R,(Ib) Design: Total 893 893 Sreq = Mma�✓Fb = 17.31 in Mmax = 1428 ft -Ib 5,,iftd = 49.91 in' 34.7% OK ,. DL 413 413 Ar„=1.SVmax/Fv= 5.95 Int V,,,x = 714 lb A,.ided = 32.38 int 18.4% OK LL 0 0 A, = L/ 360 = 0.27 in A,M„, = 0.06 in 20.9% OK RL 480 480 ADD = 0.03 in GLB Camber = 1.5 x ADS, = 0.04 in �OINEE�S O_ N CPLIFOXNIP 1417 Keel Dr, Corona Del Mar, CA 92625, USA Latitude, Longitude: 33.6041963, -117.8600351 q Inlet Dr Date Design Code Reference Document Risk Category Site Class Type Value SS 1.331 S1 0.472 SMS 1.598 SMt null -See Section 11.4.8 SDS 1.065 SD1 null -See Section 11 A.8 Type Value SDC null -See Section 11.4.8 Fa 1.2 F null -See Section 11.4.8 PGA 0.579 FPGA 1.2 PGAM 0.695 • 't Blue Key 4/7/2021, 9:52:02 AM ASCE?-16 11 D - Default (See Section 11.4.3) Description MCER ground motion. (for 0.2 second period) MCER ground motion. (for 1.Os period) Site -modified spectral acceleration value Site -modified spectral acceleration value Numeric seismic design value at 0.2 second SA Numeric seismic design value at 1.0 second SA Description Seismic design category Site amplification factor at 0.2 second Site amplification factor at 1.0 second MCEG peak ground acceleration Site amplification factor at PGA Site modified peak ground acceleration 1 Project Name: Hr 8.0 ft H2 t90 T 1Opening= 8.0ft ESI/FME INC STRUCTURAL ENGINEERS PATIO Location Ll 2.5 0% Zane C Site Information psf 100%Zone D Zip = Lattitude = Longitude = 10.3 ZoneC Occupancy Category = II psf ASCE 7-16 Equivalent Lateral Force Method Ss = 1.331 S, = 0.472 Fa = 1.2 Fv = 1.8 SMs = SSXFa =1.597 SM, = SsXFa =0.863 SDS = (2/3)xSMs =1.065 Sm = (2/3)xSMS = 0.575 .SSI CS(min) =771= = 0.036 QE =CSW SDs Cs = R/I = 0.164 <-Governs SM Cs(max)=Tx = 0.646 Page: 9 Date: 4/8/2021 Job No: M147 Client: HAWKER Plan No: 2nd Story Weight Trib. (ft) Roof = 10 psf x 26 = 260 plf Floor = 14 psf x 0 = 0 plf Weight Trib. (ft) Qty. 1 Ext. Wall = 14 psf x 4.5 x 0 = 0 Of -L Int. Wall = 10 psf x 4.5 x = 0 plf l� Ext. Wall = 14 psf x 4.5 x =0 plf Int. Wall = 10 psf x 4.5 x = 0 plf Total = 260 plf R = 6.5 Soil Site Class = D Per ASCE7-1611.4.3 1 = 1.0 Seismic Design Category = D p=1.0 hn=13.Oft T = 0.137 for All other Structural Systems Eh = .7pQE=0.115W ASCE 7-16 Simplified Wind Design Roof Slope = 4 :12 = 18.4 Degrees Kit =1.0 Wind Velocity = 100 mph hn = 13.0 ft Exposure = C A =1.21 P, = .6AK..P< n Seismic Level I I WSei x StoryS ear Seismic Roof 260 )If 9.0 2340 30 plf 30 plf 30 pif G: wind Level sxn __F" Story Shear Win Roof (8ft x 2.5psf + 1ft x 10.3psf) 30 plf 30 plf 30 plf Hozitonal Pressures I Vertical Pressures Overhangs Zone A B C D E F G H EOH GOH P530 21.3 .6.1 14.2 -3.4 -19.1 -13.0 -13.3 -9.9 -26.7 -20.9 Ps 15.5 -4.4 10.3 -2.5 -13.9 -9.5 -9.7 -7.2 -19.4 -15.2 Wind at Corner E Bld. Width a 45 ft 3.6 ft 163 plf Corner wind is the additional pressure applied at corner shearwalls. pressure IF; is to be included for a distance's' away Rom the comer Governing Load Level Story Shear Roof 30 If Wind ESI/FME INC STRUCTURAL ENGINEERS Project Name: Allen O TYp Post n LOAD (PLF) r1 1 1105 LB SOURCE WIND SEISMIC I' L1 30 30 o H GOVERNING LOAD (P) 1105 LB SEISMIC FLAGPOLE DESIGN CRITERIA D =30 in (Diameter of Footing) O = 300 PCF (Allowable Lateral Bearing Pressure) IT CONSTRAINED f~ UNCONSTRAINED Use value form table below or from Geotechnical Investigation Report. Allowable Lateral Bearing Pressure is permited to be taken as twice the value from Table 1806.2 for Wind and Seismic Loading CBC 2019 TABLE 1806.2 Lateral Bearing Pressure Class of Material (PSF/FT Bellow Natural Grade) Crystalline Bedrock 1200 (NUMBER OF POSTS) 400 Sandy Gravel and/or Gravel 200 (GW and GP) 11.0 IN Sand, Silty Sand, Clayed Sand, R = Silty Gravel, and Clayey Gravel 150 (SW, SP, SM, SC, GM, and GC) 1105 L8 Clay, Sandy Clay, Silty Clay, W = Clayey Silt, Silt, and Sandy Silt 100 (CL, ML, and CH) MINIMUM EMBEDMENT DEPTH UNCONSTRAINED CONSTRAINED 4.25 PH Depth 2 1+ (T.3 6 H Depth = S,D A— 2.34P S,=v*Depth S,D o * Depth S, = 3 Depth= 3.69ft Page: 10 Date: 9/15/2015 Job No: E418 Client: Tim Allen Plan No: TOTAL (LB) LRB (FT) WIND SEISMIC * [ 17.0 FT/2 + 0.0 FT) = 255 255 = 0 0 = 0 0 0 0 M = P*[H-(Da+3)/12] MA = fb*S*1.6 = 1105 *[ 8-(14/12)] = 1200*70.3*1.6 7551 FT -LB = 1349761N -LB = 11248 FT -LB > M Bx8 Post OK M = P*H MA= 1.S*Fy*S _ 1.5*36000*3.15 =1105*8 O 1.67 = 7551 FT -LB MA =1018561N -LB MA = 8488 FT -LB > M Washer= 4.5" Round CA = fc*Acer ANrr = 15.46SO.IN. (NET AREA OF WASHER) = 625- 15.46 12*M 12 * 7551 = 9663 LB C = D 11 C= 8237 LB (COMPRESSION FORCE ATWASHER) CA > C 3.5" DIA. WASHER TO 8x8 POST OK (0.85) 30" DIA. ROUND FOOTING STEEL ANGLE BRACKET EMBEDDED 3.75' LSXSXI/2 W/ (2)-3/4" DIA. BELOW GRADE' BOLTS AND 4.5" Round WASHER TO Bx8 POST TOTAL = 255 LB 255 LB POST DESIGN CRITERIA N = 1 (NUMBER OF POSTS) H = 8.0 FT (HEIGHT OF POST) Da= 11.0 IN (DISTANCE BETWEEN BOLTS) R = 1.5 (R VALUE FOR CANT. COL.) E = 1105 L8 (SEISMIC LOAD PER POST FOR R=1.51 W = 255 LB (WIND LOAD PERPOST) M = P*[H-(Da+3)/12] MA = fb*S*1.6 = 1105 *[ 8-(14/12)] = 1200*70.3*1.6 7551 FT -LB = 1349761N -LB = 11248 FT -LB > M Bx8 Post OK M = P*H MA= 1.S*Fy*S _ 1.5*36000*3.15 =1105*8 O 1.67 = 7551 FT -LB MA =1018561N -LB MA = 8488 FT -LB > M Washer= 4.5" Round CA = fc*Acer ANrr = 15.46SO.IN. (NET AREA OF WASHER) = 625- 15.46 12*M 12 * 7551 = 9663 LB C = D 11 C= 8237 LB (COMPRESSION FORCE ATWASHER) CA > C 3.5" DIA. WASHER TO 8x8 POST OK (0.85) 30" DIA. ROUND FOOTING STEEL ANGLE BRACKET EMBEDDED 3.75' LSXSXI/2 W/ (2)-3/4" DIA. BELOW GRADE' BOLTS AND 4.5" Round WASHER TO Bx8 POST 11 FIREPLACE ANCHORAGE: ISOKERN ASCE 7-16 - 13-3-1 Weight per MFG.: 1645 lbs Fp = 0.4a(Sds)(W)(1+0.65) / Rp + 0.2Sds Wp Fp= 0.4 x 1 x 1.065 x 1645 (1.65)/ 3 + 0.2 x 1.065 x 1645 = 735 lbs Min. Fp = 0.3 Sds W = 0.3 X 1.065 X 1645 = 5261bs HEIGHT = 64", height / 2 = 2.63' Uplift = 735 X 2.63/(25.25/12)= 918 lbs With 2 anchors per side, Uplift = 460 lbs Anchorage: Using 1/2" diameter bar at each corner: A=0.2sgin Allowable tension = 0.6FyA = 0.6 x 40000 x 0.2 = 4800 lbs > 460 lbs Allowable shear on 1/2" dia titen = 1605 lbs Use Simpson HL 33 at each corner with 1/2" titen HD's to isokern and 1/2" dia rod to slab Project Title: Engineer: Project ID: Project Descr: 12 Project Filename: M147.ec6 G@ff@P8� FOOt111g (c)ENERCALCINC19832021 DESCRIPTION: ISOKERN FTG Code References Calculations per ACI 318-14, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used: ASCE 7-16 Material Properties 2.50 ksi Soil Design Values - Allowable Soil Bearing fc : Concrete 28 day strength = Number of Bars # - fy : Rebar Yield = = 60.0 ksi 3,122.0 ksi Soil Density - Increase Bearing By Footing Weight Ec : Concrete Elastic Modulus = 145.0 pcf Soil Passive Resistance (for Sliding) Concrete Density 0.90 _ SoiVConcrete Friction Coeff. Values Flexure Shear - 0.750 Increases based on footing Depth Analysis Settings = Footing base depth below soil surface = Allow press. increase per foot of depth Min Steel % Bending Reinf. Min Allow % Temp Reinf. = 0.00180 - when footing base is below - Min. Overturning Safety Factor = 1.0 : 1 = 1.0 :1 Increases based on footing plan dimension Min. Sliding Safety Factor Yes Allowable pressure increase per foot of depth= Add Ftg Wt for Soil Pressure ... "`ate i R?5✓.y Use ftg wt for stability, moments & shears Yes when max. length or width is greater than Add Pedestal Wt for Soil Pressure No = Use Pedestal wt for stability, mom & shear No k Width parallel to X -X Axis = Length parallel to Z -Z Axis = Footing Thickness = Pedestal dimensions... px : parallel to X -X Axis pz : parallel to Z -Z Axis = Height Rebar Centerline to Edge of Concrete... at Bottom of footing = 4.50 ft 3.0 ft 12.0 in X _.. .;? in _ in in 3.0 in Reinforcing S Bars parallel to X -X Axis = 4 Number of Bars # 4 Reinforcing Bar Size - Bars parallel to Z -Z Axis 7 Number of Bars = # 4 Reinforcing Bar Size = Bandwidth Distribution Check (ACI 15.4.4.2) Direction Requiring Closer Separation ksf Bars along Z -Z Axis # Bars required within zone 80.0% # Bars required on each side of zone 20.0% Yf I, Applied Loads D P: Column Load = OB: Overburden = M-xx = M-zz = V -x = V -z = 1.70 3.0 z 1.99 ksf 110.0 pof No 250.0 pcf 0.30 It ksf ft ksf ft Lr L S W E H k ksf l Yf I, k -ft � `�v ... "`ate i R?5✓.y 1 ^�€t r r' ,��f k 4'A" a 1.99 ksf 110.0 pof No 250.0 pcf 0.30 It ksf ft ksf ft Lr L S W E H k ksf k -ft k -ft k k Project Title: Engineer: Project ID: Project Descr: 13 General Footing Project Filename. M147.ec6 DESCRIPTION: ISOKERN FTG DESIGN SUMMARY - -..--- ____.._.. Bottom, -Z Top, +Z Left, -X Right, +X . ____......_.. Ratio Load Combination... Gross Allowable Min. Ratio Item Applied Capacity Governing Load Combination PASS 0.3976 Soil Bearing ksf ksf D Only about X -X axis PASS 1.829 Overturning - X -X k -ft k -ft D Only PASS n/a Overturning -Z-Z k -ft k -ft No Overturning PASS n/a Sliding -X-X k k No Sliding PASS n/a Sliding -Z-Z k k No Sliding PASS n/a Uplift k k No Uplift PASS Z Flexure (+X) k-fVft k-ft/ft +1.40D PASS Z Flexure (-X) k-ff/ft k-fVft +1.40D PASS X Flexure (+Z) k-ft/ft k-ft/ft +1.40D PASS X Flexure (-Z) k-ft/ft k-ft/ft +1.40D PASS 1 -way Shear (+X) psi psi +1.40D PASS 1 -way Shear (-X) psi psi +1.40D PASS 1 -way Shear (+Z) psi psi +1 A0D PASS 1 -way Shear (-Z) psi psi +1.40D PASS 2 -way Punching psi psi +1.40D Detailed Results 0.2667 10.424 All units k Soil Bearing 0.3825 +X Bottom Rotation Axis & xecc cecc (in) - -..--- ____.._.. Bottom, -Z Top, +Z Left, -X Right, +X . ____......_.. Ratio Load Combination... Gross Allowable AsMin 0.3111 12.088 OK X -X, +1.40D X -X, D Only 1.990 n/a 9.843 0.0 0.7913 n/a n/a n/a 0.398 0.239 X -X, +0.60D 1.990 n/a 9.843 0.0 0.0 n/a 0.4748 n/a n/a 0.2709 0.2709 0.136 Z -Z, D Only Z -Z, +0.60D 1.990 1.990 n/a 0.0 n/a n/a n/a 0.1626 0.1626 0.082 Overturning Stability 0.3111 12.088 OK X -X, +0.90D 0.4623 +Z Bottom 0.2592 AsMin 0.3111 12.088 OK X -X, +0.90D Rotation Axis & Load Combination... -Z Overturning Moment 0.2592 Resisting Moment Stability Ratio Status X -X, D Only OK 3.0 k -ft 0.4463 5.486 k -ft Bottom 1.829 1.829 OK OK X_X +0.60D 10.424 1.80 k -ft OK 3.292 k -ft 0.0 k -it 0.4463 Infinity OK Z -Z, D Only AsMin None None 10.424 0.0 k -ft OK Infinity OK Z -Z, +0.60D Bottom 0.2592 AsMin 0.2667 10.424 All units k Sliding Stability 0.3825 +X Bottom 0.2592 AsMin 0.2667 10.424 OK Z -Z, +0.90D 0.2869 -X Bottom 0.2592 AsMin Force Application Axis Load Combination... 10.424 Sliding Force OK Resisting Force Stability Ratio Status Fooling Has NO Sliding 0.2592 AsMin 0.2667 10.424 OK One Way Shear Footing Flexure Mu Side Tension As Req'd Gvrn. As Actual As Phl"Mn Status Flexure Axis & Load Combination k -ft Surface in42 inA2 inA2 k -ft 75.00 psi X -X, +1.40D 0.7192 +Z Bottom 0.2592 AsMin 0.3111 12.088 OK X -X, +1.40D 0.2140 -Z Top 0.2592 AsMin 0.3111 12.088 OK X -X, +1.20D 0.6165 +Z Bottom 0.2592 AsMin 0.3111 12.088 OK X -X, +1.20D 0.1835 -Z Top 0.2592 AsMin 0.3111 12.088 OK X -X, +0.90D 0.4623 +Z Bottom 0.2592 AsMin 0.3111 12.088 OK X -X, +0.90D 0.1376 -Z Top 0.2592 AsMin 0.3111 12.088 OK Z -Z, +1.40D 0.4463 -X Bottom 0.2592 AsMin 0.2667 10.424 OK Z -Z, +1.40D 0.4463 +X Bottom 0.2592 AsMin 0.2667 10.424 OK Z -Z, +1.20D 0.3825 -X Bottom 0.2592 AsMin 0.2667 10.424 OK Z -Z, +1.20D 0.3825 +X Bottom 0.2592 AsMin 0.2667 10.424 OK Z -Z, +0.90D 0.2869 -X Bottom 0.2592 AsMin 0.2667 10.424 OK Z-Z,+0.90D 0.2869 +X Bottom 0.2592 AsMin 0.2667 10.424 OK One Way Shear Load Combination... Vu @ -X Vu @+X Vu @ -Z Vu @ +Z Vu:Max Phi Vn Vu I Phi"Vn Status +1.40D 2.42 psi 2.42 psi 1.41 psi 4.92 psi 4.92 psi 75.00 psi 0.07 OK +1.20D 2.08 psi 2.08 psi 1.21 psi 4.21 psi 4.21 psi 75.00 psi 0.06 OK +0.90D 1.56 psi 1.56 psi 0.91 psi 3.16 psi 3.16 psi 75.00 psi 0.04 OK Project Title: Engineer: Project ID: Project Descr: 14 Gen@I8j FootingProject Filename: M147.ec6 DESCRIPTION: ISOKERN FTG Two-way "Punching" Shear All units k Load Combination... Vu Phi*Vn Vu I Phi*Vn Status +1.40D 7.18 psi 150.00psi 0.04786 OK OK +1.20D 6.15 psi 150.00psi 0.04102 OK +0.90D 4.62 psi 150.00psi 0.03077 ESI/FME INC STRUCTURAL ENGINEERS Project Name: SWAN FAMILY RESIDENCE Client: Plan No: Page: 15 Date: 4/7/2021 Job No: Footing Design Wreg = 371 PLF x 12 = 2.971N 1500 PSF 1 Wused= 121N > 2.971N OK Reinforcement = (1) #4 T&B Pn.x=SBP x L x W x 1 144 1 P,,ax = 1500 x 43.5 x 12 x— = 5438 LB 144 DESIGN CRITERIA SOILS REPORT 1 Story BY: 2019 CBC SBP =1500 PSF (Avowable Soil Beading Pressure) JOB NO: OVB=0 PSF Soil Site Class = (overburden weight) D DATE: Roof (Design) D = 12 IN (Depth SBP = 1500 - 0 of Footing) =1500 PSF Footing Loading DL LL RL Trib (ft) Total (plf) Roof =( 15 + + 20 ) x( 7 + )= 245 p Wall =( 14 + + )x( 9 + )= 126 floor=( 14 + 40 + )x( + )= 0 Deck = ( 14 + 40 + ) X( + ) = o Total = 371 Footing Design Wreg = 371 PLF x 12 = 2.971N 1500 PSF 1 Wused= 121N > 2.971N OK Reinforcement = (1) #4 T&B Pn.x=SBP x L x W x 1 144 1 P,,ax = 1500 x 43.5 x 12 x— = 5438 LB 144 Page: 16 ESI/FME INC Date: 4/8/2021 STRUCTURAL ENGINEERS Job No: M147 Client: HAWKER Project Name: MELICAN PATIO Plan No: SOILS REPORT BY: 2019 CBC JOB NO: DATE: PAD DESIGN (CBC 2019, ACI 318-14) DESIGN CRITERIA SBP = 1500 PSF (Allowable sail Bearing Pressure) OVB = 0 PSF (Overburden Weight) Soil Site Class = D (Design) D =241N (Depth of Fouling) j SBP = 1500-0 =1500 PSF AD NO 1 /jA, _ P _ 1888 LB = 1.26 S'Q. FT. Use �_ Load Source SBP 1500 PSF 24" Sq. x 24 " Pad w/ P = 1886 LB B2 Size = (Arm) *12= 13.46 IN. SQ. 11 4 Bars @ 12" O.C. E/W @ Bottom Load Source P= Use Load Source P= Load Source P= VF - Load Source P= Use Load Source P = 1� Use Load Source P= o' <D Iif111 i` t mm as ■I�F71: :D r �Yti /1 o 0 o c e