HomeMy WebLinkAboutF2021-0381 - MiscI4w W f pk'An Pyro-Comm Systems, Inc. 15531 CONTAINER LANE - HUNTINGTON BEACH, CA 92649 Noq • �r . (714) 002-8000- FAX (714)902-8001 CIOO V4CNI Marriott Newport Beach -Room Upgrade - goo Newport Center Drive Newport Beach, California 92660 P( 11 0�1 RECEIVE® Fire Alarm System Submittal PCSI Job# 2021264.1 FIRE ALARM SYSTEM [CONTROL PANELS] NOTIFIER FCM-1 Control Module [AUXILIARY POWER SUPPLIES] NOTIFIER PSE-10 10.0 Amp Auxiliary Power Supply [DETECTORS] NOTIFIER FSP-951 Intelligent Plug in Smoke Det. [SIGNALING DEVICES] WHEELOCK RSS-24MCW Multi -Candela Wall Strobe WHEELOCK RSS-24MCC Multi -Candela Ceiling Strobe SEP 2 4 2021 NTSPOW EST CONSULTING GROUP 7300-0028:0219 7315-0028:0513 7272-0028:0503 7125-0785:0141 7125-0785:0141 WWW.PYR000MM.COM C-10612153 NORTHERN CA REGIONAL OFFICE - 10966 BIGGE STREET - SAN LEANDRO, CA 94577 (510) 632-1208 SAN DIEGO REGIONAL OFFICE ^ 5115 AVENIDA ENCINAS, SUITE G - CARLSBAD, CA 92008 (760 ) 930-6014 Pyro-Comm Systems, Inc. 15531 CONTAINER LANE - HUNTINGTON BEACH, CA 92649 (714)902-8000-FAx(714)902-8001 WWW.PYROCOMM.COM C-10 612153 NORTHERN CA REGIONAL OFFICE - 10966 BIGGE STREET ^ SAN LEANDRO, CA 94577 (510) 632-1208 SAN DIEGO REGIONAL OFFICE ^ 5115 AVENIDA ENCINAS, SUITE G = CARLSBAD, CA 9200$ (760) 930-6014 dn-6724:b2 FCM-1(A) & FIRM-1 (A) Series Control and Relay Modules General FCM-1(A) Control Module: The FCM-1(A) Addressable Con- trol Module provides Notifier intelligent fire alarm control pan- els a circuit for Notification Appliances (horns, strobes, speakers, etc.) Addressability allows the FCM-1(A) to be acti- vated, either manually or through panel programming, on a select (zone or area of coverage) basis. FRM-1(A) Relay Module: The FRM-1(A) Addressable Relay Module provides the system with a dry -contact output for acti- vating a variety of auxiliary devices, such as fans, dampers, control equipment, etc. Addressability allows the dry contact to be activated, either manually or through panel programming, on a select basis. pro- tocol ISdeveelloped by1ent 5,539 NOTIFIER89Engineer Engineering communication greatly enhances the speed of communication between analog intelli- gent devices. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new infor- mation, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other designs. Features • Built-in type identification automatically identifies these devices to the control panel. • Internal circuitry and relay powered directly by two -wire SLC loop. The FCMA (A) module requires power (for horns, strobes, etc.), or audio (for speakers). Integral• LED recei ed frkcommunication from the n control panel and turns on steady red when activated. • LED blink may be deselected globally (affects all devices). • High noise immunity (EMF/RFI). • The FCM-1(A) may be used to switch 24-volt NAC power, audio (up to 70.7 Vrms). • Wide viewing angle of LED. • SEMS screws with clamping plates for wiring ease. • Direct -dial entry of address 01— 159 for FlashScan loops, 01 — 99 for CLIP mode loops. • Speaker, and audible/visual applications may be wired for Class B or A (Style Y or Z). Applications The FCMA(A) is used to switch 24 VDC audible/visual power, high-level audio (speakers), or control telephone devices. The FRM-1(A) may be programmed to operate dry contacts for applications such as door holders or Air Handling Unit shut- down, and to reset four -wire smoke detector power. NOTE. Refer to the SLC Manual (PN 51253) for details regarding releasing applications with the FCM-1(A). Refer to the FC ah- L datasheet (DN-60390) for new FfashScanO releasing app' Construction • The face plate is made of off-white heat -resistant plastic. • Controls include two rotary switches for direct -dial entry 159 NOTI FI ER° by Honeywell FCM-1(A) • The FCM-1(A) is configured for a single Class B (Style Y) or Class A (Style Z) Notification Appliance Circuit. • The FRM-1(A) provides two Form-C dry contacts that switch together. operation Each FCM-1(A) or FRM-1(A) uses one of 159 possible module addresses on a SLC loop (99 on CLIP loops). It responds to regular polls from the control panel and reports its type and status, including the open/normal/short status of its Notifica- tion Appliance Circuit (NAC). The LED blinks with each poll received. On command, it activates its internal relay. The FCM-1(A) supervises Class B (Style Y) or Class A (Style Z) notification or control circuits. Upon code command from the panel, the FCM-1(A) will dis- connect the supervision and connect the external power sup- ply in the proper polarity across the load device. The disconnection of the supervision provides a positive indication to the panel that the control relay actually turned ON. The external power supply is always relay isolated from the com- munication loop so that a trouble condition on the external power supply will never interfere with the rest of the system. Rotary switches set a unique address for each module. The address may be set before or after mounting. The built-in TYPE CODE (not settable) will identify the module to the con- trol panel, so as to differentiate between a module and a sen- sor address. Normal operating voltage: 15 to 32 VDC. Maximum current draw: 6.5 mA (LED on). AveFaytope(afrng"currents.. 350 pA direct poll, 375 pA group Of poll with LED flashing, 485 pA Max. (LED flashing, NAC shorted.) address (01- ). dn-6724:b2. 6/17/10 — Page 1 of 2 Maximum NAC Line Loss: 4 VDC. External supply voltage (between Terminals T10 and T11): Maximum (NAC): Regulated 24 VDC; Maximum (Speakers): 70.7 V RMS, 50W. Drain on external supply: 1.7 mA maximum using 24 VDC supply; 2.2 mA Maximum using 80 VRMS supply. Max NAC Current Ratings: For class B wiring system, the current rating is 3A; For class A wiring system, the current rat- ing is 2A. Temperature range: 32-F to 120-F (0-C to 49-C). Humidity range: 10 / to 93 % non -condensing. Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x 1.25" (31.75 Mm) deep. Mounts to a 4" (101.6 mm) square x 2.125" (53.975 mm) deep box. Accessories: SMB500 Electrical Box; CB500 Barrier Specifications for FRM-1(A) Normal operating voltage: 15 to 32 VDC. Maximum current draw: 6.5 mA (LED on). Average operating current: 230 pA direct poll; 255 pA group poll. EOL resistance: not used. Temperature range: 32-F to 120'F (0-C to 49-C). Humidity range: 10% to 93% non -condensing. Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125" (53.975 mm) deep box. Accessories: SMB500 Electrical Box; CB500 Barrier Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. • UL: S635 • ULC: S3705 (A version only) • FM A proved w- },.. (r7300-0028:202, 7300-0028:219 • MEA: 14-00-E • FDNY: COA #6038, #6026 Contact Ratings for FRM-1(A) Current Maximum Load Rating Voltage Description Application 3 A 30 VDC Resistive Non -Coded 2 A 30 VDC Resistive Coded .9A 110 VDC Resistive Non -Coded 9A 125 VDC Resistive Non -Coded .5 A 30 VDC Inductive (L/R=Sms) Coded 1 A 30 VDC Inductive (L/R=2ms) Coded .3 A 125 VAC Inductive (PF=0.35) Non -Coded 1.5 A 25 VAC Inductive (PF=0.35) Non -Coded 7 A 170.7 VAC I (PF=0.35) I Non -Coded 2 A 125 VAC I (PF=0.35) I Non -Coded NOTE: Maximum (Speakers): 70.7 V RMS, 50 W Product Line Information NOTE: 'A"suffix indicates ULC Listed model. FCM-1(A): Intelligent Addressable Control Module. FRM-1(A): Intelligent Addressable Relay Module. A2143.20: Capacitor, required for Class A (Style Z) operation of speakers. SMB500: Optional Surface -Mount Backbox. CB500: Control Module Barrier — required by UL for separat- ing power -limited and non -power limited wiring in the same junction box as FCM-1(A). NOTE: For installation instructions, see the following documents: • FCM-10) Installation document 156-1 leg. • FRM-1(A) Installation document 156-35oa • Alablier SLC Wiring Manual, document 51253, Notifier® and FlashScan® are registered trademarks of Honeywell International Inc. 02010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. IV O 9UU1 This document is no[ intended to be used for installation purposes. We try to keep our product information up-to-date e��.�....� We can and accurate. FN6INEMINC�+-3:J QUALITY SYSTEMS All specif cationslalreas �bj ctl to changer wPhoutlnoticerements. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118 Made in the U.S. A. Page 2 of 2 — tln-6724:62 •6/17/10 www.notifier.com CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 0 W Page 1 of 1 LISTING No=`�00 d0$r619w<<; CATEGORY: ` 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Lisa Brant (203) 484-6105 Fax (203) 484-7309 Email: lisa.brant@honeywell.com DESIGN: Models XP6-R relay module, XP6-C, supervising control module, XP10-M input monitor module, XP6-MA six zone interface module, FMM-1, FMM-101, FZM-1, FSM-101, FDM-1, FTM-1 monitor modules, FCM-1, FRM-1 control modules, and *FDRM-1 with 2 input/2 output relay module. All devices are intended to be connected between the signaling line circuit of a compatible fire alarm control panel. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 16-33 VDC Primary INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in manner acceptable to the authority having jurisdiction. MARKING: Listee's name, product number and UL label. APPROVAL: Listed as control unit accessories for use with listee's separately listed compatible fire alarm control units. Model FTM-1 is intended to be used with Notifier Models NFS-640, NFS2-640 (CSFM Listing No. 7165-0028:214), NFS-3030, NFS2-3030 (CSFM Listing No. 7165-0028:224) Fire Alarm Control Units. NOTE: If an external power supply is used for Model XP6-MA, the negative of the external power supply is referenced to the negative of the auxiliary supply of the compatible control panel. This is done in order to detect ground faults on the initiating circuit. *Rev. 10-24-11 mt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed T the test results and/or other data but does not make an independent verification of any claims. This listing is not �,�'a,'l,°` an endorsement or recommendation of the item listed. This listing should not be used to verify correct `""' operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2021 Listing Expires June 30, 2022 Authorized By: DAVID CASTILLO„ M.E., F.P.E. Fire Engineering Division Pyro-Comm Systems, Inc. 15531 CONTAINER LANE - HUNTINGTON BEACH, CA 92649 (714) 902-8000 = FAx (714) 902-8001 WWW.PYROCOMM.COM C-10 612153 NORTHERN CA REGIONAL OFFICE - 10966 BIGGE STREET = SAN LEANDRO, CA 94577 (510) 632-1208 SAN DIEGO REGIONAL OFFICE - 5115 AVENIDA ENCINAS, SUITE G - CARLSBAD, CA 92008 (760) 930-6014 NOT 1 IF 1 E R� by Honeywell PSE-6/113SE-10 Series 6/10 Amp, 24 Volt Power Supply Expanders General The PS Series is a remote power supply line from NOTIFIER and is a direct replacement for the FCPS-24S6/8 Series. The PSE-6(C)(E) is a 6 amp and the PSE-10(C)(E) is a 10 amp, remote power supply with battery charger that may be connected to any 12 or 24 volt fire alarm control panel (FACP) or used as a standalone power supply. The PS Series provides 24 VDC power for NACs (notification appli- ance circuits) configured as either Class B or Class A (requires the ZNAC-PS option card) with multiple sync protocol options. The PS Series also provides auxiliary power, constant or resettable, suited for detectors, annunciators, door holders, and other fire alarm sys- tem peripherals. The PS Series cabinet can hold two 7 AH or 18 AH batteries and can charge up to 33 AH batteries in a separate cabi- net. The PSE-6E and PSE-10E are models rated for 240V opera- tion. Features • up to five (6 amp model) or seven (10 amp model) inde- pendently -configurable, power -limited output circuits for: — Class B and/or Class A NACs — Class B and/or Class A resettable or non-resettable 24V auxil- iary power — door holder power • Converts from Class B to Class A wiring without losing any out- puts using the ZNAC-PS converter card (sold separately) • Optimal for powering four -wire smoke detectors, annunciators, and other system peripherals requiring regulated power • Configurable for ANSI® Temporal 3 or Temporal 4 coded output • UL-Listed NAC synchronization using System Sensor®, Whee- lock®, Gentex®, or AMSECOO appliances • Synchronization can be triggered from FACP NAC/remote sync outputs, cascaded power supply, or a control module, single or multi, which may be housed within the power supply cabinet • Ability to cascade up to four power supplies • Two (6 amp model) or three (10 amp model) fully -isolated input/ control circuits which can be programmed to any output • Two Form C normally -closed trouble relays for AC Trouble and General Trouble, Ground Fault relay available on Canadian mod- els only • 6 or 10 amp full load output, respectively, with 3 A maximum/cir- cuit • Individual NAC power and trouble LEDs for diagnostic efficiency • Trouble history modes for diagnostic support • Wide range end -of -line supervision value (normal: 2K-27K ohms) • Selectable earth fault detection (enable or disable) • AC trouble report delay timer • Completely configurable via onboard DIP switches, no extra soft- ware required • Self-contained in compact, locking cabinet constructed of heavy gauge steel with a corrosion -resistant powder coat chip and scratch -resistant finish • Cabinet designed with ten double knockouts and a removable door for ease of installation and wiring • Includes integral battery charger capable of charging up to 33 AH batteries Cabinet can house two 7 AH or 18 AH batteries Battery charger may be disabled via DIP switch for applications requiring larger batteries and external battery charger Removable terminal blocks accommodate up to 12 AWG (3.1 mm2) wire Works with any UL 864 FACP which utilizes an industry -standard reverse -polarity notification circuit Optional devices include addressable control, monitor, and relay modules and power -supervision relay (EOLR-1) Standards and Codes The PSE Series comply with the following standards: NFPA 72 National Fire Alarm Code UL 864 Standard for Control Units for Fire Alarm Systems (NAC expander mode), 1Oth Edition UL 1481 Power Supplies for Fire Alarm Systems IBC 2009 (when using SEISKIT-MULTI-1) CBC 2007 (when using SEISKIT-MULTI-1) Agency Listings and Approvals These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UL Listed: S635, S674 • ULC Listed: S635 (PSE-6/10C) • cC&hMgtRrbGel:7315-0028:0513 • FDNY Approved • FM Approved DN-61092:C • 3/10/2021 — Page 1 of 2 SPECIFICATIONS Primary (AC) Power: • PSE-6(C): 120 VAC, 50/60 Hz, 5.OA maximum • PSE-10(C): 120VAC, 50/60 Hz, 6.2 A maximum • PSE-6E: 240 VAC, 50/60 Hz, 2.7A maximum • PSE-10E: 240 VAC, 50/60 Hz, 3.5A maximum • Wire Size: #12-14AWG with 600 V insulation Command Input Circuit: • Trigger Input Voltage: 9 to 32 VDC • Trigger Current: 2.0 mA (16 - 32 V); Per Input: 1.0 mA (9 - 16 V) Trouble Contact Rating: 4A at 24 VDC Output Circuits: • 24 VDC filtered, regulated • PSE-6: TB8-TB9 — 1A Regulated, 3A special applications; TB10- TB12 — 0.3A Regulated, 3A special applications PSE-10: TB8-TB11 — 1.5A Regulated, 3A special applications; TB12-TB14 — 0.3A Regulated, 3A special applications 6.OA (PSE-6) or 10.0 A (PSE-10) maximum total continuous cur- rent for all outputs Secondary Power (Battery) Charging Circuit: • Supports lead -acid batteries only • Float -charge voltage: 27.6 VDC • Maximum current charge: 1.5A • Maximum battery capacity: 18 AH (inside cabinet) • Maximum battery charging capacity: 33AH (external cabinet) Physical: • Dimensions: 20.0'H x 14.5'W x 3.5"D (cm: 50.8H x 31 x 8.9D) • Weight: with two 7Ah batteries is 24 pounds (10.9 kg), with two 18AH batteries is 39 pounds (17.7 kg) Ordering Information PSE-6: 6.0 A, 120 VAC remote charger power supply in a lockable, metal enclosure PSE-6C: Same as above, ULC-listed model PSE-6R: Same as PSE-6 with red enclosure PSE-6E: 6.0 A, 240 VAC remote charger power supply in a lock- able, metal enclosure PSE-10: 10.0 A, 120 VAC remote charger power supply in a lock- able, metal enclosure PSE-1 OC: Same as above, ULC-listed model PSE-10R: Same as PSE-10 with red enclosure PSE-1 OE: 10.0 A, 240 VAC remote charger power supply in a lock- able, metal enclosure ZNAC-PS: Optional Class A output converter module FCM-1: Addressable Control Module for one Class B or Class A zone of supervised, polarized Notification Appliances. Notification Appliance Circuit option requires external 24 VDC to power notifica- tion appliances. FRIII Addressable relay module containing two isolated sets of Form-C contacts, which operate as a DPDT switch FMM-1: Addressable Monitor Module for one zone of normally open dry -contact initiating devices. Includes plastic cover plate and end - of -line resistor. Module may be configured for either a Class B or Class A IDC. FDM-1: Dual Monitor Module. Same as FMM-1 except it provides two inputs for Class B wiring only FDRM-1: Provides two monitored inputs and two Form-C relays. Functions in Class B wiring only. XP6-C: Six -circuit supervised control module XP6-R: Six Form-C relay control module EOLR-1: 12/24 VDC end -of -line relay for monitoring four -wire smoke detector power BAT-1270-SP: Battery, 12 volt, 7.0 AH, 5-pack (two required, see BAT Series data sheet DN-6933). BAT-12180-BP: Battery, 12 volt, 18AH, 2-pack BAT-12330: Battery, 12 volt, 33AH SEISKIT-MULTI-1: Seismic kit for the PSE Series. Includes bracket and hardware for two 7AH or two 18AH batteries. '® MIMIIAIN6 S MANIMCNMM SRRrITY SYSTEMS TRisdoament is nor inteMetl to be usetl for installation Wrpgses. We W to keep our product in donation up-todate and accurate. We cannot cover all 491 applications or arrticipele all requirements. All specifications are subject to change vnPoout notice. =1 TIFIER f. and Sys_eM rrr•e, irtricei e I'd Rorayv+nli ntImefienaf Inc. le.fcc4s a e r.aee,,d ,h,_,, of _Dope T, NOTIFIER m"In re tmperi Gen xi a "ll tmn2ri Ir as Corpora 12 CllntonVllle Road ,n 15 s Is a s al t ,ai, i F tar I .�,, anrial GG ry L }VSIWi dr l tat raema rtv h c sn NaLmol Northford, CT 06472 n d l te. Inc. 203.484,7161 6 H "'el miat L.tc J Inc. na ngtts al. Unsullwwad wmw.notifierconn Origin: radmt3 Country Country of Origin: USA USA NOTI FI E RR by Honeywell CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 0 kr c r`u r Page 1 of 1 LISTING No CATEGORY: 7315-- POWER UNITS LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Lisa Brant (203) 484-6105 Fax (203) 484-7309 Email: lisa.brant@_honeywell.com DESIGN: Models PSE-6, PSE-6E, PSE-6R, PSE-10, PSE-10E, and PSE-1OR Power Supply Expander. Model ZNAC-PS Class A Converter Module. The PSE series are remote power supply and battery charger units which also provide programmable synchronized Class B NAGS. Model Variations: All PSE-6 Models: Maximum 6A Capacity; 5 Class B NAGS; 2 Command Inputs; Trouble and AC Loss Relays All PSE-10 Models: Maximum 10A Capacity; 7 Class B NAGS; 3 Command Inputs; Trouble and AC Loss Relays With Suffix "E": Nominal 240V, 50/60 Hz AC Input Without Suffix "E": Nominal 120V, 50160 Hz AC Input With Suffix "R": Red Enclosure Without Suffix "R": Black Enclosure Model ZNAC-PS: Optional Class A Conversion Module Refer to listee's printed data sheet for detailed product description and operational considerations. RATING: Models PSE-6 and PSE-6R: 120V AC, 50/60 Hz, 5.OA Maximum Models PSE-6E: 240V AC, 50/60 Hz, 2.7A Maximum Models PSE-10 and PSE-1OR: 120V AC, 50/60 Hz, 6.2A Maximum Models PSE-1 OE: 240V AC, 50/60 Hz, 3.5A Maximum Model ZNAC-PS: 24V DC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances, and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as a power supply extender when used with separately listed compatible fire alarm control units. Refer to listee's Installation Instruction Manual for details. 09-16-20 VWW ,H Thislisting is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed o the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct " operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2021 Listing Expires June 30, 2022 Authorized By: DAVID CASTILLO„ M.E., F.P.E. Fire Engineering Division FSP-951 Series Intelligent Plug-in Photoelectric Smoke Detectors General The NOTIFIER FSP-951 Series intelligent plug-in smoke detectors are designed for both performance and aesthetics. A new modern, sleek, contemporary design and enhanced optical sensing chamber is engineered to sense smoke produced by a wide range of combus- tion sources in accordance with more stringent code standards. The FSP-951 Series detector sensitivity can be programmed in the con- trol panel software. Sensitivity is continuously monitored and reported to the panel. Point ID capability allows each detector's address to be set with rotary, decimal address switches, providing exact detector location for selective maintenance when chamber contamination reaches an unacceptable level. Dual electronic thermistors add 135°F (57°C) fixed temperature thermal sensing on the FSP-951T. The FSP-951 R is a remote test capable detector for use with DNR Series duct detector housings. FSP-951 series detec- tors are available for both FlashScan® and CLIP applications as designated. Features • New modern profile for improved aesthetics. • Designed to meet UL268 7th Edition. • Stable communication technique with noise immunity. • Low standby current. • Two -wire SLC connection. • Compatible with FlashScan® and CLIP protocol systems. • Rotary, decimal addressing (1-99 on CLIP systems, 1-159 on FlashScan systems). • Optional remote, single -gang LED accessory. • Dual LED design provides 360° viewing angle. • Visible bi-color LEDs blink green every time the detector is addressed, and illuminate steady red on alarm (FlashScan sys- tems only). • Remote test feature from the panel. • Walk test with address display (an address on 121 will blink the detector LED: 12-[pause]-1(FlashScan systems only). • Built-in functional test switch activated by external magnet. • Built-in tamper -resistant feature. • Sealed against back pressure. • Expanded color options. • SEMS screws for wiring of the separate base. • Optional relay, isolator, and sounder bases. �r Sensitivity: • UL Applications: 0.5 % to 4.0 % per foot obscuration. • ULC Applications: 0.5 % to 3.5 % per foot obscuration. Size: 2.0" (5.3 cm) high; base determines diameter. — 6300-6: 6.1" (15.6 cm) diameter. — B501: 4" (10.2 cm) diameter. For a complete list of detector bases see DN-60981. Shipping weight: 3.4oz (96.4g) Operating Temperature range: FSP-951, 0°C to 50°C (32oF to 122°F). FSP-951 T, 0°C to 38°C (32°F to 100°F). DN-60977:A NOTIFIER by Honeywell FSP-951 in B300-6 Base • FSP-951R installed in a DNR/DNRW, -20°C to 70°C (-4°F to 158°F). UL/ULC Listed Velocity Range: 0-4000 ftfmin.(1219.2 m/min.), suitable for installation in ducts. Relative Humidity: 10%-93% noncondensing. Thermal Ratings: Fixed -temperature setpoint 135°F (57°C). DETECTOR SPACING AND APPLICATIONS NOTIFIER recommends spacing detectors in compliance with NFPA 72. In low airflow applications with smooth ceiling, space detectors 30 feet (9.1 m). For specific information regarding detector spacing, placement, and special applications refer to NFPA 72. System Smoke Detector Application Guide, document A05-1003, is available at systemsensor.com i ik 01CA REClFIZ'3ATIO�y9.,� 4 Voltage Range: 15-32`Volts DC peak. Standby Current (max. avg.): 200pA @ 24VDC (one communica- tion every five seconds with LED enabled). LED Current (max.): 4.5mA @ 24 VDC ("ON"). Installation FSP-951 series plug-in detectors use a separate base to simplify installation, service, and maintenance. Mount base (all base types) on an electrical backbox which is at least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes, see DN-60981. NOTE: 1) Because of inherent supervision provided by the SLC loop, end -of -line resistors are not required. Wiring 7-taps" or branches are permitted for Style 4 (Class 'B') wiring. 2) When using relay or sounder bases, consult the ISO-X(A) installation sheet 156-1380 for device limita- tions between isolator modules and isolator bases. DN-60977:A • 4117/18 — Page 1 of 3 Agency Listings and Approvals These listings and approvals apply to the detectors specified in this document. In some cases, certain detectors or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UUULC Listed: S911 • FM Approved �1��Pr..h`�%7272 0026: Q503 ; .a. Product Line Information NOTE., • Detectors must be mounted to one of the Intelligent Bases listed below. • "A" suffix indicates ULC Listed model. • "W" suffix indicates FlashScan® and CLIP device. FSP-951: White, low -profile intelligent photoelectric sensor, FlashS- can only. FSP-951 A: Same as FSP-951 but with ULC listing. FSP-9514V: Ivory, low -profile intelligent photoelectric sensor. FSP-951A-IV: Same as FSP-951-IV but with ULC listing. FSP-951T: White, same as FSP-951 but includes a built-in 135°F (57-C) fixed -temperature thermal device. FlashScan only. FSP-951TA: Same as FSP-951T but with ULC listing. FSP-9511'4V: Ivory, same as FSP-951T but includes a built-in 135'F (57°C) fixed -temperature thermal device. FSP-951TA-IV: Same as FSP-951T-IV but with. ULC listing. FSP-951R: White, low -profile intelligent photoelectric sensor, remote test capable. For use with DNR/DNRW. FlashScan only. FSP-951RA: Same as FSP-951 R but with ULC listing. For use with DNRA. FSP-951R-IV: Ivory, low -profile intelligent photoelectric sensor, remote test capable. For use with DNR/DNRW. FSP-951RA-I11: Same as FSP-951 R-IV but with ULC listing. For use with DNRA. INTELLIGENT BASES NOTE: For details on intelligent bases, see DN-60981 B300-6: White, 6" base, standard flanged low -profile mounting base. B300.64V: Ivory,6" base, standard flanged low -profile mounting base. 8300A-6: Same as B300-6, ULC listed. B30OA-6-IV: Ivory, 6" standard flanged low -profile mounting base, ULC listed. B300.6-BP: Bulk pack of B300-6, package contains 10 B501-WHITE: White, 4" standard European flangeless mounting base. UL/ULC listed. B501-BL: Black, 4" standard European flangeless mounting base. UL/ULC listed. B501-IV: Ivory color, 4" standard European flangeless mounting base. UUULC listed. B501-WHITE-BP: Bulk pack of B501-WHITE contains 10. B224RB-WH: White, relay base. B224RB-IV: Ivory, relay base. B224RBA-WH: White, relay base, ULC listing. B224RBA-IV: Ivory, relay base, ULC listing. B224BI-WH: White, Isolator detector base. B224BI-IV: Ivory isolator detector base. B224BIA-WH: White, isolator detector base, ULC listing. B224BIA-IV: Ivory isolator detector base, ULC listing. B20OS-WH: White, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone. Uses FlashScan protocol. B20OS-IV: Ivory, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone. Uses FlashScan protocol. B200SA-WH: Same as B200S-WH, ULC listing. B200SA-IV: Same as B200S-IV, ULC listing. B200SCOA-WH: White, Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with SO Series detector applications. B200SCOA-IV: Ivory Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with SO Series detector applications, ULC listing. B20OS-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. B200S-LF4V: Ivory, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. B200SR-WH: White, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended for retrofit applications. B200SR-IV: Ivory, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended for retrofit applications. B200SRA-WH: Same as B200SR-WH with, ULC listing. B200SRA-IV: Same as B200SR-IV in Ivory color, ULC listing. B200SR-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applica- tions. B200SR-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applica- tions. MOUNTING KITS AND ACCESSORIES TR300: White, replacement flange for B210LP(A) base. TR300-IV: Ivory, replacement flange for B210LP(A) base. RA100Z(A): Remote LED annunciator. 3 — 32 VDC. Mounts to a U.S. single -gang electrical box. For use with B501(A) and B300(A)- 6. M02-04.00: Test magnet. M02-09-00: Test magnet with telescoping handle. Page 2 of 3 — DN-60977:A • 4/17/18 02018 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. - This document is not intended to be used for installation purposes. I V O We try to keep our product information up-to-date and accurate. 9UU1 We Jcannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. ENGINEERING & MANUFACTURING QUALITY SYSTEMS For more information, contact Notifier. Phone: (800) 627-3473, FAX: (203) 484-7118. www.notifier.com Page 3 of 3 — DN-60977:A • 4/17/18 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE Im LISTING No. °�;`�`OQ2',0505,;,;; Page 1 of 1 ^` 4d,a _. CATEGORY: 7272 -- SMOKE DETECTOR -SYSTEM TYPE -PHOTOELECTRIC LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Lisa Brant (203) 484-6105 Fax (203) 484-7309 Email: lisa.brant@honeywell.com DESIGN: Models FSP-951, *FSP-951-SELFT, FSP-951R, FSP-951T, FSP-951T-ISO, NP-200, NP-200R, and NP-200T analog addressable, photoelectric smoke detectors for open area and duct installations. Models FSP-951T, *FSP-951T-SELFT, FSP-951T-ISO and NP-200T have complementary heat detectors. All models are similar except for population/depopulation of components on the Printed Wring Board for the intended features. Refer to listee's Installation and Maintenance Instruction for additional detailed product description and operational considerations. RATING: 24 VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances, and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as photoelectric smoke detectors. Detectors are for use with separately listed bases: Model B71OLP (CSFM No. 7300-0028:0173); System Sensor Models B224BI, B224RB (CSFM No. 7300-1653:0126); B200S, B200SR (CSFM No. 7300-1653:0213); B200S-LF, B200SR-LF (CSFM No. 7300-1653:0238); B501, B210LP, B300-6, B300-6-IS (CSFM No. 7300-1653:0109). System Sensor duct detector housings Models DNR and DNRW (CSFM No. 3240-1653:0209) and separately listed compatible fire alarm control units. *The Models FSP-951-SELFT and FSP-951T-SELFT are not Listed for use in duct environments. Refer to manufacturer's Installation Manual for details. All models comply with the applicable requirements in ANSI/UL 268, Smoke Detectors for Fire Alarm Systems, 7th Edition. NOTE: The photoelectric type detectors are generally more effective at detecting slow, smoldering fires that smolder for hours before bursting into flame. Sources of these fire may include cigarettes burning in the couched or bedding. The ionization type detectors are generally more effective at detecting fast, flaming fires that consume combustible materials rapidly and spread quickly. Sources of these fires include paper burning in a waste container or a grease fire in the kitchen. 'Revision 1-27-21 VWW This listing is based upon technical data submitted by the applicant.CSFM Fire Engineering staff has reviewed it the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2021 Listing Expires June 30, 2022 Authorized By: DAVID CASTILLO„ M.E., F.P.E. Fire Engineering Division Pyro-Comm Systems, Inc. 15531 CONTAINER LANE - HUNTINGTON BEACH, CA 92649 (714)902-8000-FAx(714)902-8001 WVWV.PYROCOMM.COM C-10 612153 NORTHERN CA REGIONAL OFFICE a 10966 BIGGE STREET - SAN LEANDRO, CA 94577 SAN DIEGO REGIONAL OFFICE - 5115 AVENIDA ENCINAS, SUITE G - CARLSBAD, CA 92008 (510) 932-1208. (760)930-6014 Wheelock RSS and RSSP Strobes and Strobe Plates Description The Wheelock patented RSS Strobe appliances and RSSP Strobe - Plates by Eaton have lower current draw while maintaining outstanding performance, reliability and cost effectiveness. These versatile. appliances will satisfy virtually all requirements for Indoor, wall or ceiling mount applications. Strobe options include the Wheelock Patented MCW multi -candela strobe with field selectable candela settings of 15/30/75/11ocd or the high intensity MCWH strobe with field selectable 135/185cd. Ceiling mount models include the patented MCC multi -candela ceiling strobe with field selectable intensities of 15/30/75/95cd or the high intensity MCCH strobe with field selectable 115/177cd. All models may be synchronized using the Wheelock DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels Incorporating the Wheelock Patented Sync Protocol. Synchronized strobes can eliminate possible restrictions on the number of strobes in the field of view. Wheelock's synchronized strobes offer an easy way to comply with ADA recommendations concerning photosensitive epilepsy as well as meeting the requirements of NFPA 72. The Wheelock Series RSS Strobes employ a Patented Integral Strobe Mounting Plate that can be mounted to a single gang, double l backb x. If t0mm European b he flush kbox has side or top space between it and the finished wall, the NATP (Notification Appliance Trimplate) may be used. It provides an additional .65" of trim for the Appliance. An attractive cover plate is provided for a clean, finished appearance on all models. The RSSP Multi -Candela Strobe Plates are a cost effective way to retrofit required wall strobe appliances to bells, horns, chimes, multitones or speakers and easily mounts to standard 4" backboxes or for surface mount use with the Wheelock SBL2 surface backbox. E_T•N Powering Business Worldwide Technical Data TD450040EN Effective July 2016 Features • Approvals include: UL Standard 1971, New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM),and Chicago (OFF) See approvals by model in Specifications and Ordering information • ADA/NFPA/UFC/ANSI compliant. Meets OSHA 29 Part 1910.16 • Wall mount Multi -Candela models are available with Field Selectable Candela Settings of 15/30/ 75/110cd or 135/185cd. • Wall mount Multi -Candela models are available with Field Selectable Candela Settings of 15/30/75/110cd or 135/185cd. • Strobes produce 1 flash per second over the regulated voltage range • 12 and 24 VDC models with wide UL "Regulated Voltage" using filtered (DC) or unfiltered VRMS input voltage • Synchronize using the Wheelock sync modules or panels with built-in Wheelock Patented Sync Protocol • Fast installation with IN/OUT screw terminals using #12 to #18 AWG wire Note:All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT W W W.EATON.COM/MASSNOTIFICATION OR CONTACT EATON FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. Audibles/Speakers for RSSP Product Series M ultitone Appliances AMT, MT Horns AH, NH, HS iviotor aells MB-G6/G70 Speakers ET-1010/1080, E70, ET70 Chimes CH70 Wheelock RSS and RSSP Strobes and Strobe Plates Drawings Figure 1. RSS wall strobe - Front & Side Views General Notes • Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range" Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL 1971. EATON..eeto , m r Wheelock RSS and RSSP Strobes and Strobe Plates Table 1 =`'kMaxrmrirtl�RMS Current �.: 6.0-33.0 MAX CURRENT 30cd 75cd 95cd 110cd 115ed 135cd 177c1 01'. 09:27 0.165 0.220 0.300 0.105 0.189 0.249 0.300 0.420 Technical Data TD450040EN Effective July 2016 Agency Approvals Table 2. Specification &Ordering Information Strobe Candela Red White Well Ceiling Non- Sync Mountin Options $ Square or Round UL MEA CSFM BFP Model Order # X X X B,D,E,F,G,H,J,N,O,R,X square X X X X X X RSS-24MCW-FR 9400 15/30/15/110 X X X B,D,E,F,G,H,J,N,O,R,X square X X X X X RSS-24MCW-FW 9401 15/30/75/110 X X X B,D,E,F,G,H,J,N,O,R,X square X X X X X RSS-24MCW-AR 9773 15/30/75/110 X X B,D,E,F,G,H,J,N,O,R,X square X X X X X RSS-l21575W-FR 7476 15 (75 on Axis) X X X X B,D,E,F,G,H,J,N,O,R,X square X X X X X RSS-121575W-FW 7468 15 (75 on Axis) X X X B,D,E,F,G,H,J,N,O,R,X square X X X X RSS-24MCC-FW 3158 15/30/75/95 X X X B,D,E,F,G,H,J,N,O,R,X square X X X X RSS-24MCC-FR 3157 15/30175/95 X X X B,D,E,F,G,H,J,N,O,R,X square X X X X RSS-24MCCH-FW 3461 115/177 X X X B,D,E,F,G,H,J,N,O,R,X square X X X X RSS-24MCWH-FR 3465 135/185 X X X B,D,E,F,G,H,J,N,O,R,X square X X X X RSS-24MCWH-FW 3464 135/185 RSSWP-2475W-FR 9013 180@77F X X X B,D,E,F,G,H,J,NO,R,X square X X X X 75@-31 F X X X B,D,E,F,G,H,J,N,O,R,X square X X X X RSSWP-2475W-FW 3034 180®77F RSSP-121575W-FR 7798 75®-31 F 15 (75 on Axis) X X X D,E,Z square X X X X X X X X X RSSP-24MCW 94 5/110 X 1X X X X D,E,Z B,D,E,F,G,H,J,N,O,R,X square square X X X RSSP-24MCWH-FR 9482 2 1335/185/18 5 X Table 3. Specifications Physical impregnated engineered plastic. Exceeds 94V-0 UL flammability rating. Material Red or white textured UV stabilized, colored Weight RSS Strobe: 0.401bs (0.181 kg) Lens GE Lexan 943A Dimensions RSS Strobe: 4.75" W x 4.75" H x 2.58" D Indoor: 33.8°F to 120.2-F (0°C to 49°C) and maximum to of 93% Operating Temperature Wire Connections #12 through AWG Power & General Strobe Output Rating UL 1971 Strobe Flash Rate Strobes are designed to flash at 1 flash per second Synchronization Models Strobes can be synchronized with Wheelock's DSM Sync Modules, Power Supplies or SAFEPATH products, using Wheelock patented sync protocol a RMS current ratings are per UL maximum RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually atthe minimum listed voltage (16v for 24v units). For audibles the max current is usually attire maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see Installation instructions. b For information on mounting options, referto specification sheet TD450028EN. EATON wwwsaton.com 3 Technical Data TD450040EN Effective July 2016 Architects and Engineers Specifications The visual notification appliances shall be Wheelock RSS Strobe appliances or approved equals. The Series RSS shall meet and be listed for UL Standard 1971 (Emergency Devices for the Hearing - Impaired) for Indoor Fire Protection Service. The strobe shall be listed for indoor use and shall meet the requirements of FCC Part 15 Class B. The strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged LexanO lens. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FRCP). When Strobe Plates are to be installed, they shall be the Wheelock Series RSSP Strobe Plate and shall have the same electronic circuitry as the Wheelock Series RSS. The RSS Strobe shall be of low current design. Where Multi - Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at 15/30/75/110cd or 135/185cd for wall mount and 15/30/75/95cd or 115/177cd for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. When synchronization is required, the appliance shall be compatible with Wheelock's DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels with built-in Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any - Wheelock RSS and RSSP Strobes and Strobe Plates time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non -synchronized flash rate. The strobes shall be designed for indoor surface of flush mounting. The RSS Strobe appliances shall incorporate a Patented, Integral Strobe Mounting Plate that shall allow mounting to single gang, double -gang, 4-inch square, 100mm European type backboxes, or the SHBB Surface Backbox. If required, an NATP (Notification Appliance Trimplate) shall be provided. An attaching cover plate shall. be provided to give the Appliance and attractive appearance. The Appliance shall not have any mounting holes or screw heads visible when the installation is completed. The RSSP Multi -Candela or single candela Strobe Plate shall mount to either a standard 4 inch square backbox for flush mounting, or the Wheelock SBL2 backbox for surface mounting. All notification appliances shall be backward compatible. UL, MEA, CSFM, BFP FM Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance Inc., dba Eaton standard terms and conditions. with Wheelock Member WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY FM,T*N AnnTrinB Business Worldwide Eaten 1000 Eaton Boulevard Cleveland, OH 44122 United States E.hm.com Eaton Life safety & mass notification solutions 273 Branchport Ave. Long Branch, NJ 07740 wvrw.eaton.com/massnotification © 2016 Eaton All Rights Reserved Printed in USA Publication No. TD450040EN July 2016 Eaton is a registered trademark. All other trademarks are property of their respective owners. CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 0 LISTING No. S Y -''�x�27$7*$CQ94�`Rq Page 1 of 2 CATEGORY: 7125-- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED LISTEE: Cooper Wheelock Inc.7246 16th St. E., Ste, 105, Sarasota, FL 34243 Contact: Thomas Conover (941) 487-2336 Email: thomaslconover@eaton.com DESIGN: Synchronized or non -synchronized Strobe Lights. Models are as follows: RSS-##W RSSP-##W RSS-##C RSSP-##C RSS-##CR RSSP-##CR 2415 2415 2415 2415 2415 2415 2475 2475 2430 2430 2430 2430 241575 241575 2475 2475 2475 2475 2430 2430 *2495 *2495 *2495 *2495 24110 24110 1215 1215 121575 121575 Also, Models RSS-24MCW and RSSP-24MCW, RSS-24MCC, RSS-24MCCR, RSSP-24MCC, RSS-24MCWH, RSS-24MCWHR, RSSP-24MCWH, RSS-24MCCH, RSS-24MCCHR, RSSP-24MCCH, *ZRS-MCC, *ZRS-MCW, *ZRS-MCCH and *ZRS-MCWH. Model numbers may be followed by any two alpha/numeric character indicating lens orientation, lettering and color. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: Electrical 12 = 8-17.5VDC/FWR OR 24=16-33VDC/FWR Candela 15=5cd, 1 575=1 5/75cd on axis, 30=30cd,75=75cd,110=110cd(Wall) RSS-24MCW, RSSP-24MCW,*ZRS-MCW: Selectable 15cd,30cd,75cd or11ocd RSS-24MCC, RSS-24MCCR, RSSP-24MCC,*ZRS-MCC: Selectable 15cd,30cd,75cd and 95cd RSS-24MCWH, RSS-24MCWHR, RSSP-24MCWH,*ZRS-MCWH:Selectable 135cd,185cd RSS-24MCCH, RSS-24MCCHR, RSSP-24MCCH,*ZRS-MCCH:Selectable 115od,177cd Flash rate 60 flashes/minute INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. Models with suffix -W, wall mount only. Models with suffix -C, ceiling mount only. All models are for indoor use only. MARKING: Listee's name, model number, electrical/candela rating, and UL label. APPROVAL: Listed as strobe light suitable for the hearing impaired when used with separately listed electrically compatible fire alarm control units. For synchronization strobes, Models *Rev. 12-13-2006 jw This listing is based upon technical data submitted by the applicant. CSFM. Fire. Engineering staff has reviewed xO` the test results and/or other data but does not make an independent verification of any claims. This listing is not i` an endorsement or recommendation of the item listed. This listing should not be used to verify correct `" operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2021 Listing Expires June 30, 2022 Authorized By: DAVID CASTILLO„ M.E., F.P.E. Fire Engineering Division a Listing No. 7125-0785:0141 Page 2 of 2 SM-12/24, SMX-12/24, DSM-12/24or DSMX-12/24 Sync Control Module (CSFM Listing No. 7300-0785:132) must be used. Refer to listee's Installation Instruction Manual for details. *Rev. 12-13-2006jw This listing is based upon technical data submitted by the .applicant. CSFM Fire Engineering staff has reviewed t) the test results and/or other data but does not make an independent verification of any claims. This listing is not ,.`'` an endorsement or recommendation of the item listed. This listing should not be used to verify correct 10RV� operational requirements or installation criteria. Refer to istee's data sheet, installation instructions and/or other Date Issued. July 01, 2021 Listing Expires June 30, 2022 Authorized By: DAVID CASTILLO„ M.E., F.P.E. Fire Engineering Division Pyro-Comm Systems, Inc. 15531 CONTAINER LANE - HUNTINGTON BEACH, CA 92649 (714) 902-8000 - FAx (714) 902-8001 / RESPONSE LETTER To: City of Newport Beach, Fire Department Attention: Susan Guzzetta Date: October 26,2021 From: Joey Villanueva Plan Check No: 2004-2021 Marriott Newport Beach Room Upgrades 900 Newport Center Drive, Newport Beach CA 92660 Responses to Comments dated October 11, 2021, by Susan Guzzetta are as follows: All responses have been provided in the same order as indicated within the original plan review comments letter. All applicable changes have been revised and indicated on the drawings with both associated revision cloud and delta symbol. 1. Revised sheet FA0.02 Riser Diagram to reflect that device in question is not new but existing. 2. Revised scope of work on sheet FA0.01 that shows the updated hearing impaired rooms per floor and room names with number. I trust the above information shall be adequate for your use, but should you have any questions or concerns please do not hesitate to contact Pyro-Comm Systems Inc. (714)902-8000 x 260. Thank You, Joey Villanueva -System Design Engineer Pyro-Comm Systems Inc. WWW.PYR000MM.COM NORTHERN CA REGIONAL OFFICE - 10966 BIGGE STREET- SAN LEANDRO, CA 94577 SAN DIEGO REGIONAL OFFICE - 5115 AVENIDA ENCINAS, SUITE G - CARLSBAD, CA 92008 C-10 612153 (510)632-1208 (760)930-6014