Loading...
HomeMy WebLinkAboutF2019-0094 - MiscO4�$wPpRr�A CITE' OF NEWPOR.T REACH n COWAIT Ti'Y DEVELOPMENT DEPARTMENT o ¢ BUI LDING DIVISION c,� osfis 100 Civic Center Drive l P.O. Box 1768 1 Newport Beach, CA 92658-8915 www.newportheachca.gov 1(949) 644-3200 FIRE SPRINKLER NFPA 13D SYSTEM FINAL CHECKLIST (RESIDENTIAL) YES NO 1. Water meter proper size ❑ 2. Fire sprinkler system installed per the approved plans ❑ 3. All construction covers removed from sprinkler heads ❑ 4. Cover plates are NOT to be installed, but shall be available on the Jobsite ❑ 5. All tape and paint removed from sprinkler heads ❑ 6. Finish trim installed around sprinkler heads ❑ 7. Proper signage posted at all required locations ❑ 8. Flow test conducted and bell tested ❑ 9. Location of inspector's testing valve in approved location ❑ SYSTEMS: 10. Clearances around sprinkler heads and riser - no obstructions ❑ 11. Operating pressure gauge installed at riser showing proper water pressure ❑ 12. Back flow preventer installed ❑ 13. System installed per manufacturers specifications ❑ NOTES: FIRE SPRINKLER NFPA 13D SYSTEM FINAL APPROVED: a. PERMIT #: / niqv gY, DATE: '!o " GC/ Forms\ Fire Sprinkler NFPA 13D Syrtem -FINAL Checklise RESIOENiIAL OS/12/2015 CITY OF NEWPORT BEACH COMMUNITY DEVELOPMENT DEPARTMENT BUILDING DIVISION 100 Civic Center Drive l P.O. Box 1768 1 Newport Beach, CA 92658-8915 www.newportbeachca.gov 1 (949) 644-3200 FIRE SPRINKLER NFPA 13D SYSTEM ROUGH INSPECTION CHECKLIST 1. Riser Construction and Location Approval a. Drain valve b. Backflow device (single check) c. Bell activation device d. Inspectors test valve e. Riser sized per approved plans 2. Pressure Test a. System tested at operating pressure for 2 hours b. Pressure gauge installed 3. Sprinkler Heads shall not be Installed In the flttings prior to the fittings being cemented in place (temporary test plugs) a. Installation and spacing of temporary test plugs 4. Piping a. Material installed per plan b. Hangers per codes/prevent upward movement C. All CPVC piping shall be installed by persons who have been certified by the manufacturer for installation of CPVC piping d. Piping protected from damage 5. Bell a, Wiring installed per code b. Boxes installed at proper locations NOTE: CPVC plastic pipe in the garage shall not be exposed. Sprinklers that are Response" or "Residential" must be used. CORRECTIONS AND FIRE SPRINKIL NF 13D SYST OUCH INSPECTION APPROVED: PERMIT* BY: DATE: YES I El as "Quick Forms\sresprinWer NFPA1505ystem-Roughlnspeotlon Ch..Wls 05/12/2015