HomeMy WebLinkAboutF2022-0154 - Misc4M Submittal Package for: WU Newport Heights Medical Campus MOB2 HRC Newport Clinic IVF 2ND Floor T.I. Ste. 200A & 200B 20360 Birch Street Newport Beach, CA 92660 Stratex Solutions, Inc. 1938 N. Batavia Street, Suite D Orange, CA 92865 Contains Cuts.heets and CSFM Listing for: UL Certificate Existing Device Fire Alarm Panel Additional Devices Added for TI Smoke Detector Heat Detector Pull Station Strobe/ Horn/Strobe/ Chime/Strobe Cable "1 14& Y Applicant ID No: 578045-001 Service Center No: 1 Expires: 31-DEC-2022' CERTIFICATE OF COMPLIANCE THIS IS TO CERTIFY that the Alarm Service Company indicated below is included by Underwriters Laboratories Inc. (UL) in its Product Directories as eligible to use the UL Listing Mark in connection with Certificated Alarm Systems. The only evidence of compliance with UL's requirements is the issuance of a UL Certificate for the Alarm' System and the Certificate is current under' UL's Certificate Verification Service, This Certificate does not apply in any way to the communication channel between the protected property and any facility that monitors signals from the protected property unless the use of a UL listed or Classified Alarm Transport Company is specified on the Certificate. Listed Service From: ORANGE, CA Alarm Service Company: (578045-001) Service Center: 1578045-0011 STRATEX SOLUTIONS INC STRATEX SOLUTIONS INC UNITE UNIT E 1938 N BATAVIA ST 1938 N BATAVIA ST ORANGE CA 92865 ORANGE CA 92865 The Alarm Service Company is Listed in the fo;Ilgyvjng Certificate Service Categories: F, File -Vol No. CCN' Listma-Ceon� log, 4 S82454 UUFX [Sighal and Fire Alarm Equipment ertdS ices] (Protective Signaling r� Services) Central Station e ' t R 4 lg ... b it t b 6 - CZ g tnK�wwlp P g E4 4 �5NO c } :'1 b C cv02PP,%b P.NMD,< t 5 yy i 4 i #4 P 4 O ***�f%S CERTIFICATE EXPIR 4 , "LOOK FOR THE. UL ALARM SYSTEM CERTI FICATE" r , ,d 4 DF -60334:A6 • Al -100 MS-9600LS(E)/MS-96000DLS(E) Fli"e•LIT@ALat-ills Intelligent Addressable FACP with Optional Second Loop by Honeywell 77 7 77 ddres`sable Control Panels _' General Fire-Lite's MS-9600LS(E) and MS-9600UDLS(E) are compact, cost effective, intelligent addressable FACPs (Fire Alarm Control Panels) with an extensive list of powerful features. The combination of Fire-Lite's newer series devices and legacy 300 Series devices, along with the MS-9600LS(E) or MS-9600UDLS(E) FACP, offer the latest in fire protection technology. LiteSpeed7m is a patented tech- nology that polls 10 devices at a time looking for new or different information. When new information is found at a specific address, the system polls that device several times for any new data. This improvement allows a fully loaded panel with up to 636 devices to report an incident and activate the notification circuits in under 10 seconds. With this polling scheme, devices can be wired on stan- dard twisted, unshielded wire up to a distance of 10,000 feet per loop. Each Signaling Line Circuit (SLC) loop supports up to 159 addressable detectors including photoelectric, photoelectric with heat, beam, ionization, photoelectric duct, fixed heat, fixed heat with rate -of -rise, and fixed high -heat detectors. It also supports up to 159 addressable modules including monitor (two -wire detector, normally open devices), dual -monitor functions (two monitor circuits from one module, two addresses used), multi -monitor (multiple monitor cir- cuits from one module, multiple addresses used), control (for Notifi- cation Appliance Circuits), and relay (two Form -C) modules. The FLPS-7 power supply is a separate board while all other elec- tronics are contained on a single main circuit board. Both boards are mounted to a quick -removable chassis and housed in a metal cabi- net. The backbox can be installed allowing field wiring to be pulled. When construction is completed, the chassis with the electronics can be quickly installed with two bolts. The MS-9600UDLS(E) includes a factory -installed 2 Digital Alarm Communicator Transmitter. The DACT transmits system status (alarm, troubles, AC loss, etc.) to a Central Station via internet (optional IPDACT installed) or the public switched telephone net- work. Optional modules, which plug into the main circuit board, are avail- able for special functions. Available accessories include LED, graphic and LCD annunciators, reverse polarity/city box transmitter, digital alarm communicator/transmitter, SLC expansion module, local and remote upload/download software and remote power expansion. FM APPROVED to UL ANSI 864. NOTE. Unless otherwise specified, the term MS-9600LS is used in this document to refer to the MS-960OLS, MS-9600ODLS, MS-9600LSE, and MS-9600ODLSE FACPs (Fire Alarm Control Panels). Controls And Indicators LED INDICATORS • AC POWER (green) • FIRE ALARM (red) • SUPERVISORY (yellow) • ALARM SILENCED (yellow) • SYSTEM TROUBLE (yellow) • MAINTENANCE/PRESIGNAL (yellow) • DISABLED (yellow) • BATTERY FAULT (yellow) • GROUND FAULT (yellow) MEMBRANE SWITCH CONTROLS • ACKNOWLEDGE/STEP • ALARM SILENCE DRILL SYSTEM RESET (lamp test) 12 -key pad with full alphabet 4 cursor keys ENTER Special Features • Easy mount chassis. • 7 amp switching power supply. • Large enclosure allows 18 amp -hour batteries • 2 plug-in communicator standard with MS-9600UDLS/E. • Optional IPDACT Internet Protocol Digital Alarm Communicator/ Transmitter Four Style Y (Class B) or two Style Z (Class A) NAC circuits. • Selectable strobe synchronization per NAC for System Sensor, Wheelock, and Gentex devices. • Certified for seismic applications when used with the appropriate seismic mounting kit • Seamless integration between fire and mass notification with the ECC -50/100 Emergency Command Center via ANN -BUS con- nections. • ECC-FFT Firefighter Telephone Option • ANN -BUS for connection to following optional modules Note: cannot be used if ACS annunciators are used. — ANN -80(-W) Remote LCD Annunciator —ANN -1/0 LED Driver Module — ANN-S/PG Serial/Parallel Printer Module DF -60334:A6 •2/20/2019 — Page 1 of 6 - ANN-RLY Relay Module - ANN -LED Annunciator Module - ANN-RLED Annunciator Module (alarms only) Compatible with SWIFTO wireless devices Standard Features SLC LOOP SLC can be configured for NFPA Style 4, 6, or 7 operation. • SLC supports up to 318 addressable devices per loop (159 detectors and 159 monitor, control, or relay modules). • SLC loop maximum length 10,000 ft. (3,048 m) @ 12 AWG (3.1 MM2) using twisted, unshielded wire (see Wire Table on page 5). NOTIFICATION APPLIANCE CIRCUITS (NACS) • Four onboard NACs with additional NAC capability using output control modules (CMF -300 or CMF -300-6). The four Class B NACs can be converted to two Class A NACs with the NACKEY (included). • Silence Inhibit and Auto Silence timer options. • Continuous, March Time, Temporal or California code for main circuit board NACs with two-stage capability. • Selectable strobe synchronization per NAC. • 3.0 amps special application, 300mA regulated maximum per each NAC circuit - Note: Maximum 24 VDC system power output is shared among all NAC circuits and 24 VDC special application auxiliary power outputs. Total available output is 7.0 amps. ADVANCED FIRE TECHNOLOGY., • Sensitivity testing with printable results, on-site or off-site. • Automatic drift compensation. PROGRAMMING AND SOFTWARE: • Autoprogramming (learn mode) reduces installation time. • Fully programmable from local keypad, local PS/2 keyboard or PC (using the standard PS -Tools Windows@ utility). • Two-level user -programmable passwords. • Custom English labels (per point) may be manually entered or selected from an internal library file. • Three Form -C relay outputs (two programmable). • 99 software zones. USER INTERFACE: • Optional plug-in- 2 communicator-- (standard with MS- 96000DLS(E) with USB port for local upload/download. • Remote Acknowledge, Silence, Reset and Drill via addressable monitor modules, ACS Series annunciators, LCD -80F remote annunciator, or ANN -80 Series Annunciators. • EIA -232 printer/PC interface (variable baud rate) on main circuit board. • Integral 80 -character LCD display with backlighting. • Real-time clock/calendar with automatic daylight savings adjust- ments. • History file with 1,000 -event capacity. EIA-485/ANN-BUS supporting up to 8 ANN Series Annunciators or 32 ACS Series annunciators. • EIA -485 supporting up to 32 ACS annunciators. • Maintenance alert warns when smoke detector dust accumula- tion is excessive. • Automatic device type -code verification. • One person audible or silent walk test with walk -test log and print- out. • `Point trouble identification. Page 2 of 6 — DF -60334:A6 • 2/20/2019 Local piezo sounder. Waterflow (non-silenceable) selection per monitor point. System alarm verification selection per detector point. PAS (Positive Alarm Sequence) and presignal delay per point (NFPA 72 compliant). Optional 4XTMF module (conventional reverse polarity/city box transmitter). Field -programming Features Off-line Programming: Create the entire program in your office using a WindowsO-based software package (download PS -Tools from www.firelite.com). Upload/download system programming locally to the MS-960OLS in less than one minute. Autoprogramming: Command the MS-960OLS to program itself (takes less than 30 seconds). In the Auto -Program mode, the MS- 9600LS scans for all possible devices at all addresses, stores the device types, and addresses found, and then loads default values for all options (General Alarm). It also checks for two or more devices set to the same address. Online Editing: While still providing fire protection, the MS-9600LS/ E may be programmed from the front panel. Simple menu trees dis- played on the LCD allow the trained user to perform all functions without referring back to the programming manual. English Label Library: Quickly select labels from a standard library of more than 50 adjectives/nouns, such as "FLR 3 HALLWAY" or enter custom labels letter -by -letter. Use recall function to repeat pre- viously used label. Program Check: Automatically catch common errors, such as con- trol modules not linked to any zone or input point. Maintenance Alert The MS-9600LS(E) continuously monitors each smoke detector and is capable of reporting maintenance conditions. This reduces the risk of false alarms due to dust accumulation. Refer to the control panel installation manual for more information. Automatic Test Operation The MS-9600LS(E) performs an automatic test of each detector every two hours. Failure to meet the test limits causes an AUTO TEST FAIL trouble type. System Reset clears this trouble. Terminal Blocks AC Power - TBI: 120 VAC, 60 Hz, 3.0 amps or 240 VAC, 50 Hz, 1.5 amps. Wire size: minimum 14 AWG (2.00 mm2) with 600 Vinsu- lation. - Battery (lead acid only) - TB2: Maximum charging circuit: Normal Float charge 27.6 VDC @ 1.0 amp. Maximum battery charger capac- ity: 26 AH. Minimum battery 12 AH. MS-960OLS cabinet holds maxi- mum of two 18 AH batteries. For 26 - 120 AH batteries, use the CHG-120F or CHG-75 Battery Charger and BB -55F Battery Box. NOTE: Jumper JP3, on the FACP main circuit board, must be cut to dis- able the FACP battery charger when using the CHG-120F or CHG-75. Communication Loop - (standard) TB8: 24 VDC nominal, 27.6 VDC maximum. Maximum length: 10,000 ft. (3048 m) total twisted, unshielded pair length. Maximum loop current: 400 mA (short circuit) or 100 mA (normal). Maximum loop resistance: 40 ohms. Super- vised and power -limited. Notification Appliance Circuits - TB4: Power -limited circuitry. Nominal operating voltage: 24 VDC. Current limit: fuseless, elec- tronic, power -limited circuitry. Maximum signaling current per circuit: 3.0 amps special application, 300mA regulated. End -of -Line Resis- tor: 4.7K ohm, 112 watt (P/N 71252 UL listed) for NACs. Refer to Fire -Lite Device Compatibility Document for listed compatible devices. Programmable and Trouble Output Relays -T65: Contact rating: CHG-120F: Remote battery charging system for lead -acid batteries 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive). with a rating of 25 to 120 AH. CHG-120F or CHG-75 required for Form -C relays. charging greater than 25 AH batteries. Four -Wire Resettable Smoke Detector Power (24 VDC nominal) -TB3, Terminals 1(+) & 2(-): Maximum ripple voltage: 10 mVRMs. Up to 1.5 amps for powering four -wire smoke detectors. Power -limited circuit. Refer to Fire -Lit- e Device Compatibility Document for listed compatible devices. Nonresettable Power#1 (24 VDC Nominal) -TB3, Terminals 3 (+) & 4 (-): Maximum ripple voltage: 10 mVRMs. Up to 1.5 amps total DC current available from each output. Power -limited circuit. TB3, Terminals 5 (+) & 6 (-): non-resettable power #2. Nonresettable Special Application Power #2 (24 VDC Nominal) - TB3, Terminals 5 (+) & 6 (-): Maximum ripple voltage: 10mVRMS. Total DC current available from each output is up to 1.5 amps. Power -limited circuit, non -supervised. EIA -485 (ACS/ANN) - TB6: Annunciator connector, programmable for type ANN or ACS. Terminal 1 (+) and Terminal 2 (-). EIA -485 (TERM) - T137: Terminal mode annunciator connector, Ter- minal 1 (Out +), 2 (In +), 3 (Out -), 4 (In -). EIA -232 - TB8: PC/printer connector, Terminal 1 (Transmit), 2 (Receive), 3 (DTR), 4 (Ground). Ordering Options MS-9600LS(E): 318 -point addressable Fire Alarm Control Panel, one SLC loop. Includes 80 -character LCD display, single printed cir- cuit board, and cabinet. CHG-75: Battery charger for lead -acid batteries with a rating of 25 to 75 AH. CHGA20F or CHG-75 required for charging greater than 25 AH batteries. BAT Series: Batteries, see data sheet DF -52397. PRN Series: UL listed compatible event printer which uses tractor - fed paper. SEISKIT-COMMENC: Seismic kit for the MS-96000DLS backbox. Includes battery bracket for two 7, 12, or 18 AH batteries. Compatible Addressable Devices All feature a polling LED and rotary switches for addressing. AD355/AD365(-IV): Low -profile, intelligent, "Adapt' multi -sensor detector; B350LP base included. BEAM355: Intelligent beam smoke detector. BEAM355S: Intelligent beam smoke detector with integral sensitiv- ity test. CP355: Addressable low -profile ionization smoke detector. D355PL: Photoelectric low -flow duct smoke detector, SD355R included. H355IH365: Fast -response, low -profile heat detector. H355R/H365R(-IV): Fast -response, low -profile heat detector with rate -of -rise option. MS-96000DLS(E): 318 -point addressable Fire Alarm Control Panel, H355HTIH365HT(-1V):. Fast -response, low -profile heat detector that one SLC loop. Includes 2, 80-charecter LCD display, single printed activates all 90* F (88"C). circuit board, and cabinet. OSI -RI -FL: Addressable long range projected beam smoke detector DACT-UD2: Optional communicator for remote monitoring (standard designed to provide open area protection with MS-96000DLS). SD355/SD365(-IV): Addressable low -profile photoelectric smoke SLC-2LS: Optional expander module, enables second SLC loop 4XTMF: Optional Transmitter Module provides a supervised output for local energy municipal box transmitter, alarm and trouble reverse polarity. It includes a disable switch and disable trouble. IPDACT-2/2UD, IPDACT Internet Monitoring Module: Mounts in bottom of enclosure with optional mounting kit (P/N: IPBRKT). Con- nects to primary and secondary DACT telephone output ports for internet communications over customer provided ethernet internet connection. Requires compatible Teldat VisorALARM Central Sta- tion Receiver. Can use. DHCP or static IP. (See data sheet DF -60407 or DF -52424 for additional information. IPBRKT: Optional mounting bracket kit consisting of screws and - battery shield with standoffs required when mounting the IPDACT in lower enclosure section of FACR IPSPLT: Optional Y -Adaptor which allows connection of both panel dialer outputs to one cable input to IPDACT (sold separately). ACM-8RF: Optional plug-in relay module provides 8 Form -C 5.0 amp relays. PS -Tools: Programming software for Windows® -based PC com- puter (cable not included). Available for download at-www.fre- lite.com. PRT/PK-CABLE: Cable printer/personal computer interface cable DP -9692: Optional dress panel for MS-9600LS(E). TR -CE: Optional Trim Ring for semi -flush mounting. BB -55F: Battery box; required to house two 25 AH batteries and one CHGA20F battery charger. For batteries greater than 25 AH, consult factory for housing/mounting arrangements. BB -26: Battery backbox, holds up to two 25 AH batteries. detector SD355T/SD365T(-IV): Addressable low -profile photoelectric smoke detector with thermal sensor CDRM-300: Dual relay Monitor Module CMF -300: Addressable Control Module for one Style Y/Z (Class B/ A) zone of supervised polarized Notification Appliances. Mounts. directly to a 4.0" (10.16 cm.) electrical box. Notification Appliance Circuit option requires external 24 VDC to power notification appli- ances. CRF -300: Addressable relay module containing two isolated sets of Form -C contacts, which operate as a DPDT switch. Mounts directly to a 4.0" (10.16 cm.) box, surface mount using. the SMB500... MDF -300: Dual Monitor Module. Same as MMF-300 except it pro- vides two Style B (Class B) only IDCs MMF-300: Addressable Monitor Module for one zone of normally - open dry -contact initiating devices. Mounts in standard 4.0".(10.16 cm.) box. Includes plastic cover plate and end -of -line resistor. Mod- ule maybe configured for either a Style B (Class B) or Style D (Class A) IDC. MMF-301: Miniature version of MMF-300. Excludes LED and Style D option. Connects with wire pigtails. May mount in device backbox. MMF302: Similar to MMF-300, but may monitor up to 20 conven- tional two -wire detectors. Requires resettable 24 VDC power. Con- sult factory for compatible smoke detectors. BG-12LX: Addressable manual pull station with interlace module mounted inside 1300: This module isolates the SLC loop from short circuit conditions (required for Style 6 or 7 operation). DF -60334:A6 • 2/20/2019 — Page 3 of 6 EIA -485 ACS/ANN-BUS ANNUNCIATORS (2 -data wires, 2 -power wires) .11 40 ANN -80 EIA -232 INTERFACE t!�* 4 PRINTER Optional REVERSE POLARITY/ CITY BOX OUTPUT (4XTMF) 2 4XTMF Reverse Polarity Module Page 4 of 6 — DF -60334:A6 • 2/20/2019 Audio Control for ECC -501100 Emergency Command Center 1 1 1 1 1 1 1 1 8 FORM -C, 5 -AMP RELAYS (optional, order ACM-8RF) NACs (Notification Appliance Circuits) BELLS, SIGNALS, STROBES IPDACT Internet Protocol DACT )porting SMOKE DETECTORS SD355(f, SD365/T, CP355 HEAT DETECTORS H355/R, H365/R DUCT DETECTORS D355PL wql INTELLIGENT BEAM DETECTORS BEAM355, BEAM355S OSI -RI -FL O° oap 0 _0 00 °o MONITOR/CONTROL. MMF-300, MDF -300, MMF-302, CMF -300, CRF -300,1300, CDRM-300 it G,J MINI MONITOR MMF-3 •- r ADDRESSABLE MULTI -MODULES MMF-300-10, MMF-302-6, CMF -300-6, CRF -300-6, ISO -6 PULL STATION BG-12LX Wireless WIRELESS MonitorGATEWAY M'?"b W GATE Module W-M Wireless o ° o o - NO Relay Relay ° Module W -CRF Wireless Pin" Photo Detector Detector ` W-SD355 Wireless Pull Station W-BG12LX it G,J MINI MONITOR MMF-3 •- r ADDRESSABLE MULTI -MODULES MMF-300-10, MMF-302-6, CMF -300-6, CRF -300-6, ISO -6 PULL STATION BG-12LX I • I ISO -6: Six -fault Isolator Module. Mount one or two modules in a BB - 2F cabinet (optional). Mount up to six modules on a CHS -6 chassis in a BB -617. SMB500: Used to mount all modules except the MMF-301 and M301 MMF-300-10: Ten -input monitor module. Mount one or two modules in a BB -2F cabinet (optional). Mount up to six modules on a CHS -6 chassis in a BB -6F MMF-302-6: Six -zone interface module. Mount one or two modules in a BB -2F cabinet (optional). Mount up to six modules on a CHS -6 chassis in a BB -6F CMF -300-6: Six -circuit supervised control module. Mount one or two modules in a BB -2F cabinet (optional). Mount up to six modules on a CHS -6 chassis in a BB -6F CRF -300.6: Six Form -C relay control module. Mount one or two modules in a BB -2F cabinet (optional). Mount up to six modules on a CHS -6 chassis in a BB -6F W -GATE: SWIFT Wireless Gateway W -DIS -D: LCD user interface for use with the W -GATE wireless gateway and an ANN -80-W Remote Annunciator W-SD355: Intelligent, wireless photo detector W-H355R: Intelligent wireless rate of rise (135°) heat detector W-SD355T: Intelligent wireless photo/heat detector W -H355: Intelligent wireless fixed -temperature (135°) heat detector W-MMF: Intelligent wireless monitor module W -CRF: Intelligent wireless relay module W-BG12LX: Intelligent wireless pullstation WAV-CRLIWAV-CWL: Intelligent wireless AV bases W -SYNC: Intelligent wireless sync module. W -USB: Wireless .USB radio/antenna dongle that plugs into the USB port of a PC running SWIFT Tools SWIFT Tools: Programming and diagnostic utility for the Wireless Gateway and devices. Available for download from firelite.com. Compatible Annunciators ANN -80(-W): Remote LCD annunciator that mimics the information displayed on the FACP's LCD display. Recommended wire type is unshielded. (Basic model is red; order -W version for white; see DF - 52417). ANN -LED: Annunciator Module provides three LEDs for each zone: Alarm, Trouble and Supervisory. Ships with red enclosure (see DF - 60241). ANN-RLED: Provides alarm (red) indicators for up to 30 input zones or addressable points (see DF -60241). ANN-RLY: Relay Module, which can be mounted inside the cabinet, provides 10 programmable Form -C relays (see DF -52431). ANN-S/PG: Serial/Parallel Printer Gateway module provides a con- nection for a Serial or Parallel printer (see DF -52429). ANN -1/0: 1/0 Driver Module provides connections to a user supplied graphic annunciator (see DF -52430). ACS -LED Zone Series: LED -type fire annunciators capable of pro- viding up to 99 software zones of annunciation. Available in incre- ments of 16 or 32 points to meet a variety of applications. ACS-LDM Graphic Series: Lamp Driver Module series for use with custom graphic annunciators. LCD -80F Annunciator: 80 -character, backlit LCD -type fire annunci- ators capable of displaying English-language text. Up to 32 LCD - 80F annunciators may be connected to the EIA -485 terminal mode serial interface on the MS-9600LS(E) motherboard. NOTE., For more information on Compatible Annunciators for use with the MS-9600LS(E), see the following data sheets (document numbers) ACM-8RF (DF -51555), ACS/ACM Series (DF -52378), LDM Series (OF - 51384), LCD -80F (DF -52185). Wiring Requirements While shielded wire is not required, it is recommended that all SLC wiring be twisted -pair to minimize the effects of electrical interfer- ence. Refer to the panel manual for wiring details. DF -60334:A6 - 2/2012019 — Page 5 of 6 SYSTEM SPECIFICATIONS System Capacity Intelligent Signaling Line Circuits ..................... I expandable to 2 Intelligent detectors ................................................. 159 per loop Addressable monitor/control modules ..................... 159 per loop Programmable software zones ................................................ 99 ANN -BUS devices..................................................................... 8 ACS Annunciators................................................................... 32 LCD Annunciators.................................................................... 32 Electrical Specifications • Primary input power: 120 VAC, 50/60 Hz, 3.0 A. 240 VAC, 50 Hz, 1.5 A. • Battery: 27.6 VDC @ 1.0 A (max). Maximum battery charger capacity: 26 AH. Minimum battery: 12 AH. MS-960OLS cabinet holds maximum of two 18AH batteries. • Communication Loop: 24 VDC nominal, supervised and power - limited. • Notification Appliance Circuits: terminal block provides connec- tions for four Style Y (Class B) or two Style Z (Class A) NACs. Maximum signaling current per circuit: 3.0 amps special applica- tion, 300mA regulated. End -of -Line Resistor: 4.7 K ohms, Y� watt (P/N 71252 UL listed) - for Style Y (Class B) NAC. -- Supervised and power -limited. Refer to panel documentation and Fire -Lite Device Compatibility Document for listed compatible devices. • Two Programmable Form -C Relays and One Fixed Trouble Form -C Relay: Contact rating: 2.0 A @ 30 VDC (resistive) 0.5 A @ 30 VAC (resistive). • Four -wire Resettable Special Application Power (24 VDC nomi- nal): Up to 1.5 A for powering four -wire smoke detectors. Power - Limited, non -supervised. Refer to Fire -Lite Device Compatibility Document for listed com- patible devices. • Non-resettable Special Application Power #1 (24VDC nominal) TB3, Terminals 3 (+) & 4 (-): Maximum ripple voltage: 10 mVRMS Total DC current available from each output is up to 1.5 A. Power -limited, non -supervised. • Non-resettable Special Application Power #2 (24VDC nominal) TB3, Terminals (+) & 6 (-) Maximum ripple voltage: 10 mVRMS Total DC current available from each output is up to 1.5 A. Power -limited, non -supervised. NOTE: Although each Special Application power output can deliver 1.5 A individually, the total power output from these circuits cannot exceed 1.5 A in standby. The total Alarm output for all Special Application power and NAC circuits cannot exceed 7A. Cabinet Specifications Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.67" (1.70 cm.) deep. Backbox: 19.00" (48.26 cm.) high x 16.65" (42.29 cm.) wide x 5.21" (13.23 cm.) deep. Trim Ring (TR -CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide. Shipping Specifications Dimensions: 20.00" (50.80 cm) high, 22.5" (57.15 cm) wide, 8.5" (21.59 cm) deep. Weight: 27.3 lbs (12.38 kg). Temperature and Humidity Ranges This system meets NFPA requirements for operation at 0 - 49'C/32 - 120°F and at a relative humidity 93% t 2% RH (noncondensing) at 32"C t 2"C (90"F t 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 - 27°C/60 - 80°F. Agency Listings and Approvals The listings and approvals below apply to the MS-960OLS(E) and MS-96000DLS(E) control panels. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • ULC: S624 (MS-9600LSC only; see DF -60438) • FM APPROVED: to UL ANSI 864 • CSFM:7170-0075:217 • MEA: 87-08-E • IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seismic). • CBC 2007 (Seismic)` - NFPA Standards The MS-9600LS(E) and MS-96000DLS(E) control panels comply with the following NFPA 72 Fire Alarm Systems requirements: - LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervi- sory). -AUXILIARY (Automatic, Manual and Waterflow) (requires 4XTMF). - REMOTE STATION (Automatic, Manual and Waterflow) (Requires 4XTMF where DACT-UD2 is not accepted.) - PROPRIETARY (Automatic, Manual and Waterflow). - CENTRAL STATION (Automatic, Manual and Waterflow, and Sprinkler Supervised). - OT (Other Technologies-PSDN) For use with IPDACT. LiteSpeedTM is a trademark; and FireLlte@ Alarms and SWIFT@ are registered trademarks of Honeywell International Inc. Windows@ is a trademark of the Microsoft Corporation. ©2019 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. ' wV\ O {900� We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. SIRINIMINR S MRNRMCTRRINR QUALITY SYSTEMS For more information, contact Fire -Lite Alarms. Phone: (800)627-3473, FAX: (877y699-4105. Country of Origin: USA wwmfirelite.com Page 6 of 6 - DF -60334:A6 • 2120/2019 These control units can generate the distinctive three -pulse Temporal Pattern Fire Alarm Evacuation Signal as required per NFPA 72, 2002 Edition and meet the requirements of `Rev. 01-20-15 gt 10.This. listing is .based upon technical: data .submitted by the applicant. CSFM Fire Engineering. staff has reviewed 'tiO'� the test results and/or other data but floes not make an independent verification of any claims. This listing is. not � an endorsement or recommendation of the item listed. This listing should not be used to verify correct "° operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or. other Date Issued: July 01, 2021 Listing. Expires June 30 2022' Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division ,. CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7165-0075:0217 Page 1 of 2 CATEGORY: 7165 -- FIRE ALARM CONTROL UNIT (COMMERCIAL) LISTEE FIRE -LITE ALARMS INC.One Fire -Lite Place, Northford, CT 06410-1653 Contact: Lisa Brant (203) 484-6105 Fax (203) 484-7309 Email: lisa.brant@honeywell.com DESIGN: Models MS-960OLS and MS-96000DLS addressable fire alarm control units. Suitable for local protective, remote, auxiliary, and central station signaling when used with appropriate optional modules and additional separate listed equipment. The panels provide one signaling line circuit for connection of up to 318 total addressable devices (159 detectors and 159 modules); two Class A or four Class B notification appliance circuits; three form C relays are provided that are default programmed for alarm, trouble, and supervisory relay outputs. The MS-96000DLS come with the DACT-UD2 factory installed. Refer to listee's data sheet for detailed product description and operational considerations. System components: MS-9600LS, MS-96000DLS Control Unit SLC-2LS Loop Card DACT-UD2 Digital Alarm Communicator Transmitter Modules 4XTMF Transmitter Module LDM-32F Lamp driver Module ACM-8RF Control Relay Module ANN-RLY Remote Relay ANN -80, ANN -LED, LCD -80F Remote Annunciator ACM-16ATF, ACM-32AF Remote Annunciator AEM-16ATF, AEM-32AF Remote Annunciator ACC-25150ZST Audio Command Center (Listing No. 6911-0075:207) RATING: 120 VAC, 50/60 Hz, 3.0 amps INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and FM label. APPROVAL: Listed as fire alarm control unit for use with separately listed compatible initiating and indicating devices. Also suitable for high-rise applications for use with Model ACC-25/50ZST Audio Command Center (Listing No. 6911-0075:207). "Models MS-960OLS and MS-96000DLS panels are also suitable for high-rise application for use with Model ECC -50/100 emergency voice evacuation panel (CSFM # 6911-0075:0226). Refer to manufacturer's Installation Manual for details. These control units can generate the distinctive three -pulse Temporal Pattern Fire Alarm Evacuation Signal as required per NFPA 72, 2002 Edition and meet the requirements of `Rev. 01-20-15 gt 10.This. listing is .based upon technical: data .submitted by the applicant. CSFM Fire Engineering. staff has reviewed 'tiO'� the test results and/or other data but floes not make an independent verification of any claims. This listing is. not � an endorsement or recommendation of the item listed. This listing should not be used to verify correct "° operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or. other Date Issued: July 01, 2021 Listing. Expires June 30 2022' Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division , Listing No. 7165-0075:0217 Page 2 of 2 UL -864, 9th Edition Standard. NOTE: 1. For Fire Alarm Verification Feature (Delay of fire alarm), the maximum Retard/Reset/Restart period must be adjusted to 30 seconds or less. 2. Combined with 7170-0075:220 " 'Rev. 01-20-15 gt This listingisbased upon technicaldata submitted by the applicant. CSFM Fire Engineering staff has reviewed < < the test results and/orother data but does not make an independent verification of any claims. This listing is not '•+,,0, ,.F an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2021 Listing Expires `June 30 2022 Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division DF -61010:C SD365 SeriesF�I'"E'.L�TE:�ALaI"t11S Addressable Photoelectric Smoke Detectors by Honeywell The Fire -Lite® Alarms SD365(A), SD365R(A), and SD365HT(A) intelligent plug-in smoke detectors are designed for both perfor- mance and aesthetics, and are direct replacements for the SD355 Series. A new modern, sleek, contemporary design and enhanced-'"�' optical sensing chamber is engineered to sense smoke produced by;+.:? -.�� ��'" •, a wide range of combustion sources in accordance with more strip- l�- gent code standards. _ '�- Exclusively e" for use with Fire-Lite's addressable fire alarm control panels, the SD365(A) Series point. ID capability allows each detec- tor's address to be set with rotary, decimal address switches, provid- ing exact detector location for emergency personnel to quickly locate a fire during its early stages, potentially saving precious rescue time while also reducing property damage. Two LEDs on each sensor light to provide a local, visible sensor indication. The SD365(A) Series also offers 135°F (57°C) fixed temperature thermal sensing on the SD365T(A) and a remote test capable detec- tor on the SD365R(A) for use with DNR(A)/DNRW duct smoke detector housings. Features SLC LOOP. • Two -wire SLC loop connection -- • Unit uses base for wiring • Compatible with LiteSpeecITM and CLIP protocol systems • Stable communication technique with noise immunity ADDRESSING: • Addressable by device • Rotary, decimal addressing (Refer to the Fire -Lite panel manuals for device capacity.) ARCHITECTURE. • Sleek, low -profile, stylish design • Unique single -source design to respond quickly and dependably to a broad range of fires • Integral communications and built-in device -type identification • Built-in tamper resistant feature • Remote test feature from the panel • Walk test with address display (an address on 121 will blink the detector LED: 12-[pause]-1(LiteSpeed systems only) • Built-in functional test switch activated by external magnet • Removable cover and insect -resistant screen for simple field cleaning • Expanded color options. OPERATION. • Designed to meet UL 268 7th Edition • Factory preset at 1.5% nominal sensitivity for panel alarm thresh- old level • LED "blinks" when the unit is polled (communicating with the fire panel) and latches in alarm. • Low standby current - MECHANICALS: • Sealed against back pressure • .SEMS screws for wiring of theseparate base • Designed for direct -surface or electrical -box mounting • Plugs into separate base for ease of installation and maintenance • Separate base allows interchange of photoelectric, ionization and thermal sensors OPTIONS: • Optional relay, isolator, and sounder bases Installation SD365 Series plug-in intelligent smoke detectors use a detachable base to simplify installation, service and maintenance. Installation instructions are shipped with each detector. Mount detector base (all base types) on an electrical backbox which is at least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes, see DF -60059. NOTE: Because of the inherent supervision provided by the SLC loop, end -of -line resistors are not required. Wiring "T -taps" or branches are permitted for Class 'B" wiring only. When using relay or sounder bases, consult the 1300(A) installation sheet 156-3626 for device limitations between isolator modules and isola- tor bases. Construction These detectors are constructed of fire-resistant plastic. The SD365 Series plug-in intelligent smoke detectors are designed to commer- cial standards and offer an attractive appearance. Operation Each SD365 Series detector uses one of the panel's addresses (total limit is panel dependent) on the Fire -Lite Signaling Line Circuit (SLC). It responds to regular polls from the control panel and reports its type and the status. If it receives a test command from the panel (or a local magnet test), it stimulates its electronics and reports an alarm. It blinks its LEDs when polled andturns the LEDs on when commanded by the panel. The SD365 Series offers features and performance that represent the latest in smoke detector technology. Detector Sensitivity Test Each detector can have its sensitivity tested (required per NFPA 72, Chapter 14 on Inspection, Testing and Maintenance) when installed/ connected to an Fire -Lite addressable fire alarm control panel. The results of the sensitivity test can be printed for record keeping. DF -61010:C • 5/28/2020 — Page 1 of 3 Product Line Information NOTE: "-11/" suffix indicates CLIP and LiteSpeed device. NOTE., "A" suffix indicates Canadian version. SD365: White, low -profile intelligent photoelectric sensor, LiteSpee only SD365A: Same as SD365 but with ULC listing. SD365-IV: Ivory, low -profile intelligent photoelectric sensor SD365A-IV: Same as SD365-IV but with ULC listing SD365T: White, same as SD365 but includes a built-in 135°F (570 fixed-temperature thermal device, LiteSpeed only SD365TA: Same as SD365T but with ULC listing SD365T-IV: Ivory, same as SD365T but includes a built-in 1350 (57°C) fixed -temperature thermal device SD365TA-IV: Same as SD365T-IV but with ULC listing SD365R: White, low -profile intelligent photoelectric sensor, remot test capable, for use with DNR/DNRW, LiteSpeed only SD365RA: Same as SD365R but with ULC listing, for use wit DNRA 8200SA-WH: Same as B200S-WH, ULC listing B200SA-IV: Same as B200S-IV, ULC listing B200SCOA-WH: White, Intelligent, programmable sounder base in d English/French (required in Canada for ULC applications with CO Series detector applications B200SCOA-IV: Ivory Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with CO Series. detector applications, ULC listing B20OS-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 -Hz +/- C) 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. (CSFM: 7300-1653:0238) B20OS-LF-IV: Ivory, Low Frequency Intelligent, programmable F .. sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. (CSFM: 7300-1653:0238) B200SR-WH: White, Intelligent sounder base capable of producing e sound output with ANSI Temporal 3 or continuous tone. Intended for retrofit applications. (CSFM: 7300-1653:0213) h B200SR-IV: Ivory, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended for t ft I' t' CSFM 7300 SD36SR-IV: Ivory, low -profile intelligent photoelectric sensor, remote re ro i app ice ions. ( -1653.0213) test capable, for use with DNR/DNRW 8200SRA-WH: Same as B200SR-WH with, ULC listing SD365RA-IV: Same as SD365R-IV but with ULC listing, for use with 8200SRA-IV: Same as B200SR-IV in Ivory color, ULC listing DNRA B200SR-LF-WH: Whit L F I t If t bl INTELLIGENT BASES 'NOTE: For details on intelligent bases, see -DF -60059. - B300-6: White, 6" base, standard flanged low -profile mounting bas (CSFM 7300-1653:0109) B300 -6 -IV: Ivory,&" base, standard flanged low -profile mountin base (CSFM: 7300-1653.0109) B300A-6: Same as B300.6, ULC listed B30OA-6-IV: Ivory, 6" standard flanged low -profile mounting bas ULC listed B300 -6 -SP: Bulk pack of B300-6, package contains 10 B501 -WHITE: White, 4" standard European flangeless mountin base. UUULC listed (CSFM., 7300-1653:0109) B501 -BL: Black, 4" standard European flangeless mounting base UUULC listed (CSFM: 7300.1653:0109) B501 -IV: Ivory. color, 4" standard European flangeless mountin base. UUULC listed (CSFM: 7300-.1653:0109). B501 -WHITE -BP: Bulk pack of B501 -WHITE contains 10 B224RB-WH: White, relay base (CSFM: 7300-1653:0216) B224RB-IV: Ivory, relay base (CSFM: 7300.1653:0216) B224RBA-WH: White, relay base, ULC listing B224RBA-IV: Ivory, relay base, ULC listing B224B1-WH: White, isolator detector base (CSFM: 7300.1653:0216) B224BI-IV: Ivory isolator detector base (CSFM: 7300-1653:0216) B224BIA-WH: White, isolator detector base, ULC listing B224BIA-IV: Ivory isolator detector base, ULC listing B20OS-WH: White, Intelligent addressable sounder base capable of producing sound output in high or low volume with. ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone. Uses LiteSpeed protocol. (CSFM: 7300-1653:0213) B200S-IV: Ivory, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4,. continuous tone, marching tone, and custom tone. Uses LiteSpeed protocol. (CSFM: 7300-1653:0213) White Page 2 of 3 — DF -51010:C • 5/28/2020 - ow requency n e igen , programme e % sounder base. Produces a fundamental frequency of 520 Hz +/- 10 with a square wave or its. equivalent; designed to meet the NFPA 72 sleeping space- requirement. Intended for retrofit applica a tions. (CSFM: 7300-1653:0238) B200SR-LFAV: Ivory, Low Frequency Intelligent, programmable 9 sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applica- tions. (CSFM: 7300-1653:0238) e' MOUNTING KITS AND ACCESSORIES TR300: White, replacement flange for B210LP(A) base g TR300-IV: Ivory, replacement flange for B210LP(A) base RA100Z(A): Remote LED annunciator. 3.32 VDC. Mounts to a U.S. single -gang electrical box. For use with B501 (A) and 8300-6(A). . M02-04-00: Test magnet g M02-09.00: Test magnet with telescoping handle CK300: Color Kit (includes cover and trim ring), white, 10 -pack CK300-IV: Color Kit (includes cover and trim ring), ivory, 10 -pack CK300-BL: Color Kit (includes cover and trim ring), black, 10 -pack SYSTEM SPECIFICATIONS Sensitivity: Listings and Approvals • UL Applications: 0.5% to 4.0% per foot obscuration. Listings and approvals below apply to the SD365 Series detectors. • ULC Applications: 0.5% to 3.5% per foot obscuration In some cases, certain modules may not be listed by certain Size: 2.0" (51 mm) high; base determines diameter approval agencies, or listing may be in process. Consult factory for —8300-6: 6.1" (15.0 cm) diameter latest listing status. — 8501:4" (10.2 cm) diameter • UUULC Listing: S1059 - For a complete list of detector bases see DF -60983 - • FM Approved Shipping weight: 3.4 oz. (95 g) • CSFM: 7272-0075:0502 Operating temperature range: • SD365: 32°F to 122°F (0°Cto 50°C) • SD365T Series: 32°F to 100°F(0°C to 38°C) • SD365R Series installed in a DNR/DNRW, -4°F to 158°F (-20°C to 70°C) UL/ULC Listed Velocity Range: 0-4000 ft/min. (1219.2 m/min.), suitable for installation in ducts Relative humidity: 10% — 93% non -condensing Thermal ratings: fixed -temperature set point 135°F (57C), rate -of - rise detection 15°F (8.3°C) per minute, high temperature heat 190°F (88°C) ELECTRICAL SPECIFICATIONS Voltage range: 15 - 32 volts DC peak Standby current (max. avg.): 200pA.@ 24 VDC (o ne communica- tion every 5 -seconds With LED enabled) - - - - - - - - Max current: 4.5 mA @ 24 VDC ("ON") DETECTOR SPACING AND APPLICATIONS Fire -Lite recommends spacing detectors in compliance with NFPA 72. In low airflow applications with smooth ceiling, space detectors 30 feet (9.1m). For specific information regarding detector spacing, placement, and special applications refer to NFPA 72. A System Smoke Detector Application Guide, document SPAG91, is available at www.systemsensor.com. LiteSpeedl- is a trademark, and Fire -Ute® Alarms and System Sensor® are Page 3 of 3 — DF -61010:C • 5/28/2020 registered trademarks of Honeywell International Inc. @2020 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document isnot intended to be used for Installation purposes. {, IVO9UU1 We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipateall requirements. All specifications are subject to change without notice:. IAUfAt11NL 8 ttAAQmmmim QUALITY SYSTEMS For more information, contact Fire -Lite Alarms. Phone: (800) 627-3473, FAX:(877) 699-4105. Country of Origin: Mexico www.firelite.com Page 3 of 3 — DF -61010:C • 5/28/2020 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL ..FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 0 LISTING No. 7272,0075:0502 Page 1 of 1 CATEGORY: 7272 -- SMOKE DETECTOR -SYSTEM TYPE -PHOTOELECTRIC LISTEE: FIRE -LITE ALARMS INC.One Fire -Lite Place, Northford, CT 06410-1653 by the applicant. rJSFM Fire Engineering staff Contact: Lisa Brant (203) 484-6105 Fax (203) 484-7309 Email: lisa.brant@honeywell.com DESIGN: Models'SD365;'SD365R and SD365T analog addressable, photoelectric smoke detectors for open area and duct installations. Model SD365T has a complementary heat detector. All item listed. This listing should not be .used to models are similarl except for population/depopulation of components on the Printed Wiring " Board for the intended features. All above models may be followed by two digit Suffix Refer to listee's data sheet, installation instructions indicating the color of the detector enclosure: no suffix for white, -IV for ivory, -BL for black. Refer to listee's Installation and Maintenance. Instruction for additional detailed product description and operational considerations. RATING: 24 VDC. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as photoelectric smoke detectors. Detectors are for use with separately listed System Sensor base Models *6501, *B210LP (CSFM Listing 7300-1653:0109), *B350LP (CSFM Listing 7300-0075:0192), B200S and B200SR (CSFM Listing 7300-1653:0213), B20OS-LF and B200SR-LF (CSFM Listing 7300-1653:0238), B300-6 and B300 -6 -IS bases (CSFM Listing 7300-1653:0109), System Sensor duct detector housings Models DNR and DNRW (CSFM listing 3240-1653:0209), Fire -Lite duct detector housing Model D355PL (CSFM listing 3240-0075:0221) and separately listed compatible fire alarm control units. Refer to manufacturer's Installation Manual for details. *All models comply with the applicable requirements in ANSI/UL 268, Smoke Detectors for Fire Alarm Systems, 7th Edition, January 11, 2016. NOTE: The photoelectric type detectors are generally more effective at detecting slow, smoldering fires that smolder for hours before bursting into flame. Sources of these fire may include cigarettes burning in the couched or bedding. The ionization type detectors are generally more effective at detecting fast, flaming fires that consume combustible materials rapidly and spread quickly. Sources of these fires include paper burning in a waste container or a grease fire in the kitchen. XLF: 7272-0028:0503 *Revision 12-17-19 VWW Date Issued` July 01, 2021 Listing Expires June 30, 2022 Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division This listing is based upon technical data submitted by the applicant. rJSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not anendorsement or recommendation of the item listed. This listing should not be .used to verify correct " operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued` July 01, 2021 Listing Expires June 30, 2022 Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division DF -61011:C H365 Series,OFIMLITaMarms Addressable Heat Detectors by Honeywell • The Fire -Lite® Alarms H365(A), H365R(A), and H365HT(A) addressable plug-in thermal detectors are designed for both perfor-.. mance and aesthetics and are a direct replacement for. the H355" Series. A new modern, sleek, contemporary design and advanced thermal technologies make the H365(A) Series ideal for both system ' r -�� NOR operation and building design.' Exclusively for use with Fire-Lite's addressable fire alarm control panels, the H365(A) Series point ID capability allows each detectors address to be set with rotary, decimal address switches, providing exact detector location for emergency personnel to quickly locate a.� fire during its early stages, potentially saving precious rescue "me� while also reducing property damage. Two LEDs on each as light to provide a local, visible sensor indication. The H365(A) Series includes fined temperature, rate -of -rise and *i v high heat fixed temperature detectors that provideeffective, intelli- gent property protection for a variety of applications. Detectors are available for both LiteSpeedm and CLIP applications as designated. ,,, Features SLC LOOP: • Two -wire SLC loop connection • Unit uses base for wiring ADDRESSING: • Addressable by device • Rotary, decimal addressing (Refer to the Fire -Lite panel manuals for device capacity.) ARCHITECTURE: • Designed to meet UL 268 7th Edition • Sleek, low -profile, stylish design • State-of-the-art thermistor technology for fast response - • Integral communications and built-in device -type identification • Built-in tamper resistant feature • Built-in functional test switch activated by external magnet OPERATION: • Fixed temperature model (H365(A)) factory preset to 135°F (57-C) • Rate -of -rise model (H365R(A)), 157 (8.3°C) per minute, • High-temperature model (H365HT(A))factory preset to 190°F (88°C) • 360° -field viewing angle of the two visual alarm indicators, LEDs blink red in Normal condition and turn on steady red in Alarm • LEDs blink every time the unit is polled MECHANICALS: • Sealed against back pressure • SEMS screws for wiring of the separate base • Designed for direct -surface or electrical -box mounting • Plugs into separate base for ease of installation and maintenance • Separate base allows interchange of photoelectric, ionization and thermal sensors OTHER SYSTEM FEATURES: • Remote test feature from the panel • Walk test with address display OPTIONS: • Remote LED output connection to optional IRA10OZ remote LED annunciator Installation H365 Series plug-in intelligent thermal detectors use a detachable base to simplify installation, service and maintenance. Installation instructions are shipped with each detector. Mount detector base (all base types) on an electrical backbox which is at least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes, see DF -60059. NOTE., Because of the inherent supervision provided by the SLC loop, end -of -line resistors are not required. Airing "T -taps" or branches are permitted for Style 4 (Class 'B') wiring only. When using relay or sounder bases, consult the 1300(A) installation sheet 156-3626 for device limitations between isolator modules and iso- lator bases. Applications Use thermal detectors for protection of property. For further informa- tion, refer to 156-6525, Applications Manual for System Smoke Detectors, which provides detailed information on detector spacing, - placement, zoning, wiring, and special applications. Construction These detectors are constructed of fire-resistant plastic. The H365 Series plug-in intelligent thermal detectors are designed to commer- cial standards and offer an attractive appearance. Operation Each H365 Series detector uses one of the panel's addresses (total limit is panel dependent) on the Fire•LiteJCI Signaling Line Circuit (SLC). It responds to regular polls from the control panel and reports its type and the status. If it receives a test command from the panel (or a local magnet test), it stimulates its electronics and reports an alarm. It blinks its LEDs when polled and turns the LEDs on when commanded by the panel. The H365 Series offers features and per- formance that represent the latest in thermal detector technology. • Low standby current DF -61011:C • 11118/2019— Page 1 of 3 Product Line Information NOTE: "-IV" suffix indicates CLIP and LiteSpeed device. NOTE: "A" suffix indicates Canadian version. H365: White, low -profile intelligent 135°F fixed thermal sensor, Lite - Speed only H365A: Same as H365 but with ULC listing H365 -IV: Ivory, low -profile intelligent 1357 fixed thermal sensor, LiteSpeed and CLIP H365A-IV: Same as H365 -IV but with ULC listing H365R: White, low -profile- intelligent rate -of -rise thermal sensor, LiteSpeed only H365RA: Same as H365R but with ULC listing. H365R-IV: Ivory, low -profile intelligent rate -of -rise fixed thermal sen- sor, LiteSpeed and CLIP H365RA-IV: Same as H365R-IV but with ULC listing H365HT: White, low -profile intelligent 190°F fixed thermal sensor, LiteSpeed only H365HTA: Same as H365H but with ULC listing H365HT-IV: Ivory, low -profile intelligent 190°F thermal sensor, Lite - Speed and CLIP H365HTA-IV Same as H365H-IV but with ULC listing INTELLIGENT BASES NOTE: For details on intelligent bases, see DF -60059. 8300-6: White, 6" base, standard flanged low -profile mounting base (CSFM: 7300-1653:0109) - B300.64V: Ivory,6". base, standard flanged low -profile mounting base (CSFM: 7300-1653:0109) B300A-6: Same as B300-6, ULC listed B30OA-6-IV: Ivory, 6" standard flanged low -profile mounting base, ULC listed 8300.6 -BP: Bulk pack of B300-6, package contains 10 B200SA-IV: Same as B200S-IV, ULC listing B200SCOA-WH: White, Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with CO Series detector applications B200SCOA-IV: Ivory Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with CO Series detector applications, ULC listing - B200S-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. (CSFM: 7300-1653:0238) B20OS-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. (CSFM: 7300-1653:0238) B200SR-WH: White, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended for retrofit applications. (CSFM: 7300-1653:0213) B200SR-IV: Ivory, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended for, retrofit applications. (CSFM: 7300-1653:0213) B200SRA-WH:.Same as B200SR-WH with, ULC listing B200SRA-IV: Same as B200SR-IV in Ivory color, ULC listing B200SR-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a. square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applica- -tions. (CSFM: 7300-1653:0238) B200SR-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applica- tions. (CSFM: 7300-1653:0238) MOUNTING KITS AND ACCESSORIES TR300: White, replacement flange for B210LP(A) base B501 -WHITE: White, 4" standard European flangeless mounting TR300-IV: Ivory, replacement flange for B210LP(A) base base. UL/ULC listed (CSFM: 7300-1653:0109) B501 -BL: Black, 4" standard European flangeless mounting base. RA100Z(A): Remote LED annunciator. 3-32 VDC. Mounts to a U.S. single -gang electrical box. For use with B501(A) and B300 -6(A). UL/ULC listed (CSFM: 7300-1653:0109) 65014V: Ivory color, 4" standard European flangeless mounting fNO2.04A0: Test magnet base. UL/ULC listed (CSFM: 7300-1653:0109) M02 -09A0: Test magnet with telescoping handle B501 -WHITE -BP: Bulk pack of 8501 -WHITE contains 10 CK300: Color Kit (includes cover and trim ring), white, 10 -pack B224RB-WH: White, relay base (CSFM: 7300-1653:0216) CK300-IV: Color Kit (includes cover and trim ring), ivory, 10 -pack B224RB4V: Ivory; relay base (CSFM: 7300-1653:0216) CK300-BL: Color Kit (includes cover and trim ring), black, 10 -pack B224RBA-WH: White, relay base, ULC listing B224RBA-IV: Ivory, relay base, ULC listing B224B1-WH: White, isolator detector base (CSFM: 7300.1653:0216) B224BI-IV: Ivory isolator detector base (CSFM: 7300-1653:0216) B224BIA-WH: White, isolator detector base, ULC listing B224BIA-IV: Ivory isolator detector base, ULC listing B20OS-WH: White, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone. Uses FlashScan protocol. (CSFM: 7300-1653:0213) B20OS-IV: Ivory, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone. Uses FlashScan protocol. (CSFM., 7300-1653:0213) B200SA-WH: Same as B200S-WH, ULC listing Page 2 o 3—DF-61011:C• 11/18/2019 SYSTEM SPECIFICATIONS Size: 2.0" (5.3 cm) high; base determines diameter - 6300-6: 6.1" (15.6 cm) diameter -.6501: 4" (10.2 cm) diameter For a complete list of detector bases see DF -60983 Shipping weight: 3.4 oz. (95 g) Operating temperature range: • H365, H365R Series: -4°F to 1007 (-20"C to 38°C) • H365H Series: -4°F to 150"F (-20"C to 66"C) Detector spacing: UL approved for 50 ft. (15.24 m) center -to -cen- ter, FM approved for 25 x 25 ft. (7.62 z 7.62 m). spacing Relative humidity: l0%-93%non-condensing Thermal ratings: fixed -temperature set point 135°F (57°C), rate -of - rise detection 15`F (8.3°C) per minute, high temperature heat 190°F (88"C) Mounting: B300 -6(A) flanged base, included See "Product Line Information: Intelligent Bases," if using a dif- ferent base. ELECTRICAL SPECIFICATIONS Voltage range: 15 - 32 volts DC peak Standby current (max. avg.): 200pA@ 24 VDC (one communica- tion every 5 seconds with LED enabled) Max current: 4.5. mA @ 24 VDC ("ON") Listings and Approvals Listings and approvals below apply to the H365 Series detectors. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest list- ing status. • UL/ULC Listing: S2517 • FM Approved • CSFM:7272-0075:0501 LiteSpeed' is a trademark and Fire -Lite® Alarms is a registered trademark of Honeywell International Inc. ©2019 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not Intended to be used for installation purposes. V V\ O 901 We We try to keep our product information up-to-date and accurate. cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. UiSIMBINI A MMIFACIUME QUALITY SYSTEMS For more information, contact Fire -Lite Alarms. Phone: (800) 627-3473, FAX:(877) 699-4105. Country of Origin: Mexico www.firelite.com Page 3 of 3 — DF -61011:13 • 11/18/2019 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE t§ LISTING No. 7270-007510501 Page 1 of 1 CATEGORY: 7270 -- HEAT DETECTOR LISTEE: FIRE -LITE ALARMS INC.One Fire -Lite Place, Northford, CT 06410-1653 has reviewed Contact: Lisa Brant (203) 484-6105 Fax (203) 484-7309 the test results and/or other data but does not Email: lisa.brant@honeywell.com DESIGN: Models 1-1366; H365HT (fixed temperature) and H365R (fixed temperature with Rate -of -Rise) an endorsement or recommendation of the electronic heat detectors. Suffix -IV for ivory color and -BL for black color. Refer to listee's verify correct data sheet for additional detailed product description and operational considerations. RATING: Model H365 (fixed temperature): 1357. and/or other Model H365HT (fixed temperature): 190°F. Motley H365R (fixed temperature with rate of rise):135°F. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical ratings, and UL label. APPROVAL: Listed as heat detectors for use with Notifier base B71OLP (CSFM#7300-0028:173); System Sensor bases 8510, B210LP, B300-6, 8300-6-1S (CSFM#7300-1653:0109); 622461, B224RB (CSFM#7300-1653:0126); B200S, B200SR (CSFM#7300-1653:0213); B200S-LF, B200SR-LF (CSFM#7300-1653:238); and separately listed compatible fire alarm control units. Refer to listee's Installation Instructions Manual for details. XLF: 7270-0028:0502 02-01-18 gt Date Issued: July 01, 2021 Listing Expires June 30, 2022 Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division This listing is based upon. technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2021 Listing Expires June 30, 2022 Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division BG-12LX" Addressable Manual Pull Station The Fire -Lite BG-12LX is a state-of-the-art, dual -action (i.e., requires two motions to activate the station) pull station that includes an addressable interface (mounted inside) for Fire-Lite's addressable fire alarm control panels (FACPs) Because the BG-12LX is addressable, the control panel can display the exact location of the activated manual station. This leads fire personnel quickly to the location of the alarm. Features • Maintenance personnel can open station for inspection and address setting without causing an alarm condition. • Built-in bicolor LED, which is visible through the handle of the station, flashes in normal operation and latches steady red when in alarm. _ • Handle latches in down position and the word "ACTIVATED" appears to clearly indicate the station has been operated. • Captive screw terminals wire -ready for easy connection to SLC loop (accepts up to 12 AWG/3.25 mm2 wire). • Can be surface mounted (with SB -10 or SB -1/0) or semi - flush mounted. Semi -flush mount to a standard single - gang, double -gang,. or 4" (10.16 cm) square electrical box. • Smooth dual -action design. • Meets ADAAG controls and operating mechanisms guide- lines (Section 4.1.3[13]); meets ADA requirement for 5 Ib. maximum activation force. • Highly visible. • Attractive shape and textured finish. • Key reset. • Includes Braille text on station handle. • Optional trim ring (BG12TR). • Meets UL 38, Standard for Manually Actuated Signaling Boxes. Construction Shell, door, and handle are molded of durable polycarbonate - - —- materialwithatexturedfinish. -- - -.- -- -- Specifications • Shipping Weight: 9.6 oz. (272.15 g) • Normal operating voltage: 24 VDC. • Maximum SLC loop voltage: 28.0 VDC. • Maximum SLC standby current: 375 pA. • Maximum SLC alarm current: 5 mA. • Temperature Range: 32°F to 120°F (0°C to 49°C) • Relative Humidity: 10% to 93%(noncondensing) • For use indoors In a dry location Installation The 3G-12LX will mount semi -flush into a single -gang, double - gang, or standard 4" (10.16 cm) square electrical outlet box, or will surface mount to the model SB -10 or SB -1/0 surface back - box. If the BG-12LX is being semi -flush mounted, then the optional trim ring (Bi12TR) may be used. The BG12TR is DF -52013:D • E-100 `a Fire -LM ALWMS by Honeywell Addressable Devices usually needed for semi -flush mounting with 4" (10.16 cm) or double -gang boxes (not with single -gang boxes). Operation Pushing in, then pulling down on the handle causes it. to latch in the down/activated position. Once latched, the word "ACTI- VATED" (in bright yellow) appears at the top of the handle, while a portion of the handle protrudes from the bottom of the station. To reset the station, simply unlock the station with the key and pull the door open. This action resets the handle; clos- ing the door automatically resets the switch. Each. .manual station, on command from .the _control panel, .. sends data to the panel representing the state of the manual switch. Two rotary decimal switches allow address settings (1 — 159 with Breakaway Tab removed for MS -9600 Series, 1 — 99 and MS-92000DLS, 1 —50 for MS-9050UD). Architectural/Engineering Specifications Manual Fire Alarm Stations shall be non -coded, with a key - operated reset lock in order that they may be tested, and so designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key. An operated sta- tion shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of.. red -colored polycarbonate material with clearly visible operat- ing instructions provided on the cover. The word FIRE shall appear on the front of the stations in white letters, 1.00 inches (2.54 cm) or larger. Stations shall be suitable for surface mounting on matching backbox SB -10 or SB -1/0; or semi -flush mounting on a standard single -gang, double -gang, or 4"(10.16 cm) square electrical .box, and shall be installed DF -520130.4/13/2012 — Page 1 of 2 within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations shall be Underwriters Laboratories listed. Manual stations shall connect with two wires to one of the con- trol panel SLC loops. The manual station shall, on command from the control panel, send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. Product Line Information BG-12LX: Dual -action addressable pull station. Includes key locking feature. (Listed for Canadian and non -Canadian appli- cations.) SB -10: Surface backbox; metal. SB -U0: Surface backbox; plastic. BG12TR: Optional trim ring. 17003: Keys, set of two. Agency Listings and Approvals In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro- cess. Consult factory for latest listing status. • UUULC Listed: S711 (listed for Canadian and non -Cana- dian applications). • MEA: 67-02-E. •. CSFM:7150-0075:0184. • FM Approved. - Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6,632,108. FireLite@ Alarms® is a registered trademark of Honeywell International Inc. 02012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. V O 901 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. _ We cannot cover all specific applications or anticipate all requirements. 01151113156 S INNIFAC13RM6 '- All specifications are subject to change without notice. - QUALITY SYSTEMS - Made in the U.S. A. For more information, contact Fire -Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Page 2 of 2 — DF -52013:0 •4/13/2012 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 0 LISTING No, 7150-0075:0184 Page 1 oft CATEGORY: 7150 —FIRE ALARM PULL BOXES LISTEE: FIRE -LITE ALARMS INC.One Fire -Lite Place, Northford, CT 06410-1653 by the applicant. CSFM Fire Engineering staff Contact: Lisa Brant (203) 484-6105 Fax (203) 484-7309 `c Email: lisa.brant@honeywell.com DESIGN: Models BG -12, BG -12S, BG-12NC, BG -12W, BG-12LW, BG-12WP, BG-12LWP, BG -12L, BG-12LX'BG-12LA, BG-12PS, BG-12LSP, BG-12SP, BG-12LR, BG-12LRA, BG-12LAO, item listed. This listing should not be used to BG-12LAOB, BG -12 -LO, BG-12LO8, BG-12LPS, BG-12LPSP, BG-12SL, UT-PS1 and ` UT-PS2 fire alarm pull boxes. The BG -12 series is a dual action pull station that has Refer to listee's data sheet, installation instructions normally open switch contacts. Refer to listee's data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number and UL label. APPROVAL: Listed as fire alarm boxes for use with separately listed compatible fire alarm control units. Models BG-12WP, BG -12W, BG-12LW and BG-12LWP are intended for outdoor use when installed with Model WPA 0 back box. Models'BG-LAOB and BG-112LOB are intended for outdoor use when installed with Model WBB or WP -10 back box. * These manual pull boxes meet the requirements of UL Standard 38, 1999 Edition and California amendments. XLF: 7150-0028:0199 *Updated 08-17-09 fm Date Issued: July 01, 2021 Listing Expires June 30, 2022 Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed `c the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct ` operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2021 Listing Expires June 30, 2022 Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division SYSTEM SENSOR Indoor 'Selectable- OutputStrobes and Horn Strobes for Coiling Applications System Sensor L -Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. Features • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • Automatic selection of 12- or 24 -volt operation at 15 and 30 candela • Field -selectable candela settings on ceiling units: 15, 30, 75, 95, 115, 150, and 177 • Horn rated at 38+ dBA at 16 volts •. Rotary switch for horn tone and two volume selections • Universal mounting plate for ceiling units • Mounting plate shorting spring feature checks wiring continuity before device installation • Electrically Compatible with legacy SpectrAlert and SpectrAlert Advance devices • Compatible with MDL3 sync module • Listed for ceiling mounting only Agency Listings SIGNALING APPPWEp LISTED 55512 FM apprw a mpl 1125-16 ,MA 59011 for ALEFT mW.1. 7135-1653:0.503 305]383 The System Sensor L•Series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry with lower current draws and modern aesthetics. With white and red plastic housings, wall and ceiling mounting options, System Sensor L -Series can meet virtually any application requirement. The entire L -Series product line of ceiling -mount strobes and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature a plug-in design with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time- consuming ground faults. To further simplify installation, the L -Series utilizes a universal mounting plate so installers can mount them to a wide array of back boxes. With an onboard shorting spring, installers can test wiring continuity before the device is installed.. Installers can also easily adapt devices to a suit a wide range of application requirements using field -selectable candela settings, automatic selection of 12- or 24 -volt operation, and a rotary switch for horn tones with two volume selections. L -Series Specifications General L -Series ceiling -mount strobes and horn strobes shall mount to a standard 4 x 4 x 11/2 -inch back box, 4 -inch octagon back box, or double - gang back box. Two -wire products shall also mount to a single -gang 2 x 4 x 178 -inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L -Series products, when used with the Sync•Circuit' Module accessory, shall be powered from a non -coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync -Circuit Module, 12 -volt -rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24 -volt -rated notification appliance circuit outputs shall operate. between 16.5 and 33 volts. Indoor L -Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full -wave rectified unfiltered power supply. Ceiling strobes and horn strobes shall have field -selectable candela settings including 15, 30, 75, 95, 115, 150, and 177. Strobe The strobe shall be a System Sensor L -Series Model listed to UL 1971 and shall be approved for fire protective service. The strobe. shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L -Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tubeand associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three pattern and a non -temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non -coded power supply. Synchronization Module The module shall be a System Sensor Sync -Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize L -Series strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns - on horn strobe models over a single pair of wires. The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8 -inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple. zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. PhysicaltElectriCal Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) 10 to 93% Strobe Flash Rate - 1 flash per second Nominal VoltageRegulated 12.VDC or regulated 24 DC/FWR' Operating Voltage Range' 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range (MDL3) 8.5 to 17.5V (12 V nominal) or 16.5 to 33 V (24V nominal) Input Terminal Wire Gauge 12 to 18 AWG Ceiling -Mount Dimensions (including lens) 6.8" diameter x 2.5" high (173 mm diameter x 64 mm high) Ceiling -Mount Surface Mount Back Box Skirt Dimensions 6.9° diameter x 3.4" high (175 mm diameter x 86 mm high) Notes: 1, Full Wave Rectified (FWR) voltage is a non-regulated, time -varying power source that is used on some power supply and panel outputs, 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 30 cd. AVDS86B66 UL Current Draw Data 8-17.5 Volts 16-33 Volts Candela DC DC FWR 15 87 - 179 - 41 223 - 60 Temporal Low - 78 101 - 172 30 153 - 262 Non -Temporal High 63 135 179 86 223 254 - 286 Non-Temportal Low 78 75 N/A - 199 111 262 3.1 K Temporal High 142 135 179. 200 225 255 95 N/A 79 :. - ,101. .134 - 171 - 196 164 260 --- _ 115 N/A 156 191 .. -_ - ....... 150 N/A 189 228- -- . 177 N/A 226 264 e , 8-125 Volts • 16-33 Volts DC Input 15cd 30cd 15cd 30cd 75cd 95cd 115cd 150cd 177cd Temporal High 103 167 71 90 143 165 187 217 254 Temporal Low 96 165. 54 71 137 161 185 211 249 - Non -Temporal High - - 106 173 - 71 90 141 165 187 230 273 - Non-Temportal Low 95 166 - 54 - 71 124 161 170 '. ..216 258 3.1 K Temporal High 111 164 69 94 . 147 - 163 - 184 229 257 3.1 K Temporal Low 103 163 54 - 88 - 143 155 185 212 252 3AK Non -Temporal High 111 172 69 94 144 164 202-: 229 271 - 3.1K Non -Temporal Low 103 169 54 88 131 155 187 -. 217 259 16-33Volts - '- FWR Input. - - 15cd 30th - 75ed 95cd - 115cd - - 150cd 177cd - - - Temporal High - 107 135 179 - 198 223 254 286 - Temporal Low - 78 101 151 172 199 229 - 262 Non -Temporal High 107 135 179 198 - - 223 254 - 286 Non-Temportal Low 78 101 151 172 199 229 262 3.1 K Temporal High 108 135 179. 200 225 255 289 3.1 K Temporal Low 79 :. - ,101. "150 - 171 - 196 229 260 3.1K Non -Temporal High 108 - 135 3.1 K Non -Temporal Low 79 101 Horn Strobe Tones and Sound o 179 200 225 255 289 150 171 Data .... .. -.... Volts 229 260 16-33 Volts - DC FWR _ 1. .Temporal __ - _ High - _ -. 84. _. - `89 89 - - 2 Temporal - Low -75 - -83 83 _ 3 Non -Temporal High 85 .'90 90 - -_ 4 Non -Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non -Temporal High 84 89 89 8 3.1 KHz Non -Temporal Low 77 83 83 - AVDS868W L -Series Di vj 6.r 2.47 1.37 Gelling -Mount Horn Strobes ! Ceiling Surface Mount Back Box 2.50 r1 -Ceiling Mount Horn Strobes with Ceiling Surface Mount Back Box - - L -Series Ordering Information • Ceiling Horn Strobes - Ceiling Strobes - PC2RL 2 -Wire, Horn Strobe, Red SCRL Strobe, Red - PC2WL 2-Wire,Horn Strobe, White - SCWL Strobe, White . _ SCWL-CLR-ALERT Strobe; White, ALERT Accessories TRC -2 Universal Ceiling Trim Ring Red. TRC -2W Universal Ceiling Trim Ring White SBBCRL Ceiling Surface Mount Back Box, Red SBBCWL Ceiling Surface Mount Back Box, White STEM @10,7 Sotem Senso,. SENSORO hon Ohio SE Ne • St. Charles, IL 60174 Ffor Mn Peorioe= pform0t. onenoewun«nnoace m fthimd ensocaom Phone, B00-SENSOR2 •Fax: 630-377-6495 for concni protivm mr«ma�mn.m_aamy me iemeiva,e�en nnmsewe enee1. nvosesam • oam Selectable Output Chimes and Chime/ Strobes System Sensor L -Series selectable -output chimes and chime/strobes are rich with features guaranteed to cut installation times and maximize profits with lower curre draw and modern aesthetics. Features • Updated modern aesthetics • Plug-in design with minimal intrusion into the back box • Mounting plate shorting spring feature checks wiring continuity before device installation • Captive mounting screw • Tamper-resistant construction • Field -selectable candela settings: —Wall: 15, 30, 75, 95, 110, 135, 185 — Ceiling: 15, 30, 75, 95, 115, 150, 177 • Automatic selection of 12- or 24 -volt operation at 15 and 30 candela • Rotary switch for tone and volume selections • Five selectable tones with high and low volume settings • Electrically compatible with legacy SpectrAlert and SpectrAlert Advance devices • Wall models listed for wall mounting only, ceiling models listed for ceiling mounting only Agency Listings SIGNALLING &FM FM ®' LISTED D 84011 3057383,3057072 713598530503 The System Sensor L•Series product line of wall andceiling- mount chimes and chime strobes include a variety of features that increase their application versatility while simplifying the installation, With white and red plastic housings, System Sensor L -Series can meet virtually any application requirement. Selectable -output chimes and chime/strobes are private mode notification appliances used to alert trained personnel to investigate possible emergency situations and to take appropriate action. Security guard and nurse workstations are ideal locations for chime products. All devices feature plug-in design with minimal intrusion into the back box, making the installation fast and foolproof while virtually eliminating costly and time-consuming ground faults. Installers can easily adapt devices to a wide range of application requirements using field -selectable candela settings, automatic selection of 12 -or -24 volt operation, and a rotary switch for chime tones and two volume selections. L -Series Specifications General System Sensor L -Series chimes and chime strobes shall mount to a standard 4 x 4 x 11/2 -inch back box, 4 -inch octagon back box, single - gang 2 x 4 x 11/8 -inch back box, or double -gang back box. A universal mounting plate shall be used for mounting products, The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, System Sensor L -Series products, when used with the Sync -Circuit Module accessory, shall be powered from a non -coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync -Circuit Module, 12 -volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24 -volt rated notification appliance circuit. outputs shall operate between 16.5 and 33 volts. Indoor L -Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC, or full -wave rectified, unfiltered power supply. Chime strobesshall have field -selectable candela settings of 15, 30, 75, 95, 110, 135, and 185 for wall units and 15, 30, 75, 95, 115, 150, and 177 for ceiling units. Chime Strobe Combination The chime strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1638 and UL 464. The chime strobe shall comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The chime shall have two audibility options and an option to switch between temporal three pattern, non-temporal(continuous) pattern, 1 second chime pattern, 1/4 second chime pattern, 5 second whoop chime pattern. These options are set by a multiple position switch. Synchronization Module The module shall be a System Sensor Sync -Circuit listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and all available chime tones. Also, while operating the strobes, the module shall silence the chimes on chime/strobe models over asingle pair of wires. The module shall mount to a 4 11/16 x 4 11/1e x 2 1/8 -inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Standard Operating Temperature 32°F to 120°F (0°C to 49°C) - Humidity Range. 10 to 93% non -condensing Strobe Flash Rate 1 flash per second 12VDC or 8 to 17 Operating Voltage Range with MLD3 8.5 to 17.5V (12V nominal) or 16.5 to 33V (24V nominal) Input terminal wire gauge 12 to 18 AWG Chime strobe dimensions (including lens) 5.6 in L x 4.7 in W x 1.91 in D (143 mm L x 119 mm W x 49 mm D) Chime dimensions - - 5.6 in L x 4.7 in W x 1.25 in D (143 mm L x 119 mm W x 32 mm D) Ceiling Chime strobe dimensions (including lens) 6.8" Dia. x 2.47' D It 73.5mm Dia. x 62.7mm D) SBBRL (red wall surface mount back box) 5.6 in L x 4.7 in W x 4.3 in D (142 mm L x 119 mm W x 109 mm D) SBBWL (white wall surface mount back box) 5.6 in L x 4.7 in W x 4.3 in D (142 mm L x 119 mm W x 109 mm D) SBBCRL (red ceiling surface mount back box) 6.9" Dia. x 2.5 D (175.8mm Dia. x 63.5mm) - SBBCWL (white ceiling surface mount back box) 6.9" Dia. x 2.5 D 1 Dia. x 63.5mm) 1. Full Wave Rectified (FWR) voltage is a non -filtered, time varying power source that is used on some power supply and panel outputs. 2. CHS products will operate at 12 V nominal only for 15 and 30 cd. - UL Current Draw Data r. fill Volts 1643 Volts Sound Pattern dB DC DC FWR 1 Second Chime High 5 8 9 1 Second Chime Low 5 8 9 '/4 Second Chime High 6 10 10 Y4 Second Chime. Low 5 9 9 Temporal Chime High 7 10 10 Temporal Chime Low 6 9 9 5 Second Whoop High 12 15 16 5 Second Whoop Low 7 10 11 Coded High 12 15 16 "This data represents coding. at 3 chimes per second. Actual current draw will vary depending upon coding selected DC Input 8-17.5 Volts 15 30 16-33 Volts 15 30 75 95 110 135 185 1 Second Chime 90 154 51 71 115 136 161 202 238 1 Second Chime 89 154 50 70 116 136 154 199 242 '/4 Second Chime 90 154 52 72 117 137 168 201 242 Y4 Second Chime 89 153 49 70 115 136 165 199 241 Temporal Chime 88 153 49 69 112 137 168 201 246 Temporal Chime - 88 152 47 68 111 136 167. 196 241 5 Second Whoop 91 154 52 70 113 132 176 206 243 5 Second Whoop 87 149 46 66 108 130 170 202 240 FWR Input 16-33 Volts 15 30 75 Low 95 110 High 135 185 1 Second Chime 70 90 160 5 Second Whoop 176 197 64 233 275 1 Second Chime 67 88 158 57 175 191 232 271 '/4 Second Chime 69 93 159 175 198 233 272 '/4 Second Chime 68 93 154 169 196 232 270 Temporal Chime 65 90 145 170 189 228 283 Temporal Chime 64 89 142 170 188 219 282 5 Second Whoop 70 93 145 168 187 223 278 5 Second Whoop 62 84 137 159 180 216 272 DC Input 8-17.5 Volts 15 30 160 16-33 Volts 15 30 75 95 115 150 .177 1 Second Chime - 95.5 165 5 Second Whoop 47 69 117 137 165 202 238 1 Second Chime 93 162 47 68 116 137 165 200 238 '/4 Second Chime 94 161 48 70 117 138 166 202 237 Y4 Second Chime 93 157 48 69 116 137 164 199 236 Temporal Chime 93 163 48 69.5 116 138 165 199 238 Temporal Chime 92 160 47 68.5 116 136 164 198 237 5 Second Whoop 98 169 54 77 124 146 173 206 245 5 Second Whoop, 95 166 49 71 117 144 168 202 239 High 16-33 Volts 1/4 Second Chime Low 61 61 61 6 - Temporal Chime Low 5 FWR Input - 15 30 75 95 115 150 177 1 Second Chime - 63 90 147 - 169 184 212 245 1 Second Chime 63 88 147 169 183 212 244 1/4 Second Chime 65 90 149 170 184 213 246 '/4 Second Chime 64 89 148 168 184 213 244 iemporai mime b4 69 148 169 184 212 245 Temporal Chime 63 -88 147 - 169 183 212 245 5 Second Whoop 75 100 155 178 193 221 255 5 Second Whoop 68 91 148 170 186 217 248 Tone Selection Chime tone selection is accomplished by using the rotary switch on the back of the product. The current draw and sound measurements for various chime tone settings are listed below. e Setting Repetition Rate dB Level Switch 8-175 Volts 16-33 Volts 1 1 Second Chime High Position Sound Pattern dB DC DC FWR 2 1 Second Chime Low 1 1 Second Chime High 61 62 62 3 '/4 Second Chime High 2 1 Second Chime Low 56 55 55 4 '/4 Second Chime Low - 3- '/4 Second Chime High 67 70 70 5 Temporal Chime High 4 1/4 Second Chime Low 61 61 61 6 - Temporal Chime Low 5 Temporal Chime High 64 66 66 7 5 Second Whoop High 6 Temporal Chime Low 59 60 60 8 - 5 Second Whoop Low 7 5 Second Whoop High 76 78 78 9 Coded— High 8 5 Second Whoop Low 62 64 64 `"For chime only. 9 Coded— High 57 51 57 L -Series Dimensions Wall Chime 06.83 Wall Chime/Strobe Ceiling Chime/Strobe Wall Surface Mount Back Box 06.92 � 2.60 o O O � O O O o O O t� O Ceiling Surface Mount Back Box Ceiling Mount Chiioe/Strobe with Ceiling Surface Mount Back Box Wall Mount Chime/Strobe with Wall Surface Mount Back Box L -Series Ordering Information _ SBBRL Surface Mount Back Box, Wall, Red SBBWL Surface Mount Back Box, Wall, White SBBCRL Surface Mount Back Box, Ceiling, Red "STEM 3825 Ohio Avenue • St. Charles, IL 60174 P2017sv��em sen:o,. Phone: 800-SENSOR2 • Fax: 630-377-6495 arod�otsps ihcauons wbji Mch nge wthow nonce. visit sysiemsensoccom SENSORa y , �maon SW90i,hae�=, e,=,nnn„h,edaaehea,. wwws stemsensor.com nyoseeso, •oa;v CHRL Chime, Wall, Red CHWL Chime, Wall, White CHSRL Chime Strobe, Wall, Red CHSWL Chime Strobe, Wall, White CHSCRL Chime Strobe, Ceiling, Red CHSCWL Chime Strobe, Ceiling, White _ SBBRL Surface Mount Back Box, Wall, Red SBBWL Surface Mount Back Box, Wall, White SBBCRL Surface Mount Back Box, Ceiling, Red "STEM 3825 Ohio Avenue • St. Charles, IL 60174 P2017sv��em sen:o,. Phone: 800-SENSOR2 • Fax: 630-377-6495 arod�otsps ihcauons wbji Mch nge wthow nonce. visit sysiemsensoccom SENSORa y , �maon SW90i,hae�=, e,=,nnn„h,edaaehea,. wwws stemsensor.com nyoseeso, •oa;v CALIFORNIA DEPARTMENT OF FORESTRY $ FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE (§ LISTING No. 7125-1653:0504 Page 1 of 2 CATEGORY: 7125 -- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED LISTEE: System Sensor, Unincorporated Div of Honeywell Int'I Inc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Lisa Brant (203) 484-6105 Fax (203) 484-7309 Email:lisa.brant@honeywell.com DESIGN: System Sensor Indoor 2 -wire Models: SRL, SWL, SGRL, SGWL, SRL-P SWL-P, SRL-SP, SWL-CLR-ALERT and SWL-ALERT Wall Strobes; SCRL, SCWL and SCWL-CLR-ALERT Ceiling Strobes. Wall Bezel Parts: BZR-F, BZR-AL, BZR-AG, BZR-EV, BZR-P, BZR-SP, BZR-PG, BZW -F, BZW -AL, BZW -AG, BZW -EV, BZW -P, BZW -SP, BZW -PG, BZGR-F, BZGR-AL, BZGR-AG; BZGR-EV, BZGR-P, BZGR-SP, BZGR-PG, BZGW-F, BZGW-AL, BZGW-AG, BZGW-EV, BZGW-P, BZGW-SP and BZGW-PG, Ceiling Bez&P—arts: - - - - - =- BZRC-F, BZRC-AL, BZRC-AG, BZRC-EV, BZRC-P, BZRC-SP, BZRC-PG, BZWC-F, BZWC-AL, BZWC-AG, BZWC-EV, BZWC-P, BZWC-SP and BZWC-PG. Color Lens: LENS -A2, LENS -B2, LENS -G2, LENS -R2, LENS-AC2, LENS-BC2, LENS-GC2 and LENS -RC2. WallTrim Rings: TR2 and TR2W CeilingTrim Rings: TRC2 and TRC2W. Wall Surface Mounted Back Boxes: SBBRL, SBBGRL, SBBWL and SBBGWL, Ceiling Surface Mounted Back Boxes: SBBCRL and SBBCWL Refer to listee's data sheet for detailed product description and operational considerations. `Rev 04-04-19 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims.. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installationinstructions and/or other Date Issued: ,July 01, 2021 Listing Expires June 30, 2022 Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division Listing No. 7125-1653:0504 Page 2 of 2 RATING: Regulated 12 VDC setting: 8-17.5 VDC Regulated 24 VDC/fwr setting: 16-33 VDC INSTALLATION: In accordance with listee's printed installation instructions, NFPA 72, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as two wire strobe units used for synchronous application when used with separately listed compatible fire alarm control units. Suitable for indoor use, vertical wall or horizontal ceiling mounted. *Listed with software code, S05-0048-001 for low temperature compensation. Authority having jurisdiction should be consulted prior to installation. Refer to listee's Installation Instruction Manual. for details. *Rev 04-04-19 gt Date Issued: July 01, 2021 Listing Expires, June 30,2022 Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division ,a* This listing is based upon technical data submitted by the applicant, CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct " operational requirements or installation criteria. Refer to Iistee's data sheet, installation instructions and/or other Date Issued: July 01, 2021 Listing Expires, June 30,2022 Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7135-1653:0503 Page 1 of 2 CATEGORY: 7135 --AUDIBLE DEVICES LISTEE: System Sensor, Unincorporated Div of Honeywell Int'I Inc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Lisa Brant (203) 484-6105 Fax (203) 484-7309 Email: lisa.brant@honeywell.com DESIGN: System Sensor Indoor 2 -wire and *4 -wire Models: HWL, HRL, HGWL and HGRL Horns; CHWL and CHRL Chimes; P2RL, P2WL, P2GRL, P2GWL, P2RL-P, P2WL-P, P2RL-SP, P2WL-SP, *P4RL and *P4WL Wall Horn Strobes; PC2RL, PC2WL, *PC4RLand *PC4WL Ceiling Horn Strobes; CHSRL and CHSWL Wall Chime Strobes; CHSCRL and CHSCWL Ceiling Chime Strobes; Wall Bezel Parts: BZR-F, BZR-AL, BZR-AG, BZR-EV, BZR-P, BZR-SP, BZR-PG, BZW -F, BZW -AL, BZW -AG, BZW -EV, BZW -P, BZW -SP, BZW -PG, BZGR-F, BZGR-AL, BZGR-AG, BZGR-EV, BZGR-P, BZGR-SP, BZGR-PG, BZGW-F, BZGW-AL, BZGW-AG, BZGW-EV, BZGW-P, BZGW-SP and BZGW-PG, Ceiling Bezel Parts: - BZRC-F, BZRC-AL, BZRC-AG, BZRC-EV, BZRC-P, BZRC-SP, BZRC-PG, BZWC-F, BZWC-AL, BZWC-AG, BZWC-EV, BZWC-P, BZWC-SP and BZWC-PG. Color Lens: LENS -A2, LENS -132, LENS -G2, LENS -R2, LENS-AC2, LENS-BC2, LENS-GC2 and LENS -RC2. WallTrim Rings: *TR -2 and *TR -2W CeilingTrim Rings: *TRC -2 and *TRC -2W. Wall Surface Mounted Back Boxes: SBBRL, SBBGRL, SBBWL and SBBGWL, Ceiling Surface Mounted Back Boxes: Revision 08-21-2017 dcc This listing is based upon technical data submitted by the applicant. CSFM .Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not O' an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2021 Listing Expires June 30, 2022' Authorized By: DAVIDCASTILLO,, M.E., F.P.E. Fire Engineering Division Listing No. 7135-1653:0503 Page 2 of 2 SBBCRL and SBBCWL MP120KL 120 VAC Adapter Mounting Plate Refer to listee's data sheet for detailed product description and operational considerations. RATING: 12 VDC regulated and 24 VDC/FWR INSTALLATION: In accordance with listee's printed installation instructions, NFPA 72, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as audible devices when used with separately listed compatible fire alarm control units. Suitable for indoor use, wall or ceiling mounted. Authority having jurisdiction should be consulted prior to installation. Refer to listee's Installation Instruction Manual for details. Revision 08-21-2017 dcc This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2021 Listing Expires June 30, 2022 Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division i GENESIS SERIES CARLE Description: 14AWG '2/CSOL FPLP Compliance: UL Standard 1424; NEC Article 760 Construction: Conductor 14 AWG Solid Bare Copper No. of Conductors 2 Assembly Tubed jacket over twisted insulated conductors Insulation Type Plenum PVC Color Black, Red Thickness 0.007" nom. Diameter 0.078" nom. Lay Length 3.0" nom. Jacket Type Plenum PVC Color Red Thickness 0.015" nom. Diameter . 0.182" nom:... Legend (Ink Print) HONEYWELL 14 AWG 2/C (ETL) FPLP/CL2P 3038058 76C (RoHS) W/O# XXXXXX-xxX C(ETL) FTS XXXXFT DEVICE/ZONE A B C D E F 1 2 3 4 5 6 7 8 9 Properties Temperature Rating Operating Voltage Capacitance Impedance DC Resistance Flame Rating -20 to 75 °C 300 Volts max. 27 pf/ft nom 54 Ohms nom. 2.5 Ohms/M' at 20°C UL 910, CSA FT6 GENESIS SERIES Description: 18'AW6'4/C SOL FPLP-CL2P Compliance: UL Standards 13 & 1424; NEC Articles 725 & 760 Construction: Conductor 18 AWG Solid Bare Copper No. of Conductors 4 Insulation Type Plenum PVC Color BIk,Red,Ylw,Grn Thickness 0.007" nom. Diameter 0.054" nom. Lay Length 4.5" nom. Jacket Type Plenum PVC Color Red Thickness 0.015" nom. Diameter 0.157" nom. Legend (Ink Print) HONEYWELL P/N 4507 4C18 E175105 (UL) FPLP OR CUP C(UL)US FT6 75C (RoHS) W/O# XXXXXX-XXXXXX XXXXFT DEVICE/ZONE A B C D E F 12 3 4 5 6_ _ 789 Properties: Temperature Rating Operating Voltage Capacitance Impedance DC Resistance Flame Rating REV A 09/01/10 OA -20 to 750C 300 Volts max. 28 pf/ft nom. 68 Ohms nom. 6.5 Ohms/M' at 20°C UL 910, NFPA 262, C(UL) FT6 , GENESIS SERIES Description: 18 AWG 2/C SOL FPLP-CL2P Compliance: UL Standards 13 & 1424; NEC Articles 725 & 760 Construction: Blk,Red Conductor 18 AWG Solid Bare Copper No. of Conductors 2 Properties: Insulation Type Plenum PVC Color Blk,Red Thickness 0.007" nom. Diameter 0.054" nom. Lay Length 2.25" nom. Flame Rating Jacket Type Plenum PVC Color Red Thickness 0.015" nom. Diameter 0.136" nom. Legend (Ink Print) HONEYWELL P/N 4506 2C18 E175105 (UL) FPLP OR CUP C(UL)US FT6 76C (RoHS) W/O# XXXXXX-XXXXXX XXXXFT DEVICE/ZONE A B C D E F 12 3 4 5 6 789 Properties: Temperature Rating -20 to 750C Operating Voltage 300 Volts max. Capacitance 28 pf/ft nom. Impedance 68 Ohms nom. DC Resistance 6.5 Ohms/M' at 200C Flame Rating UL 910, NFPA 262, C(UL) FT6 REV A 09/01/10 OA CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7161 187:0100 CATEGORY: 7,61;--CABLES-FIRE PROTECTIVE SIGNALING LISTEE: GENESIS CABLE SYSTEM7701 95TH Street, Pleasant Prairie, WI 53158 Contact: Orville Allen (262) 947-0720 Fax (262) 947-0724 Email: orville@genesiscable.com DESIGN: Model FPL F,,LPand FPLR power limited fire protective signaling cable. Page 1 of 1 Conductors: In accordance with the standard Insulation: GPT -150, Foam PP, HDPE or LDPE Assembly: 2 to 12 insulated conductors Shield (Optional): Aluminum polyester tape shield Braid (Optional): Metal braid over cable core Jacket: PVC compound Gitto/Global Corp., Grade GA -91-84, GPT -45, GA5033, GA93016 Refer to listee's data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances, NEC Article 760, and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, Type "FPL" and UL label. APPROVAL: Listed as power -limited fire protective signaling cables. Rev. 06-18-2003 Date Issued: July 01, 2021 Lisiing Expires June 30 2022 Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division :,gfQ`� 10 This listing „is based upon technical data submitted by the applicant. CSFM Fire Engineering staff the test results and/or other data but does not make an independent verification of any claims. This has reviewed listing is not �` an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2021 Lisiing Expires June 30 2022 Authorized By: DAVID CASTILLO,, M.E., F.P.E. Fire Engineering Division ENGINEERING SPECIFICATIONS Listed E-123774 Standards U UL Listed Listed E-156878 E-156879 Underwriters Laboratories Standards UL -83, UL -1063, UL -1581, UL -255Q AWM Spec 1316,1317,1318,1319,1320, 1321ASTM Stranding Class B3, B8, 8787; Federal Specification A -A-59544; American National Standards Institute; Canadian Standards Association C22.2 No. 75; NEMA WC70/ICER S-95-658; UL 1685-FF44EEE 1202 p0,000 Btwhr) Flame Test (1/0 AWG and larger); New York State DOS -16120-87-1222-1048; ICER T-29-520 (210,000 Btul Flame Test; , NFPA 70 (NEC-) Article 310; ARRA 2009 Section 1605 "Buy American" Compliant; RoHS Compliant; MasterSpec Division 26 Secfions 260519, 260523; O• C ®� - ® UL Listing #E-123774, #E-156878, #E-156879 F1.tp� CONSTRUCTION Conductors Solid, uncoated copper conductors per ASTM -133; Stranded, uncoated copper conductors per ASTM -B3, ASTM -68 and ASTM -8787 Insulation Color -coded Polyvinyl Chloride FVCI, heat and moisture -resistant, flame retardant compound per UL -83 and UL -1063 Jacket A tough, polyr ide, Nylon outer covering per UL -83 and 1063 APPLICATIONS Type THHWTHWN-2 building wire is Intended for general pugwse applications as defined by the National Electrical Code (NEQ. Type THHN/FFIWN-2 is permitted for new constructed or rewiring for 600 -volt applications. For applications requiring Type THHN or THWN-2, the conductor is appropriate for use in wet or dry locations at temperatures not to exceed 901C or not to exceed 75°C in oil or coolants, For applications requiring Type MTW, the conductor is appropriate for use in dry locations at 9TC, or not to exceed 60°0 in wet locations or where exposed to oils or coolants. FEATURES A great alternative to eliminate the need for lube. Slick Nylon outer jacket for easy pulling. SuperSlick Elite is available in sizes 14 AWG through 1000 KCMIL. All sizes rated gasoline and oil resistant 11. On 250 KCMIL and larger, sequential footage markings located every foot for easy measuring. For 1 AWG through 4/0 AWG sequential foot markings located on master reels only unless otherwise specified. 6 AWG and larger Sunlight Resistant In all colors. For 110 AWG and larger conductors are rated for cable tray use and comply with IEEE 12021FT4 Q0,000 Btu/hr.) flame test and ICER T-29-20 (210,000 BtuPon) flame test v 0 SuperSlick Elite' Nylon Jacket © PVC Insulation © Stranded Copper Conductor