HomeMy WebLinkAbout7.02_Misc Files (TAB Chlorination)_20360 Harbor Day Certified 11-15-2021# # AIR BALANCE CO., INC. PROFESSIONAL AIR & HYDRONIG SYSTEM TESTING • BUILDING SYSTEMS COMMISSIONING CERTIFIED TEST, ADJUST & BALANCE REPORT PROJECT PROJECT/JOB# CONTRACTOR ARCHITECT ENGINEER CERTIFICATION: The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the NEBB Procedural Standard for Testing, Adjusting and Balancing of Environmental Systems. The measurements shown, and the information given, in this report are certified to be accurate and complete, at the time and date the information was gathered. Any variances from design quantities, which exceed NEBB tolerances, are noted in the TAB report project summary. NEBB CERTIFICATION NUMBER 2756 TECHNICIAN APPROVED DATE RTIRCATIO 3/31/22 dronic 1240 N. Jefferson St., Suite H • Anatneim, CA92807-1632 • Ptione (714) 630-3796 • Fax (714) 630-3998 3330 W. Hacienda Ave., Suite 407 • Las Vegas, NV 89118 • Phone (702)270-2688 • Fax (702) 270-0788 7525 Mission Gorge Rd., Suite E • San Diego, CA 92120 • Phone (800) 339-3796 www.precisionairbalance.com Email: sales@precisionairbalance.com CA STATE LICENSE #633805 ACCO ENGINEERED SYSTEMS 888 EAST WALNUT ST., PASADENA, CA 91101 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR., CORONA DEL MAR, CA 92625 20360 NOT AVAILABLE ACCO ENGINEERED SYSTEMS J. HOWARD D. FOX 11/15/2021 (' P�m� AIR BALANCE co .• INC. PROFESSIONAL AIR & HYDRONIC SYSTEM TESTING• BUILDING SYSTEMS COMMISSIONING INSTRUMENTATION LIST INSTRUMENT MANUFACTURER MODEL# SERIAL# CALIBRATION DUE DATE AMP PROBE FLUKE 373 38750507 12/23/2021 AIR DATA MULTIMETER SHORTRIDGE ADM-860 M88050 12/22/2021 DIGITAL ANEMOMETER ALNOR TSI INC. RVA801 A04780 6/17/2022 TACHOMETER HERMAN STICHT MT-1B B16C85068P 12/23/2021 -WDRONIC MANOMETEF ALNOR TSI INC.HM-685 72025020 7/27/2022 HOOD #18 J.HOWARD 1240 N. Jefferson St., Suite H • Anaheim, CA 92807-1632 • Phone (714) 630-3796 • Fax (714) 630-3998 3330 W. Hacienda Ave., Suite 407 • Las Vegas, NV 89118 • Phone (702) 270-2688 • Fax (702) 270-0788 7525 Mission Gorge Rd., Suite E • San Diego, CA 92120 • Phone (800) 339-3796 www.precisionairbalance.com Email: sales@precisionairbalance.com CA STATE LICENSE #633805 AIR BALANCE CO-, INC. PROFESSIONAL AIR & HYDRONIC SYSTEM TESTING • BUILDING SYSTEMS COMMISSIONING Ni MASTER CODE SHEETS AIR DISTRIBUTION CODES CD CEILING DIFFUSER CG CEILING GRILLE CR CEILING REGISTER RG RETURN GRILLE SR SUPPLY REGISTER RR RETURN REGISTER DO DUCT OPENING FG FLOOR GRILLE FR FLOOR REGISTER AB AIR BAR LR LINEAR RETURN LD LINEAR DIFFUSER EG EXHAUST GRILLE ER EXHAUST REGISTER SG SUPPLY GRILLE SO SCREENED OPENING HO HOOD OPENING LT LIGHT TROFFER DT DUCT TRAVERSE FO FILTER OPENING 1240 N. Jefferson St., Suite H • Anaheim. CA 92807-1632 • Phone (714) 630-3796 • Fax (714) 630-3998 ^ 3330 W. Hacienda Ave., Suite 407 • Las Vegas. NV 89118 • Phone (702) 270-2688 • Fax (702) 270-0788 7525 Mission Gorge Rd., Suite E • San Diego. CA 92120 • Phone (800) 339-3796 www.precisionairbalance.com Emaii: saies@prectsionairbalance.com * CA STATE LICENSE #633805 Date:10/25/2021 Page:1 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 265 273 1,250 1,290 Total CFM - Outlet 265 273 1,260 1,290 R/A CFM NS 252 NS 1,017 O/A CFM 20 22 (3)270 273 (3) Static Pressure (Total/Ext)0.00"DUCTLESS 0.35"0.44" Inlet Pressure DUCTLESS -0.15" Discharge Pressure DUCTLESS 0.29" Fan RPM 3 SPEED HIGH SPD.(1)3 SPEED HIGH SPD.(2) Specified Actual Specified Actual Motor Manufacturer NS NA Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 206 Amperage 0.2 0.1 2.5 1.4 Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. AIR MOVING EQUIPMENT TEST SHEET 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL (3) FOR O.S.A. SEE SF 1-1 AIR DISTRIBUTION SHEET. (2) CODE 3 / FAN SPEED 4 / 106 ESP SETTING. ALL FAN SPEEDS SET TO 106 ESP. (1) CODE 3 / FAN SPEED 4 / 47 ESP SETTING. ALL FAN SPEEDS SET TO 47 ESP DIRECT DRIVEDIRECT DRIVE 011KCY1C282 ARNU283M3A4 LG 100 L0BBY 100 LOBBY DIRECT DRIVEDIRECT DRIVE SYSTEM FC-A1-1 130D ADMISSIONS DIRECTOR 130D ADMISSIONS DIRECTOR FC-A1-2 DIRECT DRIVEDIRECT DRIVE LG ARNU053TRD4 011KCPY0U184 DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 100A 1 DO 14" X 14"1.36 195 265 201 273 TOTAL (265)(273) REMARKS: 10/25/2021 AIR DISTRIBUTION 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 2 FC-A1-1 HARBOR DAY SCHOOL DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 100 1 CD 2410 1.0 *420 *437 100 2 CD 2410 1.0 *420 *432 100 3 CD 2410 1.0 *420 *421 TOTAL (1,260)(1,290) REMARKS: 10/25/2021 3 FC-A1-2 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/25/2021 Page:4 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 265 272 285 292 Total CFM - Outlet 265 272 285 292 R/A CFM NS 237 285 292 O/A CFM 35 38 (3)0 0 (4) Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS Inlet Pressure DUCTLESS DUCTLESS Discharge Pressure DUCTLESS DUCTLESS Fan RPM 3 SPEED HIGH SPD.(1)3 SPEED HIGH SPD.(2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 206 Amperage 0.2 0.1 0.2 0.1 Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-A1-3 FC-A1-4 101 NURSE 107 CONFERENCE ROOM 101 NURSE 107 CONFERENCE ROOM LG LG ARNU073TRD4 ARNU093TRD4 010KCLH0D304 012KCJZ0TW80 DIRECT DRIVE DIRECT DRIVE (1) CODE 3 / FAN SPEED 4 / 49 ESP SETTING. ALL FAN SPEEDS SET TO 49 ESP (2) CODE 3 / FAN SPEED 4 / 55 ESP SETTING. ALL FAN SPEEDS SET TO 55 ESP. (3) FOR O.S.A. SEE SF 1-1 AIR DISTRIBUTION SHEET. (4) O.S.A. SUPPLIED BY SF 1-1 WITH SEPARATE SUPPLY GRILLE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 101 1 DO 14" X 14"1.36 195 265 200 272 TOTAL (265)(272) REMARKS: 10/25/2021 5 FC-A1-3 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 107 1 DO 14" X 14"1.36 210 285 215 292 TOTAL (285)(292) REMARKS: 10/25/2021 6 FC-A1-4 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/25/2021 Page:7 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 265 272 310 302 Total CFM - Outlet 265 272 310 302 R/A CFM NS 245 310 302 O/A CFM 25 27 (3)0 0 (4) Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS Inlet Pressure DUCTLESS DUCTLESS Discharge Pressure DUCTLESS DUCTLESS Fan RPM 3 SPEED HIGH SPD.(1)3 SPEED HIGH SPD.(2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 206 Amperage 0.2 0.1 0.2 0.1 Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-A1-5 FC-A1-6 102 LOWER DIRECTOR 159 OPEN OFFICE 102 LOWER DIRECTOR 159 OPEN OFFICE LG LG ARNU053TRD4 ARNU123TRD4 011KCYQU186 012KCLH0UT76 DIRECT DRIVE DIRECT DRIVE (1) CODE 3 / FAN SPEED 4 / 49 ESP SETTING. ALL FAN SPEEDS SET TO 49 ESP (2) CODE 3 / FAN SPEED 4 / 58 ESP SETTING. ALL FAN SPEEDS SET TO 58 ESP. (3) FOR O.S.A. SEE SF 1-1 AIR DISTRIBUTION SHEET. (3) O.S.A. SUPPLIED BY SF 1-1 WITH SEPARATE SUPPLY GRILLE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 102 1 DO 14" X 14"1.36 195 265 200 272 TOTAL (265)(272) REMARKS: 10/25/2021 8 FC-A1-5 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 159 1 DO 14" X 14"1.36 228 310 222 302 TOTAL (310)(302) REMARKS: 10/25/2021 9 FC-A1-7 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/25/2021 Page:10 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 265 269 265 267 Total CFM - Outlet 265 269 265 267 R/A CFM NS 236 NS 234 O/A CFM 30 33 (3)35 33 (3) Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS Inlet Pressure DUCTLESS DUCTLESS Discharge Pressure DUCTLESS DUCTLESS Fan RPM 3 SPEED HIGH SPD.(1)3 SPEED HIGH SPD.(2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 206 Amperage 0.2 0.1 0.2 0.1 Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-A1-7 FC-A1-8 103 HEAD ASSISTANT 104 HEAD OF SCHOOL 103 HEAD ASSISTANT 104 HEAD OF SCHOOL LG LG ARNU053TRD4 ARNU073TRD4 011KCPY0U184 010KCUK0D310 DIRECT DRIVE DIRECT DRIVE (1) CODE 3 / FAN SPEED 4 / 51 ESP SETTING. ALL FAN SPEEDS SET TO 51 ESP (2) CODE 3 / FAN SPEED 4 / 53 ESP SETTING. ALL FAN SPEEDS SET TO 53 ESP. (3) FOR O.S.A. SEE SF 1-1 AIR DISTRIBUTION SHEET. DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 103 1 DO 14" X 14"1.36 195 265 198 269 TOTAL (265)(269) REMARKS: 10/25/2021 11 FC-A1-7 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 104 1 DO 14" X 14"1.36 195 265 196 267 TOTAL (265)(267) REMARKS: 10/25/2021 12 FC-A1-8 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/25/2021 Page:13 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 265 272 310 320 Total CFM - Outlet 265 272 310 320 R/A CFM NS 252 310 320 O/A CFM 20 22 (3)0 0 (4) Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS Inlet Pressure DUCTLESS DUCTLESS Discharge Pressure DUCTLESS DUCTLESS Fan RPM 3 SPEED HIGH SPD.(1)3 SPEED HIGH SPD.(2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 206 Amperage 0.2 0.1 0.2 0.1 Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-A1-9 FC-A1-10 105 FACILITIES DIRECTOR 106 WORKROOM 105 FACILITIES DIRECTOR 106 WORKROOM LG LG ARNU053TRD4 ARNU123TRD4 011KCVU0U159 012KCXM0U018 DIRECT DRIVE DIRECT DRIVE (1) CODE 3 / FAN SPEED 4 / 50 ESP SETTING. ALL FAN SPEEDS SET TO 50 ESP (2) CODE 3 / FAN SPEED 4 / 60 ESP SETTING. ALL FAN SPEEDS SET TO 60 ESP. (3) FOR O.S.A. SEE SF 1-1 AIR DISTRIBUTION SHEET. (4) O.S.A. SUPPLIED BY SF 1-1 WITH SEPARATE SUPPLY GRILLE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 105 1 DO 14" X 14"1.36 195 265 200 272 TOTAL (265)(272) REMARKS: 10/25/2021 14 FC-A1-9 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 106 1 DO 14" X 14"1.36 228 310 235 320 TOTAL (310)(320) REMARKS: 10/25/2021 15 FC-A1-10 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/5/2021 Page:16 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 240 260 918 950 Total CFM - Outlet 240 260 918 950 R/A CFM 240 260 918 950 O/A CFM -0--0--0--0- Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS Inlet Pressure DUCTLESS DUCTLESS Discharge Pressure DUCTLESS DUCTLESS Fan RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 209 208/230 209 Amperage 0.25 0.1 0.81 0.6 Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-A1-11 FC-A1-12 109 DATA 110 ELECTRICAL 109 DATA 110 ELECTRICAL LG LG ARNU123TRD4 ARNU363SVA4 011KCJZ0RR80 903KCCV0UB91 DIRECT DRIVE DIRECT DRIVE (2) CODE 3/ FAN SPEED 4/ 95 ESP SETTING. ALL FAN SPEEDS SET TO 95 ESP (2) CODE 3/ FAN SPEED 4/ 185 ESP SETTING. ALL FAN SPEEDS SET TO 185 ESP DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 110 1 S.O.23" X 3"0.48 500 240 533 260 TOTAL (240)(260) REMARKS: 11/5/2021 17 FC-A1-12 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 110 1 S.O.30 1/2 X 3 1/2 0.74 1,240 918 1,283 950 TOTAL (918)(950) REMARKS: 11/5/2021 18 FC-A1-12 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/25/2021 Page:19 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 310 315 265 279 Total CFM - Outlet 310 315 265 279 R/A CFM 310 315 NS 246 O/A CFM 0 0 (3)30 33 (4) Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS Inlet Pressure DUCTLESS DUCTLESS Discharge Pressure DUCTLESS DUCTLESS Fan RPM 3 SPEED HIGH SPD.(1)3 SPEED HIGH SPD.(2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 206 Amperage 0.2 0.1 0.2 0.1 Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (1) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-A1-13 FC-A1-14 134 ASSOCIATES 137A PSYCH 134 ASSOCIATES 137A PSYCH LG LG ARNU123TRD4 ARNU053TRD4 012KCJZ0U044 011KCCV0U211 DIRECT DRIVE DIRECT DRIVE (1) CODE 3 / FAN SPEED 4 / 61 ESP SETTING. ALL FAN SPEEDS SET TO 61 ESP (2) CODE 3 / FAN SPEED 4 / 51 ESP SETTING. ALL FAN SPEEDS SET TO 51 ESP. (3) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE (4) FOR O.S.A. SEE SF 1-2 AIR DISTRIBUTION SHEET. DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 134 1 DO 14" X 14"1.36 228 310 231 315 TOTAL (310)(315) REMARKS: 10/25/2021 20 FC-A1-13 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 137A 1 DO 14" X 14"1.36 195 265 205 279 TOTAL (265)(279) REMARKS: 10/25/2021 21 FC-A1-14 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/25/2021 Page:22 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 265 274 310 309 Total CFM - Outlet 265 274 310 309 R/A CFM NS 246 310 309 O/A CFM 30 28 (3)0 0 (4) Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS Inlet Pressure DUCTLESS DUCTLESS Discharge Pressure DUCTLESS DUCTLESS Fan RPM 3 SPEED HIGH SPD.(1)3 SPEED HIGH SPD.(2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 206 Amperage 0.2 0.1 0.2 0.1 Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-A1-15 FC-A1-16 137B LANGUAGE ARTS SPECIALIST 137 SMALL GROUP AREA 137B LANGUAGE ARTS SPECIALIST 137 SMALL GROUP AREA LG LG ARNU053TRD4 ARNU123TRD4 011KCHE0U209 012KCCV0UT71 DIRECT DRIVE DIRECT DRIVE (1) CODE 3 / FAN SPEED 4 / 50 ESP SETTING. ALL FAN SPEEDS SET TO 50 ESP (2) CODE 3 / FAN SPEED 4 / 60 ESP SETTING. ALL FAN SPEEDS SET TO 60 ESP. (3) FOR O.S.A. SEE SF 1-2 AIR DISTRIBUTION SHEET. (4) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 137B 1 DO 14" X 14"1.36 195 265 201 274 TOTAL (265)(274) REMARKS: 10/25/2021 23 FC-A1-15 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 137 1 DO 14" X 14"1.36 228 310 227 309 TOTAL (310)(309) REMARKS: 10/25/2021 24 FC-A1-16 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/4/2021 Page:25 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 265 276 1,450 1,482 Total CFM - Outlet 265 276 1,450 1,482 R/A CFM NS 249 NS 887 O/A CFM 25 27 (3)560 595 Static Pressure (Total/Ext)0.00"DUCTLESS 0.70"0.45" Inlet Pressure DUCTLESS -0.14" Discharge Pressure DUCTLESS 0.31" Fan RPM 3 SPEED HIGH SPD.(1)3 SPEED HIGH SPD. (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 206 Amperage 0.2 0.1 2.5 1.8 Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-A1-17 FC-A1-18A 137C MATH SPECIALIST 132 STORY TELLING 137C MATH SPECIALIST 132 STORY TELLING LG LG ARNU053TRD4 ARNU363M3A4 011KCYUQ0U210 008KCDG16M34 DIRECT DRIVE DIRECT DRIVE (1) CODE 3 / FAN SPEED 4 / 52 ESP SETTING. ALL FAN SPEEDS SET TO 52 ESP (2) CODE 3 / FAN SPEED 4 / 113 ESP SETTING. ALL FAN SPEEDS SET TO 113 ESP. (3) FOR O.S.A. SEE SF 1-2 AIR DISTRIBUTION SHEET. DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 137C 1 DO 14" X 14"1.36 195 265 203 276 TOTAL (265)(276) REMARKS: 10/25/2021 26 FC-A1-15 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 131 1 CD 2412 1.0 *365 *361 131 2 CD 2412 1.0 *365 *365 132 3 CD 2412 1.0 *365 *348 132 4 CD 2412 1.0 *365 *366 TOTAL (1,460)(1,440) OUTSIDE AIR LOUVER 1 RG 42'' X 18''1.0 *560 *595 TOTAL (560)(595) REMARKS: 11/4/2021 27 FC-A1-18A HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/2/2021 Page:28 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 1,450 1,463 310 320 Total CFM - Outlet 1,450 1,463 310 320 R/A CFM NS 1,038 310 320 O/A CFM 405 425 125 0 (3) Static Pressure (Total/Ext)0.70"0.45"0.00"DUCTLESS Inlet Pressure -0.25"DUCTLESS Discharge Pressure 0.20"DUCTLESS Fan RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD.(2) Specified Actual Specified Actual Motor Manufacturer NA NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 115 121 208/230 206 Amperage 2.5 1.3 0.2 0.1 Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-A1-18B FC-A1-19 133 LIBRARY 133 TINKER AREA 133 LIBRARY 133 TINKER AREA LG LG ARNU363M3A4 ARNU123TRD4 008KCLH16M32 012KCRN0U046 DIRECT DRIVE DIRECT DRIVE (1) CODE 3 / FAN SPEED 4 / 53 ESP SETTING. ALL FAN SPEEDS SET TO 53 ESP (2) CODE 3 / FAN SPEED 4 / 59 ESP SETTING. ALL FAN SPEEDS SET TO 59 ESP (3) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 131 1 CD 2410 1.0 *365 *371 131 2 CD 2410 1.0 *365 *363 131 3 CD 2410 1.0 *365 *368 131 4 CD 2410 1.0 *365 *361 TOTAL (1,460)(1,463) OUTSIDE AIR LOUVER 1 RG 42" X 18"1.0 *405 *425 TOTAL (405)(425) REMARKS: 11/4/2021 29 FC-A1-18B HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 133 1 DO 14" X 14"1.36 227 310 235 320 TOTAL (310)(320) REMARKS: 11/2/2021 30 FC-A1-1 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/2/2021 Page:31 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 390 398 390 396 Total CFM - Outlet 390 398 390 396 R/A CFM 390 398 390 396 O/A CFM 145 0 (3)150 0 (3) Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS Inlet Pressure DUCTLESS DUCTLESS Discharge Pressure DUCTLESS DUCTLESS Fan RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 206 Amperage 0.2 0.1 0.2 0.1 Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (1) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-A1-20 FC-A1-21 131A WORKROOM 131B TEACHING AREA 131A WORKROOM 131B TEACHING AREA LG LG ARNU153TQD4 ARNU153TQD4 010KCEA1AY16 010KCMR1AY15 DIRECT DRIVE DIRECT DRIVE (1) CODE 3 / FAN SPEED 4 / 53 ESP SETTING. ALL FAN SPEEDS SET TO 53 ESP (2) CODE 3 / FAN SPEED 4 / 53 ESP SETTING. ALL FAN SPEEDS SET TO 53 ESP (3) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 131A 1 DO 14" X 14"1.36 287 390 293 398 TOTAL (390)(398) REMARKS: 11/2/2021 32 FC-A1-20 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 131B 1 DO 14" X 14"1.36 287 390 291 396 TOTAL (390)(396) REMARKS: 11/2/2021 33 FC-A1-21 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/25/2021 Page:34 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 390 406 2,260 1,784 Total CFM - Outlet 390 406 1,740 1,784 R/A CFM 390 406 1325 1,333 O/A CFM 135 0 (3)415 451 (4) Static Pressure (Total/Ext)0.00"DUCTLESS 0.35"0.22" Inlet Pressure DUCTLESS -0.06" Discharge Pressure DUCTLESS 0.16" Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 205 Amperage 0.20 0.1 5.2 1.8 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-A2-1 FC-A2-2 ABOVE CEILING ABOVE CEILING 208 WORKROOM 207 STAFF LOUNGE LG LG ARNU153TQD4 ARNU763B8A4 012KCTB0569 011KCBD0L325 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 56 ESP SETTING. ALL FAN SPEEDS SET TO 56 ESP (2) CODE 3 / FAN SPEED 4/ 69 ESP SETTING. ALL FAN SPEEDS SET TO 69 ESP (3) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE (4) FOR O.S.A. SEE SF 1-2 AIR DISTRIBUTION SHEET. DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 208 1 DO 14 X 14 1.36 286 390 299 406 TOTAL (390)(406) REMARKS: 10/25/2021 35 FC-A2-1 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 207 1 CD 2410 1.0 *435 *439 207 2 CD 2410 1.0 *435 *435 207 3 CD 2410 1.0 *435 *458 207 4 CD 2410 1.0 *435 *452 TOTAL (1,740)(1,784) REMARKS: 10/25/2021 36 FC-A2-2 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/25/2021 Page:37 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 265 276 265 274 Total CFM - Outlet 265 276 265 274 R/A CFM NS 255 NS 255 O/A CFM 20 21 (3)20 19 (3) Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS Inlet Pressure DUCTLESS DUCTLESS Discharge Pressure DUCTLESS DUCTLESS Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 205 208/230 208 Amperage 0.20 0.1 0.20 0.1 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-A2-3 FC-A2-4 ABOVE CEILING ABOVE CEILING 210 DIRECTOR OF TECH 209 SYSTEMS ADMIN LG LG ARNU053TRD4 ARNU053TRD4 011KCBD0U205 011KCVU0U207 DIRECT DRIVE DIRECT DIRVE (1) CODE 3/ FAN SPEED 4/ 49 ESP SETTING. ALL FAN SPEEDS SET TO 49 ESP (2) CODE 3/ FAN SPEED 4/ 50 ESP SETTING. ALL FAN SPEEDS SET TO 50 ESP (4) FOR O.S.A. SEE SF 1-2 AIR DISTRIBUTION SHEET. DIRECT DRIVE DIRECT DIRVEDIRECT DRIVE DIRECT DIRVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 210 1 DO 14 X 14 1.36 194 265 203 276 TOTAL (265)(276) REMARKS: 10/25/2021 38 FC-A2-3 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 209 1 DO 14 X 14 1.36 194 265 202 274 TOTAL (265)(274) REMARKS: 10/25/2021 39 FC-A2-4 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/25/2021 Page:40 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 265 272 265 276 Total CFM - Outlet 265 272 265 276 R/A CFM NS 250 265 276 O/A CFM 20 22 (3)70 0 (3) Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS Inlet Pressure DUCTLESS DUCTLESS Discharge Pressure DUCTLESS DUCTLESS Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 205 Amperage 0.20 0.1 0.20 0.1 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-A2-5 FC-A2-6 ABOVE CEILING ABOVE CEILING BUSINESS OFFICE MOTHERS ROOM LG LG ARNU053TRD4 ARNU053TRD4 011KCJZ0U204 011KCFT0U203 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 50 ESP SETTING. ALL FAN SPEEDS SET TO 50 ESP (2) CODE 3/ FAN SPEED 4/ 50 ESP SETTING. ALL FAN SPEEDS SET TO 50 ESP (4) FOR O.S.A. SEE SF 1-2 AIR DISTRIBUTION SHEET. DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 206 1 DO 14 X 14 1.36 194 265 200 272 TOTAL (265)(272) REMARKS: 10/25/2021 41 FC-A2-5 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 207A 1 DO 14 X 14 1.36 194 265 203 276 TOTAL (265)(276) REMARKS: 10/25/2021 42 FC-A2-6 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/25/2021 Page:43 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 265 277 310 320 Total CFM - Outlet 265 277 310 320 R/A CFM NS 258 310 320 O/A CFM 25 19 (3)125 0 (4) Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS Inlet Pressure DUCTLESS DUCTLESS Discharge Pressure DUCTLESS DUCTLESS Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 208 Amperage 0.20 0.1 0.20 0.1 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-A2-7 FC-A2-8 ABOVE CEILING ABOVE CEILING 206 ASSISTANT BUSINESS 252 OPEN OFFICE LG LG ARNU053TRD4 ARNU123TRD4 011KCFT0U203 012KCXM0U042 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 50 ESP SETTING. ALL FAN SPEEDS SET TO 50 ESP (2) CODE 3/ FAN SPEED 4/ 60 ESP SETTING. ALL FAN SPEEDS SET TO 60 ESP (3) FOR O.S.A. SEE SF 1-2 AIR DISTRIBUTION SHEET. (4) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 205 1 DO 14 X 14 1.36 194 265 204 277 TOTAL (265)(277) REMARKS: 10/25/2021 44 FC-A2-7 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 252 1 DO 14 X 14 1.36 228 (310)236 320 TOTAL (310)(320) REMARKS: 10/25/2021 45 FC-A2-8 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/26/2021 Page:46 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 265 272 265 280 Total CFM - Outlet 265 272 265 280 R/A CFM NS 245 NS 259 O/A CFM 25 27 (3)20 21 (3) Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS Inlet Pressure DUCTLESS DUCTLESS Discharge Pressure DUCTLESS DUCTLESS Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 208 Amperage 0.20 0.1 0.20 0.1 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-A2-9 FC-A2-10 ABOVE CEILING ABOVE CEILING 204 DIRECTOR OF DEVELOPMENT 201DIR. OF DEVELOPMENT ASSIST. LG LG ARNU053TRD4 ARNU053TRD4 011KCAS0U200 011KCRN0U206 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 51 ESP SETTING. ALL FAN SPEEDS SET TO 51 ESP (2) CODE 3/ FAN SPEED 4/ 48 ESP SETTING. ALL FAN SPEEDS SET TO 48 ESP (3) FOR O.S.A. SEE SF 1-2 AIR DISTRIBUTION SHEET. DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 204 1 DO 14 X 14 1.36 194 265 200 272 TOTAL (265)(272) REMARKS: 10/26/2021 47 FC-A2-9 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 201 1 DO 14 X 14 1.36 194 265 206 280 TOTAL (265)(280) REMARKS: 10/26/2021 48 FC-A2-10 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/26/2021 Page:49 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 265 278 265 281 Total CFM - Outlet 265 278 265 281 R/A CFM NS 262 NS 248 O/A CFM 15 16 (3)35 33 (3) Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS Inlet Pressure DUCTLESS DUCTLESS Discharge Pressure DUCTLESS DUCTLESS Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 206 Amperage 0.20 0.1 0.20 0.1 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-A2-11 FC-A2-12 ABOVE CEILING ABOVE CEILING 202 DIRECTOR OF DEVELOPMENT 203 UPPER DIRECTOR LG LG ARNU053TRD4 ARNU073TRD4 011KCXM0U202 010KCLH0D328 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 50 ESP SETTING. ALL FAN SPEEDS SET TO 50 ESP (2) CODE 3/ FAN SPEED 4/ 50 ESP SETTING. ALL FAN SPEEDS SET TO 50 ESP (3) FOR O.S.A. SEE SF 1-2 AIR DISTRIBUTION SHEET. DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 202 1 DO 14 X 14 1.36 194 265 205 278 TOTAL (265)(278) REMARKS: 10/26/2021 50 FC-A2-11 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 203 1 DO 14 X 14 1.36 194 265 207 281 TOTAL (265)(281) REMARKS: 10/26/2021 51 FC-A2-12 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/26/2021 Page:52 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 240 244 375 382 Total CFM - Outlet 240 244 375 382 R/A CFM 240 244 375 382 O/A CFM 0 0 0 0 Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS Inlet Pressure DUCTLESS DUCTLESS Discharge Pressure DUCTLESS DUCTLESS Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 207 208/230 207 Amperage 0.25 0.1 0.25 0.1 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-A2-13 FC-A2-14 WALL MOUNT WALL MOUNT 241 ELECTRICAL 240 DATA LG LG ARNU053SJA4 ARNU153SJA4 011KCVU0RR83 011KCUK13D62 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 46 ESP SETTING. ALL FAN SPEEDS SET TO 46 ESP (2) CODE 3/ FAN SPEED 4/ 64 ESP SETTING. ALL FAN SPEEDS SET TO 64 ESP DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 241 1 DO 4" X 28"0.77 312 240 318 244 TOTAL (240)(244) REMARKS: 10/26/2021 53 FC-A2-13 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 240 1 DO 4" X 28"0.77 488 375 497 382 TOTAL (375)(382) REMARKS: 10/26/2021 54 FC-A2-14 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/27/2021 Page:55 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 800 NVL 1,250 1,267 Total CFM - Outlet 800 823 1,250 1,267 R/A CFM NS 574 NS 849 O/A CFM 310 328 415 418 Static Pressure (Total/Ext)0.35 0.28"0.35 0.34" Inlet Pressure -0.25"-0.14" Discharge Pressure 0.03"0.20" Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD. (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 207 208/230 206 Amperage 2.3 1.1 2.5 1.0 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD. (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-A2-15 FC-B1-1 ABOVE CEILING 108 KINDERGARTEN 211 5TH GRADE CLASSROOM 108 KINDERGARTEN LG LG ARNU243M2A4 ARNU283M3A4 011KCZP0G701 011KCQX1C284 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 84 ESP SETTING. ALL FAN SPEEDS SET TO 84 ESP (2) CODE 3 / FAN SPEED 4 / 98 ESP SETTING. ALL FAN SPEEDS SET TO 98 ESP. DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 211 1 CD 2410 1.0 *200 *201 211 2 CD 2410 1.0 *200 *212 211 3 CD 2410 1.0 *200 *197 211 4 CD 2410 1.0 *200 *213 TOTAL (800)(823) OUTSIDE AIR SYSTEM 207 1 RD 10" RD 0.55 563 310 609 335 TOTAL (310)(335) REMARKS: 10/26/2021 56 FC-A2-15 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: PROJECT: POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE A-1 221 B-1 316 1 " Dia x 0.026 =" A-2 413 B-2 444 2 " Dia x 0.082 =" A-3 401 B-3 689 3 " Dia x 0.146 =" A-4 374 B-4 803 4 " Dia x 0.226 =" A-5 814 B-5 547 5 " Dia x 0.342 =" A-6 863 B-6 422 6 " Dia x 0.685 =" A-7 877 B-7 730 7 " Dia x 0.774 =" A-8 890 B-8 764 8 " Dia x 0.854 =" A-9 B-9 9 " Dia x 0.918 =" A-10 B-10 10 " Dia x 0.974 =" SUBTOTAL SUBTOTAL (TOTAL FPM)DIVIDED BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM 9,568 16 598 0.55 329 COMMENTS:D DUCT SIZE 10" E AREA 0.55 S FPM 563 I CFM 310 G N T DUCT SIZE O.D.10" E DUCT SIZE I.D.10" S AREA 0.55 T CENTERLINE S.P.-0.13 AVERAGE FPM 598 D CFM MEASURED 329 A TEMP. CORRECTION 0 T ALT. CORRECTION 0 A ACTUAL CFM 329 INSTRUMENT USED: AIRFOIL SYSTEM #:FC-A2-15 OSA57 11/10/2021 ROUND DUCT TRAVERSE READINGS 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 108 1 CD 2410 1.0 *315 *309 108 2 CD 2410 1.0 *315 *319 108 3 CD 2410 1.0 *315 *314 108 4 CD 2410 1.0 *315 *325 TOTAL (1,260)(1,267) OUTSIDE AIR LOUVER 1 RG 42" X 18"1.0 *415 *418 TOTAL (415)(418) REMARKS: 10/27/2021 58 FC-B1-4 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/29/2021 Page:59 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 254 275 285 293 Total CFM - Outlet 254 275 285 293 R/A CFM 254 275 285 293 O/A CFM 0 0 60 0 (3) Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS Inlet Pressure DUCTLESS DUCTLESS Discharge Pressure DUCTLESS DUCTLESS Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 207 208/230 206 Amperage 0.25 0.1 0.20 0.1 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-B1-2 FC-B1-3 CEILING MOUNT 163 ABOVE CEILING 108C 163 ELECTRICAL 108C WORKROOM LG LG ARNU073SJA4 ARNU093TRD4 008KCYQ0YK22 012KCGW0TW91 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 65 ESP SETTING. ALL FAN SPEEDS SET TO 65 ESP (2) CODE 3/ FAN SPEED 4/ 58 ESP SETTING. ALL FAN SPEEDS SET TO 58 ESP (3) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 163 1 DO 4" X 28"0.77 329 254 358 275 TOTAL (254)(275) REMARKS: 10/29/2021 60 FC-B1-2 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 203 1 DO 14 X 14 1.36 209 (285)216 293 TOTAL (285)(293) REMARKS: 10/29/2021 61 FC-B1-3 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/27/2021 Page:62 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 1,250 1,278 1,250 1,262 Total CFM - Outlet 1,260 1,278 1,260 1,262 R/A CFM NS 856 NS 878 O/A CFM 410 422 350 384 Static Pressure (Total/Ext)0.35"0.33"0.35"0.27" Inlet Pressure -0.14"-0.10" Discharge Pressure 0.19"0.17" Fan RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 206 Amperage 2.5 1.0 2.5 1.0 Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-B1-4 FC-B1-5 111 KINDERGARTEN 112 1ST GRADE CLASSROOM 111 KINDERGARTEN 112 1ST GRADE CLASSROOM LG LG ARNU283M3A4 ARNU283M3A4 012KCQX0GS64 011KCCV1C283 DIRECT DRIVE DIRECT DRIVE (1) CODE 3 / FAN SPEED 4 / 94 ESP SETTING. ALL FAN SPEEDS SET TO 94 ESP (2) CODE 3 / FAN SPEED 4 / 91 ESP SETTING. ALL FAN SPEEDS SET TO 91 ESP DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 111 1 CD 2410 1.0 *315 *327 111 2 CD 2410 1.0 *315 *312 111 3 CD 2410 1.0 *315 *321 111 4 CD 2410 1.0 *315 *318 TOTAL (1,260)(1,278) OUTSIDE AIR LOUVER 1 RG 42" X 18"1.0 *410 *422 TOTAL (410)(422) REMARKS: 10/27/2021 63 FC-B1-4 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 112 1 CD 2410 1.0 *315 *319 112 2 CD 2410 1.0 *315 *312 112 3 CD 2410 1.0 *315 *309 112 4 CD 2410 1.0 *315 *322 TOTAL (1,260)(1,262) OUTSIDE AIR LOUVER 1 SWG 42" X 18"1.0 *370 *384 TOTAL (370)(384) REMARKS: 10/27/2021 64 FC-B1-5 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/2/2021 Page:65 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 310 326 1,250 1,260 Total CFM - Outlet 310 326 1,260 1,260 R/A CFM 310 326 NS 886 O/A CFM 110 0 (3)370 374 Static Pressure (Total/Ext)0.00"DUCTLESS 0.35"0.27" Inlet Pressure DUCTLESS -0.12" Discharge Pressure DUCTLESS 0.15" Fan RPM 3 SPEED HIGH SPD.(1)3 SPEED HIGH SPD. (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 206 Amperage 0.2 0.1 2.5 1.0 Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-B1-6 FC-B1-7 113 SMALL GROUP 114 1ST GRADE CLASSROOM 113 SMALL GROUP 114 1ST GRADE CLASSROOM LG LG ARNU283M3A4 ARNU283M3A4 012KCSF0UT74 011KCEA1L324 DIRECT DRIVE DIRECT DRIVE (1) CODE 3 / FAN SPEED 4 / 58 ESP SETTING. ALL FAN SPEEDS SET TO 58 ESP (2) CODE 3 / FAN SPEED 4 / 93 ESP SETTING. ALL FAN SPEEDS SET TO 93 ESP (3) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 113 1 DO 14" X 14"1.36 227 310 240 326 TOTAL (310)(326) REMARKS: 11/2/2021 66 FC-A1-1 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 114 1 CD 2410 1.0 *315 *322 114 2 CD 2410 1.0 *315 *307 114 3 CD 2410 1.0 *315 *314 114 4 CD 2410 1.0 *315 *317 TOTAL (1,260)(1,260) OUTSIDE AIR LOUVER 1 RG 42" X 18"1.0 *370 *374 TOTAL (370)(374) REMARKS: 10/27/2021 67 FC-B1-7 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/29/2021 Page:68 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 1,250 1,263 310 320 Total CFM - Outlet 1,250 1,263 310 320 R/A CFM NS 865 310 320 O/A CFM 370 398 75 80 (3) Static Pressure (Total/Ext)0.35"0.31"0.00"DUCTLESS Inlet Pressure -0.14"DUCTLESS Discharge Pressure 0.17"DUCTLESS Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 208 Amperage 2.5 1.2 0.20 0.10 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-B1-8 FC-B1-9 ABOVE CEILING RM 155 ABOVE CEILING RM 115A 155 2ND GRADE CLASSROOM 115A SMALL GROUP LG LG ARNU283M3A4 ARNU123TRD4 012KCCV0GS63 012KCHEOUT68 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 96 ESP SETTING. ALL FAN SPEEDS SET TO 96 ESP (2) CODE 3/ FAN SPEED 4/ 57 ESP SETTING. ALL FAN SPEEDS SET TO 57 ESP (3) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 114 1 CD 2410 1.0 *315 *309 114 2 CD 2410 1.0 *315 *313 114 3 CD 2410 1.0 *315 *316 114 4 CD 2410 1.0 *315 *325 TOTAL (1,260)(1,263) OUTSIDE AIR LOUVER 1 RG 42" X 18"1.0 *370 *398 TOTAL (370)(398) REMARKS: 10/29/2021 69 FC-B1-8 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 203 1 DO 14 X 14 1.36 227 310 236 320 TOTAL (310)(320) REMARKS: 10/29/2021 70 FC-B1-9 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/29/2021 Page:71 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 800 827 800 818 Total CFM - Outlet 800 827 800 818 R/A CFM NS 510 NS 496 O/A CFM 310 317 310 322 Static Pressure (Total/Ext)0.35"0.17"0.35"0.13" Inlet Pressure -0.12"-0.07" Discharge Pressure 0.05"0.06" Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 208 208/230 207 Amperage 2.3 1.3 2.3 1.1 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-B1-10 FC-B1-11 ABOCE CEILING RM 116 ABOVE CEILING RM 117 116 2ND GRADE CLASSROOM 117 3RD GRADE CLASSROOM LG LG ARNU243M2A4 ARNU243M2A4 011KCLH0G680 011KCRN0G742 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 84 ESP SETTING. ALL FAN SPEEDS SET TO 84 ESP (2) CODE 3/ FAN SPEED 4/ 82 ESP SETTING. ALL FAN SPEEDS SET TO 82 ESP DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 116 1 CD 2410 1.0 *200 *213 116 2 CD 2410 1.0 *200 *209 116 3 CD 2410 1.0 *200 *200 116 4 CD 2410 1.0 *200 *205 TOTAL (800)(827) OUTSIDE AIR LOUVER 1 RG 34" X 16"1.0 *310 *317 TOTAL (310)(317) REMARKS: 10/29/2021 72 FC-B1-10 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 117 1 CD 2410 1.0 *200 *206 117 2 CD 2410 1.0 *200 *198 117 3 CD 2410 1.0 *200 *213 117 4 CD 2412 1.0 *200 *201 TOTAL (800)(818) OUTSIDE AIR LOUVER 1 RG 34" X 16"1.0 *310 *322 TOTAL (310)(322) REMARKS: 10/29/2021 73 FC-B1-11 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/29/2021 Page:74 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 310 318 800 829 Total CFM - Outlet 310 318 800 829 R/A CFM 310 318 NS 505 O/A CFM 80 0 (3)310 324 Static Pressure (Total/Ext)0.00"DUCTLESS 0.35"0.17" Inlet Pressure DUCTLESS -0.03" Discharge Pressure DUCTLESS 0.14" Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 207 208/230 208 Amperage 0.20 0.10 2.3 1.1 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-B1-12 FC-B1-13 ABOVE CEILING RM 117A ABOVE CEILING 118 117A SMALL GROUP 118 3RD GRADE CLASSROOM LG LG ARNU123TRD4 ARNU243M2A4 012KCAS0U040 011KCJZD0G740 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 54 ESP SETTING. ALL FAN SPEEDS SET TO 54 ESP (2) CODE 3/ FAN SPEED 4/ 85 ESP SETTING. ALL FAN SPEEDS SET TO 85 ESP (3) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 117A 1 DO 14 X 14 1.36 227 310 234 318 TOTAL (310)(318) REMARKS: 10/29/2021 75 FC-B1-12 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 118 1 CD 2410 1.0 *200 *208 118 2 CD 2410 1.0 *200 *201 118 3 CD 2410 1.0 *200 *217 118 4 CD 2410 1.0 *200 *203 TOTAL (800)(829) OUTSIDE AIR LOUVER 1 RG 34" X 16"1.0 *310 *324 TOTAL (310)(324) REMARKS: 10/29/2021 76 FC-B1-13 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 119 1 CD 2410 1.0 *315 *326 119 2 CD 2410 1.0 *315 *327 119 3 CD 2410 1.0 *315 *331 119 4 CD 2410 1.0 *315 *314 TOTAL (1,260)(1,298) OUTSIDE AIR LOUVER 1 RG 42" X 18"1.0 *370 *381 TOTAL (370)(381) REMARKS: 11/1/2021 78 FC-B1-14 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/1/2021 Page:77 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 1,250 1,298 310 323 Total CFM - Outlet 1,250 1,298 310 323 R/A CFM NS 917 310 323 O/A CFM 370 381 105 0 (3) Static Pressure (Total/Ext)0.35"0.18"0.00"DUCTLESS Inlet Pressure -0.15"DUCTLESS Discharge Pressure 0.13"DUCTLESS Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 207 208/230 206 Amperage 2.5 1.3 0.20 0.1 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-B1-14 FC-B1-15 ABOVE CEILING RM 119 ABOVE CEILING RM 119A 119 4TH GRADE CLASSROOM 119A SMALL GROUP LG LG ARNU283M3A4 ARNU123TRD4 011KCVU1C279 012KCVU0U047 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 92 ESP SETTING. ALL FAN SPEEDS SET TO 92 ESP (2) CODE 3/ FAN SPEED 4/ 54 ESP SETTING. ALL FAN SPEEDS SET TO 54 ESP (3) O.S.A. SUPPLIED BY SF 1-2 WITH SEPARATE SUPPLY GRILLE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 117A 1 DO 14 X 14 1.36 227 310 238 323 TOTAL (310)(323) REMARKS: 10/29/2021 79 FC-B1-15 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/1/2021 Page:80 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 1,450 1,478 800 825 Total CFM - Outlet 1,450 1,478 800 825 R/A CFM NS 1,072 NS 506 O/A CFM 395 406 310 319 Static Pressure (Total/Ext)0.35"0.35"0.35"0.16" Inlet Pressure -0.13"-0.07" Discharge Pressure 0.22"0.09" Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 207 208/230 208 Amperage 2.5 1.5 2.3 0.9 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-B1-16 FC-B1-17 ABOVE CEILING RM 120 ABOVE CEILING RM 121 120 4TH GRADE CLASSROOM 121 WORLD ALNGUAGE CLASSRM LG LG ARNU363M3A4 ARNU243M2A4 008KCEA16M36 011KCXM0G738 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 101 ESP SETTING. ALL FAN SPEEDS SET TO 101 ESP (2) CODE 3/ FAN SPEED 4/ 82 ESP SETTING. ALL FAN SPEEDS SET TO 82 ESP DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 120 1 CD 2410 1.0 *365 *368 120 2 CD 2410 1.0 *365 *362 120 3 CD 2410 1.0 *365 *377 120 4 CD 2410 1.0 *365 *371 TOTAL (1,460)(1478) OUTSIDE AIR LOUVER 1 RG 42" X 18"1.0 *395 *406 TOTAL (395)(406) REMARKS: 11/1/2021 81 FC-B1-16 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 121 1 CD 2410 1.0 *200 *203 121 2 CD 2410 1.0 *200 *201 121 3 CD 2410 1.0 *200 *207 121 4 CD 2410 1.0 *200 *214 TOTAL (800)(825) OUTSIDE AIR LOUVER 1 RG 42" X 18"1.0 *310 *319 TOTAL (310)(319) REMARKS: 11/1/2021 82 FC-B1-17 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/5/2021 Page:83 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 1,450 1,486 1,450 1,470 Total CFM - Outlet 1450 1,486 1,450 1,470 R/A CFM NS 1,030 1,450 1,470 O/A CFM 450 456 -0--0- Static Pressure (Total/Ext)0.35"0.31"0.00"DUCTLESS Inlet Pressure -0.09"DUCTLESS Discharge Pressure 0.22"DUCTLESS Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD. (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 207 208/230 207 Amperage 2.5 1.4 2.5 0.1 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD. (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-B1-18 FC-B1-19 ABOVE CEILING RM 122 128 ELECTRICAL 122 LOWER SCHOOL SCIENCE LAB 128 ELECTRICAL LG LG ARNU363M3A4 ARNU363M3A4 008KCSF16M30 009KCFT11U59 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 101 ESP SETTING. ALL FAN SPEEDS SET TO 101 ESP (2) CODE 3/ FAN SPEED 4/ 71 ESP SETTING. ALL FAN SPEEDS SET TO 71 ESP DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 122 1 CD 2410 1.0 *365 *372 122 2 CD 2410 1.0 *365 *369 122 3 CD 2410 1.0 *365 *368 122 4 CD 2410 1.0 *365 *377 TOTAL (1,460)(1,486) OUTSIDE AIR LOUVER 1 RG 42" X 18"1.0 *450 *456 TOTAL (450)(456) REMARKS: 11/1/2021 84 FC-B1-18 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 128 1 DO 12 X 48 4.0 363 1,450 368 1,470 TOTAL (1,450)(1,470) REMARKS: 11/5/2021 85 FC-B1-19 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/1/2021 Page:86 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 240 257 285 293 Total CFM - Outlet 240 257 285 293 R/A CFM 240 257 NS 293 O/A CFM -0--0-90 0 (3) Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS Inlet Pressure DUCTLESS DUCTLESS Discharge Pressure DUCTLESS DUCTLESS Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 206 Amperage 0.25 0.1 0.20 0.1 Motor RPM 3 SPEED HIGH SPD (2)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-B1-20 FC-C2-2 127 DATA ROM ABOVE CEILING 127 DATA 211A COLLAB LG LG ARNU053SJA4 ARNU093TRD4 010KCDG1AD58 012KCCV0TW87 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 58 ESP SETTING. ALL FAN SPEEDS SET TO 58 ESP (2) CODE 3/ FAN SPEED 4/ 54 ESP SETTING. ALL FAN SPEEDS SET TO 54 ESP (3) O.S.A. SUPPLIED BY SF 2-2 WITH SEPARATE SUPPLY GRILLE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 127 1 DO 4" X 28"0.77 311 240 334 257 TOTAL (240)(257) REMARKS: 11/1/2021 87 FC-B1-20 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 211A 1 DO 14 X 14 1.36 209 285 216 293 TOTAL (285)(293) REMARKS: 10/26/2021 88 FC-C2-2 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/26/2021 Page:89 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 800 803 800 805 Total CFM - Outlet 800 803 800 805 R/A CFM NS 479 NS 434 O/A CFM 310 324 310 321 Static Pressure (Total/Ext)0.35 0.15"0.35"0.20" Inlet Pressure -0.09"-0.05" Discharge Pressure 0.06"0.15" Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 208 Amperage 2.3 1.4 2.3 1.2 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-C2-3 FC-C2-4 ABOVE CEILING ABOVE CEILING 212 5TH GRADE CLASSROOM 213 6TH-8TH CLASSROOM LG LG ARNU243M2A4 ARNU243M2A4 011KCCV0G699 011KCHE0G697 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 84 ESP SETTING. ALL FAN SPEEDS SET TO 84 ESP (2) CODE 3/ FAN SPEED 4/ 92 ESP SETTING. ALL FAN SPEEDS SET TO 92 ESP DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 212 1 CD 2410 1.0 *200 *203 212 2 CD 2410 1.0 *200 *192 212 3 CD 2410 1.0 *200 *211 212 4 CD 2410 1.0 *200 *197 TOTAL (800)(803) OUTSIDE AIR SYSTEM 207 1 DT 10" RD 0.55 564 310 590 324 TOTAL (310)(324) REMARKS: 10/26/2021 90 FC-C2-3 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: PROJECT: POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE A-1 743 B-1 689 1 " Dia x 0.026 =" A-2 739 B-2 703 2 " Dia x 0.082 =" A-3 754 B-3 688 3 " Dia x 0.146 =" A-4 727 B-4 582 4 " Dia x 0.226 =" A-5 356 B-5 541 5 " Dia x 0.342 =" A-6 358 B-6 587 6 " Dia x 0.685 =" A-7 273 B-7 652 7 " Dia x 0.774 =" A-8 303 B-8 739 8 " Dia x 0.854 =" A-9 B-9 9 " Dia x 0.918 =" A-10 B-10 10 " Dia x 0.974 =" SUBTOTAL SUBTOTAL (TOTAL FPM)DIVIDED BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM 9,434 16 590 0.55 324 COMMENTS:D DUCT SIZE 10" E AREA 1 S FPM 564 I CFM 310 G N T DUCT SIZE O.D.10" E DUCT SIZE I.D.10" S AREA 0.55 T CENTERLINE S.P.-0.04 AVERAGE FPM 590 D CFM MEASURED 324 A TEMP. CORRECTION 0 T ALT. CORRECTION 0 A ACTUAL CFM 324 10/26/2021 91SYSTEM #:FC-C2-3 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 ROUND DUCT TRAVERSE READINGS INSTRUMENT USED: ARIFOIL DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 213 1 CD 2410 1.0 *200 *198 213 2 CD 2410 1.0 *200 *203 213 3 CD 2410 1.0 *200 *196 213 4 CD 2410 1.0 *200 *208 TOTAL (800)(805) OUTSIDE AIR SYSTEM 213 1 DT 10" RD 0.55 564 310 584 321 TOTAL (310)(321) REMARKS: 10/26/2021 92 FC-C2-4 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: PROJECT: POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE A-1 579 B-1 475 1 " Dia x 0.026 =" A-2 533 B-2 574 2 " Dia x 0.082 =" A-3 595 B-3 457 3 " Dia x 0.146 =" A-4 572 B-4 633 4 " Dia x 0.226 =" A-5 553 B-5 697 5 " Dia x 0.342 =" A-6 528 B-6 691 6 " Dia x 0.685 =" A-7 582 B-7 700 7 " Dia x 0.774 =" A-8 585 B-8 583 8 " Dia x 0.854 =" A-9 B-9 9 " Dia x 0.918 =" A-10 B-10 10 " Dia x 0.974 =" SUBTOTAL SUBTOTAL (TOTAL FPM)DIVIDED BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM 9,336 16 584 0.55 321 COMMENTS:D DUCT SIZE 10" E AREA 1 S FPM 564 I CFM 310 G N T DUCT SIZE O.D.10" E DUCT SIZE I.D.10" S AREA 0.55 T CENTERLINE S.P.-0.03 AVERAGE FPM 584 D CFM MEASURED 321 A TEMP. CORRECTION 0 T ALT. CORRECTION 0 A ACTUAL CFM 321 10/26/2021 93SYSTEM #:FC-C2-4 OSA HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 ROUND DUCT TRAVERSE READINGS INSTRUMENT USED: AIRFOIL Date:10/28/2021 Page:94 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 800 806 800 801 Total CFM - Outlet 800 806 800 801 R/A CFM NS 488 NS 465 O/A CFM 310 317 310 334 Static Pressure (Total/Ext)0.35"0.18"0.35"0.20" Inlet Pressure -0.04"-0.04" Discharge Pressure 0.14"0.16" Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 207 208/230 206 Amperage 2.3 1.3 2.3 0.9 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-C2-5 FC-C2-6 ABOVE CEILING ABOVE CEILING 214 6TH 8TH CLASSROOM 215 6TH 8TH CLASSROOM LG LG ARNU243M2A4 ARNU243M2A4 011KCZP0G725 011KCVU0G695 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 90 ESP SETTING. ALL FAN SPEEDS SET TO 90 ESP (2) CODE 3/ FAN SPEED 4/ 91 ESP SETTING. ALL FAN SPEEDS SET TO 91 ESP DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 214 1 CD 2410 1.0 *200 *198 214 2 CD 2410 1.0 *200 *191 214 3 CD 2410 1.0 *200 *206 214 4 CD 2410 1.0 *200 *211 TOTAL (800)(806) OUTSIDE AIR SYSTEM 214 1 DT 10" RD 0.55 564 310 578 317 TOTAL (310)(317) REMARKS: 10/26/2021 95 FC-C2-5 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: PROJECT: POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE A-1 575 B-1 573 1 " Dia x 0.026 =" A-2 556 B-2 628 2 " Dia x 0.082 =" A-3 591 B-3 573 3 " Dia x 0.146 =" A-4 580 B-4 616 4 " Dia x 0.226 =" A-5 571 B-5 663 5 " Dia x 0.342 =" A-6 502 B-6 595 6 " Dia x 0.685 =" A-7 513 B-7 652 7 " Dia x 0.774 =" A-8 288 B-8 674 8 " Dia x 0.854 =" A-9 B-9 9 " Dia x 0.918 =" A-10 B-10 10 " Dia x 0.974 =" SUBTOTAL SUBTOTAL (TOTAL FPM)DIVIDED BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM 9,252 16 578 0.55 317 COMMENTS:D DUCT SIZE 10" E AREA 1 S FPM 564 I CFM 310 G N T DUCT SIZE O.D.10" E DUCT SIZE I.D.10" S AREA 0.55 T CENTERLINE S.P.-0.04 AVERAGE FPM 578 D CFM MEASURED 317 A TEMP. CORRECTION 0 T ALT. CORRECTION 0 A ACTUAL CFM 317 10/26/2021 96SYSTEM #:FC-C2-5 OSA HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 ROUND DUCT TRAVERSE READINGS INSTRUMENT USED: AIRFOIL DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 215 1 CD 2410 1.0 *200 *199 215 2 CD 2410 1.0 *200 *203 215 3 CD 2410 1.0 *200 *205 215 4 CD 2410 1.0 *200 *194 TOTAL (800)(801) OUTSIDE AIR SYSTEM 215 1 DT 10" RD 0.55 564 310 609 334 TOTAL (310)(334) REMARKS: 10/28/2021 97 FC-C2-6 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: PROJECT: POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE A-1 626 B-1 626 1 " Dia x 0.026 =" A-2 630 B-2 607 2 " Dia x 0.082 =" A-3 614 B-3 624 3 " Dia x 0.146 =" A-4 613 B-4 625 4 " Dia x 0.226 =" A-5 647 B-5 559 5 " Dia x 0.342 =" A-6 608 B-6 542 6 " Dia x 0.685 =" A-7 614 B-7 561 7 " Dia x 0.774 =" A-8 670 B-8 582 8 " Dia x 0.854 =" A-9 B-9 9 " Dia x 0.918 =" A-10 B-10 10 " Dia x 0.974 =" SUBTOTAL SUBTOTAL (TOTAL FPM)DIVIDED BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM 9,748 16 609 0.55 334 COMMENTS:D DUCT SIZE 10" E AREA 1 S FPM 564 I CFM 310 G N T DUCT SIZE O.D.10" E DUCT SIZE I.D.10" S AREA 0.55 T CENTERLINE S.P.-0.04 AVERAGE FPM 609 D CFM MEASURED 334 A TEMP. CORRECTION 0 T ALT. CORRECTION 0 A ACTUAL CFM 309 10/28/2021 98SYSTEM #:FC-C2-6 OSA HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 ROUND DUCT TRAVERSE READINGS INSTRUMENT USED: AIRFOIL Date:10/28/2021 Page:99 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 310 314 800 802 Total CFM - Outlet 310 314 800 802 R/A CFM 310 314 NS 479 O/A CFM 105 0 (3)310 322 Static Pressure (Total/Ext)DUCTLESS 0.35"0.23" Inlet Pressure DUCTLESS -0.05" Discharge Pressure DUCTLESS 0.18" Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 206 Amperage 0.20 0.1 2.3 1.1 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-C2-7 FC-C2-8 ABOVE CEILING ABOVE CEILING 249 COLLAB 216 6TH 8TH GRADE LG LG ARNU123TRD4 ARNU243M2A4 012KCZP0U053 011KCBD0G693 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 56 ESP SETTING. ALL FAN SPEEDS SET TO 56 ESP (2) CODE 3/ FAN SPEED 4/ 92 ESP SETTING. ALL FAN SPEEDS SET TO 92 ESP (3) O.S.A. SUPPLIED BY SF 2-2 WITH SEPARATE SUPPLY GRILLE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 211A 1 DO 14 X 14 1.36 228 310 231 314 TOTAL (310)(314) REMARKS: 10/28/2021 99 FC-C2-7 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 216 1 CD 2410 1.0 *200 *209 216 2 CD 2410 1.0 *200 *198 216 3 CD 2410 1.0 *200 *202 216 4 CD 2410 1.0 *200 *193 TOTAL (800)(802) OUTSIDE AIR SYSTEM 216 1 DT 10" RD 0.55 564 310 588 323 TOTAL (310)(323) REMARKS: 10/28/2021 100 FC-C2-8 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: PROJECT: POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE A-1 585 B-1 488 1 " Dia x 0.026 =" A-2 537 B-2 612 2 " Dia x 0.082 =" A-3 550 B-3 627 3 " Dia x 0.146 =" A-4 593 B-4 607 4 " Dia x 0.226 =" A-5 608 B-5 618 5 " Dia x 0.342 =" A-6 579 B-6 585 6 " Dia x 0.685 =" A-7 602 B-7 638 7 " Dia x 0.774 =" A-8 534 B-8 651 8 " Dia x 0.854 =" A-9 B-9 9 " Dia x 0.918 =" A-10 B-10 10 " Dia x 0.974 =" SUBTOTAL SUBTOTAL (TOTAL FPM)DIVIDED BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM 9,413 16 588 0.55 323 COMMENTS:D DUCT SIZE 10" E AREA 1 S FPM 564 I CFM 310 G N T DUCT SIZE O.D.10" E DUCT SIZE I.D.10" S AREA 0.55 T CENTERLINE S.P.-0.04 AVERAGE FPM 588 D CFM MEASURED 323 A TEMP. CORRECTION 0 T ALT. CORRECTION 0 A ACTUAL CFM 323 10/28/2021 101SYSTEM #:FC-C2-8 OSA HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 ROUND DUCT TRAVERSE READINGS INSTRUMENT USED: AIRFOIL Date:10/28/2021 Page:102 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 800 804 390 406 Total CFM - Outlet 800 804 390 406 R/A CFM NS 486 390 406 O/A CFM 310 319 135 0 (3) Static Pressure (Total/Ext)0.35"0.15"0.00"DUCTLESS Inlet Pressure -0.03"DUCTLESS Discharge Pressure 0.12"DUCTLESS Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 207 208/230 206 Amperage 2.3 1.1 0.20 0.1 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-C2-9 FC-C2-10 ABOVE CEILING ABOVE CEILING 217 6TH 8TH GRADE CLASSROOM 218 COLLAB LG LG ARNU243M2A4 ARNU153TQD4 011KCZP0G677 012KCFT0AY79 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 89 ESP SETTING. ALL FAN SPEEDS SET TO 89 ESP (2) CODE 3/ FAN SPEED 4/ 60 ESP SETTING. ALL FAN SPEEDS SET TO 60 ESP (3) O.S.A. SUPPLIED BY SF 2-3 WITH SEPARATE SUPPLY GRILLE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 217 1 CD 2410 1.0 *200 *204 217 2 CD 2410 1.0 *200 *201 217 3 CD 2410 1.0 *200 *191 217 4 CD 2410 1.0 *200 *208 TOTAL (800)(804) OUTSIDE AIR 217 1 DT 10" RD 0.55 564 310 581 319 TOTAL (310)(319) REMARKS: 10/28/2021 103 FC-C2-9 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: PROJECT: POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE A-1 614 B-1 600 1 " Dia x 0.026 =" A-2 571 B-2 572 2 " Dia x 0.082 =" A-3 554 B-3 571 3 " Dia x 0.146 =" A-4 575 B-4 613 4 " Dia x 0.226 =" A-5 593 B-5 558 5 " Dia x 0.342 =" A-6 587 B-6 558 6 " Dia x 0.685 =" A-7 611 B-7 533 7 " Dia x 0.774 =" A-8 588 B-8 598 8 " Dia x 0.854 =" A-9 B-9 9 " Dia x 0.918 =" A-10 B-10 10 " Dia x 0.974 =" SUBTOTAL SUBTOTAL (TOTAL FPM)DIVIDED BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM 9,296 16 581 0.55 319 COMMENTS:D DUCT SIZE 10" E AREA 1 S FPM 564 I CFM 310 G N T DUCT SIZE O.D.10" E DUCT SIZE I.D.10" S AREA 0.55 T CENTERLINE S.P.-0.02 AVERAGE FPM 581 D CFM MEASURED 319 A TEMP. CORRECTION 0 T ALT. CORRECTION 0 A ACTUAL CFM 319 10/28/2021 104SYSTEM #:FC-C2-9 OSA HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 ROUND DUCT TRAVERSE READINGS INSTRUMENT USED: AIRFOIL DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 218 1 DO 14 X 14 1.36 286 390 299 406 TOTAL (390)(406) REMARKS: 11/1/2021 105 FC-C2-10 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/28/2021 Page:106 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 800 821 390 401 Total CFM - Outlet 800 821 390 401 R/A CFM NS 504 390 401 O/A CFM 310 318 120 0 (3) Static Pressure (Total/Ext)0.35"0.23"0.00"DUCTLESS Inlet Pressure -0.06"DUCTLESS Discharge Pressure 0.17"DUCTLESS Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 206 Amperage 2.3 1.3 0.2 0.1 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-C2-11 FC-C2-12 ABOVE CEILING ABOVE CEILING 219 6TH 8TH CLASSROOM 254 COLLAB LG LG ARNU243M2A4 ARNU153TQD4 011KCDG0G682 012KCDG0N570 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 94 ESP SETTING. ALL FAN SPEEDS SET TO 94 ESP (2) CODE 3/ FAN SPEED 4/ 58 ESP SETTING. ALL FAN SPEEDS SET TO 58 ESP (3) O.S.A. SUPPLIED BY SF 2-3 WITH SEPARATE SUPPLY GRILLE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 219 1 CD 2410 1.0 *200 *208 219 2 CD 2410 1.0 *200 *198 219 3 CD 2410 1.0 *200 *205 219 4 CD 2410 1.0 *200 *210 TOTAL (800)(821) OUTSIDE AIR 219 1 DT 10" RD 0.55 564 310 578 318 TOTAL (310)(318) REMARKS: 10/28/2021 107 FC-C2-11 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: PROJECT: POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE A-1 576 B-1 573 1 " Dia x 0.026 =" A-2 581 B-2 610 2 " Dia x 0.082 =" A-3 589 B-3 663 3 " Dia x 0.146 =" A-4 596 B-4 683 4 " Dia x 0.226 =" A-5 544 B-5 510 5 " Dia x 0.342 =" A-6 549 B-6 571 6 " Dia x 0.685 =" A-7 517 B-7 518 7 " Dia x 0.774 =" A-8 563 B-8 600 8 " Dia x 0.854 =" A-9 B-9 9 " Dia x 0.918 =" A-10 B-10 10 " Dia x 0.974 =" SUBTOTAL SUBTOTAL (TOTAL FPM)DIVIDED BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM 9,242 16 578 0.55 318 COMMENTS:D DUCT SIZE 10" E AREA 1 S FPM 564 I CFM 310 G N T DUCT SIZE O.D.10" E DUCT SIZE I.D.10" S AREA 0.55 T CENTERLINE S.P.-0.02 AVERAGE FPM 578 D CFM MEASURED 318 A TEMP. CORRECTION 0 T ALT. CORRECTION 0 A ACTUAL CFM 318 10/28/2021 108SYSTEM #:FC-C2-11 OSA HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 ROUND DUCT TRAVERSE READINGS INSTRUMENT USED: AIRFOIL DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 254 1 DO 14 X 14 1.36 286 390 295 401 TOTAL (390)(401) REMARKS: 10/28/2021 109 FC-C2-12 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:10/28/2021 Page:110 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 800 824 800 801 Total CFM - Outlet 800 824 800 801 R/A CFM NS 498 NS 492 O/A CFM 310 327 310 310 Static Pressure (Total/Ext)0.35"0.19"0.35"0.21" Inlet Pressure -0.07"-0.03" Discharge Pressure 0.12"0.18" Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 208 208/230 206 Amperage 2.3 0.9 2.3 1.2 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-C2-13 FC-C2-14 ABOVE CEILING ABOVE CEILING 220 6TH 8TH CLASSROOM 221 6TH 8TH CLASSROOM LG LG ARNU243M2A4 ARNU243M2A4 011KCCV0G675 011KCHE0G673 DIRECT DIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 90 ESP SETTING. ALL FAN SPEEDS SET TO 90 ESP (2) CODE 3/ FAN SPEED 4/ 97 ESP SETTING. ALL FAN SPEEDS SET TO 97 ESP DIRECT DIVE DIRECT DRIVEDIRECT DIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 220 1 CD 2410 1.0 *200 *218 220 2 CD 2410 1.0 *200 *197 220 3 CD 2410 1.0 *200 *217 220 4 CD 2410 1.0 *200 *192 TOTAL (800)(824) OUTSIDE AIR 220 1 DT 10" RD 0.55 564 310 595 327 TOTAL (310)(327) REMARKS: 10/28/2021 111 FC-C2-13 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: PROJECT: POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE A-1 -387 B-1 764 1 " Dia x 0.026 =" A-2 719 B-2 825 2 " Dia x 0.082 =" A-3 665 B-3 710 3 " Dia x 0.146 =" A-4 594 B-4 783 4 " Dia x 0.226 =" A-5 470 B-5 629 5 " Dia x 0.342 =" A-6 662 B-6 635 6 " Dia x 0.685 =" A-7 659 B-7 644 7 " Dia x 0.774 =" A-8 694 B-8 460 8 " Dia x 0.854 =" A-9 B-9 9 " Dia x 0.918 =" A-10 B-10 10 " Dia x 0.974 =" SUBTOTAL SUBTOTAL (TOTAL FPM)DIVIDED BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM 9,526 16 595 0.55 327 COMMENTS:D DUCT SIZE 10" E AREA 1 S FPM 564 I CFM 310 G N T DUCT SIZE O.D.10" E DUCT SIZE I.D.10" S AREA 0.55 T CENTERLINE S.P.-0.02 AVERAGE FPM 578 D CFM MEASURED 327 A TEMP. CORRECTION 0 T ALT. CORRECTION 0 A ACTUAL CFM 327 10/28/2021 112SYSTEM #:FC-C2-13 OSA HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 ROUND DUCT TRAVERSE READINGS INSTRUMENT USED: AIRFOIL DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 221 1 CD 2410 1.0 *200 *208 221 2 CD 2410 1.0 *200 *203 221 3 CD 2410 1.0 *200 *196 221 4 CD 2410 1.0 *200 *194 TOTAL (800)(801) OUTSIDE AIR 221 1 DT 10" RD 0.55 564 310 564 310 TOTAL (310)(310) REMARKS: 10/28/2021 113 FC-C2-14 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: PROJECT: POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE A-1 546 B-1 521 1 " Dia x 0.026 =" A-2 604 B-2 533 2 " Dia x 0.082 =" A-3 600 B-3 510 3 " Dia x 0.146 =" A-4 565 B-4 566 4 " Dia x 0.226 =" A-5 585 B-5 588 5 " Dia x 0.342 =" A-6 577 B-6 585 6 " Dia x 0.685 =" A-7 558 B-7 5567 7 " Dia x 0.774 =" A-8 525 B-8 608 8 " Dia x 0.854 =" A-9 B-9 9 " Dia x 0.918 =" A-10 B-10 10 " Dia x 0.974 =" SUBTOTAL SUBTOTAL (TOTAL FPM)DIVIDED BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM 9,038 16 564 0.55 310 COMMENTS:D DUCT SIZE 10" E AREA 1 S FPM 564 I CFM 310 G N T DUCT SIZE O.D.10" E DUCT SIZE I.D.10" S AREA 0.55 T CENTERLINE S.P.-0.04 AVERAGE FPM 564 D CFM MEASURED 310 A TEMP. CORRECTION 0 T ALT. CORRECTION 0 A ACTUAL CFM 310 10/28/2021 114SYSTEM #:FC-C2-14 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 ROUND DUCT TRAVERSE READINGS INSTRUMENT USED: AIRFOIL Date:11/3/2021 Page:115 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 800 829 800 820 Total CFM - Outlet 800 829 800 820 R/A CFM NS 520 NS 486 O/A CFM 310 309 310 334 Static Pressure (Total/Ext)0.35"0.19"0.35"0.19" Inlet Pressure -0.04"-0.03" Discharge Pressure 0.15"0.16" Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 208 208/230 206 Amperage 2.3 1.4 2.3 1.1 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. (1) CODE 3/ FAN SPEED 4/ 93 ESP SETTING. ALL FAN SPEEDS SET TO 93 ESP (2) CODE 3/ FAN SPEED 4/ 92 ESP SETTING. ALL FAN SPEEDS SET TO 92 ESP DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE 011KCLH0G776 011KCSF0G774 DIRECT DRIVE DIRECT DRIVE LG LG ARNU243M2A4 ARNU243M2A4 ABOVE CEILING RM 222 ABOVE CEILING RM 223 222 6TH 8TH CLASSROOM 223 6TH 8TH CLASSROOM HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-C2-15 FC-C2-16 DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 222 1 CD 2410 1.0 *200 *208 222 2 CD 2410 1.0 *200 *200 222 3 CD 2410 1.0 *200 *212 222 4 CD 2410 1.0 *200 *209 TOTAL (800)(829) OUTSIDE AIR 222 1 DT 10" RD 0.55 564 310 563 309 TOTAL (310)(309) REMARKS: 11/3/2021 116 FC-C2-15 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: PROJECT: POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE A-1 596 B-1 565 1 " Dia x 0.026 =0.32 " A-2 576 B-2 544 2 " Dia x 0.082 =1.05 " A-3 587 B-3 568 3 " Dia x 0.146 =1.94 " A-4 586 B-4 606 4 " Dia x 0.226 =3.23 " A-5 558 B-5 606 5 " Dia x 0.342 =6.77 " A-6 554 B-6 596 6 " Dia x 0.685 =8.06 " A-7 564 B-7 513 7 " Dia x 0.774 =8.95 " A-8 583 B-8 406 8 " Dia x 0.854 =9.68 " A-9 B-9 9 " Dia x 0.918 =" A-10 B-10 10 " Dia x 0.974 =" SUBTOTAL SUBTOTAL (TOTAL FPM)DIVIDED BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM 9007 16 563 0.55 309 COMMENTS:D DUCT SIZE 10" E AREA 1 S FPM 564 I CFM 310 G N T DUCT SIZE O.D.10" E DUCT SIZE I.D.10" S AREA 0.55 T CENTERLINE S.P.-0.02 AVERAGE FPM 563 D CFM MEASURED 309 A TEMP. CORRECTION NA T ALT. CORRECTION NA A ACTUAL CFM 309 11/3/2021 117SYSTEM #:FC-C2-15 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 ROUND DUCT TRAVERSE READINGS INSTRUMENT USED: AIRFOIL DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 223 1 CD 2410 1.0 *200 *208 223 2 CD 2410 1.0 *200 *204 223 3 CD 2410 1.0 *200 *195 223 4 CD 2410 1.0 *200 *213 TOTAL (800)(820) OUTSIDE AIR 223 1 DT 10" RD 0.55 564 310 608 334 TOTAL (310)(334) REMARKS: 11/3/2021 18 FC-C2-16 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: PROJECT: POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE A-1 591 B-1 615 1 " Dia x 0.026 =0.32 " A-2 553 B-2 520 2 " Dia x 0.082 =1.05 " A-3 579 B-3 655 3 " Dia x 0.146 =1.94 " A-4 632 B-4 598 4 " Dia x 0.226 =3.23 " A-5 620 B-5 673 5 " Dia x 0.342 =6.77 " A-6 598 B-6 644 6 " Dia x 0.685 =8.06 " A-7 619 B-7 638 7 " Dia x 0.774 =8.95 " A-8 599 B-8 592 8 " Dia x 0.854 =9.68 " A-9 B-9 9 " Dia x 0.918 =" A-10 B-10 10 " Dia x 0.974 =" SUBTOTAL SUBTOTAL (TOTAL FPM)DIVIDED BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM 9,726 16 608 0.55 334 COMMENTS:D DUCT SIZE 10" E AREA 1 S FPM 564 I CFM 310 G N T DUCT SIZE O.D.10" E DUCT SIZE I.D.10" S AREA 0.55 T CENTERLINE S.P.-0.04 AVERAGE FPM 608 D CFM MEASURED 334 A TEMP. CORRECTION 0 T ALT. CORRECTION 0 A ACTUAL CFM 334 11/3/2021 119SYSTEM #:FC-C2-16 OSA HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 ROUND DUCT TRAVERSE READINGS INSTRUMENT USED:AIRFOIL Date:11/3/2021 Page:120 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 800 809 800 813 Total CFM - Outlet 800 809 800 813 R/A CFM NS 499 NS 585 O/A CFM 310 310 230 228 Static Pressure (Total/Ext)0.35"0.18"0.35"0.23" Inlet Pressure -0.06"-0.05" Discharge Pressure 0.12"0.18" Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 207 208/230 207 Amperage 2.3 0.9 2.3 1.2 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. (1) CODE 3/ FAN SPEED 4/ 88 ESP SETTING. ALL FAN SPEEDS SET TO 88 ESP (2) CODE 3/ FAN SPEED 4/ 90 ESP SETTING. ALL FAN SPEEDS SET TO 90 ESP DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE 011KCKJ0G613 012KCAS0EW76 DIRECT DRIVE DIRECT DRIVE LG LG ARNU243M2A4 ARNU243M2A4 ABOVE CEILING 224 ABOVE CEILING 225 224 6TH 8TH CLASSROOM 225 6TH 8TH CLASSROOM HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-C2-17 FC-C2-18 DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 224 1 CD 2410 1.0 *200 *195 224 2 CD 2410 1.0 *200 *198 224 3 CD 2410 1.0 *200 *203 224 4 CD 2410 1.0 *200 *213 TOTAL (800)(809) OUTSIDE AIR 224 1 DT 10" RD 0.55 564 310 564 310 TOTAL (310)(310) REMARKS: 11/3/2021 121 FC-C2-17 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: PROJECT: POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE A-1 496 B-1 639 1 " Dia x 0.026 =0.32 " A-2 499 B-2 613 2 " Dia x 0.082 =1.05 " A-3 572 B-3 663 3 " Dia x 0.146 =1.94 " A-4 566 B-4 517 4 " Dia x 0.226 =3.23 " A-5 561 B-5 541 5 " Dia x 0.342 =6.77 " A-6 526 B-6 606 6 " Dia x 0.685 =8.06 " A-7 559 B-7 575 7 " Dia x 0.774 =8.95 " A-8 571 B-8 514 8 " Dia x 0.854 =9.68 " A-9 B-9 9 " Dia x 0.918 =" A-10 B-10 10 " Dia x 0.974 =" SUBTOTAL SUBTOTAL (TOTAL FPM)DIVIDED BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM 9,017 16 564 0.55 310 COMMENTS:D DUCT SIZE 10" E AREA 1 S FPM 564 I CFM 310 G N T DUCT SIZE O.D.10" E DUCT SIZE I.D.10" S AREA 0.55 T CENTERLINE S.P.-0.05 AVERAGE FPM 564 D CFM MEASURED 310 A TEMP. CORRECTION NA T ALT. CORRECTION NA A ACTUAL CFM 310 11/3/2021 122SYSTEM #:FC-C2-17 OSA HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 ROUND DUCT TRAVERSE READINGS INSTRUMENT USED: AIRFOIL DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 225 1 CD 2410 1.0 *200 *195 225 2 CD 2410 1.0 *200 *205 225 3 CD 2410 1.0 *200 *200 225 4 CD 2410 1.0 *200 *213 TOTAL (800)(813) OUTSIDE AIR 225 1 DT 10" RD 0.55 418 230 416 228 TOTAL (230)(228) REMARKS: 11/3/2021 123 FC-C2-18 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: PROJECT: POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE A-1 356 B-1 490 1 " Dia x 0.026 =0.32 " A-2 406 B-2 468 2 " Dia x 0.082 =1.05 " A-3 380 B-3 488 3 " Dia x 0.146 =1.94 " A-4 367 B-4 489 4 " Dia x 0.226 =3.23 " A-5 449 B-5 434 5 " Dia x 0.342 =6.77 " A-6 392 B-6 369 6 " Dia x 0.685 =8.06 " A-7 444 B-7 393 7 " Dia x 0.774 =8.95 " A-8 358 B-8 378 8 " Dia x 0.854 =9.68 " A-9 B-9 9 " Dia x 0.918 =" A-10 B-10 10 " Dia x 0.974 =" SUBTOTAL SUBTOTAL (TOTAL FPM)DIVIDED BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM 6,661 16 416 0.55 228 COMMENTS:D DUCT SIZE 10" E AREA 1 S FPM 418 I CFM 230 G N T DUCT SIZE O.D.10" E DUCT SIZE I.D.10" S AREA 0.55 T CENTERLINE S.P.-0.02 AVERAGE FPM 416 D CFM MEASURED 228 A TEMP. CORRECTION NA T ALT. CORRECTION NA A ACTUAL CFM 228 11/3/2021 124SYSTEM #:FC-C2-18 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 ROUND DUCT TRAVERSE READINGS INSTRUMENT USED: AIRFOIL Date:11/4/2021 Page:125 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 800 828 500 514 Total CFM - Outlet 800 828 500 514 R/A CFM NS 597 500 514 O/A CFM 230 231 -0--0- Static Pressure (Total/Ext)0.35"0.16"0.00"DUCTLESS Inlet Pressure -0.03"DUCTLESS Discharge Pressure 0.13"DUCTLESS Fan RPM 3 SPEED HIGH SPD (1)3 SPEED LOW SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 207 Amperage 2.3 1.4 0.52 0.3 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED LOW SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. (1) CODE 3/ FAN SPEED 4/ 88 ESP SETTING. ALL FAN SPEEDS SET TO 88 ESP (2) CODE 3/ FAN SPEED 4/ 20 ESP SETTING. ALL FAN SPEEDS SET TO 20 ESP DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE 012KCSF0EW66 009KCYQ16M58 DIRECT DRIVE DIRECT DRIVE LG LG ARNU183M2A4 ARNU183SKA4 ABOVE CEILING RM 226 WAL MOUNT 243 226 6TH 8TH CLASSROOM 233 ELECTRICAL HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-C2-19 FC-C2-20 DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 226 1 CD 2410 1.0 *200 *200 226 2 CD 2410 1.0 *200 *211 226 3 CD 2410 1.0 *200 *209 226 4 CD 2410 1.0 *200 *208 TOTAL (800)(828) OUTSIDE AIR 226 1 DT 10" RD 0.55 418 230 421 231 TOTAL (230)(231) REMARKS: 11/4/2021 126 FC-C2-19 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: PROJECT: POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE A-1 460 B-1 491 1 " Dia x 0.026 =0.32 " A-2 512 B-2 485 2 " Dia x 0.082 =1.05 " A-3 467 B-3 479 3 " Dia x 0.146 =1.94 " A-4 341 B-4 447 4 " Dia x 0.226 =3.23 " A-5 320 B-5 419 5 " Dia x 0.342 =6.77 " A-6 328 B-6 371 6 " Dia x 0.685 =8.06 " A-7 392 B-7 455 7 " Dia x 0.774 =8.95 " A-8 366 B-8 408 8 " Dia x 0.854 =9.68 " A-9 B-9 9 " Dia x 0.918 =" A-10 B-10 10 " Dia x 0.974 =" SUBTOTAL SUBTOTAL (TOTAL FPM)DIVIDED BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM 6,741 16 421 0.55 231 COMMENTS:D DUCT SIZE 10" E AREA 1 S FPM 418 I CFM 230 G N T DUCT SIZE O.D.10" E DUCT SIZE I.D.10" S AREA 0.55 T CENTERLINE S.P.-0.03 AVERAGE FPM 421 D CFM MEASURED 231 A TEMP. CORRECTION NA T ALT. CORRECTION NA A ACTUAL CFM 231 11/4/2021 127SYSTEM #:FC-C2-19 OSA HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 ROUND DUCT TRAVERSE READINGS INSTRUMENT USED: AIRFOIL DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 223 1 DO 34" X 4"0.94 531 500 547 514 TOTAL (500)(514) REMARKS: (1) T STAT IS NOT WORKING, UNABLE TO BALANCE 11/4/2021 11/4/2021 128 FC-C2-20 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/4/2021 Page:129 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 240 258 1,730 1754 Total CFM - Outlet 240 258 1,730 1754 R/A CFM 240 258 NS 1076 O/A CFM -0--0-665 678 Static Pressure (Total/Ext)0.00"DUCTLESS 0.47"0.40" Inlet Pressure DUCTLESS -0.12" Discharge Pressure DUCTLESS 0.28" Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 207 208/230 206 Amperage 0.25 0.1 5.2 2.3 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. (1) CODE 3/ FAN SPEED 4/ 74 ESP SETTING. ALL FAN SPEEDS SET TO 74 ESP (2) CODE 3/ FAN SPEED 4/ 78 ESP SETTING. ALL FAN SPEEDS SET TO 78 ESP DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE 010KCKJ1AD61 104KCYQ04258 DIRECT DRIVE DIRECT DRIVE LG LG ARNU053SJA4 ARNU363B8A4 WAL MOUNT RM 233B ABOVE CEILING RM 126 233B DATA 126 LOWER SCHOOL ART LAB HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-C2-21 FC-D1-1 DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 223 1 DO 3" X 28"0.58 413 240 445 258 TOTAL (240)(258) REMARKS: 11/4/2021 130 FC-C2-21 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 126 1 CD 2410 1.0 *290 *294 126 2 CD 2410 1.0 *290 *281 126 3 CD 2410 1.0 *290 *306 126 4 CD 2410 1.0 *290 *278 126 5 CD 2410 1.0 *290 *297 126 6 CD 2410 1.0 *290 *298 TOTAL (1,740)*(1754) OUTSIDE AIR LOUVER 1 RG 48" X 12"1.0 *665 *678 TOTAL (665)(678) REMARKS: 11/1/2021 131 FC-D1-1 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/2/2021 Page:132 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 1,915 2,015 800 812 Total CFM - Outlet 1,915 2,015 800 812 R/A CFM NS 1,297 NS 489 O/A CFM 705 718 310 323 Static Pressure (Total/Ext)0.47"0.39"0.45"0.26" Inlet Pressure 0.21"-0.08" Discharge Pressure -0.18"0.18" Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 207 208/230 206 Amperage 5.2 1.2 2.3 1.1 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. (1) CODE 3/ FAN SPEED 4/ 80 ESP SETTING. ALL FAN SPEEDS SET TO 80 ESP (2) CODE 3/ FAN SPEED 4/ 92 ESP SETTING. ALL FAN SPEEDS SET TO 92 ESP DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE 012KCYQ10698 011KCCV0G723 DIRECT DRIVE DIRECT DRIVE LG LG ARNU423B8A4 ARNU243M2A4 ABOVE CEILING RM 125 ABOVE CEILING RM 125A 125 LOWER SCHOOL ART LAB 125A CERAMICS HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-D1-3 FC-D1-4 DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 125 1 CD 2410 1.0 *320 *326 125 2 CD 2410 1.0 *320 *342 125 3 CD 2410 1.0 *320 *328 125 4 CD 2410 1.0 *320 *337 125 5 CD 2410 1.0 *320 *344 125 6 CD 2410 1.0 *320 *338 TOTAL (1,920)(2,015) OUTSIDE AIR 125 1 RG 48" X 12"1.0 *705 *718 TOTAL (705)(718) REMARKS: 11/1/2021 133 FC-D1-3 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 125A 1 CD 2410 1.0 *195 *196 125A 2 CD 2410 1.0 *195 *183 125A 3 CD 2410 1.0 *195 *199 125A 4 CD 2410 1.0 *195 *201 125B 5 SWG 10" X 6"1.0 *30 *33 TOTAL (810)(812) OUTSIDE AIR 125A 1 RG 48" X 12"1.0 *310 *323 TOTAL (310)(323) REMARKS: 11/2/2021 134 FC-D1-4 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/2/2021 Page:135 Project Name: Equipment Location Area Served Equipment Manufacturer Model A Serial Number Specified Actual Specified Actual Total CFM - fan 1,750 1,743 265 277 Total CFM - Outlet 1,750 1,743 265 277 R/A CFM NS 1,052 NS 244 O/A CFM 655 691 30 33 (3) Static Pressure (Total/Ext)0.35"0.19"0.00"DUCTLESS Inlet Pressure -0.15"DUCTLESS Discharge Pressure 0.04"DUCTLESS Fan RPM 3 SPEED HIGH SPD. (1) 3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NA NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 207 208/230 207 Amperage 2.5 1.8 0.20 0.1 Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. (1) CODE 3/ FAN SPEED 4/ 110 ESP SETTING. ALL FAN SPEEDS SET TO 110 ESP (2) CODE 3/ FAN SPEED 4/ 51 ESP SETTING. ALL FAN SPEEDS SET TO 51 ESP (3) FOR O.S.A. SEE SF 1-3 AIR DISTRIBUTION SHEET. DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE 011KCCV0RT87 011KCPY0U208 DIRECT DRIVE DIRECT DRIVE LG LG ARNU543M3A4 ARNU053TRD4 ABOVE CEILING 124 WOODSHOP ABOVE CEILING RM 124 WOODSHOP 124A OFFICE HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-D1-5 FC-D1-6 DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 124 1 SG 16" X 10"0.88 500 440 412 363 124 2 SG 16" X 10"0.88 500 440 340 299 124 3 SG 16" X 10"0.88 500 440 536 472 124 4 SG 16" X 10"0.88 500 440 692 609 TOTAL (1,760)(1,743) OUTSIDE AIR LOUVER 1 RG 46" X 18"1.0 *655 *691 TOTAL (655)(691) REMARKS: 11/5/2021 136 FC-D1-5 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 124A 1 DO 14" X 14"1.36 195 265 198 270 TOTAL (265)(270) REMARKS: 10/25/2021 137 FC-A1-3 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/2/2021 Page:138 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 2,260 2,188 1,250 1,264 Total CFM - Outlet 2,260 2,188 1,250 1,264 R/A CFM NS 1,384 NS 853 O/A CFM 765 804 400 411 Static Pressure (Total/Ext)0.4"0.44"0.35"0.28" Inlet Pressure -0.39"-0.12" Discharge Pressure 0.05"0.16" Fan RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2) Specified Actual Specified Actual Motor Manufacturer NA NA Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 206 Amperage 5.2 2.5 2.5 1.4 Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-D1-7 FC-D1-8 123 MAKERSPACE 123A TECH LAB 123 MAKERSPACE 123A TECH LAB LG LG ARNU763B8A4 ARNU283M3A4 011KCVU0L327 011KCPY1C280 DIRECT DRIVE DIRECT DRIVE (1) CODE 3/ FAN SPEED 4/ 84 ESP SETTING. ALL FAN SPEEDS SET TO 84 ESP (2) CODE 3/ FAN SPEED 4/ 92 ESP SETTING. ALL FAN SPEEDS SET TO 92 ESP DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 123 1 SG 16" X 10"0.83 337 280 322 267 123 2 SG 16" X 10"0.83 337 280 327 272 123 3 SG 16" X 8"0.66"424 280 253 167 123 4 SG 16" X 8"0.66"424 280 455 300 123 5 SG 16" X 10"0.83 337 280 304 252 123 6 SG 16" X 10"0.83 337 280 487 389 123 7 SG 16" X 8"0.66"424 280 332 219 123 8 SG 16" X 8"0.66"424 280 487 322 TOTAL (2,240)(1)(2,188) OUTSIDE AIR LOUVER 1 RG 42" X 18"1.0 *765 *804 TOTAL (765)(804) REMARKS: (1) DAMPERS INSTALLED FOR BRANCHES BUT NOT INDIVIDUAL GRILLES. SET FOR TOTAL . SERVES COMMON AREA. 11/2/2021 139 FC-D1-7 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 123A 1 CD 2410 1.0 *315 *322 123A 2 CD 2410 1.0 *315 *315 123A 3 CD 2410 1.0 *315 *317 123A 4 CD 2410 1.0 *315 *310 TOTAL (1,260)(1,264) OUTSIDE AIR LOUVER 1 RG 42" X 18"1.0 *400 *411 TOTAL (400)(411) REMARKS: 11/2/2021 140 FC-D1-8 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/5/2021 Page:141 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 2,545 2,593 800 834 Total CFM - Outlet 2,545 2,593 800 834 R/A CFM NS 2,593 NS 600 O/A CFM -0--0-225 234 Static Pressure (Total/Ext)0.25"DUCTLESS 0.35"0.20" Inlet Pressure DUCTLESS -0.04" Discharge Pressure DUCTLESS 0.16" Fan RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NA NA Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 209 208/230 207 Amperage 2.5 1.7 2.3 0.9 Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. (1) CODE 3/ FAN SPEED 4/ ESP SETTING. ALL FAN SPEEDS SET TO ESP (2) CODE 3/ FAN SPEED 4/ 90 ESP SETTING. ALL FAN SPEEDS SET TO 90 ESP DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE 011KCCV0RT87 012KCLH0EW68 DIRECT DRIVE DIRECT DRIVE LG LG ARNU963B8A4 ARNU183M2A4 125B KILN ROOM ABOVE CEILING RM 277 125B KILN ROOM 277 6TH 8TH CLASSROOM HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-D1-9 FC-D2-1 DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 128 1 DO 60" X 15"6.25 407 2,545 415 2,593 TOTAL (2,545)(2,593) REMARKS: 11/5/2021 142 FC-B1-19 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 227 1 CD 2410 1.0 *200 *202 227 2 CD 2410 1.0 *200 *213 227 3 CD 2410 1.0 *200 *209 227 4 CD 2410 1.0 *200 *210 TOTAL (800)(834) OUTSIDE AIR 227 1 DT 10" RD 0.55 409 225 427 234 TOTAL (225)(234) REMARKS: 11/2/2021 143 FC-D2-1 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: PROJECT: POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE A-1 396 B-1 412 1 " Dia x 0.026 =0.32 " A-2 387 B-2 435 2 " Dia x 0.082 =1.05 " A-3 378 B-3 305 3 " Dia x 0.146 =1.94 " A-4 370 B-4 417 4 " Dia x 0.226 =3.23 " A-5 474 B-5 385 5 " Dia x 0.342 =6.77 " A-6 498 B-6 465 6 " Dia x 0.685 =8.06 " A-7 495 B-7 464 7 " Dia x 0.774 =8.95 " A-8 464 B-8 493 8 " Dia x 0.854 =9.68 " A-9 B-9 9 " Dia x 0.918 =" A-10 B-10 10 " Dia x 0.974 =" SUBTOTAL SUBTOTAL (TOTAL FPM)DIVIDED BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM 3,838 16 427 0.55 234 COMMENTS:D DUCT SIZE 10" RD E AREA 0.55 S FPM 409 I CFM 225 G N T DUCT SIZE O.D.10" RD E DUCT SIZE I.D.10" RD S AREA 0.55 T CENTERLINE S.P.-0.04 AVERAGE FPM 427 D CFM MEASURED 234 A TEMP. CORRECTION 0 T ALT. CORRECTION 0 A ACTUAL CFM 234 11/2/2021 144SYSTEM #:FC-D2-1 OSA HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 32925 ROUND DUCT TRAVERSE READINGS INSTRUMENT USED: AIRFOIL Date:11/2/2021 Page:145 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 390 401 1,750 1,767 Total CFM - Outlet 390 401 1,750 1,767 R/A CFM NS 401 NS 1,100 O/A CFM 135 0 (3)660 667 Static Pressure (Total/Ext)0.00"DUCTLESS 0.50"0.40" Inlet Pressure DUCTLESS -0.07" Discharge Pressure DUCTLESS 0.33" Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 207 Amperage 0.20 0.1 2.5 1.8 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. (1) CODE 3/ FAN SPEED 4/ 56 ESP SETTING. ALL FAN SPEEDS SET TO 56 ESP (2) CODE 3/ FAN SPEED 4/ 112 ESP SETTING. ALL FAN SPEEDS SET TO 112 ESP (4) O.S.A. SUPPLIED BY SF 2-2 WITH SEPARATE SUPPLY GRILLE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE 010KCTB1AY13 011KCHE0RT85 DIRECT DRIVE DIRECT DRIVE LG LG ARNU153TQD4 ARNU543M3A4 ABOVE CEILING RM 228 ABOVE CEILING RM 229 228 WORKROOM 229 UPPER SCHOOL SCIENCE LAB HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-D2-2 FC-D2-3 DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 228 1 DO 14 X 14 1.36 287 390 295 401 TOTAL (390)(401) REMARKS: 11/2/2021 146 FC-D2-2 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 229 1 CD 2408 1.0 *295 *289 229 2 CD 2408 1.0 *295 *296 229 3 CD 2408 1.0 *295 *299 229 4 CD 2408 1.0 *295 *287 229 5 CD 2408 1.0 *295 *301 229 6 CD 2408 1.0 *295 *295 TOTAL (1,770)(1,767) RETURN AIR SYSTEM 229 1 DT 12" RD 0.79 NS NS 703 555 229 2 DT 12" RD 0.79 NS NS 691 545 TOTAL (NS)(1,100) OUTSIDE AIR 229 1 16''RD 660 667 TOTAL (660)(1)(667) REMARKS: (1) UNABLE TO TRAVERSE OSA DUCT. SUPPLY MINUS RETURN = OSA 11/2/2021 147 FC-D2-3 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/2/2021 Page:148 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 390 403 1,750 1,769 Total CFM - Outlet 390 403 1,750 1,769 R/A CFM NS 403 NS 1,145 O/A CFM 135 0 (3)610 624 Static Pressure (Total/Ext)0.00"DUCTLESS 0.50"0.43" Inlet Pressure DUCTLESS -0.12" Discharge Pressure DUCTLESS 0.31" Fan RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 208 Amperage 0.20 0.1 2.5 1.4 Motor RPM 3 SPEED HIGH SPD (1)3 SPEED HIGH SPD (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. (1) CODE 3/ FAN SPEED 4/ 54 ESP SETTING. ALL FAN SPEEDS SET TO 54 ESP (2) CODE 3/ FAN SPEED 4/ 116 ESP SETTING. ALL FAN SPEEDS SET TO 116 ESP (4) O.S.A. SUPPLIED BY SF 2-4 WITH SEPARATE SUPPLY GRILLE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE 009KCXM07Q10 011KCV0U0RT83 DIRECT DRIVE DIRECT DRIVE LG LG ARNU153TQD4 ARNU543M3A4 ABOVE CEILING RM 226A ABOVE CEILING RM 230 226A PREP ROOM 230 UPPER SCHOOL SCIENCE LAB HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-D2-4 FC-D2-5 DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 226A 1 DO 14 X 14 1.36 287 390 297 403 TOTAL (390)(403) REMARKS: 11/2/2021 149 FC-D2-4 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 230 1 CD 2408 1.0 *295 *288 230 2 CD 2408 1.0 *295 *290 230 3 CD 2408 1.0 *295 *293 230 4 CD 2408 1.0 *295 *303 230 5 CD 2408 1.0 *295 *304 230 6 CD 2408 1.0 *295 *291 TOTAL (1,770)(1,769) RETURN AIR SYSTEM 230 1 DT 12" RD 0.79 NS NS 713 563 230 2 DT 12" RD 0.79 NS NS 738 582 TOTAL (NS)(1)(1,145) OUTSIDE AIR 230 1 16"RD 610 624 TOTAL (610)(1)(624) REMARKS: (1) UNABLE TO TRAVERSE OSA DUCT. SUPPLY MINUS RETURN = OSA 11/2/2021 150 FC-D2-5 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/2/2021 Page:151 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 1,450 1,415 Total CFM - Outlet 1,450 1,415 R/A CFM NS 1,051 O/A CFM 350 364 Static Pressure (Total/Ext)0.35"0.26" Inlet Pressure -0.09" Discharge Pressure 0.17" Fan RPM 3 SPEED HIGH SPD (1) Specified Actual Specified Actual Motor Manufacturer NS Motor H.P.NS NS Phase 1 1 Voltage 208/230 207 Amperage 2.5 1.4 Motor RPM 3 SPEED HIGH SPD (1) Motor Service Factor NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. (1) CODE 3/ FAN SPEED 4/ 92 ESP SETTING. ALL FAN SPEEDS SET TO 92 ESP DIRECT DRIVE DIRECT DRIVE 008KCUK16L62 DIRECT DRIVE LG ARNU363M3A4 ABOVE CEILING RM 231 231 COLLAB HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM FC-D2-6 DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 231 1 CD 2412 1.0 *365 *363 231 2 CD 2412 1.0 *365 *368 231 3 CD 2412 1.0 *365 *329 231 4 CD 2412 1.0 *365 *375 TOTAL (1,460)(1,435) OUTSIDE AIR 231 1 DT 10" RD 0.55 648 350 663 364 TOTAL (350)(364) REMARKS: 11/2/2021 152 FC-D2-6 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: PROJECT: POINT FPM POINT FPM SPACES BETWEEN READINGS ON PITOT TUBE A-1 648 B-1 686 1 " Dia x 0.026 =0.32 " A-2 696 B-2 709 2 " Dia x 0.082 =1.05 " A-3 681 B-3 710 3 " Dia x 0.146 =1.94 " A-4 671 B-4 700 4 " Dia x 0.226 =3.23 " A-5 674 B-5 686 5 " Dia x 0.342 =6.77 " A-6 625 B-6 636 6 " Dia x 0.685 =8.06 " A-7 600 B-7 627 7 " Dia x 0.774 =8.95 " A-8 585 B-8 671 8 " Dia x 0.854 =9.68 " A-9 B-9 9 " Dia x 0.918 =" A-10 B-10 10 " Dia x 0.974 =" SUBTOTAL SUBTOTAL (TOTAL FPM)DIVIDED BY:(NO. READINGS)=(AVG.FPM)X (AREA)=TOTAL CFM 10,607 16 663 0.55 364 COMMENTS:D DUCT SIZE 10" RD E AREA 0.55 S FPM 648 I CFM 350 G N T DUCT SIZE O.D.10" RD E DUCT SIZE I.D.10" RD S AREA 0.55 T CENTERLINE S.P.-0.06 AVERAGE FPM 663 D CFM MEASURED 364 A TEMP. CORRECTION NA T ALT. CORRECTION NA A ACTUAL CFM 364 11/2/2021 153SYSTEM #:FC-D2-6 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 32925 ROUND DUCT TRAVERSE READINGS INSTRUMENT USED: AIRFOIL Date:11/3/2021 Page:154 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 200 200 1,215 1,175 Total CFM - Outlet 200 200 1,215 1,175 R/A CFM -0--0--0- O/A CFM -0--0--0- Static Pressure (Total/Ext)0.40"0.20"0.65"0.88" Inlet Pressure -0.15"-0.33" Discharge Pressure 0.05"0.55" Fan RPM SPD. DIAL 0-100%40%SPD. DIAL 0-100%100% Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 115 121 115 121 Amperage 1.42 0.6 7.4 7.1 Motor RPM SPD. DIAL 0-100%40%SPD. DIAL 0-100%100% Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM EF1-1 EF1-2 NORTHEAST 1ST FLOOR RR'S NORTH 1ST FLOOR RR'S NORTHEAST 1ST FLOOR RR'S NORTH 1ST FLOOR RR'S GREENHECK GREENHECK CSP-A390 CSP-A1410 NS NS DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. EXHAUST AIR SYSTEM 100A 1 CE 2408 1.0 *100 *101 100B 2 CE 2408 1.0 *100 *99 TOTAL (200)(200) REMARKS: 11/4/2021 155 EF 1-1 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. EXHAUST AIR SYSTEM 111A 1 CE 2408 1.0 *100 *101 108A 2 CE 2408 1.0 *100 *103 144 3 CE 2410 1.0 *300 *283 142 4 CE 2408 1.0 *100 *103 145 5 CE 2408 1.0 *100 *92 136 6 EG 17" X 4"0.43 500 215 477 205 143 7 CE 2410 1.0 *300 *288 TOTAL (1,215)(1,175) REMARKS: 11/3/2021 156 EF 1-2 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/3/2021 Page:157 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 940 965 670 1,231 Total CFM - Outlet 940 965 1,220 1,231 R/A CFM -0--0--0--0- O/A CFM -0--0--0--0- Static Pressure (Total/Ext)0.75"0.57"0.40"0.63" Inlet Pressure -0.41"-0.26" Discharge Pressure 0.16"0.37" Fan RPM SPD. DIAL 0-100%50%SPD. DIAL 0-100%100% Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 115 121 115 121 Amperage 7.4 7.0 7.4 7.0 Motor RPM SPD. DIAL 0-100%50%SPD. DIAL 0-100%100% Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM EF 1-3 EF 1-4 SOUTH RR'S LOWER SCHOOL SCIENCE LAB SOUTH RR'S LOWER SCHOOL SCIENCE LAB GREENHECK GREENHECK CSP-A1410 CSP-A14110 NS NS DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. EXHAUST AIR SYSTEM 140 1 CE 2410 1.0 *300 *303 139 2 CE 2410 1.0 *300 *308 151 3 EG 10" X 4"0.25 560 140 594 149 152 4 CE 2408 1.0 *100 *101 153 5 CE 2408 1.0 *100 *104 TOTAL (940)(965) REMARKS: 11/3/2021 158 EF 1-3 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. EXHAUST AIR SYSTEM 122 1 CE 2416 1.0 *1,220 *1,231 TOTAL (1,220)(1,231) REMARKS: 11/3/2021 159 EF 1-4 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/3/2021 Page:160 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 670 813 (1)760 762 Total CFM - Outlet 710 813 (1)760 762 R/A CFM -0--0--0--0- O/A CFM -0--0--0--0- Static Pressure (Total/Ext)0.40"0.20"0.40"0.30" Inlet Pressure -0.13"-0.19" Discharge Pressure 0.07"0.11" Fan RPM SPD. DIAL 0-100%10%SPD. DIAL 0-100%40% Specified Actual Specified Actual Motor Manufacturer NA NA Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 115 121 115 121 Amperage 7.4 5.3 3.0 2.1 Motor RPM SPD. DIAL 0-100%10%SPD. DIAL 0-100%40% Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM EF 1-5 EF 1-6 MAKERSPACE WOODSHOP MAKERSPACE WOODSHOP GREENHECK GREENHECK CSP-A1410 CSP-A900 NS NS DIRECT DRIVE DIRECT DRIVE (1) EXHAUST FAN TESTED AT LOWEST POSSIBLE SPEED. DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. EXHAUST AIR SYSTEM 123 1 EG 12" X 8"1.0 *355 *398 123 2 EG 12" X 8"1.0 *355 *415 TOTAL (710)(813) REMARKS: 11/3/2021 161 EF 1-6 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. EXHAUST AIR SYSTEM 124 1 EG 12" X 10"1.0 *380 *358 124 2 EG 12" X 10"1.0 *380 *404 TOTAL (760)(762) REMARKS: 11/3/2021 162 EF 1-6 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/3/2021 Page:162 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 1,920 1,559 (1)940 948 Total CFM - Outlet 1,920 1,559 (1)950 948 R/A CFM -0--0--0--0- O/A CFM -0--0--0--0- Static Pressure (Total/Ext)0.50"0.28"0.45"0.30" Inlet Pressure -0.26"-0.24" Discharge Pressure 0.02"0.06" Fan RPM SPD. DIAL LOW/HI HIGH SPD.SPD. DIAL 0-100%35% Specified Actual Specified Actual Motor Manufacturer NA NA Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 115 121 115 121 Amperage 11.6 9.8 7.4 5.8 Motor RPM SPD. DIAL LOW/HI HIGH SPD.SPD. DIAL 0-100%35% Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM EF 1-8 EF 2-1 ART LABS 2ND FLOOR SOUTH RR'S ART LABS 2ND FLOOR SOUTH RR'S GREENHECK GREENHECK CSP-A2150 CSP-A1410 17752097 NS DIRECT DRIVE DIRECT DRIVE (1) EXHAUST FAN TESTED AT 100% FAN SPEED DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. EXHAUST AIR SYSTEM 126 1 CE 2414 1.0 *960 *781 125 2 CE 2414 1.0 *960 *778 TOTAL (1,920)(1,559) REMARKS: 11/3/2021 164 EF 1-8 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. EXHAUST AIR SYSTEM 245 1 CE 2410 1.0 *300 *291 247 2 CE 2408 1.0 *100 *98 244 3 CE 2408 1.0 *100 *105 246 4 CE 2410 1.0 *300 *299 242 5 EG 17" X 4"0.43 348 150 360 155 TOTAL (950)(948) REMARKS: 11/5/2021 165 EF 2-1 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/4/2021 Page:166 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 940 932 1,290 960 Total CFM - Outlet 940 932 1,290 960 R/A CFM -0--0--0--0- O/A CFM -0--0--0--0- Static Pressure (Total/Ext)0.75"0.32"0.45"0.28" Inlet Pressure -0.24"-0.18" Discharge Pressure 0.08"0.10" Fan RPM SPD. DIAL 0-100%100%SPD. DIAL 0-100%DIAL @ 100% Specified Actual Specified Actual Motor Manufacturer NS NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 120 120 115 Amperage 7.4 6.6 7.4 6.3 Motor RPM SPD. DIAL 0-100%100%SPD. DIAL 0-100%DIAL @ 100% Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE NS NS DIRECT DRIVE DIRECT DRIVE GREENHECK GREENHECK CSP-A1410 CSP-A1410 ABOVE CEILING HALLWAY ABOVE CEILING RM 229 2ND FLOOR SOUTH RR'S 229 UPPER SCHOOL SCIENCE LAB HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM EF 2-2 EF 2-3 DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. EXHAUST AIR SYSTEM 238 1 CE 2410 1.0 *300 *284 237 2 CE 2410 1.0 *300 *294 235 3 EG 16" X 4"0.44 327 140 333 146 239 4 CE 2408 1.0 *100 *103 236 5 CE 2408 1.0 *100 *105 TOTAL (940)(932) REMARKS: 11/4/2021 167 EF 2-2 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. EXHAUST AIR SYSTEM 229 1 CE 22" X 22"1.0 *1,290 *960 TOTAL (1,290)(960) REMARKS: 11/4/2021 168 EF 2-3 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/4/2021 Page:169 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 1,290 1,248 Total CFM - Outlet 1,290 1,248 R/A CFM -0--0- O/A CFM -0--0- Static Pressure (Total/Ext)0.45"0.21" Inlet Pressure -0.18" Discharge Pressure 0.03" Fan RPM SPD. DIAL 0-100%100% Specified Actual Specified Actual Motor Manufacturer NS Motor H.P.NS NS Phase 1 1 Voltage 115 116 Amperage 7.4 6.8 Motor RPM SPD. DIAL 0-100%100% Motor Service Factor NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. DIRECT DRIVEDIRECT DRIVE NS DIRECT DRIVE GREENHECK CSP-A1410 ABOVE CEILING RM 230 230 UPPER SCHOOL SCIENCE LAB HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM EF 2-4 DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. EXHAUST AIR SYSTEM 230 1 CE 22" X 22"1.0 *1,290 *1,248 TOTAL (1,290)(1,248) REMARKS: 11/4/2021 170 EF 2-4 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/5/2021 Page:171 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 540 512 540 552 Total CFM - Outlet 540 512 540 552 R/A CFM -0--0--0--0- O/A CFM -0--0--0--0- Static Pressure (Total/Ext)0.00"DUCTLESS 0.00"DUCTLESS Inlet Pressure DUCTLESS DUCTLESS Discharge Pressure DUCTLESS DUCTLESS Fan RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2) Specified Actual Specified Actual Motor Manufacturer NA NA Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 208/230 206 208/230 206 Amperage 0.52 0.4 0.52 0.4 Motor RPM 3 SPEED HIGH SPD. (1)3 SPEED HIGH SPD. (2) Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM SS-1 SS 1-2 ELEVATOR MACHINE ROOM ELEVATOR MACHINE ROOM ELEVATOR MACHINE ROOM NORTH ELEVATOR MACHINE ROOM SOUTH LG LG ARNU243SKA4 ARNU243SKA4 011KCH0RE53 011KCH0RE37 DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 234 1 D.O.34" X 3"0.71 761 540 721 512 TOTAL (540)(512) REMARKS: 11/5/2021 172 SS-1 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. SUPPLY AIR SYSTEM 234 1 D.O.34 X 3 0.71 761 540 778 552 TOTAL (540)(552) REMARKS: 11/5/2021 173 SS-2 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/5/2021 Page:174 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 700 696 1,145 1,166 Total CFM - Outlet 705 696 1,145 1,166 R/A CFM -0--0--0--0- O/A CFM 705 696 1,145 1,166 Static Pressure (Total/Ext)0.75"0.22"1.15 0.57" Inlet Pressure -0.16"-0.46" Discharge Pressure 0.06"0.11" Fan RPM SPD. DIAL 0-100%25%SPD. DIAL 0-100 100% Specified Actual Specified Actual Motor Manufacturer NA NA Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 115 121 115 121 Amperage 5.0 3.3 7.4 5.5 Motor RPM SPD. DIAL 0-100%25%SPD. DIAL 0-100%100% Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM SF 1-1 SF 1-2 HEAD ASST. 103 MATH SPECIALIST FC'S OSA FC'S OSA GREENHECK GREENHECK CSP-A1050 CSP-A1050 NS NS DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. OUTSIDE AIR SYSTEM FC-A1-1 1 DT 6"0.2 100 20 110 22 FC-A1-3 2 DT 6"0.2 175 35 190 38 107 3 CD 2406 1.0 *90 *94 FC-A1-2 4 DT 10"0.55 490 270 496 273 FC-A1-5 5 DT 6"0.2 125 25 135 27 159 6 CD 2406 1.0 *95 *98 FC-A1-7 7 DT 6"0.2 150 30 165 33 106 8 CD 2406 1.0 *60 *63 FC-A1-9 9 DT 6"0.2 100 20 110 22 FC-A1-8 10 DT 6"0.2 175 35 165 33 TOTAL (680)(703) REMARKS: 11/5/2021 175 SF 1-1 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. OUTSIDE AIR SYSTEM 108C 1 CD 2406 1.0 *60 *64 113 2 CD 2408 1.0 *110 *109 FC-A1-14 3 DT 6"0.2 150 30 165 33 FC-A1-15 4 DT 6"0.2 150 30 140 28 137 5 CD 2408 1.0 *120 *112 FC-A1-17 6 DT 6"0.2 125 25 135 27 134 7 CD 2406 1.0 *90 *87 115A 8 CD 2406 1.0 *75 *80 133 9 CD 2408 1.0 *125 *128 117A 10 CD 2406 1.0 *NS *85 131A 11 CD 2408 1.0 *145 *151 131B 12 CD 2408 1.0 *150 *155 119A 13 CD 2408 1.0 *105 *107 TOTAL (1,065)(1,166) REMARKS: 11/5/2021 176 SF 1-2 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/3/2021 Page:177 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 135 145 925 994 Total CFM - Outlet 135 145 925 959 R/A CFM -0--0--0--0- O/A CFM 135 145 925 994 Static Pressure (Total/Ext)0.50"0.23"0.85"0.18" Inlet Pressure -0.03"-0.14" Discharge Pressure 0.20"0.04" Fan RPM SPD. DIAL 0-100%5%SPD. DIAL 0-100%50% Specified Actual Specified Actual Motor Manufacturer NA NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 115 121 115 116 Amperage 0.79 0.2 7.4 4.8 Motor RPM SPD. DIAL 0-100%5%SPD. DIAL 0-100%50% Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE NS NS DIRECT DRIVE DIRECT DRIVE GREENHECK GREENHECK CSP-A250 CSP-A1410 ART LAB 126 STAFF LOUNGE 207 FC'S OSA FC,S OSA HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM SF 1-3 SF 2-1 DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. OUTSIDE AIR SYSTEM 162 1 SG 12" X 12"1.0 *105 *112 FC-D1-6 2 DT 6"0.2 150 30 165 33 TOTAL (135)(145) REMARKS: 11/5/2021 178 SF 1-3 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. OUTSIDE AIR SYSTEM 208 1 CD 2408 1.0 *135 *137 FC-A2-3 2 DT 6"0.20 100 20 106 21 FC-A2-4 3 DT 6"0.20 100 20 95 19 FC-A2-5 4 DT 6"0.20 100 20 110 22 FC-A2-2 5 DT 12"0.79 525 415 572 451 207A 6 CD 2406 1.0 *70 *72 FC-A2-7 7 DT 6"0.20 100 25 96 19 252 8 CD 2408 1.0 *125 *121 FC-A2-9 9 DT 6"0.20 125 25 137 27 FC-A2-12 10 DT 6"0.20 175 35 166 33 FC-A2-11 11 DT 6"0.20 75 15 81 16 FC-A2-10 12 DT 6"0.20 100 20 109 21 TOTAL (925)(959) REMARKS: 11/3/2021 179 SF 2-1 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/5/2021 Page:180 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 195 199 255 244 Total CFM - Outlet 195 199 255 244 R/A CFM -0--0--0--0- O/A CFM 195 199 255 244 Static Pressure (Total/Ext)0.80"0.16"0.60"0.10" Inlet Pressure -0.09"-0.06" Discharge Pressure 0.07"0.04" Fan RPM SPD. DIAL 0-100%NS SPD. DIAL 0-100%100% Specified Actual Specified Actual Motor Manufacturer NA NS Motor H.P.NS NS NS NS Phase 1 1 1 1 Voltage 115 121 115 121 Amperage 1.33 0.6 1.42 0.7 Motor RPM SPD. DIAL 0-100%NS SPD. DIAL 0-100%100% Motor Service Factor NS NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM SF 2-2 SF 2-3 6TH-8TH CLASSROOM 213 COLAB 218 FC'S OSA FC'S OSA GREENHECK GREENHECK CSP-A390 CSP-A390 NS NS DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. OUTSIDE AIR SYSTEM 211A 1 CD 2408 1.0 *90 *91 249 2 CD 2408 1.0 *105 *108 TOTAL (195)(199) REMARKS: 11/3/2021 181 SF 2-2 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. OUTSIDE AIR SYSTEM 218 1 CD 2406 1.0 *135 *131 254 2 CD 2406 1.0 *120 *113 TOTAL (255)(244) REMARKS: 11/4/2021 182 SF 2-3 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION Date:11/4/2021 Page:183 Project Name: Equipment Location Area Served Equipment Manufacturer Model Serial Number Specified Actual Specified Actual Total CFM - fan 270 272 Total CFM - Outlet 270 272 R/A CFM -0--0- O/A CFM 270 272 Static Pressure (Total/Ext)0.75"0.14" Inlet Pressure -0.10" Discharge Pressure 0.04" Fan RPM SPD. DIAL 0-100%70% Specified Actual Specified Actual Motor Manufacturer NS Motor H.P.NS NS Phase 1 1 Voltage 115 121 Amperage 1.42 0.4 Motor RPM SPD. DIAL 0-100%70% Motor Service Factor NS Motor Sheave Pitch Motor Sheave & Shaft Size Fan Sheave & Shaft SizeBelts Remarks: .. HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR MOVING EQUIPMENT TEST SHEET SYSTEM SF 2-2 SCIENCE LAB 229 FC'S OSA GREENHECK CSP-A390 NS DIRECT DRIVE DIRECT DRIVEDIRECT DRIVE DATE: PAGE: SYSTEM #: PROJECT: ROOM NO.CODE SIZE AK FACTOR REQUIRED F.P.M. REQUIRED C.F.M. ACTUAL F.P.M. ACTUAL C.F.M. OUTSIDE AIR SYSTEM 229A 1 CD 2408 1.0 *135 *139 228 2 CD 2408 1.0 *135 *133 TOTAL (270)(272) REMARKS: 11/4/2021 184 SF 2-4 HARBOR DAY SCHOOL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 AIR DISTRIBUTION APPLICABLE CODES CALIFORNIA MECHANICAL PROJECTS: ALL WORK SHALL BE IN FULL ACCORDANCE WITH APPLICABLE LOCAL, STATE, AND FEDERAL CODES, LAWS AND REGULATIONS. ALL WORK AND MATERIALS SHALL BE IN FULL ACCORDANCE WITH, BUT NOT LIMITED TO: • CALIFORNIA CODE OF REGULATIONS (CCR) • 2016 CALIFORNIA BUILDING CODE -CCR TITLE 24 PART 2 • 2016 CALIFORNIA ELECTRICAL CODE -CCR TITLE 24 PART 3 • 2016 CALIFORNIA MECHANICAL CODE -CCR TITLE 24 PART 4 • 2016 CALIFORNIA PLUMBING CODE -CCR TITLE 24 PART 5 • 2016 CALIFORNIA ENERGY CODE -CCR TITLE 24 PART 6 • 2016 CALIFORNIA FIRE CODE -CCR TITLE 24 PART 9 • 2016 CALIFORNIA GREEN BUILDING STANDARDS CODE -CCR TITLE 24 PART 11 ALL WORK SHALL BE IN ACCORDANCE WITH THE FOLLOWING ADDITIONAL GUIDELINES WHERE REQUIRED BY CODE: • AMERICAN SOCIETY OF SANITARY ENGINEERS (ASSE) • AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) • AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE) • NATIONAL FIRE PROTECTION AGENCY (NFPA) • OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA) • LOCAL UTILITY GUIDELINES AND REGULATIONS • LOCAL AIR QUALITY MANAGEMENT DISTRICTS SCOPE OF WORK AT 3443 PACIFIC VIEW DRIVE, A NEW TWO-STORY BUILDING IS BEING CONSTRUCTED. THE MECHANICAL SCOPE OF WORK INCLUDES A VRF SYSTEM TO SUPPLY HEATING AND COOLING TO THE BUILDING, OUTSIDE AIR FANS TO SUPPLY OUTSIDE AIR TO THE VRF FAN COILS, AND EXHAUST FANS TO EXHAUST ENVIRONMENTAL AIR FROM THE SPACE TO THE OUTDOORS. CORRESPONDING REFRIGERANT LINES, DUCTWORK, DIFFUSERS, AND PERMANANT OPENINGS WILL BE INSTALLED TO ADEQUATELY PROVIDE THESE SERVICES. DRAWING INDEX DRAWING INDEX KEY NOT INCLUDED WITH ISSUE NEW OR REVISED NO CHANGES DR A W I N G I S S U E DA T E SHEET NO.SHEET TITLE REVISION AFF AHJ ASD BDD BF BOD BOI BOP CS CR CE CL CLG CFM CHWR CHWS CMU CONC CONT'R CWR CWS COND DSD DWG (E) EA EG ELB ELEC EQ EXH EXT (F) FD FLEX FLR FR FS FSD ABOVE FINISHED FLOOR AUTHORITY HAVING JURISDICTION AREA SMOKE DETECTOR BACKDRAFT DAMPER BOTTOM FLAT BOTTOM OF DUCT BOTTOM OF INSULATION BOTTOM OF PIPE CEILING SUPPLY CEILING RETURN CEILING EXHAUST CENTERLINE CEILING CUBIC FEET PER MINUTE CHILLED WATER RETURN CHILLED WATER SUPPLY CONCRETE MASONRY UNIT CONCRETE CONTRACTOR CONDENSER WATER RETURN CONDENSER WATER SUPPLY CONDENSATE DUCT SMOKE DETECTOR DRAWING EXISTING EXHAUST AIR EXHAUST AIR GRILLE ELBOW ELECTRICAL EQUIPMENT EXHAUST EXTERIOR FUTURE FIRE DAMPER FLEXIBLE FLOOR FLOOR RETURN FLOOR SUPPLY FIRE SMOKE DAMPER GA GALV GC GPH GPM GYP BD HT HOA HWR HWS ID INS INT (L) LR LS MA MECH MFR MTD MTL MUA MVD (N) N/A NC NIC NO NTS OBD OC OD OPN'G OSA POC GAUGE GALVANIZED GENERAL CONTRACTOR GALLONS PER HOUR GALLONS PER MINUTE GYPSUM BOARD HEIGHT HAND-OFF-AUTO HOT WATER RETURN HOT WATER SUPPLY INSIDE DIMENSION INSULATION INTERIOR LINED LINEAR RETURN LINEAR SUPPLY MIXED AIR MECHANICAL MANUFACTURER MOUNTED METAL MAKE UP AIR MANUAL VOLUME DAMPER NEW NOT APPLICABLE NORMALLY CLOSED NOT IN CONTRACT NORMALLY OPEN NOT TO SCALE OPPOSED BLADE DAMPER ON CENTER OUTSIDE DIMENSION OPENING OUTSIDE AIR POINT OF CONNECTION (R) RA RG RMF RND REQ'D SA SG SM SS STD TF TOD TOP T'STAT UBC UC UG UMC UNO UTR V VAV VFD VOL WMS XFER RELOCATE RETURN AIR RETURN OR TRANSFER GRILLE RAPID MOUNT FRAME ROUND REQUIRED SUPPLY AIR SUPPLY GRILLE SHEET METAL STAINLESS STEEL STANDARD TOP FLAT TOP OF DUCT TOP OF PIPE THERMOSTAT UNIFORM BUILDING CODE UNDERCUT UNDERGROUND UNIFORM MECHANICAL CODE UNLESS NOTED OTHERWISE UP THROUGH ROOF VENT VARIABLE AIR VOLUME VARIABLE SPEED DRIVE VOLUME WIRE MESH SCREEN TRANSFER ABBREVIATIONS ABBR.DESCRIPTION ABBR. DESCRIPTION ABBR. DESCRIPTION HVAC LEGEND LEGEND PIPING SYMBOL LEGEND SYMBOL DESCRIPTION SYMBOL DESCRIPTION PIPING SYMBOL LEGEND SYMBOL DESCRIPTION LEGEND SYMBOL DESCRIPTION NEW (N) & EXISTING (E) RECTANGULAR SUPPLY AIR DUCT RISER SUPPLY AIR DIFFUSER (NEW & EXISTING - 24X24)PNEUMATIC 2W-CV FLEX CONNECTOR NEW (N) & EXISTING (E) RECTANGULAR RETURN AIR DUCT RISER RETURN AIR GRILLE (NEW & EXISTING - 24X24)PNEUMATIC 3W-CV TWIN RUBBER SPHERICAL CONNECTOR NEW (N) & EXISTING (E) RECTANGULAR EXHAUST AIR DUCT RISER RETURN AIR GRILLE (NEW & EXISTING - 24X12)PNEUMATIC BUTTERFLY 2W-CV TRIPLE GROOVED COUPLINGS NEW (N) & EXISTING (E) ROUND AIR DUCT RISER SUPPLY AIR GRILLE (NEW & EXISTING - 24X24)PNEUMATIC BUTTERFLY 3W-CV (DIVERTING)END CAP NEW SINGLE LINE & DOUBLE LINE RECTANGULAR OR ROUND DUCT RETURN AIR GRILLE (NEW & EXISTING - 24X24 WITH ROUND NECK)PNEUMATIC BUTTERFLY 3W-CV (MIXING)BLIND FLANGE EXISTING SINGLE LINE & DOUBLE LINE RECTANGULAR OR ROUND DUCT EXHAUST AIR GRILLE (NEW & EXISTING - 24X24 WITH ROUND NECK)MOTORIZED 2W-CV CONCENTRIC REDUCER EXISTING SINGLE LINE DUCTWORK TO BE DEMOLISHED ("X" OPTION) EXISTING DOUBLE LINE DUCTWORK TO BE DEMOLISHED ("X" OPTION) EXHAUST GRILLE (NEW & EXISTING - 24X24)MOTORIZED 3W-CV ECCENTRIC REDUCER EXISTING DUCTWORK TO BE DEMOLISHED (HATCH OPTION)ROUND DIFFUSER MOTORIZED BUTTERFLY 2W-CV UNION DUCT WITH LINING. DIMENSIONS SHOWN ARE O.D. OF SHEETMETAL (W X H). THICKNESS OF INSULATION AS SHOWN ON PLANS SIDE WALL GRILLE MOTORIZED BUTTERFLY 3W-CV (DIVERTING)SCHRAEDER VALVE SINGLE & DOUBLE LINE DUCTWORK WITH TRANSITIONAL FITTING LINEAR DIFFUSER (SUPPLY)MOTORIZED BUTTERFLY 3W-CV (MIXING)FLOW ARROW DOUBLE LINE SQUARE TO ROUND TRANSITIONAL FITTING WALL LOUVER GATE VALVE PRESSURE GAUGE WITH SHUT-OFF VALVE 90° RADIUS ELBOW 90° SQUARE ELBOW WITH TURNING VANES SPIRAL SIDEWALL (WITH EXTRACTOR & WITHOUT EXTRACTOR)BALL VALVE TEMPERATURE SENSOR & THERMO WELL ROUND DUCT TURNING VERTICAL RECT. DUCT TURNING VERTICAL FLEXIBLE DUCT BALL VALVE WITH MEMORY STOP THERMOMETER SINGLE LINE MANUAL VOLUME DAMPER DOUBLE LINE MANUAL VOLUME DAMPER SECTION NUMBER SECTION CALL OUT SYMBOL SHEET NUMBER GLOBE VALVE PETE'S PLUG MOTORIZED DAMPER (ELECTRIC) GRILLE TYPE - DIFFUSER NECK SIZE AIR VOLUME CUBIC FEET PER MINUTE - AIR THROW PATTERN BUTTERFLY VALVE FLOW SWITCH MOTORIZED DAMPER (PNEUMATIC)EQUIPMENT LABEL TAG CHECK VALVE TRIPLE DUTY VALVE FIRE DAMPER (SINGLE LINE AND DOUBLE LINE)COOLING ONLY VAV BOX TAG STRAINER RELIEF VALVE FIRE/SMOKE DAMPER (SINGLE LINE AND DOUBLE LINE)REHEAT VAV BOX TAG STRAINER WITH BLOWDOWN VALVE 3-WAY WAX VALVE SMOKE DETECTOR (DUCT TYPE)CEILING OR DUCT ACCESS PANEL BY GENERAL CONTRACTOR BASKET STRAINER VACUUM BREAKER SMOKE DETECTOR (AREA TYPE)COOLING ONLY VAV BOX WITH SQUARE TO ROUND OUTLET SUCTION DIFFUSER STEAM TRAP THERMOSTAT WITH ZONE NUMBER REHEAT VAV BOX WITH SQUARE TO ROUND OUTLET AIR VENT - MANUAL ANGLE VALVE CO2 SENSOR COOLING ONLY VAV BOX WITH RECTANGULAR LINED SHEET METAL PLENUM AIR VENT - AUTO SIGHT GLASS CO SENSOR REHEAT VAV BOX WITH RECTANGULAR LINED SHEET METAL PLENUM PRESSURE REDUCING VALVE FILTER DRIER WALL SWITCH FLOW ARROW PRESSURE SUSTAINING VALVE SOLENOID VALVE POINT OF CONNECTION FLOW ARROW - CURVED AUTO FLOW CONTROL TXV WITH SENSING BULB REVISION DELTA REVISION CLOUD CIRCUIT SETTER PRESSURE GAUGE - STEAM GAS STUB-UP BY PLUMBING CONTRACTOR CONDENSATE LINE WITH TRAP TO APPROVED RECEPTOR BY PLUMBING CONTRACTOR BALL VALVE WITH HOSE CONNECTION DIFFERENTIAL PRESSURE SENSOR COLD WATER STUB-UP BY PLUMBING CONTRACTOR FLOOR SINK WITH TRAP TO APPROVED RECEPTOR BY PLUMBING CONTRACTOR FLOW METER INLINE HOSE BIBB ELECTRICAL EQUIPMENT CONNECTION LOCATION BY ELECTRICAL CONTRACTOR FLOW METER TURBINE FM DP T FS T S FM T (N) (E) ROUNDSQUARE (E)(N) (E)(N) (E)(N) EQ # CS-1- 12" 500 4W 10 10 10 10 CO2 CO $ X VAV-CO XX-YY-ZZ VAV-RH XX-YY-ZZ 24X12(1"L) 1 2 21 1 2 1 2 # E P E E P E ASD DSD A # HARBOR DAY SCHOOL EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By 2/ 5 / 2 0 2 1 3 : 3 8 : 4 5 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC0.00 COVER SHEET & DRAWING INDEX 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t N/A AC0.00 COVER SHEET & DRAWING INDEX AC0.01 EQUIPMENT SCHEDULES AND GENERAL NOTES AC0.02 EQUIPMENT SCHEDULES AC0.03 EQUIPMENT SCHEDULES AC0.05 TITLE-24, MANDATORY MEASURES, & GENERAL NOTES AC0.06 TITLE-24 (CONT.) AC0.07 ENERGY COMPLIANCE AC0.08 ENERGY COMPLIANCE (CONT.) AC0.09 ENERGY COMPLIANCE (CONT.) AC1.01 MECHANICAL LEVEL 01 FLOOR PLAN OVERALL AC1.01A MECHANICAL LEVEL 01 FLOOR PLAN NORTH AC1.01B MECHANICAL LEVEL 01 FLOOR PLAN SOUTH AC1.02 MECHANICAL LEVEL 02 FLOOR PLAN OVERALL AC1.02A MECHANICAL LEVEL 02 FLOOR PLAN NORTH AC1.02B MECHANICAL LEVEL 02 FLOOR PLAN SOUTH AC1.03 MECHANICAL ROOF FLOOR PLAN OVERALL AC1.03A MECHANICAL ROOF FLOOR PLAN NORTH AC1.03B MECHANICAL ROOF FLOOR PLAN SOUTH AC2.01 MECHANICAL PIPING LEVEL 01 FLOOR PLAN OVERALL AC2.01A MECHANICAL PIPING LEVEL 01 FLOOR PLAN NORTH AC2.01B MECHANICAL PIPING LEVEL 01 FLOOR PLAN SOUTH AC2.02 MECHANICAL PIPING LEVEL 02 FLOOR PLAN OVERALL AC2.02A MECHANICAL PIPING LEVEL 02 FLOOR PLAN NORTH AC2.02B MECHANICAL PIPING LEVEL 02 FLOOR PLAN SOUTH AC4.01 MECHANICAL ENLARGED PLANS AC5.01 MECHANICAL DETAILS AC5.02 MECHANICAL DETAIL (CONT.) AC5.03 MECHANICAL DETAIL (CONT.) AC6.01 MECHANICAL VRF PIPING DIAGRAM AC6.02 MECHANICAL VRF PIPING DIAGRAMS (CONT.) AC7.01 POWER LOAD DIAGRAMS AC7.02 POWER LOAD DIAGRAMS (CONT.) AC7.03 SEQUENCE OF OPERATIONS AC9.01 MECHANICAL LEVEL 01 HVAC ZONE PLAN AC9.02 MECHANICAL LEVEL 02 HVAC ZONE PLAN 10 0 % D E S I G N D E V E L O P M E N T 08 / 1 6 / 1 9 A 1S T C I T Y S U B M I T T A L 10 / 2 5 / 1 9 B A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 0 09/11/20 ISSUED FOR CONSTRUCTION CD 1 01/22/21 CITY PERMIT AMENDMENT CD 2 xx/xx ACOUSTICAL CHANGES DN C 2N D C I T Y S U B M I T T A L 02 / 1 4 / 2 0 D 3R D C I T Y S U B M I T T A L 05 / 0 1 / 2 0 IS S U E D F O R C O N S T R U C T I O N 09 / 1 1 / 2 0 0 CI T Y P E R M I T A M E N D M E N T 09 / 1 1 / 2 0 1 AC O U S T I C A L C H A N G E S 2 xx / x x CU-A ARUM408DTE5 VRF FC'S 34 R410-A 408.0 87.0 459.0 39.0 (a) ARUM192DTE5 35.7 50 460V-3ɸ-60 5 N 9.7 3.22 N 1325 117% -(b) ARUM216DTE5 38.3 50 460V-3ɸ-60 5 N N/A N/A N/A N/A N/A - - CU-B ARUM408DTE5 VRF FC'S 34 R410-A 408.0 87.0 459.0 39.0 (a) ARUM192DTE5 35.7 50 460V-3ɸ-60 5 N 9.7 3.22 N 1325 108% -(b) ARUM216DTE5 38.3 50 460V-3ɸ-60 5 N N/A N/A N/A N/A N/A - - CU-C ARUM384DTE5 VRF FC'S 32 R410-A 384.0 87.0 432.0 39.0 (a) ARUM168DTE5 28.5 35 460V-3ɸ-60 5 N 9.8 3.22 N 1305 104% -(b) ARUM216DTE5 38.3 50 460V-3ɸ-60 5 N (c) N/A N/A N/A N/A - - CU-D ARUM504DTE5 VRF FC'S 42 R410-A 504.0 87.0 567.0 39.0 (a) ARUM121DTE5 18.4 25 460V-3ɸ-60 5 N 9.6 3.21 N 1664 112% -(b) ARUM168DTE5 28.5 35 460V-3ɸ-60 5 N (c) ARUM192DTE5 38.3 50 460V-3ɸ-60 5 N FC-A1-1 LG ARNU053TRD4 130D ADMISSIONS DIRECTOR 0.46 20 265 0 - R410A 5.5 - 78.8 - 6.1 69.5 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A1-2 LG ARNU283M3A4 100 LOBBY 2.5 270 1250 0.35 - R410A 28.0 - 80.2 - 31.5 64.9 - 2.5 650 109 208/230V-1ɸ-60 N - Y 100 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-A1-3 LG ARNU073TRD4 101 NURSE 0.63 35 265 0 - R410A 7.5 - 79.3 - 8.5 67.6 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A1-4 LG ARNU093TRD4 107 CONFERENCE ROOM 0.8 90 285 0 - R410A 9.6 - 81.2 - 10.9 61.6 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A1-5 LG ARNU053TRD4 102 LOWER DIRECTOR 0.45 25 265 0 - R410A 5.5 - 78.9 - 6.1 68.9 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A1-6 LG ARNU123TRD4 159 OPEN OFFICE 1.0 95 310 0 - R410A 12.3 - 81.1 - 13.6 61.9 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A1-7 LG ARNU053TRD4 103 HEAD ASSISTANT 0.63 30 265 0 - R410A 5.5 - 79.1 - 6.1 68.3 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A1-8 LG ARNU073TRD4 104 HEAD OF SCHOOL 0.63 35 265 0 - R410A 7.5 - 79.3 - 8.5 67.6 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A1-9 LG ARNU053TRD4 105 FACILITIES DIRECTOR 0.45 20 265 0 - R410A 5.5 - 78.8 - 6.1 69.5 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A1-10 LG ARNU123TRD4 106 WORKROOM 1.0 60 310 0 - R410A 12.3 - 79.9 - 13.6 65.6 - 0.20 -30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A1-11 LG ARNU053SJA4 109 DATA 0.46 N/A 240 0 - R410A 5.5 - - - 6.1 - - 0.25 - 30 208/230V-1ɸ-60 N 8 Y 20 INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-A1-12 LG ARNU363SVA4 110 ELECT. 3.0 N/A 918 0 - R410A 35.5 - - - 37.0 - - 0.81 - 104 208/230V-1ɸ-60 N 8 Y 40 INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-A1-13 LG ARNU123TRD4 134 ASSOCIATES 1.0 90 310 0 - R410A 12.3 - 80.9 - 13.6 62.4 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A1-14 LG ARNU053TRD4 137A PSYCH 0.45 30 265 0 - R410A 5.5 - 79.1 - 6.1 68.3 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A1-15 LG ARNU053TRD4 137B LANGUAGE ARTS SPECIALIST 0.45 30 265 0 - R410A 5.5 - 79.1 - 6.1 68.3 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A1-16 LG ARNU123TRD4 137 SMALL GROUP AREA 1.0 120 310 0 - R410A 12.3 - 81.9 - 13.6 59.2 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A1-17 LG ARNU053TRD4 137C MATH SPECIALIST 0.45 25 265 0 - R410A 5.5 - 78.9 - 6.1 68.9 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A1-18A LG ARNU363M3A4 132 STORY TELLING 3.0 560 1450 0.70 - R410A 36.2 - 81.9 - 40.6 59.3 - 2.5 650 161 208/230V-1ɸ-60 N 8 Y 100 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-A1-18B LG ARNU363M3A4 133 LIBRARY 3.0 405 1450 0.70 - R410A 36.2 - 80.8 - 40.6 62.7 - 2.5 650 161 208/230V-1ɸ-60 N 8 Y 100 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-A1-19 LG ARNU123TRD4 133 TINKER AREA 1.0 125 310 0 - R410A 12.3 - 82.0 - 13.6 58.7 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A1-20 LG ARNU153TQD4 131A WORKROOM 1.3 145 390 0 - R410A 15.4 - 81.7 - 17.1 59.7 - 0.20 - 30 208/230V-1ɸ-60 N - N 45 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A1-21 LG ARNU153TQD4 131B TEACHING AREA 1.3 150 390 0 - R410A 15.4 - 81.8 - 17.1 59.3 - 0.20 - 30 208/230V-1ɸ-60 N - N 45 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A2-1 LG ARNU153TQD4 208 WORKROOM 1.3 135 390 0 - R410A 15.4 - 81.5 - 17.1 60.6 - 0.20 - 30 208/230V-1ɸ-60 N - N 45 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A2-2 LG ARNU763B8A4 207 STAFF LOUNGE 6.4 415 2260 0.35 - R410A 76.4 - 79.8 - 86.0 65.9 - 5.2 800 765 208/230V-1ɸ-60 N - Y 200 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-A2-3 LG ARNU053TRD4 210 DIRECTOR OF TECH 0.45 20 265 0 - R410A 5.5 - 78.8 - 6.1 69.5 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A2-4 LG ARNU053TRD4 209 SYSTEMS ADMIN 0.45 20 265 0 - R410A 5.5 - 78.8 - 6.1 69.5 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A2-5 LG ARNU053TRD4 BUSINESS OFFICE 0.45 20 265 0 - R410A 5.5 - 78.8 - 6.1 69.5 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A2-6 LG ARNU053TRD4 MOTHERS ROOM 0.45 70 265 0 - R410A 5.5 - 80.6 - 6.1 63.3 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A2-7 LG ARNU053TRD4 206 ASSISTANT BUSINESS 0.45 25 265 0 - R410A 5.5 - 78.9 - 6.1 68.9 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A2-8 LG ARNU123TRD4 252 OPEN OFFICE 1.0 125 310 0 - R410A 12.3 - 82.0 - 13.6 58.7 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A2-9 LG ARNU053TRD4 204 DIRECTOR OF DEVELOPMENT 0.45 25 265 0 - R410A 5.5 - 78.9 - 6.1 68.9 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A2-10 LG ARNU053TRD4 201 DIR. OF DEVELOPMENT ASST 0.45 20 265 0 - R410A 5.5 - 78.8 - 6.1 69.5 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A2-11 LG ARNU053TRD4 202 DIRECTOR OF DEVELOPMENT 0.45 15 265 0 - R410A 5.5 - 78.6 - 6.1 70.1 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A2-12 LG ARNU073TRD4 203 UPPER DIRECTOR 0.63 35 265 0 - R410A 7.5 - 79.3 - 8.5 67.6 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-A2-13 LG ARNU053SJA4 241 ELECT. 0.46 N/A 240 0 - R410A 5.5 - - - 6.1 - - 0.25 - 30 208/230V-1ɸ-60 N 8 Y 20 INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-A2-14 LG ARNU153SJA4 240 DATA 1.3 N/A 375 0 - R410A 15.4 - - - 17.1 - - 0.25 - 30 208/230V-1ɸ-60 N 8 Y 20 INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-A2-15 LG ARNU243M2A4 211 5TH GRADE CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-B1-1 LG ARNU283M3A4 108 KINDERGARTEN 2.3 415 1250 0.35 - R410A 28.0 - 81.3 - 31.5 61.0 - 2.5 650 109 208/230V-1ɸ-60 N 8 Y 100 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-B1-2 LG ARNU073SJA4 163 ELECTRICAL 0.63 N/A 254 0 - R410A 7.5 - - - 8.5 - - 0.25 - 30 208/230V-1ɸ-60 N 8 Y 20 INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-B1-3 LG ARNU093TRD4 108C WORKROOM 0.8 60 285 0 - R410A 9.6 - 80.1 - 10.9 65.1 - 0.20 -30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-B1-4 LG ARNU283M3A4 111 KINDERGARTEN 2.3 410 1250 0.35 - R410A 28.0 - 81.3 - 31.5 61.2 - 2.5 650 109 208/230V-1ɸ-60 N 8 Y 100 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-B1-5 LG ARNU283M3A4 112 1ST GRADE CLASSROOM 2.3 370 1250 0.35 - R410A 28.0 - 81.0 - 31.5 62.2 - 2.5 650 109 208/230V-1ɸ-60 N 8 Y 100 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH SYMBOL MANUFACTURER & MODEL No.SERVING NOMINAL TON REF. TYPE COOLING HEATING ELECTRICAL RATED EFFICIENCY @ AHRI CAPACITY / POWER INPUT VIB. ISO TOTAL WEIGHT (lbs) CONNECTIVITY RATIO (>50% & <130%)REMARKSTOTAL MBH AMB (°F) TOTAL MBH AMB (°F)FRAME FRAME MODEL MCA MOCP VOLTAGE SCCR (KAIC)E-PWR COOLING HEATING EER COP SYMBOL MANUFACTURER & MODEL No.SERVING NOMINAL TON OSA CFM CFM E.S.P. (IN.)RPM REF. TYPE COOLING HEATING RLA MAX POWER INPUT (W) POWER INPUT (W) VOLTAGE EMERGENCY POWER FILTER MERV VIB. ISO WEIGHT (lbs)REMARKSTOTAL MBH SENSIBLE MBH EDB (°F)LDB/LWB (°F) TOTAL MBH EDB (°F) LDB (°F) AIR COOLED CONDENSING UNIT (VRF) FAN COIL (VRF) EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By 2/ 5 / 2 0 2 1 3 : 1 0 : 1 7 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC0.01 EQUIPMENT SCHEDULES AND GENERAL NOTES 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t N/A A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 0 09/11/20 ISSUED FOR CONSTRUCTION CD 1 01/22/21 CITY PERMIT AMENDMENT CD FC-B1-6 LG ARNU123TRD4 113 SMALL GROUP 1.0 110 310 0 - R410A 12.3 - 81.5 - 13.6 60.3 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-B1-7 LG ARNU283M3A4 114 1ST GRADE CLASSROOM 2.3 370 1250 0.35 - R410A 28.0 - 81.0 - 31.5 62.2 - 2.5 650 109 208/230V-1ɸ-60 N 8 Y 100 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-B1-8 LG ARNU283M3A4 115 2ND GRADE CLASSROOM 2.3 370 1250 0.35 - R410A 28.0 - 81.0 - 31.5 62.2 - 2.5 650 109 208/230V-1ɸ-60 N 8 Y 100 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-B1-9 LG ARNU123TRD4 115A SMALL GROUP 1.0 75 310 0 - R410A 12.3 - 80.4 - 13.6 64.0 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-B1-10 LG ARNU243M2A4 116 2ND GRADE CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-B1-11 LG ARNU243M2A4 117 3RD GRADE CLASSROOM 2.0 310 800 0.45 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-B1-12 LG ARNU123TRD4 117A SMALL GROUP 1.0 80 310 0 - R410A 12.3 - 80.6 - 13.6 63.5 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-B1-13 LG ARNU243M2A4 118 3RD GRADE CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-B1-14 LG ARNU283M3A4 119 4TH GRADE CLASSROOM 2.3 370 1250 0.35 - R410A 28.0 - 81.0 - 31.5 62.2 - 2.5 650 109 208/230V-1ɸ-60 N 8 Y 100 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-B1-15 LG ARNU123TRD4 119A SMALL GROUP 1.0 105 310 0 - R410A 12.3 - 81.4 - 13.6 60.8 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-B1-16 LG ARNU363M3A4 120 4TH GRADE CLASSROOM 3.0 395 1450 0.35 - R410A 36.2 - 80.7 - 40.6 63.0 - 2.5 650 161 208/230V-1ɸ-60 N 8 Y 100 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-B1-17 LG ARNU243M2A4 121 WORLD LANGUAGE CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-B1-18 LG ARNU363M3A4 122 LOWER SCHOOL SCIENCE LAB 3.0 450 1450 0.45 - R410A 36.2 - 81.1 - 40.6 61.8 - 2.5 650 161 208/230V-1ɸ-60 N 8 Y 100 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-B1-19 LG ARNU363M3A4 128 ELECT. 3.0 N/A 1450 0.35 - R410A 36.2 - - - 40.6 - - 2.5 650 161 208/230V-1ɸ-60 N 8 Y 100 INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-B1-20 LG ARNU053SJA4 127 DATA 2.0 N/A 240 0 - R410A 5.5 - - - 6.1 - - 0.25 - 30 208/230V-1ɸ-60 N 8 Y 20 INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-C2-2 LG ARNU093TRD4 211A COLLAB 0.8 90 285 0 - R410A 9.6 - 81.2 - 10.9 61.6 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-C2-3 LG ARNU243M2A4 212 5TH GRADE CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-C2-4 LG ARNU243M2A4 213 6TH 8TH CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-C2-5 LG ARNU243M2A4 214 6TH 8TH CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-C2-6 LG ARNU243M2A4 215 6TH 8TH CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-C2-7 LG ARNU123TRD4 249 COLLAB 1.0 105 310 0 - R410A 12.3 - 81.4 - 13.6 60.8 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-C2-8 LG ARNU243M2A4 216 6TH 8TH CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-C2-9 LG ARNU243M2A4 217 6TH 8TH CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-C2-10 LG ARNU153TQD4 218 COLLAB 1.3 135 390 0 - R410A 15.4 - 81.5 - 17.1 60.6 - 0.20 - 30 208/230V-1ɸ-60 N - N 45 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-C2-11 LG ARNU243M2A4 6TH 8TH CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-C2-12 LG ARNU153TQD4 254 COLLAB 1.3 120 390 0 - R410A 15.4 - 81.1 - 17.1 61.8 - 0.20 - 30 208/230V-1ɸ-60 N - N 45 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-C2-13 LG ARNU243M2A4 6TH 8TH CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-C2-14 LG ARNU243M2A4 6TH 8TH CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-C2-15 LG ARNU243M2A4 6TH 8TH CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-C2-16 LG ARNU243M2A4 223 6TH 8TH CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-C2-17 LG ARNU243M2A4 224 6TH 8TH CLASSROOM 2.0 310 800 0.35 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-C2-18 LG ARNU183M2A4 225 6TH 8TH CLASSROOM 1.6 230 800 0.35 - R410A 19.1 - 80.9 - 21.5 62.5 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-C2-19 LG ARNU183M2A4 226 6TH 8TH CLASSROOM 1.6 230 800 0.35 - R410A 19.1 - 80.9 - 21.5 62.5 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-C2-20 LG ARNU183SKA4 234 ELECT. 1.6 N/A 500 0 - R410A 19.1 - - - 21.5 - - 0.52 - 53 208/230V-1ɸ-60 N 8 Y 30 INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FC-C2-21 LG ARNU053SJA4 233 DATA 0.46 N/A 240 0 - R410A 5.5 - - - 6.1 - - 0.25 - 30 208/230V-1ɸ-60 N 8 Y 20 INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FC-D1-1 LG ARNU363B8A4 126 UPPER SCHOOL ART LAB 3.0 665 1730 0.47 - R410A 36.2 - 81.8 - 40.6 59.3 - 2.5 800 478 208/230V-1ɸ-60 N 8 Y 222 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-D1-2 (NOT USED) - - - - - - - - - - - - - - - - - - - - - - -- FC-D1-3 LG ARNU423B8A4 125 LOWER SCHOOL ART LAB 3.5 705 1915 0.47 - R410A 42.0 - 81.7 - 43.5 59.1 - 2.5 800 528 208/230V-1ɸ-60 N 8 Y 222 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-D1-4 LG ARNU243M2A4 125A CERAMICS 2.0 310 800 0.45 - R410A 24.2 - 81.9 - 27.3 59.2 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-D1-5 LG ARNU543M3A4 124 WOODSHOP 4.5 655 1750 0.35 - R410A 54.0 - 81.7 - 61.4 59.6 - 2.5 650 260 208/230V-1ɸ-60 N 8 Y 100 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-D1-6 LG ARNU053TRD4 124A OFFICE 0.46 30 265 0 - R410A 5.5 - 79.1 - 6.1 68.3 - 0.20 - 30 208/230V-1ɸ-60 N - N 40 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-D1-7 LG ARNU763B8A4 123 MAKERSPACE 6.4 765 2260 0.4 - R410A 76.4 - 81.4 - 86.0 60.8 - 5.2 800 765 208/230V-1ɸ-60 N 8 Y 200 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-D1-8 LG ARNU283M3A4 123A TECH LAB 2.3 400 1250 0.35 - R410A 28.0 - 81.2 - 31.5 61.4 - 2.5 650 109 208/230V-1ɸ-60 N 8 Y 100 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-D1-9 LG ARNU963B8A4 125B KILN ROOM 8.0 N/A 2545 0.25 - R410A 95.9 - - - 107.5 - - 5.2 800 800 208/230V-1ɸ-60 N 8 Y 200 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-D2-1 LG ARNU183M2A4 227 6TH 8TH CLASSROOM 1.6 225 800 0.35 - R410A 19.1 - 80.8 - 21.5 62.7 - 2.3 430 67 208/230V-1ɸ-60 N 8 Y 85 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-D2-2 LG ARNU153TQD4 228 WORKROOM 1.3 135 390 0 - R410A 15.4 - 81.5 - 17.1 60.6 - 0.20 - 30 208/230V-1ɸ-60 N - N 45 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-D2-3 LG ARNU543M3A4 229 UPPER SCHOOL SCIENCE LAB 4.5 660 1750 0.5 - R410A 54.0 - 81.8 - 61.4 59.6 - 2.5 650 260 208/230V-1ɸ-60 N 8 Y 100 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-D2-4 LG ARNU153TQD4 229A PREP ROOM 1.3 135 390 0 - R410A 15.4 - 81.5 - 17.1 60.6 - 0.20 - 30 208/230V-1ɸ-60 N - N 45 OSA FILTERED AT SUPPLY FAN, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH, FAN SETTING: HIGH, TRUE 2'X2' GRILLE FC-D2-5 LG ARNU543M3A4 230 UPPER SCHOOL SCIENCE LAB 4.5 610 1750 0.5 - R410A 54.0 - 81.5 - 61.4 60.5 - 2.5 650 260 208/230V-1ɸ-60 N 8 Y 100 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH FC-D2-6 LG ARNU363M3A4 231 COLLAB 3.0 350 1450 0.35 - R410A 36.2 - 80.4 - 40.6 64.1 - 2.5 650 161 208/230V-1ɸ-60 N 8 Y 100 W/ FILTER BOX, INTERNAL MANUFACTURER PROVIDED CONDENSATE PUMP, INTERNAL CONDENSATE OVERFLOW SWITCH SYMBOL MANUFACTURER & MODEL No.SERVING NOMINAL TON OSA CFM CFM E.S.P. (IN.)RPM REF. TYPE COOLING HEATING RLA MAX POWER INPUT (W) POWER INPUT (W) VOLTAGE EMERGENCY POWER FILTER MERV VIB. ISO WEIGHT (lbs)REMARKSTOTAL MBH SENSIBLE MBH EDB (°F)LDB/LWB (°F) TOTAL MBH EDB (°F) LDB (°F) FAN COIL (VRF) EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By 2/ 5 / 2 0 2 1 3 : 1 0 : 1 8 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC0.02 EQUIPMENT SCHEDULES 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t N/A A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 0 09/11/20 ISSUED FOR CONSTRUCTION CD 018 12/07/20 CCD-018 DN 1 01/22/21 CITY PERMIT AMENDMENT CD SKUTT KM/KMT-1027-3 KILN ROOM 3 208V-1ɸ-60 48.0 9984 10 2350°F 6.4 6-50 18,940 KILNS PROVIDED AND INSTALLED BY OWNER. ACCESSORIES: SKUTT ENIVROLINK, SKUTT ENVIROVENT 2 DOWNDRAFT VENTING SYSTEM. MANUFACTURER & MODEL No.LOCATION QTY VOLTAGE POWER MAXIMUM CHAMBER NEMA RECEPTACLE BTU's REMARKSAMPS WATTS CONE TEMP CU. FT. KILN (FOR REFERENCE ONLY) EF1-1 - GREENHECK CSP-A390 NORTHEAST 1ST FLOOR RR'S 200 0.40 935 - - - ODP 0.05 - 1.42 115V/1ɸ/60 - Y 25 1.5 W/ BDD, SPEED CONTROLLER EF1-2 - GREENHECK CSP-A1410 NORTH 1ST FLOOR RR'S 1,215 0.65 1,360 - - - ODP 0.72 - 7.4 115V/1ɸ/60 - Y 60 3.0 W/ BDD, SPEED CONTROLLER EF1-3 - GREENHECK CSP-A1410 SOUTH RR'S 940 0.75 1,207 - - - ODP 0.44 - 7.4 115V/1ɸ/60 - Y 60 2.0 W/ BDD, SPEED CONTROLLER EF1-4 - GREENHECK CSP-A1410 LOWER SCHOOL SCIENCE LAB 1,220 0.40 1,275 - - - ODP 0.65 - 7.4 115V/1ɸ/60 - Y 60 2.0 W/ BDD, SPEED CONTROLLER EF1-5 - GREENHECK CSP-A1410 MAKERSPACE 670 0.40 871 - - - ODP 0.16 - 7.4 115V/1ɸ/60 - Y 60 0.8 W/ BDD, SPEED CONTROLLER EF1-6 - GREENHECK CSP-A900 WOODSHOP 760 0.40 866 - - - ODP 0.43 - 3.0 115V/1ɸ/60 - Y 60 0.8 W/ BDD, SPEED CONTROLLER (NOT USED) - - - - - - - - - - - - - - - - - - - EF1-8 - GREENHECK CSP-A2150 ART LABS 1,920 0.50 790 - --ODP 1.72 - 11.6 115V/1ɸ/60 - Y 69 3.5 W/ BDD, SPEED CONTROLLER EF2-1 - GREENHECK CSP-A1410 2ND FLOOR NORTH RR'S 940 0.45 1,087 - - - ODP 0.36 - 7.4 115V/1ɸ/60 - Y 60 1.0 W/ BDD, SPEED CONTROLLER EF2-2 - GREENHECK CSP-A1410 2ND FLOOR SOUTH RR'S 940 0.75 1,207 - - - ODP 0.44 - 7.4 115V/1ɸ/60 - Y 60 2.0 W/ BDD, SPEED CONTROLLER EF2-3 - GREENHECK CSP-A1410 UPPER SCHOOL SCIENCE LAB 1,290 0.45 1,290 - - - ODP 0.77 - 7.4 115V/1ɸ/60 - Y 60 2.5 W/ BDD, SPEED CONTROLLER EF2-4 - GREENHECK CSP-A1410 UPPER SCHOOL SCIENCE LAB 1,290 0.45 1,290 - - - ODP 0.77 - 7.4 115V/1ɸ/60 - Y 60 2.5 W/ BDD, SPEED CONTROLLER FSD-1 POTTORFF FSD RA - 1000 FPM SA - 1800 FPM II 1-1/2 165°F N/A 120V/1ɸ/60 N Y SEE PLANS FOR SIZE AND LOCATION, HORIZONTAL POSITION CS1 SUPPLY PRICE SPD 24"X24" LAY-IN STEEL - WHITE N N - CR1 RETURN PRICE PDDR 24"X24" LAY-IN STEEL - WHITE N N - CE1 EXHAUST PRICE PDDR 24"X24"SURFACE MOUNT STEEL FLUSH WHITE Y N - CE2 EXHAUST PRICE PDDR 24"X24" LAY-IN STEEL - WHITE N N - CT1 TRANSFER PRICE PDDR 24"X24" LAY-IN STEEL - WHITE N N - CT2 TRANSFER PRICE PDDR 24"X24"SURFACE MOUNT STEEL FLUSH WHITE Y N - SWG1 SUPPLY PRICE SDGE SEE PLANS DUCT MOUNTED STEEL FLUSH DUCT N N W/ AIR SCOOP SWG2 RETURN / TRANSFER PRICE 530 SEE PLANS WALL MOUNTED STEEL FLUSH WHITE N N - SWG3 SUPPLY PRICE 520 SEE PLANS WALL MOUNTED STEEL FLUSH WHITE N N - L-1 PER PLANS CONSTRUCTION SPECIALTIES A2097 PER PLANS PER PLANS - - CU-1 - LG ARUN024GSS4 SS-1 R-410A 24 - - - - 19.6 30 - 208V/1ɸ/60 N 10.70 N 180 - CU-2 - LG ARUN024GSS4 SS-1 R-410A 24 - - - - 19.6 30 - 208V/1ɸ/60 N 10.70 N 180 - BS-A1 LG PRHR083A FC'S 1 8 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 - BS-A2 LG PRHR043A FC'S 1 4 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 - BS-A3 LG PRHR083A FC'S 1 8 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 - BS-A4 LG PRHR023A FC'S 1 2 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 - BS-A5 LG PRHR083A FC'S 1 8 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 - BS-A6 LG PRHR083A FC'S 1 8 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 - BS-B1 LG PRHR083A FC'S 1 8 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 - BS-B2 LG PRHR063A FC'S 1 6 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 - BS-B3 LG PRHR083A FC'S 1 8 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 - BS-C1 LG PRHR063A FC'S 1 6 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 - BS-C2 LG PRHR063A FC'S 1 6 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 - BS-C3 LG PRHR023A FC'S 1 2 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 - BS-C4 LG PRHR063A FC'S 1 6 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 - BS-D1 LG PRHR083A FC'S 1 8 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 - BS-D2 LG PRHR043A FC'S 1 4 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 - BS-D3 LG PRHR043A FC'S 1 4 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 - BS-D4 LG PRHR043A FC'S 1 4 R-410A 60 230 - 0.09 - 208V/1ɸ/60 N Y 68 - SF-1-1 HEAD ASST. 103 GREENHECK CSP-A1050 FC'S OSA 700 0.75 1,013 0.63 - 8 30x14x1 5.0 115V/1ɸ/60 N - Y 60 W/ FILTER, BDD, & SPEED CONTROLLER SF-1-2 MATH SPECIALIST 137C GREENHECK CSP-A1410 FC'S OSA 1,145 1.15 1,450 0.75 - 8 24x18x1 7.4 115V/1ɸ/60 N - Y 60 W/ FILTER, BDD, & SPEED CONTROLLER SF-1-3 ART LAB 126 GREENHECK CSP-A250 FC'S OSA 135 0.50 1,000 0.03 - 8 12x12x1 0.79 115V/1ɸ/60 N - Y 25 W/ FILTER, BDD, & SPEED CONTROLLER SF-2-1 STAFF LOUNGE 207 GREENHECK CSP-A1410 FC'S OSA 925 0.85 1,238 0.45 - 8 24x16x1 7.4 115V/1ɸ/60 N - Y 60 W/ FILTER, BDD, & SPEED CONTROLLER SF-2-2 6TH-8TH CLASSROOM 213 GREENHECK CSP-A390 FC'S OSA 195 0.80 1,532 0.08 - 8 12x12x1 1.33 115V/1ɸ/60 N - Y 25 W/ FILTER, BDD, & SPEED CONTROLLER SF-2-3 COLAB 218 GREENHECK CSP-A390 FC'S OSA 255 0.60 1,166 0.11 - 8 16x16x1 1.42 115V/1ɸ/60 N - Y 24 W/ FILTER, BDD, & SPEED CONTROLLER SF-2-4 SCIENCE LAB 229 GREENHECK CSP-A390 FC'S OSA 270 0.75 1,272 0.14 - 8 16x16x1 1.42 115V/1ɸ/60 N - Y 24 W/ FILTER, BDD, & SPEED CONTROLLER FAN COILS TO AIR DISTRIBUTION GALVANIZED STEEL 2" (+) SUPPLY OUTSIDE AIR DUCT GALVANIZED STEEL 2" (+) ALL EXHAUST AIR DUCT GALVANIZED STEEL 2" (-) KILN EXHAUST AIR DUCT GALVANIZED STEEL 2" (-) DUST COLLECTOR EXHAUST DUCT GALVANIZED STEEL, WELDED OR FLANGED MIN. 18 GA. PIPE FROM CONDENSING UNITS TO BRANCH SELECTORS HARD DRAWN, ACR TUBE SEE PLANS FOR ROUTING AND SIZES. PIPE FROM BRANCH SELECTORS TO FAN COILS SOFT COPPER, LINE SETS SEE PLANS FOR ROUTING AND SIZES. DC-1 (NOT USED) - - - - - - - - - - - - - - - - GV-1 ROOF GREENHECK GSR-20 UPPER SCHOOL SCIENCE LAB 1290 0.04 573 20"Ø 24 4 HOODED GRAVITY RELIEF VENTILATOR. 1/4" WIRE MESH BIRDSCREEN. SLOPED ROOF CURB. BDD. GV-2 ROOF GREENHECK GRSI-15 UPPER SCHOOL SCIENCE LAB 660 0.057 589 15"Ø 13 2 HOODED GRAVITY INTAKE VENTILATOR. 1/4" WIRE MESH BIRDSCREEN. SLOPED ROOF CURB. BDD. GV-3 ROOF GREENHECK GRSI-10 SECOND FLOOR CLASSROOMS 300 0.046 526 10"Ø 8 18 HOODED GRAVITY INTAKE VENTILATOR. 1/4" WIRE MESH BIRDSCREEN. SLOPED ROOF CURB. BDD. SKUTT ENVIROVENT-2 KILN ROOM 3 KILN 140 160°F 12 ODP 1.4 115V/1ɸ/60 N N UL LISTED, WALL MOUNTED BLOWER. SS-1 ELEVATOR MACHINE ROOM LG ARNU243SKA4 ELEVATOR MACHINE ROOM NORTH 540 - - R-410A 24 - - 0.52 53 208V/1ɸ/60 N N 30 CONDENSATE PUMP SS-2 ELEVATOR MACHINE ROOM LG ARNU243SKA4 ELEVATOR MACHINE ROOM SOUTH 540 - - R-410A 24 - - 0.52 53 208V/1ɸ/60 N N 30 CONDENSATE PUMP SYMBOL LOCATION MANUFACTURER & MODEL No.SERVING CFM ESP (IN.)FRPM MOTOR POSITION ROT DIS MOTOR ENCL.BHP HP FLA VOLTAGE VFD (Y/N)VIB. ISO WEIGHT (lbs) SONES REMARKSSYMBOLMANUFACTURER & MODEL No. MAX VELOCITY / BLADE TYPE LEAKAGE CLASS RESISTANCE RATING (HOURS) FIRE CLOSURE TEMPERATURE & DEVICE SMOKE CONTROL (PASSIVE & ACTIVE) ACTUATOR VOLTAGE EMERGENCY POWER POSITION SWITCHES REMARKS SYMBOL TYPE MANUFACTURER & MODEL No. MODULE SIZE BORDER TYPE MATERIAL FACE TYPE COLOR RAPID MOUNT FRAME OBD REMARKS SYMBOL LOCATION MANUFACTURER & MODEL No.SERVING SIZE (W" x H") FREE AREA (%) POINT OF WATER PENETRATION (FPM)REMARKS SYMBOL LOCATION MANUFACTURER & MODEL No.SERVING COOLING COMP'R SINGLE POINT POWER EER @ ARI VIB. ISO WEIGHT (lbs) REMARKS REF. TYPE TOTAL MBH SUCT. °F AMB (°F)QTY.# OF CIRCUITS MCA MFA/ MOCP SCCR (KA)VOLTAGE EMERGENCY POWER SYMBOL MANUFACTURER & MODEL No.SERVING QUANTITY PORTS REF. TYPE MAX PORT CAPACITY (MBH) MAX UNIT CAPACITY (MBH) MCA FLA MFA VOLTAGE EMERGENCY POWER VIB. ISO. WEIGHT (lbs) REMARKS SYMBOL LOCATION MANUFACTURER & MODEL No.SERVING SUPPLY FAN FILTER SINGLE POINT POWER VFD (Y/N)VIB. ISO WEIGHT (lbs)REMARKSCFME.S.P. (IN.)FRPM BHP HP MERV SIZE FLA VOLTAGE EMERGENCY POWER CRITERIA MATERIAL DETAILS CRITERIA MATERIAL DETAILS SYMBOL LOCATION MANUFACTURER & MODEL No.SERVING EXHAUST FANS SINGLE POINT POWER VIB. ISO UNIT WEIGHT (lbs) SILENCER WEIGHT (lbs) TOTAL WEIGHT (lbs)REMARKS CFM E.S.P. (IN. WG)HP RPM FLA MFA/ MOCP VOLTAGE EMERGENCY POWER SYMBOL LOCATION MANUFACTURER & MODEL No.SERVING CFM S.P. THROAT VELOCITY THROAT SIZE WEIGHT (lbs)QTY.REMARKS MANUFACTURER & MODEL No.LOCATION QTY SERVING CFM MAXIMUM MOTOR ENCL.FLA VOLTAGE VFD (Y/N)VIB. ISO REMARKSTEMP CU. FT. SERVED SYMBOL LOCATION MANUFACTURER & MODEL No.SERVING SUPPLY FAN REF. TYPE DX COOLING COIL RLA POWER INPUT (W)VOLTAGE EMERGENCY POWER VIB. ISO WEIGHT (lbs) REMARKS CFM FRPM HP TOTAL MBH EDB/EWB (°F) LDB/LWB (°F) WEATHER ASSUMPTIONS SYSTEM ASSUMPTIONS SUPPLY RETURN ELEVATION (FT) LATITUDE (DEG) SUMMER DB/WB (°F, 0.1%) WINTER DB (°F, 0.2%) SUPPLY TEMP VENTILATION (CFM/PERSON) THERMOSTAT SETPOINTS COOLING/HEATING EXHAUST 10 33.68°N 87°F / 68°F 39°F 55°F 15 76°F/70°F ACH . . . . . AIR CHANGES PER HOUR AMB . . . . . AMBIENT TEMPERATURE CONN AIF . . CONNECTION-AIR IN FACE DIS . . . . . DISCHARGE DpA . . . . . AIR PRESSURE DROP Dpw . . . . . WATER PRESSURE DROP EDB . . . . . ENTERING DRY BULB EWB . . . . . ENTERING WET BULB EWT . . . . . ENTERING WATER TEMPERATURE FPM . . . . . FEET PER MINUTE FLA . . . . . FULL LOAD AMPS. RETURN AIR PLENUM 78°F JANITOR'S CLOSET: 1.0 CFM/SQ.FT. RR: 100 CFM/FIXTURE SCIENCE LABS: 1.0 CFM/SQ.FT ART LABS: 0.7 CFM/SQ.FT. LOW PRESSURE DUCT SUPPLY 0.10"/100' THROUGH FSD <1000 FPM THROUGH FSD <1800 FPM MAKERSPACE: 0.5 CFM/SQ.FT. LDB . . . . . LEAVING DRY BULB LWB . . . . . LEAVING WET BULB LWT . . . . . LEAVING WATER TEMPERATURE MCA . . . . . MINIMUM CURRANT AMPACITY MFA . . . . . MAXIMUM FUSE AMPS. MOCP . . . . MAXIMUM OVER CURRANT PROTECTION REF . . . . . REFRIGERANT TYPE RLA . . . . . RATED LOAD AMPS. ROT . . . . . ROTATION RR . . . . . . RESTROOMS BASIS OF DESIGN DUCT SIZING CRITERIA ABBREVIATIONS GENERAL NOTES EXHAUST FANFIRE / SMOKE DAMPER AIR DISTRIBUTION LOUVER SPLIT SYSTEM CONDENSING UNIT BRANCH SELECTOR (VRF) SUPPLY FAN DUCT CONSTRUCTION SCHEDULE PIPE CONSTRUCTION SCHEDULE DUST COLLECTOR GRAVITY AIR VENT KILN DOWNDRAFT VENT SYSTEM FAN COIL (DX) SPLIT SYSTEM EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By 2/ 5 / 2 0 2 1 3 : 1 0 : 1 9 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC0.03 EQUIPMENT SCHEDULES 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t N/A A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 0 09/11/20 ISSUED FOR CONSTRUCTION CD 016 12/09/20 CCD-016 DN 1 01/22/21 CITY PERMIT AMENDMENT CD ANY APPLIANCE FOR WHICH THERE IS A CALIFORNIA STANDARD ESTABLISHED IN THE APPLIANCE EFFICIENCY REGULATIONS MAY BE INSTALLED ONLY IF THE MANUFACTURER HAS CERTIFIED TO THE COMMISSION THAT THE APPLIANCE COMPLIES WITH THE APPLICABLE STANDARD FOR THAT APPLIANCE. MECHANICAL EQUIPMENT INSTALLED IN A BUILDING SUBJECT TO THESE REGULATIONS MUST BE CERTIFIED AS MEETING CERTAIN MINIMUM EFFICIENCY. THESE REQUIREMENTS ARE CONTAINED IN §112. THE AFUE, COP, EER, IPLV, COMBUSTION EFFICIENCY, AND THERMAL EFFICIENCY VALUES OF ALL EQUIPMENT MUST BE DETERMINED USING THE APPLICABLE TEST METHOD SPECIFIED IN THE STANDARDS. THE FOLLOWING SPACE-CONDITIONING EQUIPMENT MAY BE INSTALLED ONLY IF THE MANUFACTURER HAS CERTIFIED THAT THE EQUIPMENT MEETS OR EXCEEDS ALL APPLICABLE EFFICIENCY REQUIREMENTS OF THE STANDARDS: ALL AIR CONDITIONERS, HEAT PUMPS AND CONDENSING UNITS >135,000 BTU/HR; ALL WATER CHILLERS; ALL GAS AND OIL FIRED AIR FURNACES WITH INPUT RATING >225,000 BTU/HR SHALL HAVE AN INTERMITTENT IGNITION OR INTERRUPTED DEVICE (IDD), AND HAVE EITHER POWER VENTING OR A FLUE DAMPER. ALL ENCLOSED SPACES IN A BUILDING THAT ARE NORMALLY USED BY HUMANS SHALL BE VENTILATED IN ACCORDANCE WITH THE REQUIREMENTS OF THIS SECTION AND THE CBC. THE OUTDOOR AIR-VENTILATION RATE AND AIR-DISTRIBUTION ASSUMPTIONS MADE IN THE DESIGN OF THE VENTILATING SYSTEM SHALL BE CLEARLY IDENTIFIED ON THE BUILDING PLANS REQUIRED BY §10-103 OF TITLE 24, PART 1. EVERY SPACE IN A BUILDING SHALL BE DESIGNED TO HAVE OUTDOOR AIR-VENTILATION EITHER BY NATURAL VENTILATION OR MECHANICAL VENTILATION. TIMES OF OCCUPANCY. THE MINIMUM RATE OF OUTDOOR AIR REQUIRED BY SECTION 120.1 SHALL BE SUPPLIED TO EACH SPACE AT ALL TIMES WHEN THE SPACE IS USUALLY OCCUPIED. DUCTING FOR ZONAL HEATING AND COOLING UNITS. WHERE A RETURN PLENUM IS USED TO DISTRIBUTE OUTDOOR AIR TO A ZONAL HEATING OR COOLING UNIT WHICH THEN SUPPLIES THE AIR TO A SPACE IN ORDER TO MEET THE REQUIREMENTS OF SECTION 120.1(d), THE OUTDOOR AIR SHALL BE DUCTED TO DISCHARGE EITHER: WITHIN 5 FEET OF THE UNIT; OR WITHIN 15 FEET OF THE UNIT, SUBSTANTIALLY TOWARD THE UNIT, AND AT A VELOCITY NOT LESS THAN 500 FEET PER MINUTE. DESIGN AND CONTROL REQUIREMENTS FOR QUANTITIES OF OUTDOOR AIR. ALL MECHANICAL VENTILATION AND SPACE-CONDITIONING SYSTEMS SHALL BE DESIGNED WITH AND HAVE INSTALLED DUCTWORK, DAMPERS, AND CONTROLS TO ALLOW OUTSIDE AIR RATES TO BE OPERATED AT THE LARGER OF (1) THE MINIMUM LEVELS SPECIFIED IN SECTION 120.1(b) 1 OR 2 THE RATE REQUIRED FOR MAKE-UP OF EXHAUST SYSTEMS THAT ARE REQUIRED FOR A PROCESS, FOR CONTROL OF ODORS, OR FOR THE REMOVAL OF CONTAMINANTS WITHIN THE SPACE. EVERY SPACE REQUIRING DEMAND CONTROL VENTILATION. THEY MUST HAVE AN AIR ECONOMIZER; AND THEY SERVE A SPACE WITH A DESIGN OCCUPANT DENSITY, OR A MAXIMUM OCCUPANT LOAD FACTOR FOR EGRESS PURPOSES, GREATER THAN OR EQUAL TO 25 PEOPLE PER 1000 FT² (40 FT² PER PERSON); AND IS EITHER A SINGLE ZONE SYSTEM WITH ANY CONTROLS OR MULTIPLE ZONE SYSTEMS WITH DIRECT DIGITAL CONTROLS (DDC) TO THE ZONE LEVEL. HEAT PUMPS WITH SUPPLEMENTARY ELECTRIC RESISTANCE HEATERS; SHOULD PREVENT SUPPLEMENTARY HEATER OPERATION WHEN THE HEATING LOAD CAN BE MET BY THE HEAT PUMP ALONE; AND IN WHICH THE CUT-ON TEMPERATURE FOR COMPRESSION HEATING IS HIGHER THAN THE CUT-ON TEMPERATURE FOR SUPPLEMENTARY HEATING, AND THE CUT-OFF TEMPERATURE FOR COMPRESSION HEATING IS HIGHER THAN THE CUT-OFF TEMPERATURE FOR SUPPLEMENTARY HEATING. THERMOSTATS, ALL UNITARY HEATING AND/OR COOLING SYSTEMS HEAT PUMPS THAT ARE NOT CONTROLLED BY A CENTRAL ENERGY MANAGEMENT CONTROL SYSTEM (CEMS) SHALL HAVE A SETBACK THERMOSTAT. THERMOSTATIC CONTROLS FOR EACH ZONE. THE SUPPLY OF HEATING AND COOLING ENERGY TO EACH SPACE-CONDITIONING ZONE OR DWELLING UNIT SHALL BE CONTROLLED BY AN INDIVIDUAL THERMOSTATIC CONTROL THAT RESPONDS TO TEMPERATURE WITHIN THE ZONE AND THAT MEETS THE APPLICABLE REQUIREMENTS OF SECTION 120.2(a). CRITERIA FOR ZONAL THERMOSTATIC CONTROLS. THE INDIVIDUAL THERMOSTATIC CONTROLS REQUIRED BY SECTION 120.2(b) SHALL MEET REQUIREMENTS; FOR HEATING SHALL BE CAPABLE OF BEING SET, LOCALLY OR REMOTELY, DOWN TO 55°F OR LOWER. OR FOR COOLING IT SHALL BE CAPABLE OF BEING SET, LOCALLY OR REMOTELY, UP TO 85°F OR HIGHER. FOR HOTEL/MOTEL GUEST ROOM AND HIGH-RISE RESIDENTIAL DWELLING UNIT THERMOSTATS; SHALL HAVE: NUMERIC TEMPERATURE SETPOINTS IN °F; AND SETPOINT STOPS ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, TO RESTRICT OVER-HEATING AND OVER-COOLING AND MEET SECTION 150(i). HEAT PUMP CONTROLS. ALL HEAT PUMPS WITH SUPPLEMENTARY ELECTRIC RESISTANCE HEATERS SHALL BE INSTALLED WITH CONTROLS THAT COMPLY WITH SECTION 110.2(b). SHUT-OFF AND RESET CONTROLS FOR SPACE-CONDITIONING SYSTEMS; SHALL BE INSTALLED WITH CONTROLS THAT COMPLY WITH CONTROLS CAPABLE OF AUTOMATICALLY SHUTTING OFF THE SYSTEM DURING PERIODS OF NONUSE AND SHALL HAVE BY HAVING AN AUTOMATIC TIME SWITCH CONTROL DEVICE AND ACCESSIBLE MANUAL OVERRIDE THAT ALLOWS OPERATION OF THE SYSTEM FOR UP TO 4 HOURS. DAMPERS FOR AIR SUPPLY AND EXHAUST EQUIPMENT. OUTDOOR AIR SUPPLY AND EXHAUST EQUIPMENT SHALL BE INSTALLED WITH DAMPERS THAT AUTOMATICALLY CLOSE UPON FAN SHUTDOWN. ISOLATION AREA DEVICES. EACH SPACE-CONDITIONING SYSTEM SERVING MULTIPLE ZONES WITH A COMBINED CONDITIONED FLOOR AREA OF MORE THAN 25,000 SQUARE FEET SHALL BE DESIGNED, INSTALLED, AND CONTROLLED TO SERVE ISOLATION AREAS. AUTOMATIC DEMAND SHED CONTROLS. HVAC SYSTEMS WITH DDC TO THE ZONE LEVEL SHALL BE PROGRAMMED TO ALLOW CENTRALIZED DEMAND SHED FOR NON-CRITICAL ZONES. THE PIPING FOR ALL SPACE-CONDITIONING AND SERVICE WATER-HEATING SYSTEMS WITH FLUID TEMPERATURES LISTED IN TABLE 120.3-A SHALL INSTALL THE AMOUNT OF INSULATION SPECIFIED. ALL AIR DISTRIBUTION SYSTEM DUCTS AND PLENUMS, INCLUDING, BUT NOT LIMITED TO, BUILDING CAVITIES, MECHANICAL CLOSETS, AIR-HANDLER BOXES AND SUPPORT PLATFORMS USED AS DUCTS OR PLENUMS, SHALL BE INSTALLED, SEALED AND INSULATED TO MEET THE REQUIREMENTS OF THE 2016 CMC SECTIONS 601, 602, 603, 604, 605, AND SMACNA-006-2006 HVAC DUCT CONSTRUCTION STANDARDS METAL & FLEXIBLE, 3RD EDITION. BEFORE AN OCCUPANCY PERMIT IS GRANTED THE CERTIFICATE OF ACCEPTANCE SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY THAT CERTIFIES THAT THE EQUIPMENT AND SYSTEMS MEET THE ACCEPTANCE REQUIREMENTS. ALL NEWLY INSTALLED AIR COOLED PACKAGED DX UNITS GREATER THAN 54,000 BTU/HR WITH AN ECONOMIZER SHALL HAVE FAULT DETECTION AND DIAGNOSTICS. DDC CONTROLS TO ZONE SHALL BE PROVIDED AS SPECIFIED BY TABLE 120.2-A. SPACE CONDITIONING SYSTEMS WITH DDC CONTROLS SHALL HAVE OPTIMUM START/STOP CONTROLS. NEW NONRESIDENTIAL BUILDINGS SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF SECTIONS 120.8(a) THROUGH 120.8(i) IN THE BUILDING DESIGN AND CONSTRUCTION PROCESSES. ALL NEW BOILERS OVER 2,500,000 BTU/HR SHALL COMPLY WITH COMBUSTION AIR AND COMBUSTION AIR FAN REQUIREMENTS. MECHANICAL MANDATORY MEASURES 2016 Certification of Equipment Efficiencies (§110.2 thru §110.11) HVAC Equipment Efficiencies (§110.2) Ventilation (§120.1) Demand Controlled Ventilation (§120.1(c)3) Controls (§120.2) Pipe Insulation (§120.3) Duct Construction and Insulation (§120.4) Acceptance Tests (§120.5 and Reference Nonresidential NA7.5) Nonresidential Building Commissioning (§120.8) Commercial Boilers (§120.9) GENERAL NOTES 1.REMOVABLE CEILING PANEL OR PANELS AT FACE OF ALL FIRE AND FIRE/SMOKE DAMPERS BY GENERAL CONTRACTOR (24" x 24" MIN.) UNLESS OTHERWISE NOTED. 2.INCOMBUSTIBLE PLENUM ABOVE CEILING FOR RETURN/RECIRCULATING AIR BY GENERAL CONTRACTOR. CONCEALED BUILDING SPACES USED AS RETURN AIR PLENUMS SHALL BE IN COMPLIANCE WITH CMC 602.2. 3.ACCESS DOORS AND/OR ACCESS PANELS THROUGH FIRE RATED WALLS, SHAFTS, CEILINGS, ETC., MUST EQUAL THE MATERIAL PENETRATED. 4. ALL AIR SHAFTS SHALL BE MADE AIR TIGHT BY GENERAL CONTRACTOR. 5. ALL UNDERCUT DOORS AND DOOR LOUVERS ARE BY GENERAL CONTRACTOR. 6. ALL APPLIANCES DESIGNED TO BE FIXED IN POSITION SHALL BE SECURELY FASTENED IN PLACE. 7. ALL SPACE CONDITIONING EQUIPMENT SHALL BE LABELED AS TO WHICH AREA IT SERVES. ACCO INSTALLATION PRACTICES OF SOFT-COPPER REFRIGERANT PIPING FOLLOW THE INTERPRETATION THAT CEILING STRUCTURES AND WALL STRUCTURES MEET THE REQUIREMENTS OF PIPING PROTECTION REQUIRED BY 2016 CMC 1109.7 8. FOR NEW BUILDINGS 10,000 SQUARE FEET AND OVER, BUILDING COMMISSIONING SHALL BE INCLUDED IN THE DESIGN AND CONSTRUCTION PROCESSES OF THE BUILDING PROJECT TO VERIFY THAT THE BUILDING SYSTEMS AND COMPONENTS MEET THE OWNER OR OWNER'S REPRESENTATIVE'S PROJECT REQUIREMENTS. IF THE HVAC SYSTEM IS USED DURING CONSTRUCTION, USE RETURN AIR FILTERS WITH A MERV 8 RATING. REPLACE ALL FILTERS IMMEDIATELY PRIOR TO OCCUPANCY, OR, IF THE BUILDING IS OCCUPIED DURING ALTERATION, AT THE CONCLUSION OF CONSTRUCTION. TESTING AND ADJUSTING OF SYSTEMS SHALL BE REQUIRED FOR BUILDINGS LESS THAN 10,000 SQUARE FEET. AT THE TIME OF ROUGH INSTALLATION, OR DURING THE STORAGE ON THE CONSTRUCTION SITE AND UNTIL FINAL STARTUP OF THE HEATING AND COOLING EQUIPMENT, ALL DUCT AND OTHER RELATED AIR DISTRIBUTION COMPONENT OPENINGS SHALL BE COVERED. IN MECHANICALLY VENTILATED BUILDING, PROVIDE REGULARLY OCCUPIED AREA OF THE BUILDING WITH AIR FILTRATION MEDIA FOR OUTSIDE AND RETURN AIR PRIOR TO OCCUPANCY THAT PROVIDES AT LEAST MERV OF 8. INSTALLED FILTERS SHALL BE CLEARLY LABELED BY THE MANUFACTURER INDICATING THE MERV RATING. WHERE OUTDOOR AREAS ARE PROVIDED FOR SMOKING, PROHIBIT SMOKING WITHIN 25 FT OF BUILDING ENTRIES, OUTDOOR AIR INTAKES, AND OPERABLE WINDOWS AND WITHIN THE BUILDING AS ALREADY PROHIBITED BY OTHER LAWS OR REGULATIONS. BUILDINGS SHALL MEET OR EXCEED THE PROVISIONS OF CALIFORNIA BUILDING CODE, CCR, TITLE 24, PART 2, SECTIONS 1203 (VENTILATION) AND CHAPTER 14 (EXTERIOR WALLS). BUILDINGS SHALL MEET OR EXCEED THE PROVISIONS OF CALIFORNIA BUILDING CODE, CCR, TITLE 24, PART 2, SECTIONS 1203 (VENTILATION) AND CHAPTER 14 (EXTERIOR WALLS). FOR BUILDINGS EQUIPPED WITH DEMAND CONTROL VENTILATION, CO2 SENSORS AND VENTILATION CONTROLS SHALL BE SPECIFIED AND INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE CURRENT EDITION OF THE CALIFORNIA ENERGY CODE, CCR, TITLE 24, PART 6, SECTION 120.1(c)(3) INSTALL HVAC, REFRIGERATION, AND FIRE SUPPRESSION EQUIPMENT THAT DO NOT CONTAIN CFCS OR HALONS. CALGREEN MANDATORY MEASURES COMMISSIONING (§ 5.410.2) POLLUTANT CONTROL (§ 5.504) INDOOR MOISTURE CONTROL (§ 5.505) INDOOR AIR QUALITY (§ 5.506) OUTDOOR AIR QUALITY (§ 5.508) CEC-NRCC-MCH-01-E (Revised 01/16)CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-01-E Mechanical Systems (Page 1 of 4) A. MECHANICAL COMPLIANCE FORMS & WORKSHEETS (check box if worksheet is included) YES NO Form/Worksheet #Title NRCC-MCH-01-E (Part 1 of 3) Certificate of Compliance, Declaration. Required on plans for all submittals. NRCC-MCH-01-E (Part 2 of 3) Certificate of Compliance, Required Acceptance Tests (MCH-02A to 11A). Required on plans for all submittals. NRCC-MCH-01-E (Part 3 of 3) Certificate of Compliance, Required Acceptance Tests (MCH-12A to 18A). Required on plans where applicable. NRCC-MCH-02-E (Part 1 of 2) Mechanical Dry Equipment Summary is required for all submittals with Central Air Systems. It is optional on plans. NRCC-MCH-02-E (Part 2 of 2) Mechanical Wet Equipment Summary is required for all submittals with chilled water, hot water or condenser water systems. It is optional on plans. NRCC-MCH-03-E Mechanical Ventilation and Reheat is required for all submittals with multiple zone heating and cooling systems. It is optional on plans. Project Name:Date Prepared: NRCC-MCH-07-E (Part 1 of 2) Powered Consumption of Fans. Required on plans where applicable. NRCC-MCH-07-E (Part 2 of 2) Powered Consumption of Fans. Declaration. Required on plans where applicable. For detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, refer to the 2016 Nonresidential Manual Note: The Enforcement Agency may require all forms to be incorporated onto the building plans. Test Description MCH-02A MCH-03A MCH-04A MCH-05A MCH-06A MCH-07A MCH-08A MCH-09A MCH-10A MCH-11A Equipment Requiring Testing or Verification # of units Outdoor Air Single Zone Unitary Air Distribution Ducts Economizer Controls Demand Controlled Ventilation (DCV) Supply Fan VAV Valve Leakage Test Supply Water Temp. Reset Hydronic System Variable Flow Control Automatic Demand Shed Control CEC-NRCC-MCH-01-E (Revised 01/16)CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-01-E Mechanical Systems (Page 2 of 4) Project Name:Date Prepared: B. MECHANICAL HVAC ACCEPTANCE FORMS (check box for required forms) Test Performed By: Designer: This compliance document is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for HVAC systems. The designer is required to check the applicable boxes for all acceptance tests that apply and list all equipment that requires an acceptance test. All equipment of the same type that requires a test, list the equipment description and the number of systems. Installing Contractor: The contractor who installed the equipment is responsible to either conduct the acceptance test themselves or have a qualified entity run the test for them. If more than one person has responsibility for the acceptance testing, each person shall sign and submit the Certificate of Acceptance applicable to the portion of the construction or installation for which they are responsible. Enforcement Agency: Plancheck -- The NRCC-MCH-01-E compliance document is not considered a completed document and is not to be accepted by the building department unless the correct boxes are checked. Inspector - Before occupancy permit is granted all newly installed process systems must be tested to ensure proper operations. CEC-NRCC-MCH-01-E (Revised 01/16)CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-01-E Mechanical Systems (Page 3 of 4) C. MECHANICAL HVAC ACCEPTANCE FORMS (check box for required forms) Test Description MCH-12A MCH-13A MCH-14A MCH-15A MCH-16A MCH-17A MCH-18A Equipment Requiring Testing or Verification # of units Fault Detection & Diagnostics for DX Units Automatic Fault Detection & Diagnostics for Air & Zone Distributed Energy Storage DX AC Systems Thermal Energy Storage (TES) Systems Supply Air Temperature Reset Controls Condenser Water Reset Controls ECMS Project Name:Date Prepared: Designer: This compliance document is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for HVAC systems. The designer is required to check the applicable boxes for all acceptance tests that apply and list all equipment that requires an acceptance test. All equipment of the same type that requires a test, list the equipment description and the number of systems. Installing Contractor: The contractor who installed the equipment is responsible to either conduct the acceptance test themselves or have a qualified entity run the test for them. If more than one person has responsibility for the acceptance testing, each person shall sign and submit the Certificate of Acceptance applicable to the portion of the construction or installation for which they are responsible. Enforcement Agency: Plancheck -- The NRCC-MCH-01-E compliance document is not considered a completed document and is not to be accepted by the building department unless the correct boxes are checked. Inspector - Before occupancy permit is granted all newly installed process systems must be tested to ensure proper operations. CEC-NRCC-MCH-02-E (Revised 01/16)CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-02-E HVAC Dry System Requirements (Page 1 of 3) A. Equipment Tags and System Description 1 MANDATORY MEASURES T-24 Sections Reference to the Requirements in the Contract Documents 2 Heating Equipment Efficiency 3 110.1 or 110.2(a) Cooling Equipment Efficiency 3 110.1 or 110.2(a) HVAC or Heat Pump Thermostats 110.2(b), 110.2(c) Furnace Standby Loss Control 110.2(d) Low leakage AHUs 110.2(f) Ventilation4 120.1(b) Demand Control Ventilation 5 120.1(c)4 Occupant Sensor Ventilation Control 6 120.1(c)5, 120.2(e)3 Shutoff and Reset Controls 7 120.2(e) Outdoor Air and Exhaust Damper Control 120.2(f) Isolation Zones 120.2(g) Automatic Demand Shed Controls 120.2(h) Economizer FDD 120.2(i) Duct Insulation 120.4 PRESCRIPTIVE MEASURES Equipment is sized in conformance with 140.4 (a & b)140.4(a & b) Supply Fan Pressure Control 140.4(c) Simultaneous Heat/Cool 8 140.4(d) Economizer 140.4(e) Heat and Cool Air Supply Reset 140.4(f) Electric Resistance Heating 9 140.4(g) Duct Leakage Sealing and Testing 10 140.4(l) Project Name:Date Prepared: Yes No Yes No Yes No Notes: 1. Provide equipment tags (e.g. AHU 1 to 10) and system description (e.g. Single Duct VAV reheat) as appropriate. Multiple units with common requirements can be grouped together. 2. Provide references to plans (i.e. Drawing Sheet Numbers) and/or specifications (including Section name/number and relevant paragraphs) where each requirement is specified. Enter "N/A" if the requirement is not applicable to this system. 3. The referenced plans and specifications must include all of the following information: equipment tag, equipment nominal capacity, Title 24 minimum efficiency requirements, and actual rated equipment efficiencies. Where multiple efficiency requirements are applicable (e.g. full and part load) include all. Where appliance standards apply (110.1), identify where equipment is required to be listed per Title 20 1601 et seq. 4. Identify where the ventilation requirements are documented for each central HVAC system. Include references to both central unit schedules and sequences of operation. If one or more space is naturally ventilated identify where this is documented in the plans and specifications. Multiple zone central air systems must also provide a MCH-03-E compliance document. 5. If one or more space has demand controlled ventilation identify where it is specified including the sensor specifications and the sequence of operation. 6. If one or more space has occupant sensor ventilation control identify where it is specified including the sensor specifications and the sequence of operation 7. If the system is DDC identify the sequences for the system start/stop, optimal start, setback (if required) and setup (if required). For all systems identify the specification for the thermostats and time clocks (If applicable). 8. Identify where the heating, cooling and deadband airflows are scheduled for this system. Include a reference to the specification of the zone controls. Provide a MCH-03-E compliance document. 9. Enter N/A if there is no electric heating. If the system has electric heating indicate which exception to 140.4(g) applies. 10. If duct leakage sealing and testing is required, a MCH-04-A compliance document must be submitted. I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. 2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer). 3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy. CEC-NRCC-MCH-02-E (Revised 01/16)CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-02-E HVAC Dry & Wet System Requirements (Page 3 of 3) DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. I certify that this Certificate of Compliance documentation is accurate and complete. CEA/HERS Certification Identification (if applicable): RESPONSIBLE PERSON'S DECLARATION STATEMENT Project Name:Date Prepared: Responsible Designer Name:Responsible Designer Signature: Company:Date Signed: Address:License: City/State/Zip:Phone: Documentation Author Name:Documentation Author Signature: Signature Date:Company: Address: City/State/Zip:Phone: CEC-NRCC-MCH-01-E (Revised 01/16)CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-01-E Mechanical Systems (Page 4 of 4) DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. I certify that this Certificate of Compliance documentation is accurate and complete. CEA/HERS Certification Identification (if applicable): RESPONSIBLE PERSON'S DECLARATION STATEMENT Project Name:Date Prepared: Documentation Author Name:Documentation Author Signature: Signature Date:Company: Address: City/State/Zip:Phone: Responsible Designer Name:Responsible Designer Signature: Company:Date Signed: Address:License: City/State/Zip:Phone: I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. 2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer). 3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy. STATE OF CALIFORNIA MECHANICAL SYSTEMS CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016 CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016 STATE OF CALIFORNIA MECHANICAL SYSTEMS STATE OF CALIFORNIA Mechanical Systems CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016 STATE OF CALIFORNIA HVAC DRY & WET SYSTEM REQUIREMENTS CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016 STATE OF CALIFORNIA HVAC SYSTEM REQUIREMENTS CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016 STATE OF CALIFORNIA Mechanical Systems CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance January 2016 HARBOR DAY SCHOOL 08/13/2019 HARBOR DAY SCHOOL 08/13/19 CU'S 2 - - - - - - FCU'S (W/ OSA)83 HARBOR DAY SCHOOL 08/13/19 FCU'S W/ OSA 83 CU'S 4 - - - - - HARBOR DAY SCHOOL 04/24/20 FC/CU VRF SS 1-1/1-2 - AC0.01, AC0.02 - AC0.01, AC0.02 - AC1.01, AC1.02 - N/A - - AC0.01, AC0.02 - - N/A - -- -- N/A - N/A - N/A - AC0.05 - N/A N/A - N/A N/A - N/A N/A - N/A N/A - N/A N/A - HARBOR DAY SCHOOL 04/24/20 CALEB DAVIES ACCO ENGINEERED SYSTEMS INC. 265 MCCORMICK AVE. COSTA MESA, CA 92626 714-352-2226 04/24/20 M33701 04/24/20 ASHLEY DAVITT ACCO ENGINEERED SYSTEMS INC. 265 MCCORMICK AVE. COSTA MESA, CA 92626 714-352-2226 HARBOR DAY SCHOOL 04/24/20 CALEB DAVIES ACCO ENGINEERED SYSTEMS INC. 265 MCCORMICK AVE COSTA MESA, CA 92626 714-352-2226 04/24/20 M33701 04/24/20 ASHLEY DAVITT ACCO ENGINEERED SYSTEMS INC. 265 MCCORMICK AVE COSTA MESA, CA 92626 714-352-2226 N/A N/A N/A N/A - - AC0.01, AC0.02 AC0.01, AC0.02 AC1.01, AC1.02 N/A AC0.01, AC0.02 N/A - - N/A N/A N/A AC0.05 N/A N/A EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By 2/ 5 / 2 0 2 1 3 : 1 0 : 2 0 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC0.05 TITLE-24, MANDATORY MEASURES, & GENERAL NOTES 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t N/A A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 1 01/22/21 CITY PERMIT AMENDMENT CD DUCT INSULATION REQUIREMENTS (PER 2016 BUILDING ENERGY EFFICIENCY STANDARDS) DUCT LOCATION INSULATION R-VALUE INSTALLED INSULATION THICKNESS R-8 - OUTDOORS - SPACE BETWEEN ROOF & INSULATED CEILING - IN VENTED ATTIC SPACES - IN UNCONDITIONED SPACES 2" - IN RETURN AIR PLENUM - ALL OTHER SPACES R-4.2 1" - ENCLOSED IN DIRECTLY CONDITIONED SPACE NONE REQUIRED N/A NOTES: 1. INSULATION THICKNESS VALUES BASED ON JOHNS MANVILLE INSULATION. 2. THE INSTALLED INSULATION THICKNESS OF DUCT LINING FOR PURPOSE OF COMPLIANCE IS EQUIVALENT TO ITS NOMINAL THICKNESS. 3. THE INSTALLED INSULATION THICKNESS OF DUCT WRAP FOR PURPOSE OF COMPLIANCE IS 75% OF ITS NOMINAL THICKNESS. LG 90-116 0.5 (ANY DIAM.) 130-176 0.75≤1-1/8" PIPE 1.0≥1-3/8" PIPE 40-70 0.75≤1-1/8" PIPE 1.0≥1-3/8" PIPE MANUF. LIQUID LINE HIGH PRESSURE VAPOR LINE LOW PRESSURE VAPOR LINE TEMPERATURE RANGE (°F) INSULATION REQUIREMENTS (INCHES) TEMPERATURE RANGE (°F) INSULATION REQUIREMENTS (INCHES) TEMPERATURE RANGE (°F) INSULATION REQUIREMENTS (INCHES) FC-A1-1 265 N/A 265 Y N/A 108 0.15 17 1 15 15 N/A 17 Y N/A N/A N/A N/A N/A N/A FC-A1-2 1250 N/A 1250 Y N/A 429 0.50 215 14 15 210 N/A 215 Y N/A N/A N/A N/A N/A N/A FC-A1-3 265 N/A 265 Y N/A 215 0.15 33 2 15 30 N/A 33 Y N/A N/A N/A N/A N/A N/A FC-A1-4 285 N/A 285 Y N/A 179 0.50 90 6 15 90 N/A 90 Y N/A N/A N/A N/A N/A N/A FC-A1-5 265 N/A 265 Y N/A 142 0.15 22 1 15 15 N/A 22 Y N/A N/A N/A N/A N/A N/A FC-A1-6 310 N/A 480 Y N/A 617 0.15 93 6 15 90 N/A 93 Y N/A N/A N/A N/A N/A N/A FC-A1-7 265 N/A 265 Y N/A 130 0.15 20 2 15 30 N/A 30 Y N/A N/A N/A N/A N/A N/A FC-A1-8 265 N/A 460 Y N/A 207 0.15 31 1 15 15 N/A 31 Y N/A N/A N/A N/A N/A N/A FC-A1-9 265 N/A 265 Y N/A 123 0.15 19 1 15 15 N/A 19 Y N/A N/A N/A N/A N/A N/A FC-A1-10 310 N/A 265 Y N/A 123 0.38 47 4 15 60 N/A 60 Y N/A N/A N/A N/A N/A N/A FC-A1-13 310 N/A 310 Y N/A 418 0.15 63 6 15 90 N/A 90 Y N/A N/A N/A N/A N/A N/A FC-A1-14 265 N/A 265 Y N/A 126 0.15 19 2 15 30 N/A 30 Y N/A N/A N/A N/A N/A N/A FC-A1-15 265 N/A 265 Y N/A 178 0.15 27 1 15 15 N/A 27 Y N/A N/A N/A N/A N/A N/A FC-A1-16 310 N/A 285 Y N/A 227 0.50 114 8 15 120 N/A 120 Y N/A N/A N/A N/A N/A N/A FC-A1-17 265 N/A 265 Y N/A 148 0.15 23 1 15 15 N/A 23 Y N/A N/A N/A N/A N/A N/A FC-A1-18A 1450 N/A 1915 Y N/A 1343 0.38 511 33 15 495 N/A 511 Y N/A N/A N/A N/A N/A N/A FC-A1-18B 1450 N/A 1735 Y N/A 892 0.38 338 23 15 345 N/A 345 Y N/A N/A N/A N/A N/A N/A FC-A1-19 310 N/A 265 Y N/A 321 0.38 122 8 15 120 N/A 122 Y N/A N/A N/A N/A N/A N/A FC-A1-20 390 N/A 390 Y N/A 371 0.38 141 9 15 135 N/A 141 Y N/A N/A N/A N/A N/A N/A FC-A1-21 390 N/A 390 Y N/A 383 0.38 146 10 15 150 N/A 150 Y N/A N/A N/A N/A N/A N/A FC-A2-1 390 N/A 565 Y N/A 351 0.38 134 9 15 135 N/A 135 Y N/A N/A N/A N/A N/A N/A FC-A2-2 2260 N/A 1745 Y N/A 830 0.50 415 16 15 240 N/A 415 Y N/A N/A N/A N/A N/A N/A FC-A2-3 265 N/A 265 Y N/A 117 0.15 17 1 15 15 N/A 17 Y N/A N/A N/A N/A N/A N/A FC-A2-4 265 N/A 265 Y N/A 118 0.15 18 1 15 15 N/A 18 Y N/A N/A N/A N/A N/A N/A FC-A2-5 265 N/A 265 Y N/A 115 0.15 17 1 15 15 N/A 17 Y N/A N/A N/A N/A N/A N/A FC-A2-6 265 N/A 265 Y N/A 113 0.50 67 3 15 45 N/A 67 Y N/A N/A N/A N/A N/A N/A FC-A2-7 265 N/A 265 Y N/A 142 0.15 21 1 15 15 N/A 21 Y N/A N/A N/A N/A N/A N/A FC-A2-8 310 N/A 530 Y N/A 466 0.15 70 5 15 75 N/A 75 Y N/A N/A N/A N/A N/A N/A FC-A2-9 265 N/A 265 Y N/A 142 0.15 21 1 15 15 N/A 21 Y N/A N/A N/A N/A N/A N/A FC-A2-10 265 N/A 265 Y N/A 118 0.15 18 1 15 15 N/A 18 Y N/A N/A N/A N/A N/A N/A FC-A2-11 265 N/A 265 Y N/A 101 0.15 15 1 15 15 N/A 15 Y N/A N/A N/A N/A N/A N/A FC-A2-12 265 N/A 460 Y N/A 230 0.15 35 2 15 30 N/A 35 Y N/A N/A N/A N/A N/A N/A FC-A2-15 1000 N/A 1320 Y N/A 800 0.38 304 20 15 300 N/A 304 Y N/A N/A N/A N/A N/A N/A FC-B1-1 1250 N/A 1735 Y N/A 924 0.38 352 23 15 345 N/A 352 Y N/A N/A N/A N/A N/A N/A FC-B1-3 285 N/A 480 Y N/A 130 0.38 50 4 15 60 N/A 60 Y N/A N/A N/A N/A N/A N/A FC-B1-4 1250 N/A 1735 Y N/A 920 0.38 350 23 15 345 N/A 350 Y N/A N/A N/A N/A N/A N/A FC-B1-5 1250 N/A 1735 Y N/A 756 0.38 288 19 15 285 N/A 288 Y N/A N/A N/A N/A N/A N/A FC-B1-6 310 N/A 495 Y N/A 214 0.50 107 7 15 105 N/A 107 Y N/A N/A N/A N/A N/A N/A FC-B1-7 1250 N/A 1320 Y N/A 743 0.38 282 19 15 285 N/A 285 Y N/A N/A N/A N/A N/A N/A FC-B1-8 1250 N/A 1320 Y N/A 776 0.38 295 20 15 300 N/A 300 Y N/A N/A N/A N/A N/A N/A FC-B1-9 310 N/A 310 Y N/A 151 0.50 75 5 15 75 N/A 75 Y N/A N/A N/A N/A N/A N/A FC-B1-10 1000 N/A 1320 Y N/A 734 0.38 279 19 15 285 N/A 285 Y N/A N/A N/A N/A N/A N/A FC-B1-11 1000 N/A 1320 Y N/A 736 0.38 280 19 15 285 N/A 285 Y N/A N/A N/A N/A N/A N/A FC-B1-12 310 N/A 480 Y N/A 152 0.50 76 5 15 75 N/A 76 Y N/A N/A N/A N/A N/A N/A FC-B1-13 1000 N/A 1320 Y N/A 766 0.38 291 20 15 300 N/A 300 Y N/A N/A N/A N/A N/A N/A FC-B1-14 1250 N/A 1320 Y N/A 747 0.38 284 19 15 285 N/A 285 Y N/A N/A N/A N/A N/A N/A FC-B1-15 310 N/A 310 Y N/A 197 0.50 98 7 15 105 N/A 105 Y N/A N/A N/A N/A N/A N/A FC-B1-16 1450 N/A 1900 Y N/A 799 0.38 304 20 15 300 N/A 304 Y N/A N/A N/A N/A N/A N/A FC-B1-17 1000 N/A 1320 Y N/A 658 0.38 251 17 15 255 N/A 255 Y N/A N/A N/A N/A N/A N/A FC-B1-18 1450 N/A 1745 Y N/A 1,179 0.38 448 30 15 450 N/A 450 Y N/A N/A N/A N/A N/A N/A FC-C2-2 285 N/A 265 Y N/A 208 0.15 35 6 15 90 N/A 90 Y N/A N/A N/A N/A N/A N/A FC-C2-3 1000 N/A 1320 Y N/A 801 0.38 304 20 15 300 N/A 304 Y N/A N/A N/A N/A N/A N/A FC-C2-4 800 N/A 1320 Y N/A 577 0.38 219 15 15 225 N/A 225 Y N/A N/A N/A N/A N/A N/A FC-C2-5 800 N/A 1320 Y N/A 584 0.38 221 15 15 225 N/A 225 Y N/A N/A N/A N/A N/A N/A FC-C2-6 800 N/A 1320 Y N/A 567 0.38 216 15 15 225 N/A 225 Y N/A N/A N/A N/A N/A N/A FC-C2-7 310 N/A 495 Y N/A 268 0.15 45 7 15 105 N/A 105 Y N/A N/A N/A N/A N/A N/A FC-C2-8 800 N/A 1320 Y N/A 582 0.38 221 15 15 225 N/A 225 Y N/A N/A N/A N/A N/A N/A FC-C2-9 800 N/A 1320 Y N/A 558 0.38 213 14 15 210 N/A 213 Y N/A N/A N/A N/A N/A N/A FC C2-10 390 N/A 530 Y N/A 327 0.15 50 9 15 135 N/A 135 Y N/A N/A N/A N/A N/A N/A FC-C2-11 800 N/A 1320 Y N/A 558 0.38 213 14 15 210 N/A 213 Y N/A N/A N/A N/A N/A N/A FC-C2-12 390 N/A 530 Y N/A 286 0.15 45 8 15 120 N/A 120 Y N/A N/A N/A N/A N/A N/A FC-C2-13 800 N/A 1320 Y N/A 595 0.38 226 15 15 225 N/A 226 Y N/A N/A N/A N/A N/A N/A FC-C2-14 800 N/A 1320 Y N/A 567 0.38 216 15 15 225 N/A 225 Y N/A N/A N/A N/A N/A N/A FC-C2-15 800 N/A 1320 Y N/A 567 0.38 216 15 15 225 N/A 225 Y N/A N/A N/A N/A N/A N/A FC-C2-16 800 N/A 1320 Y N/A 577 0.38 220 15 15 225 N/A 225 Y N/A N/A N/A N/A N/A N/A FC-C2-17 800 N/A 1320 Y N/A 581 0.38 221 15 15 225 N/A 225 Y N/A N/A N/A N/A N/A N/A FC-C2-18 800 N/A 1320 Y N/A 599 0.38 227 15 15 225 N/A 227 Y N/A N/A N/A N/A N/A N/A FC-C2-19 800 N/A 1320 Y N/A 597 0.38 227 15 15 225 N/A 227 Y N/A N/A N/A N/A N/A N/A FC-D1-1 1800 N/A 2020 Y N/A 1,194 0.50 597 34 15 510 N/A 597 Y N/A N/A N/A N/A N/A N/A FC-D1-2 390 N/A 495 Y N/A 261 0.38 100 7 15 105 N/A 105 Y N/A N/A N/A N/A N/A N/A FC-D1-3 1800 N/A 1745 Y N/A 1297 0.50 649 36 15 540 N/A 649 Y N/A N/A N/A N/A N/A N/A FC-D1-4 800 N/A 1320 Y N/A 511 0.50 256 13 15 195 N/A 256 Y N/A N/A N/A N/A N/A N/A FC-D1-5 1750 N/A 1520 Y N/A 1311 0.50 655 33 15 495 N/A 655 Y N/A N/A N/A N/A N/A N/A FC-D1-6 265 N/A 265 Y N/A 170 0.15 26 2 15 30 N/A 30 Y N/A N/A N/A N/A N/A N/A FC-D1-7 2260 N/A 1770 Y N/A 1,530 0.50 765 39 15 585 N/A 765 Y N/A N/A N/A N/A N/A N/A FC-D1-8 1250 N/A 1880 Y N/A 730 0.50 365 19 15 285 N/A 390 Y N/A N/A N/A N/A N/A N/A FC-D2-1 800 N/A 1320 Y N/A 574 0.38 220 15 15 225 N/A 225 Y N/A N/A N/A N/A N/A N/A FC-D2-2 390 N/A 530 Y N/A 335 0.38 127 9 15 135 N/A 135 Y N/A N/A N/A N/A N/A N/A FC-D2-3 1750 N/A 1770 Y N/A 1311 0.50 656 33 15 495 N/A 656 Y N/A N/A N/A N/A N/A N/A FC-D2-4 390 N/A 565 Y N/A 289 0.50 145 9 15 135 N/A 145 Y N/A N/A N/A N/A N/A N/A FC-D2-5 1750 N/A 1770 Y N/A 1,219 0.50 610 31 15 465 N/A 610 Y N/A N/A N/A N/A N/A N/A FC-D2-6 1450 N/A 1735 Y N/A 818 0.15 125 21 15 315 N/A 315 Y N/A N/A N/A N/A N/A N/A LVL 1 HALLWAY N/A N/A N/A N/A N/A 6915 0.15 1040 N/A N/A N/A N/A 1040 Y N/A N/A N/A N/A N/A N/A LVL 2 HALLWAY N/A N/A N/A N/A N/A 5673 0.15 855 N/A N/A N/A N/A 855 Y N/A N/A N/A N/A N/A N/A Notes: 2. The largest amount of primary air supplied by the terminal unit when it's operating in the cooling mode. 3. The smallest amount of primary air supplied by the terminal unit in the deadband mode. 4. The largest amount of primary air supplied by the terminal unit when it's operating in the heating mode. 5. A terminal unit can be controlled with DDC controls, or non-DDC controls. Each control category has different reheat limitations in code. 6. Transfer Air must be provided where Required Ventilation Airflow (Column 14) is greater than the Design Primary Deadband Airflow (Column 3). 8. Minimum ventilation rate per Section §120.1. Table 120.1-A. 10. Based on number of fixed seats where applicable or the greater of the expected number of occupants and 50% of the CBC occupant load for egress purposes for space without fixed seating. 14. Required Ventilation Airflow (Req'd Ventilation Airflow) is the larger of the ventilation rates calculated on an AREA BASIS or OCCUPANCY BASIS (Column 9 or 12) 15. This column identifies whether or not the Design Primary Deadband Airflow complies or not. It compares the value in column 14 to the value in column 3 and column 6. 16. Design Primary Cooling Airflow * 0.50 for DDC, Design Primary Cooling Airflow * 0.30 for Non‐DDC. If the Design Primary Cooling Airflow is less than 300 cfm, then this is not applicable. 17. Maximum of Column 14 and Column 16. If the Design Primary Cooling Airflow is 300 cfm or less, then this is not applicable. 18. This column identifies whether or not the Design Primary Reheat Airflow at the zone level, complies or not. It compares the value in column 17 to the value in column 4. 19. Design Primary Cooling Airflow * 0.20 for DDC. Not applicable for Non‐DDC zones or zones where Design Primary Cooling Airflow is 300 cfm or less. 20. Maximum of Column 14 and Column 19. Not applicable if the Design Primary Cooling Airflow is 300 cfm or less. 21. This column identifies whether or not the Design Primary Deadband Airflow at the zone level, complies or not. It compares the value in column 20 to the value in column 3. CEC-NRCC-MCH-03-E (Revised 05/16)CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-03-E Mechanical Ventilation & Reheat (Page 1 of 2) ACTUAL DESIGN INFO (FROM EQUIPMENT SCHEDULES, ETC)AREA BASIS OCCUPANCY BASIS ROOM BASIS VAV Reheated Primary Air CFM VAV Deadband Primary Air CFM 01 02 Project Name:Date Prepared: ZO N E / S Y S T E M / V A V BO X T A G DE S I G N P R I M A R Y CO O L I N G A I R F L O W (C F M ) DE S I G N P R I M A R Y DE A D B A N D AI R F L O W ( C F M ) DE S I G N P R I M A R Y HE A T I N G A I R F L O W (C F M ) CO N T R O L T Y P E D D C (Y / N ) TR A N S F E R A I R F L O W (C F M ) CO N D I T I O N E D A R E A (f t ² ) MI N C F M P E R A R E A (C F M / f t ² ) MI N C F M B Y A R E A NU M B E R O F P E O P L E CF M P E R P E R S O N MI N C F M B Y OC C U P A N T MI N C F M B Y R O O M CO M P L I E S ? MA X I M U M R E H E A T (C F M ) CO M P L I E S ? PR I M A R Y CO O L I N G A I R AI R F L O W CO M P L I E S ? BA S E D D E S I G N PR I M A R Y C O O L I N G AI R 03 04 05 06 07 08 09 10 11 12 13 14 16 17 18 19 20 21 MINIMUM 15 RE Q ' D V E N T AI R F L O W ( C F M ) A. Mechanical Ventilation and Reheat In lieu of this compliance document, the required outdoor ventilation rates and airflows may be shown on the plans or the calculations can be presented in a spreadsheet. Mechanical Ventilation and Reheat worksheet available on the Energy commission's website at: http://www.energy.ca.gov/title24/2016standard/. Note: In all calculations that compare a supply quantity to the REQ'D V.A. quantity, the actual percentage of outdoor air in the supply is ignored. Area in building for which natural ventilation is used should be clearly designated. Specifications must require that building operating instructions include explanations of the natural ventilation system. CEC-NRCC-MCH-03-E (Revised 05/16)CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-03-E Mechanical Ventilation & Reheat (Page 2 of 2) DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. I certify that this Certificate of Compliance documentation is accurate and complete. RESPONSIBLE PERSON'S DECLARATION STATEMENT Project Name:Date Prepared: Documentation Author Name: Company: Address: City/State/Zip: Documentation Author Signature: Signature Date: Phone: Responsible Designer Name: Company: City/State/Zip: Address: Responsible Designer Signature: Date Signed: License: Phone: CEA/HERS Certification Identification (if applicable): I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. 2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer). 3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy. STATE OF CALIFORNIA MECHANICAL VENTILATION AND REHEAT CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance May 2016 STATE OF CALIFORNIA MECHANICAL VENTILATION AND REHEAT CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance May 2016 HARBOR DAY SCHOOL 04/24/20HARBOR DAY SCHOOL 04/24/20 CALEB DAVIES ACCO ENGINEERED SYSTEMS INC. 265 MCCORMICK AVE. COSTA MESA, CA 92626 714-352-2226 04/24/20 M33701 04/24/20 ASHLEY DAVITT ACCO ENGINEERED SYSTEMS INC. 265 MCCORMICK AVE. COSTA MESA, CA 92626 714-352-2226 VRF PIPE INSULATION REQUIREMENTS (2016) EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By 2/ 5 / 2 0 2 1 3 : 1 0 : 2 2 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC0.06 TITLE-24 (CONT.) 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t N/A A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 0 09/11/20 ISSUED FOR CONSTRUCTION CD 1 01/22/21 CITY PERMIT AMENDMENT CD EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By 2/ 5 / 2 0 2 1 3 : 1 0 : 2 3 P M C. DAVIES A. DAVITT C. DAVIES AC0.07 ENERGY COMPLIANCE 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t 030 01/15/21 CCD-030 CD 1 01/22/21 CITY PERMIT AMENDMENT CD EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By 2/ 5 / 2 0 2 1 3 : 1 0 : 2 4 P M C. DAVIES A. DAVITT C. DAVIES AC0.08 ENERGY COMPLIANCE (CONT.) 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t 030 01/15/21 CCD-030 CD 1 01/22/21 CITY PERMIT AMENDMENT CD EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By 2/ 5 / 2 0 2 1 3 : 1 0 : 2 5 P M C. DAVIES A. DAVITT C. DAVIES AC0.09 ENERGY COMPLIANCE (CONT.) 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t 030 01/15/21 CCD-030 CD 1 01/22/21 CITY PERMIT AMENDMENT CD PC J J J J J J J J UTILITY NOTES POWER WIRING TO EQUIPMENT BY ELECTRICIAN CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN, INSTALLED BY ACCO AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED, INSTALLED, AND WIRED BY ELECTRICIAN DSD ASD CCCC 1 1 3 3 10 10 16 16 20 20 22 22 25 25 ZZ YY V V SS NN KK HH EE BB 27 27 2 2 4 4 5 5 18 18 DD FF GG AAAA XX DDDD UU QQ C 8 8 13 13 19 19 21 21 17 17 11 11 OFFICE 124A 4TH GRADE CLASSROOM 120 3RD GRADE CLASSROOM 118 SMALL GROUP 119A 4TH GRADE CLASSROOM 119 LOWER SCHOOL SCIENCE CLASSROOM 122 WORLD LANGUAGE CLASSROOM 121 CERAMICS 125A KILN 125B UPPER SCHOOL ART LAB 125 1ST GRADE CLASSROOM 112 SMALL GROUP 113 2ND GRADE CLASSROOM 115 1ST GRADE CLASSROOM 114 SMALL GROUP 115A TEACHING AREA 131B WORKROOM 131A ELEV. E-1-1 ELECT. 110 DATA 109 CONFERENCE ROOM 107 ASSOCIATES 134 PSYCH. 137A SMALL GROUP AREA 137 2ND GRADE CLASSROOM 116 SMALL GROUP 117A 3RD GRADE CLASSROOM 117 LANGUAGE ARTS SPECIALIST 137B CUSTODIAL 136 STAIR 1 STR1-1 ELECTRICAL 163 STAFF TOILET 145 UNISEX TOILET 142 STAIR 2 STR2-1 LOBBY 100 GIRLS' RESTROOM 140 BOYS' RESTROOM 139 GIRLS' RESTROOM 143 BOYS' RESTROOM 144 WORKROOM 106 FACILITIES DIR. 105 LOWER DIR. 102 TECHNOLOGY DIRECTOR 103 HEAD OF SCHOOL 104 HALLWAY 161 LIBRARY 131 TINKER AREA 133 STORY TELLING 132 MATH SPECIALIST 137C MAKER SPACE 123 LOWER SCHOOL ART LAB 126 OPEN OFFICE 159 HALLWAY 160 HALLWAY 162 ? ? (1,325 LBS.) (1,325 LBS.) (1,305 LBS.) (1,664 LBS.) FC A1-1 FC A1-3 FC A1-4 FC A1-5 FC A1-7 FC A1-8 FC A1-9 FC A1-10 FC A1-11 FC A1-12 FC B1-4 FC B1-1 FC B1-2 FC B1-5 FC B1-7 FC A1-13 FC A1-14 FC A1-16 FC A1-17 FC A1-15 FC A1-19 FC A1-18B FC B1-8 FC B1-9 FC B1-10 FC B1-11 FC B1-12 FC B1-13 FC B1-14 FC A1-20 FC A1-21 FC B1-15 FC B1-16 FC B1-17 FC D1-8 FC B1-19 FC B1-20 FC D1-1 FC D1-3 FC D1-5 FC D1-6 FC D1-7 FC B1-6 NURSE 101 TOILET 111A TOILET 108A WORK ROOM 108C STOR. 111B KINDERGARTEN 108 KINDERGARTEN 111 STOR. 108B TOILET 101A TECH LAB 123A DESIGN CENTER 124 FC B1-3 SF 1-2 SF 1-1 SF 1-3 FC A1-2 FC D1-4 FC A1-6 BS A1 BS A2 BS A-3 BS B-1 BS A-4 BS D-2 BS D-1 EF 1-6 EF 1-1 EF 1-2 EF 1-5 EF 1-4 EF 1-8 (180 LBS.) (180 LBS.) FSD 1 FSD 1 1 SQ. FT. TRANSFER AIR OPN'G (TYP) FSD 1 NORMALWEIGHT CONCRETE PAD BY G.C. BS B-2 BS B-3 L 1 L 1 L 1 L 1 (TYP. 3) L 1 L 1 L 1 L 1 L 1 L 1 L 1 L 1 L 1 L 1 L 1 L 1 L 1 L 1 L 1 (TYP. 3) L 1 L 1 L 1 L 1 L 1 L 1 L 1 FC A1-18A ADMISSIONS DIR. 100A TOILET 100B STAFF TOILET 153ELECT. 146 CUSTODIAN 151 UNISEX TOILET 152 ELEV. E-2-1 CORRIDOR 154 FIRE RISER 112A PP MM 12 126 6 LL RR TT W W 24 24 26 26 23 2315 15 14 14 7 7 9 9 BBBB AA JJ DATA 147 L 1 FC D1-9 L 1 L 1 L 1 FC B1-18 NORMALWEIGHT CONCRETE PAD BY G.C. CU 1 CU A CU B CU D CU C CU 2 FSD 1 FSD 1 INSTALL DUCT EXTENSIONS ATOP CU-A & CU-B SUCH THAT AIR WILL DISCHARGE AT THE SAME ELEVATION AS THE TOP OF THE ADJACENT CONCRETE WALL (SEE DET. 3/AC5.03) INSTALL DUCT EXTENSIONS ATOP CU-C & CU-D SUCH THAT AIR WILL DISCHARGE AT THE SAME ELEVATION AS THE TOP OF THE ADJACENT CONCRETE WALL (SEE DET. 3/AC5.03) EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 N Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By A B 2/ 5 / 2 0 2 1 3 : 1 0 : 3 8 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC1.01 MECHANICAL LEVEL 01 FLOOR PLAN OVERALL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t 1/16" = 1'-0" AC1.01A AC1.01B A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 0 09/11/20 ISSUED FOR CONSTRUCTION CD 1 01/22/21 CITY PERMIT AMENDMENT CD J J J J J J UTILITY NOTES POWER WIRING TO EQUIPMENT BY ELECTRICIAN CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN, INSTALLED BY ACCO AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED, INSTALLED, AND WIRED BY ELECTRICIAN DSD ASD 1 1 3 3 10 10 16 16 20 20 SS NN K HH EE BB 2 2 4 4 5 5 18 18 DD FF GG QQ C 8 8 13 13 19 19 17 17 11 11 1ST GRADE CLASSROOM 112 SMALL GROUP 113 2ND GRADE CLASSROOM 115 1ST GRADE CLASSROOM 114 SMALL GROUP 115A ELEV. E-1-1 ELECT. 110 DATA 109 CONFERENCE ROOM 107 ASSOCIATES 134 PSYCH. 137A SMALL GROUP AREA 137 2ND GRADE CLASSROOM 116 3RD GRADE CLASSROOM 117 LANGUAGE ARTS SPECIALIST 137B CUSTODIAL 136 STAIR 1 STR1-1 ELECTRICAL 163 STAFF TOILET 145 UNISEX TOILET 142 LOBBY 100 GIRLS' RESTROOM 143 BOYS' RESTROOM 144 WORKROOM 106 FACILITIES DIR. 105 LOWER DIR. 102 TECHNOLOGY DIRECTOR 103 HEAD OF SCHOOL 104 LIBRARY 131 TINKER AREA 133 STORY TELLING 132 MATH SPECIALIST 137C OPEN OFFICE 159 HALLWAY 160 FC A1-1 FC A1-3 FC A1-4 FC A1-5 FC A1-7 FC A1-8 FC A1-9FC A1-10 FC B1-1FC B1-4 FC B1-5 FC B1-6 FC A1-13 FC A1-14 FC A1-15 FC A1-17 FC A1-16 FC B1-10 FC B1-9 FC A1-19 FC A1-12 FC A1-11 FC B1-2 SF 1-2 SF 1-1 FC A1-2 FC B1-3 FSD 1 BS A1 FC A1-6 1 SQ. FT. TRANSFER AIR OPENING BY G.C. (TYP. UNLESS OTHERWISE STATED) EF 1-2 BS A2 BS B-1 FC B1-7 FC B1-8 FSD 1 FC A1-18B BS A-3 3RD GRADE CLASSROOM 117 NURSE 101TOILET 111A TOILET 108A WORK ROOM 108C STOR. 111B KINDERGARTEN 108 KINDERGARTEN 111 STOR. 108B ADMISSIONS DIR. 100A TOILET 101A TOILET 100B EF 1-1 12"ø OSA 8"ø 8"ø OSA 6"ø OSA 20 CFM 16"ø OSA 6"ø OSA 30 CFM 14"ø OSAFSD 1 6"ø OSA 60 CFM 8"ø OSA 110 CFM DURATECH FLUE UP TO SECOND FLOOR. SEE AC1.02A FOR CONTINUATION AND TERMINATION. 8"ø EA 8"ø EA 1" U.C. DOOR BY G.C. 1" U.C. DOOR BY G.C. 1" U.C. DOOR BY G.C. 10"Ø CS1 315 CFM (TYP. 4) 8"Ø CE1 100 CFM 10"Ø CS1 420 CFM (TYP. 3) FILTER BOX 12"ø SA 10"ø SA 10"ø SA 16"ø SA 8"Ø CE1 100 CFM8"Ø CE1 100 CFM 8"Ø CE1 100 CFM 1" U.C. DOOR BY G.C. 1" U.C. DOOR BY G.C. 12"ø OSA FILTER BOX 8"Ø CE1 100 CFM8"Ø CE1 100 CFM10"Ø CE1 300 CFM 10"Ø CE1 300 CFM 10"Ø CS1 315 CFM (TYP. 4) 10"Ø CS1 315 CFM (TYP. 4) 12"ø SA 12"⌀RA (TYP. 2) FILTER BOX 14"⌀RA FILTER BOX 10"ø SA 10"Ø CS1 315 CFM (TYP. 4) 14"⌀RA FILTER BOX 10"ø SA 10"Ø CS1 200 CFM (TYP. 4) 12"⌀RA FILTER BOX 12"ø OSA 560 CFM 12"ø SA 14"⌀RA FILTER BOX 12"Ø CS1 365 CFM (TYP. 4) 14"⌀RA FILTER BOX FC A1-18A CR1 CR1 CR1 CR1 CR1 CR1 CT2 CT2 16"Ø CT1 CT1 16"ø CR1 (TYP. 2) 16"Ø CT1 16"Ø CT1 16"Ø CT1 16"Ø CT1 16"Ø CT1 16"Ø CT1 12"Ø CT1 CR1 10"Ø CS1 315 CFM (TYP. 4) 6"ø OSA 35 CFM 14"ø OSA SWG1 12"X6" 215 CFM EA PP MM 12 126 6 L L RR 15 15 14 14 7 7 9 9 AA JJ 10X10 SOUND BOOT (1" L) (TYP. 2, SEE DET. 8/AC5.03) FSD 1 6"Ø CS1 60 CFM 6"ø OSA 6"ø OSA 6"ø 6"ø 8"ø OSA 6"ø 12"ø OSA 6"ø 10"ø OSA 270 CFM 8"ø EA 8"ø EA 48"x14" 12"Ø RA (TYP. 2) 10"ø 10"ø 10"ø SA 14"Ø RA 12"ø OSA 6"Ø CS1 60 CFM 6"ø OSA 14"Ø RA 48"x14" 12"Ø SA TAP (TYP. 2) 10"ø SA 10"ø SA EXHAUST FAN TO HAVE GYPSUM ENCLOSURE BY G.C. 10"ø SA10"ø SA 16"Ø SA 10"ø OSA 16"Ø CT1 8"ø EA 8"ø EA12"ø EA 8"ø EA 14"ø EA 8"Ø CS1 110 CFM 12"ø EA 48"x14" 10"ø SA 10"ø SA 12"Ø SA TAP (TYP. 2) 10"ø OSA 10"ø OSA 12"Ø SA TAP (TYP. 2) 10"ø SA 48"x14" 6"Ø CS1 75 CFM 6"ø OSA 10"ø SA 12"Ø SA TAP (TYP. 2) 48"x14" 10"ø OSA 12"ø OSA 12"ø OSA 8"Ø CS1 125 CFM 8"ø OSA 20"x8" SA 14"ø SA 12"ø SA 48"x14" 12"x8" SA 20"x8" SA 12"ø 12"ø OSA 6"Ø CS1 90 CFM 8"Ø CS1 120 CFM 16"ø OSA 8"ø OSA 16"x16" SWG2 36"X19" BLDG. RELIEF LOUVER W/ BAROMETRIC B.D.D. (TYP. 2, VIF DIMENSIONS). 29-1/8"X19" BLDG. RELIEF LOUVER W/ BAROMETRIC B.D.D. (VIF DIMENSIONS). FILTER BOX FILTER BOX 20 CFM OSA 35 CFM OSA 700 CFM OSA 6"Ø CS1 95 CFM 30 CFM OSA 25 CFM OSA FILTER BOX 6"Ø CS1 90 CFM 415 CFM OSA410 CFM OSA 370 CFM OSA 370 CFM OSA 370 CFM OSA 310 CFM OSA 25 CFM OSA .6"ø 1145 CFM OSA 6"ø30 CFM OSA 46" x 18" LOUVER 36" x 18" LOUVER 46" x 18" LOUVER 36" x 18" LOUVER 46" x 18" LOUVER 46" x 18" LOUVER 46" x 18" LOUVER 36" x 18" LOUVER 36" x 18" LOUVER 36" x 18" LOUVER 36" x 18" LOUVER 36" x 18" LOUVER 1 SQ. FT. TRANSFER AIR OPN'G IN SOFFIT ABOVE CEILING BY G.C. 1 SQ. FT. TRANSFER AIR OPN'G IN SOFFIT ABOVE CEILING BY G.C. 10"Ø CR1 10"Ø CR1 10"Ø CR1 10"Ø CR1 10"Ø CR1 10"Ø CR1 10"Ø CR1 10"Ø CR110"Ø CR1 10"Ø CR1 10"Ø CR1 10"Ø CR1 10"Ø CR1 10"Ø CR1 ACOUSTICAL WRAP BY OTHERS. 2 ACOUSTICAL WRAP BY OTHERS. 2 ACOUSTICAL WRAP BY OTHERS. 2 ACOUSTICAL WRAP BY OTHERS. 2 2 2 2 2 10X10 SOUND BOOT (1" L) (TYP. 6, SEE DET. 9/AC5.03) 2 2 2 2 EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 N Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By A B 2/ 5 / 2 0 2 1 3 : 1 0 : 4 0 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC1.01A MECHANICAL LEVEL 01 FLOOR PLAN NORTH 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t 1/8" = 1'-0" AC1.01A AC1.01B A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 0 09/11/20 ISSUED FOR CONSTRUCTION CD 013 11/23/20 CCD-013 CD 017 11/30/20 CCD-017 DN 1 01/22/21 CITY PERMIT AMENDMENT CD 2 xx/xx ACOUSTICAL CHANGES DN PC J J UTILITY NOTES POWER WIRING TO EQUIPMENT BY ELECTRICIAN CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN, INSTALLED BY ACCO AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED, INSTALLED, AND WIRED BY ELECTRICIAN DSD ASD CCCC 1 1 3 3 10 10 16 16 20 20 22 22 25 25 ZZ YY VV SS 27 27 2 2 4 4 5 5 18 18 AAAA XX DDDD UU 8 8 13 13 19 19 21 21 17 17 11 11 OFFICE 124A 4TH GRADE CLASSROOM 120 3RD GRADE CLASSROOM 118 SMALL GROUP 119A 4TH GRADE CLASSROOM 119 LOWER SCHOOL SCIENCE CLASSROOM 122 WORLD LANGUAGE CLASSROOM 121 CERAMICS 125A KILN 125B UPPER SCHOOL ART LAB 125 TEACHING AREA 131B WORKROOM 131A SMALL GROUP 117A 3RD GRADE CLASSROOM 117 STAIR 2 STR2-1 GIRLS' RESTROOM 140 BOYS' RESTROOM 139 HALLWAY 161 LIBRARY 131 TINKER AREA 133 MAKER SPACE 123 LOWER SCHOOL ART LAB 126 HALLWAY 162 FC B1-11 FC B1-12 FC B1-13 FC B1-15 FC B1-17 FC A1-18B FC A1-20 FC A1-21 FC D1-8 FC D1-1 FC B1-20 FC B1-19 FC D1-3 FC D1-5 FC D1-6 FC D1-7 SF 1-3 BS D-2 EF 1-6 FC D1-4BS D-1 EF 1-8 BS A-4 FC B1-14 FC B1-16 EF 1-4 EF 1-5 8"ø OSA 8"ø OSA 8"ø OSA 14"ø EA EXHAUST FAN TO HAVE GYPSUM ENCLOSURE BY G.C. 8"ø OSA 14"ø EA 20"ø EXHAUST FAN TO HAVE GYPSUM ENCLOSURE BY G.C. TECH LAB 123A DESIGN CENTER 124 1" U.C. DOOR BY G.C. BS B-3 BS B-2 10"ø SA 10"Ø CS1 365 CFM (TYP. 4)14"⌀RA FILTER BOX 12"ø SA 10"ø SA 10"Ø CS1 365 CFM (TYP. 4) FILTER BOX 10"ø OSA 12"⌀ RA 10 " ø S A 10 " ø S A 10"Ø CS1 200 CFM (TYP. 4) 22"x22" CE1 1220 CFM 16"Ø 12"⌀OSA FILTER BOX 12"⌀OSA FILTER BOX 12"⌀OSA FILTER BOX 12"X8" SWG1 355 CFM (TYP. 2) 14"Ø CE2 960 CFM (TYP. 2) 12"Ø CS1 365 CFM (TYP. 4) 10"Ø CS1 200 CFM (TYP. 4) 10"ø SA 10"Ø CS1 315 CFM (TYP. 4) FILTER BOX 12"⌀RA FILTER BOX 12"⌀RA FILTER BOX 12"⌀RA (TYP. 2) 10"ø SA 12"ø SA 10"ø SA 10"Ø CS1 200 CFM (TYP. 4) 12"ø SA 10"ø SA 10"ø SA 10"Ø CS1 290 CFM (TYP. 6) 14"⌀RA FILTER BOX 14"ø OSA 10"Ø CS1 320 CFM (TYP. 6) 10"ø SA 14"⌀RA FILTER BOX 12"⌀RA (TYP. 2) FILTER BOX 10"ø OSA CR1 (TYP. 2)CR1 CR1 CS1 CR1 CR1 CR1 CR1 CR1 CR1 CT2CT1 CT1 CT2 16"ø 12"x12" SWG2 12"x12" SWG2 12"x12" SWG2 12"x12" SWG2 AC1.01AAC1.01B AC1.01A 10"Ø CE1 300 CFM 10"Ø CE1 300 CFM 16"Ø CT2 16"Ø CT1 16"Ø CT1 16"Ø CT1 16"Ø CT1 16"Ø CT1 6"⌀OSA 30 CFM STAFF TOILET 153 ELECT. 146 CUSTODIAN 151 ELEV. E-2-1 CORRIDOR 154 FSD 1 FSD 1 8"ø EA 8"Ø CE1 100 CFM 8"Ø CE1 100 CFM SWG1 10"X4" 140 CFM 8"Ø CS1 195 CFM (TYP. 4) 12"x10" SWG1 280 CFM (TYP. 8) 12 126 6 TT WW 24 24 26 26 23 2315 15 14 14 7 7 9 9 BBBB DATA 147 FC D1-9 12"ø EA SKUTT "ENVIROVENT 2" DOWNDRAFT KILN VENT W/ WALL MOUNTED BLOWER (TYP. 3, SEE DET. 1/AC5.01) SKUTT ELECTRIC KILN (TYP. 3) PROVIDED AND INSTALLED BY OTHERS FILTER BOX 10"x6" SWG3 30 CFM 10"x6" SWG2 48"x13" FILTER BOX 14"⌀RA 12"ø OSA 12"x12" OSA 10"ø OSA12"ø SA 12"ø SA 12"x8" SA12"x8" SA 12"ø SA12"ø SA 20"x8" SA 20"x8" SA 10"ø SA 10"ø SA 48"x14" 48"x16" 14"Ø SA EF 1-3 48"x14" 48"x16" 10"ø SA 10"ø OSA 12"ø OSA 10"ø OSA 10"ø OSA EXHAUST FAN TO HAVE GYPSUM ENCLOSURE BY G.C. 36"X19" BLDG. RELIEF LOUVER W/ BAROMETRIC B.D.D. (TYP. 2, VIF DIMENSIONS). 12"Ø SA TAP 12"Ø SA TAP 12"Ø SA TAP 10"ø SA 14"Ø SA TAP 14"Ø SA TAP 12"Ø SA TAP (TYP. 2) 48"x14" 16"Ø CT1 FC B1-18 12"⌀RA (TYP. 2) 10"ø SA 48"x14" 12"Ø SA TAP 12"⌀RA 16"ø 12"ø SA B.D.D. (TYP. 3) 12"⌀OSA 10"Ø SA TAP (TYP. 2) 8"ø SA 6"ø OSA 8"ø SA 48"x14" 48"x14" 12"ø SA 10"ø SA 10"ø SA 12"Ø SA TAP 10"ø SA48"x14" 12"ø SA 10"ø SA 12"Ø SA TAP 8"ø EA UNISEX TOILET 152 16"ø 14"ø EA 8"ø 12"ø EA 10"ø EA 8"ø EA8"ø EA 8"Ø CS1 150 CFM 35-1/4"X19" BLDG. RELIEF LOUVER W/ BAROMETRIC B.D.D. (VIF DIMENSIONS). FILTER BOX 10"ø OSA 310 CFM OSA 310 CFM OSA 370 CFM OSA 8"Ø CS1 105 CFM 395 CFM OSA 310 CFM OSA 450 CFM OSA 400 CFM OSA 765 CFM OSA 655 CFM OSA 310 CFM OSA 705 CFM OSA 135 CFM OSA665 CFM OSA 8"Ø CS1 145 CFM 560 CFM OSA 405 CFM OSA 12"X12" OPENING IN SOFFIT FOR FLEX DUCT TRANSFER AIR CR1 46" x 18" LOUVER 46" x 18" LOUVER 46" x 18" LOUVER 46" x 18" LOUVER 46" x 18" LOUVER 46" x 18" LOUVER 46" x 18" LOUVER 46" x 18" LOUVER 46" x 18" LOUVER 46" x 18" LOUVER 46" x 18" LOUVER 46" x 18" LOUVER 46" x 18" LOUVER 46" x 18" LOUVER 46" x 18" LOUVER46" x 18" LOUVER 46" x 18" LOUVER 36" x 18" LOUVER 46" x 18" LOUVER 46" x 18" LOUVER 36" x 18" LOUVER 12"⌀RA 22"x12" EA 10"Ø CR1 10"Ø CR1 10"Ø CR1 10"Ø CR1 10"Ø CR1 12"x12" SWG2 16"Ø CT2 12"x12" SWG2 6"ø OSA 8"ø OSA 105 CFM 14"ø EA L 1 12"⌀RA (TYP. 2) L 1 18"x10" SWG1 440 CFM (TYP. 4) 14"ø SA 20"x14" FILTER BOX 14"ø OSA 12"X10" SWG1 380 CFM (TYP. 2) 12"x12" SWG2 12"X12" SOUND BOOT (1"L) SEE DET. 8/AC5.03 20"ø SA 16"ø 2 16"ø 12"ø ACOUSTICAL WRAP BY OTHERS. 2 ACOUSTICAL WRAP BY OTHERS. 2 ACOUSTICAL WRAP BY OTHERS. 2 SHEET NOTES 1. INSTALLATION OF ELECTRIC KILNS (BY OTHERS) SHALL COMPLY WITH CLEARANCES AS NOTED BY CMC 932.5.1: KILNS SHALL BE LOCATED NOT LESS THAN 18 INCHES FROM A NON-COMBUSTIBLE WALL SURFACE, AND 3 FEET FROM A COMBUSTIBLE WALL SURFACE. IN NO CASE SHALL THE CLEARANCE ON THE CONTROL SIDE OF THE KILN BE REDUCED TO LESS THAN 30 INCHES. EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 N Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By A B 2/ 5 / 2 0 2 1 3 : 1 0 : 4 6 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC1.01B MECHANICAL LEVEL 01 FLOOR PLAN SOUTH 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t 1/8" = 1'-0" A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 0 09/11/20 ISSUED FOR CONSTRUCTION CD 013 11/23/20 CCD-013 CD 018 12/07/20 CCD-018 DN 016 12/09/20 CCD-016 DN 1 01/22/21 CITY PERMIT AMENDMENT CD 2 xx/xx ACOUSTICAL CHANGES DN RE F . R E F . DW RE F . DW REF. PC PC PC PC J UTILITY NOTES POWER WIRING TO EQUIPMENT BY ELECTRICIAN CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN, INSTALLED BY ACCO AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED, INSTALLED, AND WIRED BY ELECTRICIAN DSD ASD CCCC 1 1 3 3 10 10 16 16 20 20 22 22 25 25 ZZ YY V V SS NN KK HH EE BB 27 27 2 2 4 4 5 5 18 18 DD FF GG AAAA XX DDDD UU QQ C 8 8 13 13 19 19 21 21 17 17 11 11 UPPER SCHOOL SCIENCE LAB 230 PREP ROOM 229A UPPER SCHOOL SCIENCE LAB 229 WORKROOM 228 6TH -8TH CLASSROOM 226 6TH -8TH CLASSROOM 224 READING ROOM 231 STAIR 2 STR-2-2 6TH -8TH CLASSROOM 220 6TH -8TH CLASSROOM 216 6TH -8TH CLASSROOM 214 STAFF WORKROOM 208 SYSTEMS ADMIN. 209 UNASSIGNED 210 6TH -8TH CLASSROOM 219 6TH -8TH CLASSROOM 217 COLAB 218 COLAB 249 STORAGE 248 ELEV. E-1-2 CUSTODIAL 242 STAFF TOILET 244 UNISEX TOILET 247 DATA 240 ELECT 241 STAIR 1 STR-1-2 COLAB 211A 5TH GRADE CLASSROOM 211 STAFF LOUNGE 207 UNASSIGNED 204 UPPER DIRECTOR 203DEVELOPMENT DIRECTOR 202 COMMUNICATIONS DIR. 201 5TH GRADE CLASSROOM 212 BOYS' RESTROOM 245 GIRLS' RESTROOM 246 HALLWAY 250 ROOF DECK 253 GIRLS' RESTROOM 238 BOYS' RESTROOM 237 6TH -8TH CLASSROOM 221 6TH -8TH CLASSROOM 223 6TH -8TH CLASSROOM 222 6TH -8TH CLASSROOM 215 6TH -8TH CLASSROOM 225 6TH -8TH CLASSROOM 227 6TH -8TH CLASSROOM 213 COLAB 254 ROOF DECK 254 OPEN OFFICE 252 HALLWAY 251 HALLWAY 255 FC A2-5 FC A2-7 FC A2-9 FC A2-12 FC A2-11 FC A2-10 FC A2-4 FC A2-3 FC A2-13 FC A2-14 FC C2-2 FC C2-5 FC C2-4 FC C2-6 FC C2-8 FC C2-9 FC C2-10 FC C2-11 FC C2-13 FC C2-14 FC C2-15 FC C2-16 FC C2-17 FC C2-18 FC C2-19 FC D2-1 FC D2-2 FC D2-3 FC D2-5 FC D2-6 FC C2-20 FC C2-21 FC C2-12 FC C2-7 FC D2-4 BUSINESS OFFICE 205 HUMAN RESOURCES DIR. 206 MOTHER'S ROOM 207A FC A2-1 FC A2-8 SF 2-3 SF 2-1 SF 2-2 FC A2-6 BS D-4 SF 2-4EF 2-3 EF 2-4 EF 2-2 FC C2-3 FC A2-15 BS C-4 BS D-3 BS C-3 BS C-2 BS C-1 BS A-6 BS A-5 EF 2-1 FSD 1 FSD 1 ELECT 233 CUSTODIAL 235 ELEV. E-2-2 UNISEX TOILET 239 STAFF TOILET 236 PP MM 12 126 6 LL RR TT W W 24 24 26 26 23 2315 15 14 14 7 7 9 9 BBBB AA JJ FC A2-2 ELEV. MACHINE ROOM 243 L 1 L 1 L 1 FSD 1 L 1 (TYP. 3) (TYP. 3) L 1 FSD 1 FSD 1 DATA 233B ELEV. MACH. ROOM 234 SS 1-2 FSD 1 EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 N Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By A B 2/ 5 / 2 0 2 1 3 : 1 1 : 0 2 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC1.02 MECHANICAL LEVEL 02 FLOOR PLAN OVERALL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t 1/16" = 1'-0" AC1.02A AC1.02B A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 0 09/11/20 ISSUED FOR CONSTRUCTION CD 1 01/22/21 CITY PERMIT AMENDMENT CD RE F . R E F . DW REF. PC PC UTILITY NOTES POWER WIRING TO EQUIPMENT BY ELECTRICIAN CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN, INSTALLED BY ACCO AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED, INSTALLED, AND WIRED BY ELECTRICIAN DSD ASD 1 1 3 3 10 10 16 16 20 20 SS NN K HH EE BB 2 2 4 4 5 5 18 18 DD FF GG QQ C 8 8 13 13 19 19 17 17 11 11 6TH -8TH CLASSROOM 216 6TH -8TH CLASSROOM 214 STAFF WORKROOM 208 SYSTEMS ADMIN. 209 UNASSIGNED 210 6TH -8TH CLASSROOM 217 COLAB 218 COLAB 249 STORAGE 248 ELEV. E-1-2 CUSTODIAL 242 STAFF TOILET 244 UNISEX TOILET 247 DATA 240 ELECT 241 STAIR 1 STR-1-2 COLAB 211A 5TH GRADE CLASSROOM 211 STAFF LOUNGE 207 UNASSIGNED 204 UPPER DIRECTOR 203 DEVELOPMENT DIRECTOR 202 COMMUNICATIONS DIR. 201 5TH GRADE CLASSROOM 212 BOYS' RESTROOM 245 GIRLS' RESTROOM 246 ROOF DECK 253 6TH -8TH CLASSROOM 215 6TH -8TH CLASSROOM 213 OPEN OFFICE 252 HALLWAY 251 FC A2-15 FC C2-2 FC A2-3 FC A2-4 FC A2-5 FC A2-7 FC A2-9 FC A2-12 FC A2-11 FC A2-10 FC A2-14 FC A2-13 FC C2-7 FC C2-5 FC C2-4 FC C2-6 FC C2-8 FC C2-10 FC C2-3 SF 2-1 SF 2-2 SF 2-3 FC A2-6 FC A2-1 BS C-1 EF 2-1 FSD 1 FC A2-8 BS A-5 BS A-6 BS C-2 FC C2-9 36"X19" BLDG. RELIEF LOUVER W/ BAROMETRIC B.D.D. (TYP. 2, VIF DIMENSIONS). 1 SQ. FT. TRANSFER AIR WALL OPENING BY G.C. (TYP. UNLESS OTHERWISE NOTED) 12"ø OSA 8"ø OSA 10"ø OSA 6"ø OSA 14"ø OSA 8"ø OSA 8"ø EA 12"ø EA 12"ø EA EXHAUST FAN TO HAVE GYPSUM ENCLOSURE BY G.C.1" U.C. DOOR BY G.C. 12"ø OSA 415 CFM 12"Ø CS1 435 CFM (TYP. 4) 8"Ø CE1 100 CFM8"Ø CE1 100 CFM10"Ø CE1 300 CFM 10"Ø CE1 300 CFM 10"Ø CS1 200 CFM (TYP. 4) FILTER BOX 12"⌀RA FILTER BOX 10"ø SA8"Ø CS1 200 CFM (TYP. 4) 10"⌀RA (TYP. 2) FILTER BOX 8"Ø CS1 200 CFM (TYP. 4) FILTER BOX 10"⌀RA (TYP. 2) FILTER BOX 10"⌀RA (TYP. 2) FILTER BOX 10"⌀RA (TYP. 2) FILTER BOX 8"Ø CS1 200 CFM (TYP. 4) 10"ø SA 8"Ø CS1 200 CFM (TYP. 4) 8"Ø CS1 200 CFM (TYP. 4) CR1CR1 CR1 CR1 CR1 CR1 CR1 CR1 16"Ø CT2 16"Ø CT2 16"Ø CT1 16"Ø CT1 16"Ø CT1 16"Ø CT1 16"Ø CT1 16"Ø CT1 CR1 CR1 (TYP. 2) 16"Ø CT1 16"Ø CT1 6"⌀OSA 15 CFM BUSINESS OFFICE 205 HUMAN RESOURCES DIR. 206 MOTHER'S ROOM 207A DURATECH FLUE UP THROUGH ROOF WITH CHIMNEY CAP. TO BE MIN. 1'-0" ABOVE ROOF PENETRATION AND MIN. 1'-8" FROM PARAPET. MAINTAIN 2'-0" SPACING BETWEEN FLUE DISCHARGES. SEE DETAIL 10 ON AC5.02 FOR SECTION VIEW. 12"Ø RA (TYP. 2) 8"ø SA (TYP. 4) 6"ø OSA 10"ø OSA SWG1 12"X6" 150 CFM PP MM 12 126 6 L L RR 15 15 14 14 7 7 9 9 AA JJ 10"⌀OSA 310 CFM 10"⌀OSA 310 CFM 10"⌀OSA 310 CFM 10"⌀OSA 310 CFM 10"⌀OSA 310 CFM 10"Ø OSA UP TO ROOF 255 CFM OSA 10"Ø UP TO ROOF 195 CFM OSA ELEV. MACHINE ROOM 243 10X10 SOUND BOOT (1" L) (TYP. 6, SEE DET. 9/AC5.03) FSD 1 6"⌀OSA 20 CFM 6"⌀OSA 35 CFM 6"⌀OSA 25 CFM 6"⌀OSA 25 CFM 14"ø OSA FC A2-2 6"ø OSA CR1 6"⌀OSA 20 CFM 14"Ø RA 14"Ø RA CR1 14"ø SA 14"Ø SA TAP 12"ø OSA 44"x16" 6"⌀OSA 20 CFM 10"ø OSA 10"ø OSA 8"Ø CS1 135 CFM 6"ø OSA 6"Ø CS1 70 CFM 10"ø SA 48"x14"12"Ø SA 10"Ø SA 48"x14" 6"⌀OSA 20 CFM 12"⌀RA 10"Ø SA10"Ø SA 10"ø OSA 12"ø SA 48"x12" 10"ø SA 10"Ø SA TAP 8"Ø SA (TYP. 4) 10"Ø SA TAP (TYP. 2) 48"x14" 10"ø OSA 16"Ø EA 48"x14" 10"Ø SA TAP (TYP. 2) 10"ø SA 8"Ø SA (TYP. 4) 8"Ø SA (TYP. 4) 8"Ø SA (TYP. 4) 6"Ø CS1 135 CFM 6"ø OSA 8"Ø CS1 105 CFM 8"ø EA SS 1-1 10"Ø SA TAP (TYP. 2) SWG2 16"X16" 29-1/8"X19" BLDG. RELIEF LOUVER W/ BAROMETRIC B.D.D. (VIF DIMENSIONS). 10"Ø CS1 200 CFM (TYP. 4) FILTER BOX FILTER BOX FILTER BOX FILTER BOX 8"Ø CS1 125 CFM 925 CFM OSA 6"⌀OSA 20 CFM 310 CFM OSA 310 CFM OSA 8"Ø CS1 90 CFM 8"ø OSA 36" x 18" LOUVER 46" x 18" LOUVER 46" x 18" LOUVER 10"Ø CR1 10"Ø CR1 10"Ø CR1 10"Ø CR1 10"Ø CR1 10"Ø CR1 10"Ø CR110"Ø CR110"Ø CR1 10"Ø CR1 10"Ø CR1 10"Ø CR1 10"Ø CR1 16"Ø CT1 16"Ø CT1 ACOUSTICAL WRAP BY OTHERS. 2 ACOUSTICAL WRAP BY OTHERS. 2 2 2 2 2 2 2 FSD 1 FSD 1 FSD 1 2 2 10X10 SOUND BOOT (1" L) (TYP. 5, SEE DET. 8/AC5.03) 2 2 16"Ø CT1 2 2 EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 N Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By A B 2/ 5 / 2 0 2 1 3 : 1 1 : 0 7 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC1.02A MECHANICAL LEVEL 02 FLOOR PLAN NORTH 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t 1/8" = 1'-0" AC1.02A AC1.02B A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 0 09/11/20 ISSUED FOR CONSTRUCTION CD 1 01/22/21 CITY PERMIT AMENDMENT CD 2 xx/xx ACOUSTICAL CHANGES DN RE F . DW PC PC J UTILITY NOTES POWER WIRING TO EQUIPMENT BY ELECTRICIAN CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN, INSTALLED BY ACCO AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED, INSTALLED, AND WIRED BY ELECTRICIAN DSD ASD CCCC 1 1 3 3 10 10 16 16 20 20 22 22 25 25 ZZ YY VV SS 27 27 2 2 4 4 5 5 18 18 AAAA XX DDDD UU 8 8 13 13 19 19 21 21 17 17 11 11 UPPER SCHOOL SCIENCE LAB 230 PREP ROOM 229A UPPER SCHOOL SCIENCE LAB 229 WORKROOM 228 6TH -8TH CLASSROOM 226 6TH -8TH CLASSROOM 224 READING ROOM 231 STAIR 2 STR-2-2 6TH -8TH CLASSROOM 220 6TH -8TH CLASSROOM 219 COLAB 218 HALLWAY 250 ROOF DECK 253 GIRLS' RESTROOM 238 BOYS' RESTROOM 237 6TH -8TH CLASSROOM 221 6TH -8TH CLASSROOM 223 6TH -8TH CLASSROOM 222 6TH -8TH CLASSROOM 225 6TH -8TH CLASSROOM 227 COLAB 254 ROOF DECK 254 HALLWAY 255 FC C2-13 FC C2-14 FC C2-15 FC C2-16 FC C2-17 FC C2-18 FC C2-19 FC D2-1 FC D2-2 FC D2-4 FC D2-6 FC C2-21 FC C2-20 FC C2-12 BS C-3 BS C-4 EF 2-2 BS D-4 FC D2-3 FC D2-5 EF 2-4 SF 2-4 EF 2-3 BS D-3 FC C2-11 36"X19" BLDG. RELIEF LOUVER W/ BAROMETRIC B.D.D. (TYP. 2, VIF DIMENSIONS). 1 SQ. FT. TRANSFER AIR WALL OPENING (TYP. UNLESS OTHERWISE NOTED) FSD 1 6"ø OSA EXHAUST FAN TO HAVE GYPSUM ENCLOSURE BY G.C. 10"ø EA EXHAUST FAN TO HAVE GYPSUM ENCLOSURE BY G.C. EXHAUST FAN TO HAVE GYPSUM ENCLOSURE BY G.C. 1" U.C. DOOR BY G.C. 8"Ø CE1 100 CFM 10"Ø CE1 300 CFM 10"Ø CE1 300 CFM 22"x22" CE2 1290 CFM 22"x22" CE2 1290 CFM 8"Ø CS1 200 CFM (TYP. 4) FILTER BOX 10"⌀RA (TYP. 2) FILTER BOX 10"⌀RA (TYP. 2) 10"ø SA 8"Ø CS1 200 CFM (TYP. 4) 8"Ø CS1 200 CFM (TYP. 4) FILTER BOX 10"⌀RA (TYP. 2) 8"Ø CS1 200 CFM (TYP. 4) FILTER BOX 10"⌀RA (TYP. 2) 8"Ø CS1 200 CFM (TYP. 4) FILTER BOX 10"⌀RA (TYP. 2) 8"Ø CS1 200 CFM (TYP. 4) FILTER BOX 10"⌀RA (TYP. 2) 8"Ø CS1 200 CFM (TYP. 4) FILTER BOX 10"⌀RA (TYP. 2) FILTER BOX 10"⌀RA (TYP. 2) 8"Ø CS1 200 CFM (TYP. 4) FILTER BOX 10"⌀RA (TYP. 2) 12"ø SA 12"Ø CS1 365 CFM (TYP. 4) FILTER BOX 12"⌀RA (TYP. 2) 8"Ø CS1 295 CFM (TYP. 6) 8"ø SA 8"ø SA FILTER BOX 12"⌀RA (TYP. 2) 8"ø SA 8"Ø CS1 295 CFM (TYP. 6) FILTER BOX 12"⌀RA (TYP. 2) CR1 CR1 CR1 CR1 CR1 CR1 CR1 CR1 CR1 CR1 CR1 CR1 CT1 CT1 CT1 CT1 16"ø 16"ø 10"Ø CT1 16"Ø CT116"Ø CT1 16"Ø CT1 16"Ø CT1 16"Ø CT1 5 SQ. FT. TRANSFER AIR WALL OPENING BY G.C. AC1.02A AC1.02B ELECT 233 ELEV. E-2-2 STAFF TOILET 236 SWG1 16"X4" 140 CFM10"ø EA FSD 1 FSD 1 8"Ø CE1 100 CFM 12"ø EA 10"ø SA 10"ø SA 10"ø SA 8"ø SA 8"ø SA 8"ø SA 10"ø SA 8"Ø CS1 200 CFM (TYP. 4) 8"ø SA 12"ø SA8"ø SA 12"ø SA 12 126 6 TT WW 24 24 26 26 23 2315 15 14 14 7 7 9 9 BBBB 10"⌀OSA 310 CFM 10"⌀OSA 310 CFM 10"⌀OSA 310 CFM 10"⌀OSA 310 CFM 10"⌀OSA 310 CFM 10"⌀OSA 310 CFM 10"⌀OSA 230 CFM 10"⌀OSA 230 CFM 10"⌀OSA 225 CFM 10"⌀OSA 350 CFM 18"⌀UP 16"⌀OSA 660 CFM 16"⌀OSA 610 CFM 16"⌀UP DATA 233B ELEV. MACH. ROOM 234 UNISEX TOILET 239 CUSTODIAL 235 8"ø SA (TYP. 4) 10"Ø SA TAP (TYP. 2) 48"x14" 8"ø SA (TYP. 4) 48"x14" 48"x14" 8"Ø SA (TYP. 4) 10"Ø SA TAP 10"Ø SA 16"Ø SA 8"ø SA CR1 (TYP. 2) 10"Ø SA 16"Ø SA 48"x12" 8"ø SA (TYP. 4) 10"⌀SA TAP (TYP. 2) 48"x12"48"x12"48"x12" 8"ø SA (TYP. 4) 10"⌀SA TAP (TYP. 2)10"⌀SA TAP (TYP. 2) 8"ø SA (TYP. 4) 6"Ø CS1 120 CFM 10"⌀SA TAP (TYP. 2) 8"ø SA (TYP. 4) 48"x16" 8"ø SA 12"Ø SA TAP 8"ø SA 12"ø SA 10"⌀UP TO ROOF 270 CFM OSA 8"Ø CS1 135 CFM 12"⌀SA TAP 8"ø SA 18"ø SA 14"ø SA 12"ø SA 10"ø 16"⌀UP SS 1-2 35-1/4"X19" BLDG. RELIEF LOUVER W/ BAROMETRIC B.D.D. (VIF DIMENSIONS). FILTER BOX FSD 1 8"Ø CS1 135 CFM 14"x6"10"x6" 10"Ø CR1 10"Ø CR1 10"Ø CR1 ACOUSTICAL WRAP BY OTHERS. 2 ACOUSTICAL WRAP BY OTHERS. 2 EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 N Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By A B 2/ 5 / 2 0 2 1 3 : 1 1 : 1 2 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC1.02B MECHANICAL LEVEL 02 FLOOR PLAN SOUTH 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t 1/8" = 1'-0" A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 0 09/11/20 ISSUED FOR CONSTRUCTION CD 1 01/22/21 CITY PERMIT AMENDMENT CD 2 xx/xx ACOUSTICAL CHANGES DN CCCC 1 1 3 3 10 10 16 16 20 20 22 22 25 25 ZZ YY V V SS NN KK HH EE BB 27 27 2 2 4 4 5 5 18 18 DD FF GG AAAA XX DDDD UU QQ C 8 8 13 13 19 19 21 21 17 17 11 11 PP MM 12 126 6 LL RR TT W W 24 24 26 26 23 2315 15 14 14 7 7 9 9 BBBB AA JJ GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 GV 2 GV 1 GV 2 GV 1 GV 3 GV 1 GV 1 EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 N Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By A B 1/16" = 1'-0" 2/ 5 / 2 0 2 1 3 : 1 1 : 1 4 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC1.03 MECHANICAL ROOF FLOOR PLAN OVERALL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t AC1.03A AC1.03B B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 1 01/22/21 CITY PERMIT AMENDMENT CD 1 1 3 3 10 10 16 16 20 20 SS NN K HH EE BB 2 2 4 4 5 5 18 18 DD FF GG QQ C 8 8 13 13 19 19 17 17 11 11 PP MM 12 126 6 L L RR 15 15 14 14 7 7 9 9 AA JJ GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 MIN. 10'-0" FROM EXHAUST OR VENT (TYP. 2) MIN. 10'-0" FROM EXHAUST OR VENT MIN. 10'-0" FROM EXHAUST OR VENT MIN. 10'-0" FROM EXHAUST OR VENT (TYP. 3) GV 1 300 CFM OSA 195 CFM OSA 950 CFM EA 300 CFM OSA MIN. 10'-0" FROM OSA INTAKE 300 CFM OSA 300 CFM OSA 300 CFM OSA 300 CFM OSA EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 N Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By A B 1/8" = 1'-0" 2/ 5 / 2 0 2 1 3 : 1 1 : 1 7 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC1.03A MECHANICAL ROOF FLOOR PLAN NORTH 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t AC1.03A AC1.03B B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 1 01/22/21 CITY PERMIT AMENDMENT CD CCCC 1 1 3 3 10 10 16 16 20 20 22 22 25 25 ZZ YY VV SS 27 27 2 2 4 4 5 5 18 18 AAAA XX DDDD UU 8 8 13 13 19 19 21 21 17 17 11 11 12 126 6 TT WW 24 24 26 26 23 2315 15 14 14 7 7 9 9 BBBB GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 GV 3 GV 2 GV 1 GV 1 GV 2 MIN. 10'-0" FROM OSA INTAKE MIN. 10'-0" FROM EXHAUST OR VENT MIN. 10'-0" FROM OSA INTAKE MIN. 10'-0" FROM EXHAUST OR VENTMIN. 10'-0" FROM EXHAUST OR VENT MIN. 10'-0" FROM EXHAUST OR VENT MIN. 10'-0" FROM EXHAUST OR VENT MIN. 10'-0" FROM EXHAUST OR VENT MIN. 10'-0" FROM EXHAUST OR VENT 300 CFM OSA 300 CFM OSA 300 CFM OSA 300 CFM OSA 300 CFM OSA GV 1 1035 CFM EA MIN. 10'-0" FROM OSA INTAKE 300 CFM OSA 230 CFM OSA 230 CFM OSA 225 CFM OSA 330 CFM OSA 1,290 CFM EA GV 3 270 CFM OSA660 CFM OSA 610 CFM OSA 1,290 CFM EA EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 N Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By A B 1/8" = 1'-0" 2/ 5 / 2 0 2 1 3 : 1 1 : 1 9 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC1.03B MECHANICAL ROOF FLOOR PLAN SOUTH 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t AC1.03A AC1.03B B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 1 01/22/21 CITY PERMIT AMENDMENT CD J J J J J J J J CCCC 1 1 3 3 10 10 16 16 20 20 22 22 25 25 ZZ YY V V SS NN KK HH EE BB 27 27 2 2 4 4 5 5 18 18 DD FF GG AAAA XX DDDD UU QQ C 8 8 13 13 19 19 21 21 17 17 11 11 OFFICE 124A 4TH GRADE CLASSROOM 120 3RD GRADE CLASSROOM 118 SMALL GROUP 119A 4TH GRADE CLASSROOM 119 LOWER SCHOOL SCIENCE CLASSROOM 122 WORLD LANGUAGE CLASSROOM 121 CERAMICS 125A KILN 125B UPPER SCHOOL ART LAB 125 1ST GRADE CLASSROOM 112 SMALL GROUP 113 2ND GRADE CLASSROOM 115 1ST GRADE CLASSROOM 114 SMALL GROUP 115A TEACHING AREA 131B WORKROOM 131A ELEV. E-1-1 ELECT. 110 DATA 109 CONFERENCE ROOM 107 ASSOCIATES 134 PSYCH. 137A SMALL GROUP AREA 137 2ND GRADE CLASSROOM 116 SMALL GROUP 117A 3RD GRADE CLASSROOM 117 LANGUAGE ARTS SPECIALIST 137B CUSTODIAL 136 STAIR 1 STR1-1 NURSE 101 ELECTRICAL 163 STAFF TOILET 145 UNISEX TOILET 142 STAIR 2 STR2-1 LOBBY 100 GIRLS' RESTROOM 140 BOYS' RESTROOM 139 GIRLS' RESTROOM 143 BOYS' RESTROOM 144 WORKROOM 106 FACILITIES DIR. 105 HEAD OF SCHOOL 104 HALLWAY 161 LIBRARY 131 TINKER AREA 133 STORY TELLING 132 MATH SPECIALIST 137C MAKER SPACE 123 LOWER SCHOOL ART LAB 126 OPEN OFFICE 159HALLWAY 160 HALLWAY 162 ? ? FC B1-2 FC A1-1 FC A1-5 FC A1-7 FC A1-4 FC B1-1 FC B1-5 FC B1-6 FC B1-7 FC A1-12 FC A1-11 FC A1-10 FC A1-9 FC A1-8 FC A1-14 FC A1-13 FC A1-16 FC A1-17 FC A1-15 FC A1-19 FC A1-18B FC B1-9 FC B1-8 FC B1-10 FC B1-11 FC B1-12 FC B1-13 FC B1-14 FC A1-20 FC A1-21 FC B1-19 FC B1-20 FC D1-1 FC D1-3 FC D1-8 FC D1-7 FC B1-17FC B1-16 FC B1-15 FC D1-5 FC B1-4 FC A1-3 SF 1-1 BS A1 BS A-3 BS A-4 SF 1-2 BS B-1 BS B-2 BS B-3 FC D1-4 BS D-2 BS D-1 FC A1-6 FC A1-2 NORMALWEIGHT CONCRETE PAD BY G.C. SEE DETAIL 5/AC5.02 14"X46" PAD OPENING 6" PVC MIN. 12" U.G. 12" PVC MIN. 12" U.G. (TYP. 2) 14"X46" PAD OPENING 6" PVC MIN. 12" U.G. 12" PVC MIN. 12" U.G. (TYP. 2) EF 1-5 EF 1-6 EF 1-8 EF 1-4 EF 1-2 EF 1-1 NORMALWEIGHT CONCRETE PAD BY G.C. SEE DETAIL 5/AC5.02 FC A1-18A TOILET 111A TOILET 108A WORK ROOM 108C STOR. 111B KINDERGARTEN 108 KINDERGARTEN 111 STOR. 108B ADMISSIONS DIR. 100A TOILET 101A TECH LAB 123A DESIGN CENTER 124 TOILET 100B LOWER DIR. 102 CUSTODIAN 151 UNISEX TOILET 152 STAFF TOILET 153 PP MM 12 126 6 LL RR TT W W 24 24 26 26 23 2315 15 14 14 7 7 9 9 BBBB AA JJ TECHNOLOGY DIRECTOR 103 BS A2 FC B1-3 FC B1-18 ELECT. 146 DATA 147 FC D1-6 FC D1-9 EF 1-3 CU 1 CU A CU B (180 LBS.) (1,325 LBS.) (1,325 LBS.) (1,664 LBS.) CU 2 (180 LBS.) CU D CU C (1,305 LBS.) SF 1-3 UTILITY NOTES POWER WIRING TO EQUIPMENT BY ELECTRICIAN CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN, INSTALLED BY ACCO AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED, INSTALLED, AND WIRED BY ELECTRICIAN DSD ASD SHEET NOTES 1. FOR VRF PIPING FROM CONDENSING UNITS TO HEAT RECOVERY UNITS: L -LIQUID HV -HIGH VAPOR LV -LOW VAPOR 2. FOR VRF PIPING FROM HEAT RECOVERY UNITS TO FAN COILS: L -LIQUID V -VAPOR 3. MIN. 20" OF STRAIGHT PIPE INTO FAN COIL UNITS 4. REFER TO SHEETS AC6.01 & AC6.02 FOR VRF PIPING DIAGRAMS. EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 N Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By A B 2/ 5 / 2 0 2 1 3 : 1 1 : 2 9 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC2.01 MECHANICAL PIPING LEVEL 01 FLOOR PLAN OVERALL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t 1/16" = 1'-0" AC2.01A AC2.01B A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 0 09/11/20 ISSUED FOR CONSTRUCTION CD 1 01/22/21 CITY PERMIT AMENDMENT CD J J J J J J 1 1 3 3 10 10 16 16 20 20 SS NN K HH EE BB 2 2 4 4 5 5 18 18 DD FF GG QQ C 8 8 13 13 19 19 17 17 11 11 1ST GRADE CLASSROOM 112 SMALL GROUP 113 2ND GRADE CLASSROOM 115 1ST GRADE CLASSROOM 114 SMALL GROUP 115A ELEV. E-1-1 ELECT. 110 DATA 109 CONFERENCE ROOM 107 ASSOCIATES 134 PSYCH. 137A SMALL GROUP AREA 137 2ND GRADE CLASSROOM 116 LANGUAGE ARTS SPECIALIST 137B CUSTODIAL 136 STAIR 1 STR1-1 ELECTRICAL 163 STAFF TOILET 145 UNISEX TOILET 142 LOBBY 100 GIRLS' RESTROOM 143 BOYS' RESTROOM 144 WORKROOM 106 FACILITIES DIR. 105 LOWER DIR. 102 TECHNOLOGY DIRECTOR 103 HEAD OF SCHOOL 104 LIBRARY 131 TINKER AREA 133 STORY TELLING 132 MATH SPECIALIST 137C OPEN OFFICE 159 HALLWAY 160 FC A1-1 FC A1-3 FC A1-4 FC A1-5 FC A1-7 FC A1-8 FC A1-9 FC A1-10 FC A1-11 FC A1-12 FC B1-1 FC B1-4 FC B1-2 FC B1-5 FC B1-6 FC B1-7 FC A1-15 FC A1-14 FC A1-13 FC A1-16 FC A1-17 FC B1-8 FC B1-9 FC B1-10 FC A1-19 NURSE 101 TOILET 111A TOILET 108A WORK ROOM 108C STOR. 111B KINDERGARTEN 108 KINDERGARTEN 111 STOR. 108B ADMISSIONS DIR. 100ATOILET 101A TOILET 100B FC A1-2 EF 1-1 SF 1-1 FC A1-6 EF 1-2 BS A2 BS A1 SF 1-2 FC A1-18B BS A-3 BS B-1 FC B1-3 FC A1-18A PP MM 12 126 6 L L RR 15 15 14 14 7 7 9 9 AA JJ VRF PIPING UP TO 2ND FLOOR VRF PIPING UP TO 2ND FLOOR MAINTAIN MINIMUM 45'-0" EQUIVALENT PIPE LENGTH BETWEEN BRANCH SELECTOR BOX A-3 & ANY ASSOCIATED FAN COIL UNIT MAINTAIN MINIMUM 45'-0" EQUIVALENT PIPE LENGTH BETWEEN BRANCH SELECTOR BOX A-3 & ANY ASSOCIATED FAN COIL UNIT MAINTAIN MINIMUM 45'-0" EQUIVALENT PIPE LENGTH BETWEEN BRANCH SELECTOR BOX A-3 & ANY ASSOCIATED FAN COIL UNIT UTILITY NOTES POWER WIRING TO EQUIPMENT BY ELECTRICIAN CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN, INSTALLED BY ACCO AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED, INSTALLED, AND WIRED BY ELECTRICIAN DSD ASD SHEET NOTES 1. FOR VRF PIPING FROM CONDENSING UNITS TO HEAT RECOVERY UNITS: L -LIQUID HV -HIGH VAPOR LV -LOW VAPOR 2. FOR VRF PIPING FROM HEAT RECOVERY UNITS TO FAN COILS: L -LIQUID V -VAPOR 3. MIN. 20" OF STRAIGHT PIPE INTO FAN COIL UNITS 4. REFER TO SHEETS AC6.01 & AC6.02 FOR VRF PIPING DIAGRAMS. EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 N Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By A B 2/ 5 / 2 0 2 1 3 : 1 1 : 3 5 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC2.01A MECHANICAL PIPING LEVEL 01 FLOOR PLAN NORTH 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t 1/8" = 1'-0" AC2.01A AC2.01B A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 0 09/11/20 ISSUED FOR CONSTRUCTION CD 017 11/30/20 CCD-017 DN 1 01/22/21 CITY PERMIT AMENDMENT CD J J CCCC 1 1 3 3 10 10 16 16 20 20 22 22 25 25 ZZ YY VV SS 27 27 2 2 4 4 5 5 18 18 AAAA XX DDDD UU 8 8 13 13 19 19 21 21 17 17 11 11 OFFICE 124A ? ? 4TH GRADE CLASSROOM 120 3RD GRADE CLASSROOM 118 SMALL GROUP 119A 4TH GRADE CLASSROOM 119 LOWER SCHOOL SCIENCE CLASSROOM 122 WORLD LANGUAGE CLASSROOM 121 CERAMICS 125A KILN 125B UPPER SCHOOL ART LAB 125 TEACHING AREA 131B WORKROOM 131A SMALL GROUP 117A 3RD GRADE CLASSROOM 117 STAIR 2 STR2-1 GIRLS' RESTROOM 140 BOYS' RESTROOM 139 HALLWAY 161 LIBRARY 131 TINKER AREA 133 MAKER SPACE 123 LOWER SCHOOL ART LAB 126 HALLWAY 162 ? ? FC B1-11FC B1-12 FC B1-13 FC B1-15 FC B1-16 FC B1-17 FC B1-19 FC B1-20 FC A1-20 FC A1-21 FC A1-18B FC A1-19 FC D1-1 FC D1-3 FC D1-6 FC D1-7 FC D1-8 FC D1-5 BS B-2 FC B1-13 BS A-4 FC B1-14 BS B-3 BS D-2 BS D-1 EF 1-8 EF 1-6 FC D1-4 EF 1-5 EF 1-4 TECH LAB 123A DESIGN CENTER 124 STAFF TOILET 153ELECT. 146 CUSTODIAN 151 UNISEX TOILET 152 ELEV. E-2-1 CORRIDOR 154 12 126 6 TT WW 24 24 26 26 23 2315 15 14 14 7 7 9 9 BBBB VRF PIPING UP TO 2ND FLOOR VRF PIPING UP TO 2ND FLOOR FC D1-9 FC B1-18 DATA 147 EF 1-3 SF 1-3 UTILITY NOTES POWER WIRING TO EQUIPMENT BY ELECTRICIAN CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN, INSTALLED BY ACCO AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED, INSTALLED, AND WIRED BY ELECTRICIAN DSD ASD SHEET NOTES 1. FOR VRF PIPING FROM CONDENSING UNITS TO HEAT RECOVERY UNITS: L -LIQUID HV -HIGH VAPOR LV -LOW VAPOR 2. FOR VRF PIPING FROM HEAT RECOVERY UNITS TO FAN COILS: L -LIQUID V -VAPOR 3. MIN. 20" OF STRAIGHT PIPE INTO FAN COIL UNITS 4. REFER TO SHEETS AC6.01 & AC6.02 FOR VRF PIPING DIAGRAMS. EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 N Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By A B 2/ 5 / 2 0 2 1 3 : 1 1 : 4 0 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC2.01B MECHANICAL PIPING LEVEL 01 FLOOR PLAN SOUTH 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t 1/8" = 1'-0" AC2.01A AC2.01B A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 018 12/07/20 CCD-018 DN 1 01/22/21 CITY PERMIT AMENDMENT CD DW DW TD TDTDTDTDTDTD TDTDTDTDTDTDTDTDTDTDTDTD TD TD TD TD TD J CCCC 1 1 3 3 10 10 16 16 20 20 22 22 25 25 ZZ YY V V SS NN KK HH EE BB 27 27 2 2 4 4 5 5 18 18 DD FF GG AAAA XX DDDD UU QQ C 8 8 13 13 19 19 21 21 17 17 11 11 UPPER SCHOOL SCIENCE LAB 230PREP ROOM 229A UPPER SCHOOL SCIENCE LAB 229 WORKROOM 228 6TH -8TH CLASSROOM 226 6TH -8TH CLASSROOM 224 READING ROOM 231 STAIR 2 STR-2-2 6TH -8TH CLASSROOM 220 6TH -8TH CLASSROOM 216 6TH -8TH CLASSROOM 214 STAFF WORKROOM 208 6TH -8TH CLASSROOM 219 6TH -8TH CLASSROOM 217 COLAB 218 COLAB 249 STORAGE 248 ELEV. E-1-2 CUSTODIAL 242 STAFF TOILET 244 UNISEX TOILET 247 DATA 240 ELECT 241 STAIR 1 STR-1-2 COLAB 211A 5TH GRADE CLASSROOM 211 STAFF LOUNGE 207 UNASSIGNED 204 UPPER DIRECTOR 203 DEVELOPMENT DIRECTOR 202 COMMUNICATIONS DIR. 201 5TH GRADE CLASSROOM 212 BOYS' RESTROOM 245 GIRLS' RESTROOM 246 HALLWAY 250 ROOF DECK 253 GIRLS' RESTROOM 238 BOYS' RESTROOM 237 6TH -8TH CLASSROOM 221 6TH -8TH CLASSROOM 223 6TH -8TH CLASSROOM 222 6TH -8TH CLASSROOM 215 6TH -8TH CLASSROOM 225 6TH -8TH CLASSROOM 227 6TH -8TH CLASSROOM 213 COLAB 254 ROOF DECK 254 OPEN OFFICE 252 HALLWAY 251 HALLWAY 255 FC A2-3 FC A2-4 FC A2-5 FC A2-7 FC A2-14 FC A2-13 FC C2-2 FC A2-15 FC C2-3 FC A2-10 FC A2-11 FC A2-12 FC A2-9 FC C2-7 FC C2-4 FC C2-5 FC C2-6 FC C2-8 FC C2-9 FC C2-10 FC C2-11 FC C2-12 FC C2-14 FC C2-13 FC C2-15 FC C2-16 FC C2-17 FC C2-18 FC C2-19 FC C2-20 FC C2-21 FC D2-1 FC D2-2 FC D2-3 FC D2-5 FC D2-4 FC D2-6 SF 2-1 SF 2-2 SF 2-3 SF 2-4 FC A2-1 FC A2-6 FC A2-8 BS A-5 BS A-6 BS D-4 BS C-1 BS C-2 BS C-3 BS C-4 BS D-3 EF 2-1 EF 2-2 EF 2-3 EF 2-4 ELECT 233 CUSTODIAL 235 ELEV. E-2-2 SYSTEMS ADMIN. 209 UNASSIGNED 210 UNISEX TOILET 239 STAFF TOILET 236 BUSINESS OFFICE 205 HUMAN RESOURCES DIR. 206 MOTHER'S ROOM 207A ELEV. MACHINE ROOM 243 PP MM 12 126 6 LL RR TT W W 24 24 26 26 23 2315 15 14 14 7 7 9 9 BBBB AA JJ FC A2-2 DATA 233B ELEV. MACH. ROOM 234 SS 1-2 SS 1-1 UTILITY NOTES POWER WIRING TO EQUIPMENT BY ELECTRICIAN CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN, INSTALLED BY ACCO AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED, INSTALLED, AND WIRED BY ELECTRICIAN DSD ASD SHEET NOTES 1. FOR VRF PIPING FROM CONDENSING UNITS TO HEAT RECOVERY UNITS: L -LIQUID HV -HIGH VAPOR LV -LOW VAPOR 2. FOR VRF PIPING FROM HEAT RECOVERY UNITS TO FAN COILS: L -LIQUID V -VAPOR 3. MIN. 20" OF STRAIGHT PIPE INTO FAN COIL UNITS 4. REFER TO SHEETS AC6.01 & AC6.02 FOR VRF PIPING DIAGRAMS. EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 N Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By A B 2/ 5 / 2 0 2 1 3 : 1 1 : 4 9 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC2.02 MECHANICAL PIPING LEVEL 02 FLOOR PLAN OVERALL 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t 1/16" = 1'-0" AC2.02A AC2.02B A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 1 01/22/21 CITY PERMIT AMENDMENT CD DW 1 1 3 3 10 10 16 16 20 20 SS NN K HH EE BB 2 2 4 4 5 5 18 18 DD FF GG QQ C 8 8 13 13 19 19 17 17 11 11 6TH -8TH CLASSROOM 216 6TH -8TH CLASSROOM 214 STAFF WORKROOM 208 SYSTEMS ADMIN. 209 UNASSIGNED 210 6TH -8TH CLASSROOM 219 6TH -8TH CLASSROOM 217 COLAB 218 COLAB 249 STORAGE 248 ELEV. E-1-2 CUSTODIAL 242 STAFF TOILET 244 UNISEX TOILET 247 DATA 240 ELECT 241 STAIR 1 STR-1-2 COLAB 211A 5TH GRADE CLASSROOM 211 STAFF LOUNGE 207 UNASSIGNED 204 UPPER DIRECTOR 203 DEVELOPMENT DIRECTOR 202 COMMUNICATIONS DIR. 201 5TH GRADE CLASSROOM 212 BOYS' RESTROOM 245 GIRLS' RESTROOM 246 HALLWAY 250 ROOF DECK 253 6TH -8TH CLASSROOM 215 6TH -8TH CLASSROOM 213 COLAB 254 OPEN OFFICE 252 HALLWAY 251 FC A2-15 FC A2-3 FC A2-4 FC A2-5 FC A2-7 FC A2-9 FC A2-14 FC A2-13 FC C2-2 FC C2-3 FC C2-4 FC C2-5 FC C2-7 FC C2-6 FC C2-8 FC C2-10 FC A2-10 FC A2-11 FC A2-12 SF 2-1 BS A-5 BS A-6 EF 2-1 SF 2-2 SF 2-3 BS C-2 FC C2-9 BS C-1 FC A2-1 FC A2-6 FC A2-8 MATCH LINE SEE SHEET -AC2.02B BUSINESS OFFICE 205 MOTHER'S ROOM 207A HUMAN RESOURCES DIR. 206 ELEV. MACHINE ROOM 243 PP MM 12 126 6 L L RR 15 15 14 14 7 7 9 9 AA JJ VRF PIPING DN TO 1ST FLOOR FC A2-2 SS 1-1 VRF PIPING DN TO 1ST FLOOR UTILITY NOTES POWER WIRING TO EQUIPMENT BY ELECTRICIAN CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN, INSTALLED BY ACCO AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED, INSTALLED, AND WIRED BY ELECTRICIAN DSD ASD SHEET NOTES 1. FOR VRF PIPING FROM CONDENSING UNITS TO HEAT RECOVERY UNITS: L -LIQUID HV -HIGH VAPOR LV -LOW VAPOR 2. FOR VRF PIPING FROM HEAT RECOVERY UNITS TO FAN COILS: L -LIQUID V -VAPOR 3. MIN. 20" OF STRAIGHT PIPE INTO FAN COIL UNITS 4. REFER TO SHEETS AC6.01 & AC6.02 FOR VRF PIPING DIAGRAMS. EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 N Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By A B 2/ 5 / 2 0 2 1 3 : 1 1 : 5 5 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC2.02A MECHANICAL PIPING LEVEL 02 FLOOR PLAN NORTH 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t 1/8" = 1'-0" AC2.02A AC2.02B A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 1 01/22/21 CITY PERMIT AMENDMENT CD DW J CCCC 1 1 3 3 10 10 16 16 20 20 22 22 25 25 ZZ YY VV SS 27 27 2 2 4 4 5 5 18 18 AAAA XX DDDD UU 8 8 13 13 19 19 21 21 17 17 11 11 UPPER SCHOOL SCIENCE LAB 230 PREP ROOM 229A UPPER SCHOOL SCIENCE LAB 229 WORKROOM 228 6TH -8TH CLASSROOM 226 6TH -8TH CLASSROOM 224 READING ROOM 231 STAIR 2 STR-2-2 6TH -8TH CLASSROOM 220 6TH -8TH CLASSROOM 219 COLAB 218 HALLWAY 250 ROOF DECK 253 GIRLS' RESTROOM 238 BOYS' RESTROOM 237 6TH -8TH CLASSROOM 221 6TH -8TH CLASSROOM 223 6TH -8TH CLASSROOM 222 6TH -8TH CLASSROOM 225 6TH -8TH CLASSROOM 227 COLAB 254 ROOF DECK 254 HALLWAY 255 FC C2-11 FC C2-13 FC C2-12 FC C2-14 FC C2-15 FC C2-20 FC D2-6 FC D2-2 FC D2-1 FC C2-19 FC C2-18 FC C2-17FC C2-16 FC D2-3 FC D2-4 FC D2-5 BS C-3 BS C-4 EF 2-2 EF 2-3 EF 2-4 BS D-4 BS D-3 ELECT 233 CUSTODIAL 235 ELEV. E-2-2 UNISEX TOILET 239 STAFF TOILET 236 12 126 6 TT WW 24 24 26 26 23 2315 15 14 14 7 7 9 9 BBBB VRF PIPING DN TO 1ST FLOOR VRF PIPING DN TO 1ST FLOOR ELEV. MACH. ROOM 234DATA 233B FC C2-21 SS 1-2 SF 2-4 UTILITY NOTES POWER WIRING TO EQUIPMENT BY ELECTRICIAN CONDENSATE LINE W/ TRAP TO APPROVED RECEPTOR BY PLUMBER SUPPLY DUCT SMOKE DETECTOR; FURNISHED AND WIRED BY ELECTRICIAN, INSTALLED BY ACCO AREA SMOKE DETECTOR, MOUNTED WITHIN 5 FT. OF FSD; FURNISHED, INSTALLED, AND WIRED BY ELECTRICIAN DSD ASD SHEET NOTES 1. FOR VRF PIPING FROM CONDENSING UNITS TO HEAT RECOVERY UNITS: L -LIQUID HV -HIGH VAPOR LV -LOW VAPOR 2. FOR VRF PIPING FROM HEAT RECOVERY UNITS TO FAN COILS: L -LIQUID V -VAPOR 3. MIN. 20" OF STRAIGHT PIPE INTO FAN COIL UNITS 4. REFER TO SHEETS AC6.01 & AC6.02 FOR VRF PIPING DIAGRAMS. EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 N Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By A B 2/ 5 / 2 0 2 1 3 : 1 2 : 0 0 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC2.02B MECHANICAL PIPING LEVEL 02 FLOOR PLAN SOUTH 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t 1/8" = 1'-0" AC2.02A AC2.02B A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 1 01/22/21 CITY PERMIT AMENDMENT CD EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By 2/ 5 / 2 0 2 1 3 : 1 2 : 0 0 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC4.01 MECHANICAL ENLARGED PLANS 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t 1/4" = 1'-0" A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH 016 12/09/20 CCD-016 DN 1 01/22/21 CITY PERMIT AMENDMENT CD MAX 12" HEIGHT 1" MINIMUM (CPC 801.2) SS - FC - 91011 5678 4 3 2 1 RECTANGULAR DUCT ROUND DUCT CONDENSATE TRAP DETAIL CONCEALED REFRIG. PIPING HANGING DETAILEXPOSED REFRIG. PIPING HANGING DETAILDUCT HANGING DETAILDIFFUSER HANGING DETAIL INLINE EXHAUST FAN HANGING DETAIL WALL MOUNTED FAN COIL DETAIL HANGING VRF FAN COIL ATTACHMENT DETAIL CONDENSING UNIT MOUNTING DETAIL FOR DUCTS OVER 20" DEEP ONLY #10 TEK SCREW (TYP.) FOR DUCTS OVER 12" DEEP ONLY #10 TEK SCREW (TYP.) SEE DETAIL 9 FOR UPPER ATTACHMENTS 1/2" MIN. 1" MAX. OFFSET SAND-LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE (MIN. f'c = 3000 PSI) OVER MIN. 20ga METAL DECK UNISTRUT SPREADER HANGER ROD ROD COUPLER 1"-18 GA DUCT STRAP (TYP.) 1"-18 GA DUCT STRAP (TYP.) 1"-18 GA DUCT STRAP (TYP.) SHOT PIN (TYP.) **THE FOLLOWING UPPER ATTACHMENTS ARE OPTIONS FOR DIFFERENT LOWER ATTACHMENTS. FOR THE LOWER ATTACHMENT DETAILS, PLEASE SEE THE HANGING DETAILS FOR THE DIFFERENT PIECES OF EQUIPMENT 1-1/4" RADIUS MIN. 1"-18 GA DUCT STRAP (TYP.) ROD INSERTS SHEET METAL CURL INSERTS HANGER RODHANGER ROD SHOT PIN (TYP.) 1" MAX. OFFSET UNISTRUT SPREADER HANGER ROD ROD COUPLER 2ND FLOOR 1"-18 GA DUCT STRAP (TYP.) HANGER ROD 1"-18 GA DUCT STRAP (TYP.) #10 TEK SCREW (TYP.) 1"-18 GA DUCT STRAP (TYP.) 1-1/4" RADIUS MIN. #10 TEK SCREW (TYP.) SHEET METAL CURL INSERTS 1"-18 GA DUCT STRAP (TYP.) #10 TEK SCREW (TYP.)#10 TEK SCREW (TYP.) 1ST FLOOR NOTE: SUPPORTING HANGERS AND ANCHOR BOLTS FOR MECHANICAL EQUIPMENT WILL BE DESIGNED BY ACCO'S STRUCTURAL ENGINEER PER SMACNA GUIDELINES. ANCHOR BOLT SEE SEISMIC SUPPORT PACKAGE (TYPICAL) MANUF. HANGER BRACKET WITH RUBBER GROMETS. (TYPICAL OF 4) 3/8"Ø THREADED ROD (TYP. OF 4) ATTACHMENT TO STRUCTURE. SEE DETAIL 9 FOR UPPER ATTACHMENT OPTIONS CABLE WITH 1-1/2" SLACK, AT EACH CORNER, AT 45° ANGLEFC # CONDENSATE DRAIN PIPING TAG MIN. DIAMETER (IN.) MIN. H-VALUE (IN.) ALL FC'S 3/4 1.50 NEGATIVE PRESSURE CHAMBER VENT H" DRAW THRU SYSTEM H - MAXIMUM ANTICIPATED PRESSURE DIFFERENTIAL BETWEEN ATMOSPHERE AND CHAMBER HOUSING DRAIN PAN. ADD 50% SAFETY FACTOR FOR "H" CALCULATION. 3/4 INCH 1 INCH 1 1/4 INCH 1 1/2 INCH 2 INCH EQUIPMENT CAPACITY IN TONS OF REFRIGERATION MINIMUM CONDENSATE PIPE DIAMETER UP TO 20 OVER 21 TO 40 OVER 41 TO 90 OVER 91 TO 125 OVER 126 TO 250 H" UP TO 20 OVER 21 TO 40 OVER 41 TO 90 OVER 91 TO 125 OVER 126 TO 250 EQUIPMENT CAPACITY IN TONS OF REFRIGERATION PER 2016 CALIFORNIA PLUMBING CODE (FOR DRAIN LINES (INDIRECT WASTE) FROM EQUIPMENT TO APPROVED RECEPTOR) (CPC 814.3) PER 2016 CALIFORNIA MECHANICAL CODE (FOR CONDENSATE PIPE LINES FROM EQUIPMENT TO APPROVED RECEPTACLE) (CMC 310.3) NOTES: PER 2016 CALIFORNIA MECHANICAL CODE 1109.9, PIPING AND FITTINGS WHICH CONVEY BRINE, REFRIGERANT OR COOLANTS WHICH DURING NORMAL OPERATION COULD REACH A SURFACE TEMPERATURE BELOW THE DEW POINT OF THE SURROUNDING AIR AND THAT ARE LOCATED IN SPACES OR AREAS WHERE CONDENSATION COULD CAUSE A HAZARD TO THE BUILDING OCCUPANTS OR DAMAGE TO THE STRUCTURE OR ELECTRICAL OR OTHER EQUIPMENT SHALL BE PROTECTED TO PREVENT SUCH DAMAGE. ** PER 2016 CALIFORNIA PLUMBING CODE 703.2, SANITARY DRAINAGE PIPING SHALL BE SIZED TO ALLOW FOR TWO (2) FIXTURE UNITS FOR EACH GALLON PER MINUTE OF FLOW. PITCH TO OPEN DRAIN 1/4" PER FOOT RECOMMENDED, 1/8" PER FOOT MINIMUM (CPC 814.1) (CMC 310.3) FLOOD-LEVEL RIM OF RECEPTOR (CPC 810.4) ** INSULATED REFER. LINES TOLCO OR BLINE FELTED J-HANGER 3/8" ALL-THREAD SEE DETAIL 9 FOR UPPER ATTACHMENT TO SURFACE ABOVE TO STRUCTURE ABOVE. SEE DETAIL 9 FOR OTHER UPPER ATTACHMENT OPTIONS. #12 GA. WIRE OR 1" WIDE HANGER STRAP FLEXIBLE ROUND DUCT ROUND TO SQUARE METAL CAP, AS REQUIRED OBD @ AIR REGISTER ONLY AS REQUIRED CEILING #10 TEK SCREW VOLUME DAMPER WHERE SHOWN ON PLANS #10 TEK SCREW CEILING DIFFUSER SHEET METAL DRAW BAND AROUND FLEX. UL APPROVED TAPE OR DUCT SEALER REFRIGERANT PIPING B-LINE ROOF SUPPORT "FLOATING" WITH ADJUSTABLE HEIGHT ALL THREAD ROD OR EQUAL.UNI-STRUT PIPE CLAMP ASSEMBLY OR EQUAL. CONCRETE PAD BY G.C. EXPANSION ANCHORS BY ACCO NORMALWEIGHT CONCRETE PAD BY G.C. CU A NEOPRENE VIB. ISO CU B DUPLEX RECEPTACLE BY ELECTRICAL CONTRACTOR CEILING EXTERNAL CONDENSATE PUMP BY PLUMBING CONTRACTOR DISCONNECT BY ELECTRICAL CONTRACTOR POWER BY ELECTRICAL CONTRACTOR FINISHED FLOOR EXPOSED PIPING RACKED ON WALL (TYP) REFRIGERANT PIPING POWER BY ELECTRICAL CONTRACTOR CONDENSATE DRAIN NOTE: MOUNT INSTALLATION PLATE LEVEL WITH A MINIMUM OF FOUR (4) #10 x 2 TEK SCREWS LANDING TEK SCREWS IN A MINIMUM OF TWO STUDS. STUD BY G.C. (TYP.) MOUNTING BRACKET PROVIDED WITH UNIT. FASTEN TO STUDS INSULATED REFER. LINES TOLCO OR BLINE FELTED J-HANGER 3/8" ALL-THREAD FOR UPPER ATTACHMENT DETAIL SEE 9 CU C CU D CU 1 CU 2 UPPER ATTACHMENTS DETAILREFRIGERANT PIPING MOUNTING DETAIL AIRCRAFT CABLE FOR LATERAL BRACING TYPICAL @ 45° ANGLE TO STRUCTURE ABOVE. SEE DETAIL 9 FOR OTHER UPPER ATTACHMENT OPTIONS. EF 1-8 3" MAX. EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By 2/ 5 / 2 0 2 1 3 : 1 2 : 0 1 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC5.01 MECHANICAL DETAILS 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t N/A B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 1 01/22/21 CITY PERMIT AMENDMENT CD 14"X46 OPENING IN NORMALWEIGHT CONCRETE PAD FOR REFRIGERANT PIPING TO GO UNDERGROUND. LOCATION PER PLANS. MIN 6" EDGE DISTANCE. VRF PIPING TO BE ENCLOSED IN 12" PVC. SPLIT SYSTEM PIPING TO BE ENCLOSED IN 6" PVC. 6" EDGE DISTANCE TO BE CONFIRMED BY STRUCTURAL DRAWINGS PAD THICKNESS PER STRUCTURAL DRAWINGS TRANSFER AIR OPENING (TYP. 1 SQ. FT. UNLESS OTHERWISE STATED SHEET METAL CAN FLEX (TYP. 16"Ø) 24"X24" CT1 LAY-IN GRILLE VRF LINES ENCASED IN 12" PVC LINES SPLIT SYSTEM LINES ENCASED IN 6" PVC LINES HARDSCAPE CHIMNEY CAP (TYP.) PARAPET TOP OF CHIMNEY CAP TO BE BELOW TOP OF PARAPET LINE 1/4" (MIN.) 1" MIN. 33'-7" 7'-6" 6" 6" 3'-10" 1'-2" 6" MIN. 6" MIN. 12" MIN. 6" MIN.6" MIN. 1' - 0" 20"20"2'-0" 910 34 78 2 1 56 DUST COLTR MOUNTING DETAIL (NOT USED)HALLWAY TRANSFER AIR DETAILREFRIGERANT TRENCH DETAILFIREPLACE FLUE TERMINATION DETAIL DUST COLTR. EQUIP. ATTCH DETAIL (NOT USED)DUST COLTR. DUCT ATTCH DETAIL (NOT USED)CONDENSING UNIT PAD DETAIL FIRE SMOKE DAMPER DETAIL OPTIONAL FIRESTAT OR END SWITCHES AUXILIARY OPERATING JACK SHAFT OPENING TO BE FRAMED AND SHEETROCKED BY G.C. (WITH REQUIRED CLEARANCE) PFMA OR CONVENTIONAL MOUNTING ANGLES S JOINT/DUCTMATE, SLEEVE TO DUCT BREAKAWAY CONNECTION PFMA OR 1-1/2"x1-1/2" STEEL ANGLE NO EXPANSION GAP REQUIRED, TYPICAL OF ALL SIDES #10 TEK SCREWS MAX. 12" O.C. MOUNTING ANGLES TO OVERLAP WALL A MINIMUM OF 1" ON ALL 4 SIDES CEILING AIRFLOW DIRECTION T-BAR CLG RATED WALL T-BAR CLG RATED WALL T-BAR CLG AD ONE SIDE MOUNTING ANGLE INSTALLATION FASTENED DIRECTLY TO METAL STUD ONE SIDE MOUNTING ANGLE INSTALLATION FASTENED DIRECTLY TO WALL FSD IN DUCT ALTERNATE UL LISTED MOUNTING DETAILS UL 555 AND UL 555S LISTED, CLASS II FSD SEE FLOOR PLANS FOR LOCATION AND SIZE OF DAMPER CONSISTENT WITH SMACNA'S "FIRE DAMPER & HEAT STOP GUIDE" S JOINT/DUCTMATE, SLEEVE TO DUCT BREAKAWAY CONNECTION DAMPER ACTUATOR SLEEVE EXTENDED MIN. 3" EACH SIDE OF PARTITION SUPPLY OR RETURN DUCT WHERE OCCURSAIRFOIL BLADES [MODEL#] 18x18 CEILING ACCESS PANEL (FIRE RATED WHERE REQ'D) FOR ACTUATOR AND DAMPER ACCESS FIRE/SMOKE DAMPER DUCT ACCESS FIRE RATED WALL MOUNTING ANGLES FASTENED TO SLEEVE BY #10 TEK SCREWS 6-8" O.C. MOUNTING ANGLES TO OVERLAP WALL A MINIMUM OF 1" ON ALL 4 SIDES CONTROL LINKAGE DAMPER CBC 717.3.3.2: Smoke dampers shall be closed by actuation of a smoke detector installed in accordance with the Fire Code and one of the following applicable methods: 1. Where a damper is installed within a duct, a smoke detector shall be installed in the duct within 5 feet (1524 mm) of the damper with no air outlets or inlets between the detector and the damper. The detector shall be listed for the air velocity, temperature and humidity anticipated at the point where it is installed. 2. Where a damper is installed within an unducted opening in a wall, a spot-type detector listed for releasing service shall be installed within 5 feet (1524 mm) horizontally of the damper. 3. Where a damper is installed in a ceiling, a spot-type detector listed for releasing service shall be installed on the ceiling within 5 feet (1524 mm) of the damper. 4. Where a damper is installed in a corridor wall or ceiling, the damper may be controlled by a smoke-detection system installed in the corridor. 5. When a total-coverage smoke-detection system is provided within all areas served by an HVAC system, dampers may be controlled by the smoke-detection system. INSTALL FSD SUCH THAT DAMPER BLADES ARE IN THE RATED WALL ASSEMBLY WHEN CLOSED NOTE: WHERE INSTALLATION DETAIL AND MANUFACTURER'S INSTALLATION INSTRUCTIONS CONFLICT, MFR'RS INSTRUCTIONS SHALL PREVAIL. DUCTMATE WITH PLASTIC CLEATS PER MFR'RS INSTRUCTIONS MOUNTING ANGLES TO OVERLAP WALL A MINIMUM OF 1" ON ALL 4 SIDES #10 TEK SCREWS MAX. 12" O.C. SCREWS 1/2" LONGER THAN SHEETROCK DEPTH FSD IN WALL NOTE: SMOKE DETECTORS FOR FIRE/SMOKE DAMPERS TO BE FURNISHED BY FIRE LIFE SAFETY CONTRACTOR AND WIRED BY ELECTRICIAN. SEE ABOVE FOR APPROVED LOCATIONS FOR SMOKE DETECTORS PER CBC 717.3.3.2. SA/RA DUCT PROVIDE SHUTDOWN OF HVAC SYSTEM SERVING SMOKE DAMPERS OR COMBINATION SMOKE-FIRE DAMPERS WHEN AUTOMATIC ACTIVATION OF DAMPER OCCURS. PIPE PENETRATION THRU FIRE-RATED WALL DETAIL DUST COLLECTOR DETAIL (NOT USED) CEILING CLASSROOMHALLWAY DECK SAND OR SANDY LOAM UNDISTURBED GRADE NOTE: SEE FIRE STOPPING DETAILS ON A9.06, A9.07 AND A9.08. A DSD E E PENDANT AREA SMOKE DETECTOR LOCATED IN PLENUM, WITHIN 5' OF FSDOR TOTAL COVERAGE SMOKE DETECTION SYSTEM EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By 2/ 5 / 2 0 2 1 3 : 1 2 : 0 2 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC5.02 MECHANICAL DETAIL (CONT.) 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t N/A B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 016 12/09/20 CCD-016 DN 1 01/22/21 CITY PERMIT AMENDMENT CD B.D.D. 1" FIBERGLASS DUCT LINING OPEN BOTH ENDS ONLY SHEET METAL ACCOUSTICAL SEALANT RETURN AIR BOOT ABOVE CEILING 4" DUCT SKUTT ENVIROLINK SHALL BE INSTALLED FOR AUTOMATED INTERLOCK BETWEEN KILN & DOWNDRAFT VENTING SYSTEM SKUTT ENVIROVENT 2 PLENUM CUP & CUP STAND SKUTT ENVIROVENT 2 BLOWER W/ MOTOR KILN CONTROL PANEL ACCOUSTICAL SEALANT RETURN AIR BOOT ABOVE CEILING 1" FIBERGLASS DUCT LINING OPEN BOTH ENDS ONLY SHEET METAL ELBOW CAN BE IN ANY PLANE. PREFERRED ORIENTATION IS UP. 89 567- 4 3 2 1 TYP "L" AIR RETURN RELIEF BOOT HEAT RECOVERY UNIT HANGING DETAILGRAVITY VENTILATOR DETAILREF. PIPE THERMAL EXPANSION DETAIL- INLINE EXHAUST / SUPPLY FAN DETAIL REFRIGERANT WALL PIPING DETAIL GRAVITY VENTILATOR MOUNTING DETAIL KILN DOWNDRAFT EXHAUST VENT SKUTT KM/KMT-1027-3 ELECTRIC KILN 1ST FLOOR SUPPLEMENTAL STRUCTURE AS REQUIRED PER STRUCTURAL BY G.C. O.S.A. DUCT DOWN TO FAN COIL RETURN PLENUM MANUF'R ROOF CURB FURNISHED BY ACCO WOOD NAILER (TYP.) TEK SCREW (TYP.) ROOFING BY G.C. WITH SCREEN HAVING NOT LESS THAN 1/4-INCH OPENINGS AND NOT MORE THAN 1/2-INCH OPENINGS 12" EA CONCRETE WALL TO STRUCTURE ABOVE. SEE DETAIL 9/AC5.01 FOR OTHER UPPER ATTACHMENT OPTIONS. EF 1-1 EF 1-2 EF 1-3 EF 1-4 EF 1-5 EF 1-6 EF 1-7 EF 2-1 EF 2-2 EF 2-3 EF 2-4 SF 1-1 SF 1-2 SF 1-3 SF 2-1 SF 2-2 SF 2-3 SF 2-4 SPRING HANGERS OR NEOPRENE PAD NOTE: SUPPORTING HANGERS AND ANCHOR BOLTS FOR MECHANICAL EQUIPMENT WILL BE DESIGNED BY ACCO'S STRUCTURAL ENGINEER PER SMACNA GUIDELINES. MANUF. HANGER BRACKET WITH RUBBER GROMETS. (TYPICAL OF 4) 3/8"Ø THREADED ROD (TYP. OF 4) ATTACHMENT TO STRUCTURE. SEE DETAIL 9 FOR UPPER ATTACHMENT OPTIONS BS # NEOPRENE PAD GRAVITY VENTILATOR VRF FAN COIL RETURN PLENUM SEE DETAIL 2 FOR GRAVITY VENTILATOR MOUNTING DETAIL CONDENSING UNIT (TYP.) B.D.D. 18" FLEX CONNECTOR ON HIGH PRESSURE VAPOR LINE FOR THERMAL EXPANSION. FINAL LENGTH TO BE CONFIRMED BY ENGINEERING. PVC PIPE REFRIGERANT LINES INSIDE PVC PIPING, UNDERGROUND KILN PLACEMENT NOTES (INSTALLED BY OTHERS): 1. THE SIDES AND TOPS OF KILNS SHALL BE LOCATED NOTE LESS THAN 18 INCHES FROM A NON-COMBUSTIBLE WALL SURFACE AND 3 FEET FROM A COMBUSTIBLE WALL SURFACE. [CMC 932.5.1] 2. KILNS SHALL BE INSTALLED ON NONCOMBUSTIBLE FLOORING CONSISTING OF NOT LESS THAN 2 INCHES OF SOLID MASONRY OR CONCRETE EXTENDING NOT LESS THAN 12 INCHES BEYOND THE BASE OR SUPPORTING MEMBERS OF THE KILN. [CMC 932.5.1] 3. IN NO CASE SHALL THE CLEARANCE ON THE GAS OR ELECTRICAL CONTROL SIDE OF A KILN BE REDUCED TO LESS THAN 30 INCHES. [CMC 932.5.1] INSTALL DUCT EXTENSION ATOP CONDENSING UNIT SUCH THAT AIR DISCHARGES AT THE SAME LEVEL AS THE TOP OF THE ADJACENT CONCRETE WALL DUCT EXTENSION SEE PLANS FOR SIZES TYP "U" AIR RETURN RELIEF BOOT SLOPE PIPE TO MAINTAIN 12" FROM TOP OF PIPE TO TOP OF LANDSCAPING. W W 2W 2W 2W W 3W, MIN 2W 2 EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By 2/ 5 / 2 0 2 1 3 : 2 8 : 0 7 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC5.03 MECHANICAL DETAIL (CONT.) 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t N/A B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 016 12/09/20 CCD-016 DN 1 01/22/21 CITY PERMIT AMENDMENT CD 2 xx/xx ACOUSTICAL CHANGES DN EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By 2/ 5 / 2 0 2 1 3 : 1 2 : 0 6 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC6.01 MECHANICAL VRF PIPING DIAGRAM 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t N/A A 08/16/19 100% DESIGN DEVELOPMENT PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 0 09/11/20 ISSUED FOR CONSTRUCTION CD 1 01/22/21 CITY PERMIT AMENDMENT CD EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By 2/ 5 / 2 0 2 1 3 : 1 2 : 1 0 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC6.02 MECHANICAL VRF PIPING DIAGRAMS (CONT.) 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t N/A A 08/16/19 100% DESIGN DEVELOPMENT PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 0 09/11/20 ISSUED FOR CONSTRUCTION CD 1 01/22/21 CITY PERMIT AMENDMENT CD M BAS BAS BAS BAS BAS BAS E E E E E E E E E E E E E E M BAS BAS BAS BAS BAS BAS E E E E E E E E E E E E E E M BAS BAS BAS BAS BAS BAS E E E E E E E E E E E E E E CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CIRCUIT BREAKER OR FUSED DISCONNECT S REQUIRED SHIELD GROUND AT CHASSIS CEN SHIELD GROUNDS AT THE END OF LINE MASTER CU ONLY SHIELD WIRE TWISTED AND TAPED TO CABLE SODU/IDU SHIELDS GROUND AT ALL MASTER CU'S SINGLE OR DOUBLE POLE DRY CONTACT INPUT RELAY (RIB RELAY) UNGROUNDED SHIELD CONNECTION WIRE NUT SUPPLY AIR SMOKE DETECTOR INSTALLED BY ACCO IN DISCHARGE DUCTWORK. FURNISHED AND WIRED BY ELECTRICIAN LG PROVIDED THREE-CORE COMMUNICATION CABLE OR 18-3 TWISTED, STRANDED, AND UNSHIELDED CABLE. TYPICAL ALL THERMOSTATS 18-2 SHIELDED & STRANDED LOW VOLTAGE WIRING 18-2 SHIELDED & STRANDED LOW VOLTAGE WIRING TO ADDITIONAL MASTER UNIT OR CENTRAL CONTROLLER. CHAIN TERMINATES AT CENTRAL CONTROLLER (REQUIRES 24 VAC POWER, 40 VA) 18-2 SHIELDED & STRANDED LOW VOLTAGE WIRING CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CIRCUIT BREAKER OR FUSED DISCONNECT S REQUIRED SHIELD GROUND AT CHASSIS CEN SHIELD GROUNDS AT THE END OF LINE MASTER CU ONLY SHIELD WIRE TWISTED AND TAPED TO CABLE SODU/IDU SHIELDS GROUND AT ALL MASTER CU'S SINGLE OR DOUBLE POLE DRY CONTACT INPUT RELAY (RIB RELAY) UNGROUNDED SHIELD CONNECTION WIRE NUT SUPPLY AIR SMOKE DETECTOR INSTALLED BY ACCO IN DISCHARGE DUCTWORK. FURNISHED AND WIRED BY ELECTRICIAN LG PROVIDED THREE-CORE COMMUNICATION CABLE OR 18-3 TWISTED, STRANDED, AND UNSHIELDED CABLE. TYPICAL ALL THERMOSTATS 18-2 SHIELDED & STRANDED LOW VOLTAGE WIRING 18-2 SHIELDED & STRANDED LOW VOLTAGE WIRING TO ADDITIONAL MASTER UNIT OR CENTRAL CONTROLLER. CHAIN TERMINATES AT CENTRAL CONTROLLER (REQUIRES 24 VAC POWER, 40 VA) 18-2 SHIELDED & STRANDED LOW VOLTAGE WIRING CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CIRCUIT BREAKER OR FUSED DISCONNECT S REQUIRED SHIELD GROUND AT CHASSIS CEN SHIELD GROUNDS AT THE END OF LINE MASTER CU ONLY SHIELD WIRE TWISTED AND TAPED TO CABLE SODU/IDU SHIELDS GROUND AT ALL MASTER CU'S SINGLE OR DOUBLE POLE DRY CONTACT INPUT RELAY (RIB RELAY) UNGROUNDED SHIELD CONNECTION WIRE NUT SUPPLY AIR SMOKE DETECTOR INSTALLED BY ACCO IN DISCHARGE DUCTWORK. FURNISHED AND WIRED BY ELECTRICIAN LG PROVIDED THREE-CORE COMMUNICATION CABLE OR 18-3 TWISTED, STRANDED, AND UNSHIELDED CABLE. TYPICAL ALL THERMOSTATS 18-2 SHIELDED & STRANDED LOW VOLTAGE WIRING 18-2 SHIELDED & STRANDED LOW VOLTAGE WIRING TO ADDITIONAL MASTER UNIT OR CENTRAL CONTROLLER. CHAIN TERMINATES AT CENTRAL CONTROLLER (REQUIRES 24 VAC POWER, 40 VA) 18-2 SHIELDED & STRANDED LOW VOLTAGE WIRING 3 2 1VRF-A POWER LOAD DIAGRAM CENSODUIDU A B A B A B CENSODUIDU A B A B A B 4 3 HEAT RECOVERY UNIT TO NEXT FCU/HRU IN SERIES, SEE SCHEDULE & FLOOR PLAN FOR QUANTITIES INDOOR UNIT INDOOR UNIT GROUNDGROUND 208V-1Ø208V-1Ø TO FIRE ALARM PANEL BY ELECTRICIAN THERMOSTAT THERMOSTAT 4 3 R G Y4 3 R G Y 208V-1Ø460V-3Ø460V-3Ø NOTE: UNGROUNDED SHIELD MAY USE WIRE NUT AS INDICATED ABOVE. ALL OTHER LG VRF COMMUNICATION WIRES MAY NOT CONTAIN SPLICES OR WIRE NUTS. WIRED CONTROLLER (PROVIDED WITH UNIT) SET THERMOSTAT @ 75°F COOLING, 70°F HEATING WIRED CONTROLLER (PROVIDED WITH UNIT) SET THERMOSTAT @ 75°F COOLING, 70°F HEATING OUTDOOR UNIT MASTER (LARGEST TONNAGE) OUTDOOR UNIT SLAVE SHIELD GROUND CU A LG VRF CONDENSING UNIT ON GRADE (QTY. 2 AS SHOWN) HRU - LG VRF HEAT RECOVERY UNIT SEE FLOOR PLAN FOR LOCATION (QTY. 6) FCU - LG VRF FAN COIL SEE FLOOR PLAN FOR FAN COILS WHICH DO NOT NEED SMOKE DETECTORS FCU - LG VRF FAN COIL W/ DSD SEE FLOOR PLAN FOR FAN COILS WHICH NEED SMOKE DETECTORS CENSODUIDU A B A B A B CENSODUIDU A B A B A B 4 3 HEAT RECOVERY UNIT TO NEXT FCU/HRU IN SERIES, SEE SCHEDULE & FLOOR PLAN FOR QUANTITIES INDOOR UNIT INDOOR UNIT GROUNDGROUND 208V-1Ø208V-1Ø TO FIRE ALARM PANEL BY ELECTRICIAN THERMOSTAT THERMOSTAT 4 3 R G Y4 3 R G Y 208V-1Ø460V-3Ø460V-3Ø NOTE: UNGROUNDED SHIELD MAY USE WIRE NUT AS INDICATED ABOVE. ALL OTHER LG VRF COMMUNICATION WIRES MAY NOT CONTAIN SPLICES OR WIRE NUTS. WIRED CONTROLLER (PROVIDED WITH UNIT) SET THERMOSTAT @ 75°F COOLING, 70°F HEATING WIRED CONTROLLER (PROVIDED WITH UNIT) SET THERMOSTAT @ 75°F COOLING, 70°F HEATING OUTDOOR UNIT MASTER (LARGEST TONNAGE) OUTDOOR UNIT SLAVE SHIELD GROUND CU B LG VRF CONDENSING UNIT ON GRADE (QTY. 2 AS SHOWN) HRU - LG VRF HEAT RECOVERY UNIT SEE FLOOR PLAN FOR LOCATION (QTY. 3) FCU - LG VRF FAN COIL SEE FLOOR PLAN FOR FAN COILS WHICH DO NOT NEED SMOKE DETECTORS FCU - LG VRF FAN COIL W/ DSD SEE FLOOR PLAN FOR FAN COILS WHICH NEED SMOKE DETECTORS CENSODUIDU A B A B A B CENSODUIDU A B A B A B 4 3 HEAT RECOVERY UNIT TO NEXT FCU/HRU IN SERIES, SEE SCHEDULE & FLOOR PLAN FOR QUANTITIES INDOOR UNIT INDOOR UNIT GROUNDGROUND 208V-1Ø208V-1Ø TO FIRE ALARM PANEL BY ELECTRICIAN THERMOSTAT THERMOSTAT 4 3 R G Y4 3 R G Y 208V-1Ø460V-3Ø460V-3Ø NOTE: UNGROUNDED SHIELD MAY USE WIRE NUT AS INDICATED ABOVE. ALL OTHER LG VRF COMMUNICATION WIRES MAY NOT CONTAIN SPLICES OR WIRE NUTS. WIRED CONTROLLER (PROVIDED WITH UNIT) SET THERMOSTAT @ 75°F COOLING, 70°F HEATING WIRED CONTROLLER (PROVIDED WITH UNIT) SET THERMOSTAT @ 75°F COOLING, 70°F HEATING OUTDOOR UNIT MASTER (LARGEST TONNAGE) OUTDOOR UNIT SLAVE SHIELD GROUND CU C LG VRF CONDENSING UNIT ON GRADE (QTY. 2 AS SHOWN) HRU - LG VRF HEAT RECOVERY UNIT SEE FLOOR PLAN FOR LOCATION (QTY. 4) FCU - LG VRF FAN COIL SEE FLOOR PLAN FOR FAN COILS WHICH DO NOT NEED SMOKE DETECTORS FCU - LG VRF FAN COIL W/ DSD SEE FLOOR PLAN FOR FAN COILS WHICH NEED SMOKE DETECTORS VRF-B POWER LOAD DIAGRAM VRF-C POWER LOAD DIAGRAM EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By 2/ 5 / 2 0 2 1 3 : 1 2 : 1 1 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC7.01 POWER LOAD DIAGRAMS 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t N/A B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 1 01/22/21 CITY PERMIT AMENDMENT CD M BAS BAS BAS BAS BAS E E E E E E E E E E E E E E BAS E E ELECTRICAL SHEET NOTES 8 7. 2. 1. 3. 4. 9. WIRING AND INSTALLATION SHALL CONFORM TO ALL GOVERNING CODES. INDICATES ITEMS FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR. INDICATES ITEMS FURNISHED BY MECHANICAL CONTRACTOR. ALL COPPER AND/OR ALUMINUM CONDUCTOR CONNECTIONS SHALL BE MADE AS PRESCRIBED BY ESTABLISHED ELECTRICAL INDUSTRY AND ENGINEERING STANDARDS. EXTREME CARE MUST BE TAKEN WHEN CONNECTIONS INVOLVE DISSIMILAR MATERIALS. INDICATES LINE VOLTAGE WIRING BY ELECTRICAL CONTRACTOR. INDICATES LOW VOLTAGE WIRING. INDICATES ITEMS FURNISHED AND INSTALLED BY BUILDING AUTOMATION SYSTEM CONTRACTOR. 10. FROM 2016 CMC, SEC. 301.4: "EQUIPMENT REGULATED BY THIS CODE REQUIRING ELECTRICAL CONNECTIONS OF MORE THAN 50 VOLTS SHALL HAVE A POSITIVE MEANS OF DISCONNECT ADJACENT TO AND IN SIGHT FROM THE EQUIPMENT SERVED. A 120-VOLT RECEPTACLE SHALL BE LOCATED WITHIN 25 FEET OF THE EQUIPMENT FOR SERVICE AND MAINTENANCE PURPOSES. THE SERVICE RECEPTACLE NEED NOT BE LOCATED ON THE SAME LEVEL AS THE EQUIPMENT. LOW VOLTAGE WIRING OF 50 VOLTS OR LESS WITHIN A STRUCTURE SHALL BE INSTALLED IN A MANNER TO PREVENT PHYSICAL DAMAGE." ELECTRICAL WIRING, CONTROLS, AND CONNECTIONS TO EQUIPMENT AND APPLIANCES REGULATED BY THIS CODE SHALL BE IN ACCORDANCE WITH NFPA 70. 5.INDICATES ITEMS FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR TO BE ON EMERGENCY POWER. 6.INDICATES ITEMS FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR TO BE ON UPS POWER. E M BAS EMP UPS M BAS BAS E E E E E BAS BAS BAS E E E E E E BAS M BAS BAS E E E E E BAS M M E E E E CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CIRCUIT BREAKER OR FUSED DISCONNECT S REQUIRED SHIELD GROUND AT CHASSIS CEN SHIELD GROUNDS AT THE END OF LINE MASTER CU ONLY SHIELD WIRE TWISTED AND TAPED TO CABLE SODU/IDU SHIELDS GROUND AT ALL MASTER CU'S SINGLE OR DOUBLE POLE DRY CONTACT INPUT RELAY (RIB RELAY) UNGROUNDED SHIELD CONNECTION WIRE NUT SUPPLY AIR SMOKE DETECTOR INSTALLED BY ACCO IN DISCHARGE DUCTWORK. FURNISHED AND WIRED BY ELECTRICIAN LG PROVIDED THREE-CORE COMMUNICATION CABLE OR 18-3 TWISTED, STRANDED, AND UNSHIELDED CABLE. TYPICAL ALL THERMOSTATS 18-2 SHIELDED & STRANDED LOW VOLTAGE WIRING 18-2 SHIELDED & STRANDED LOW VOLTAGE WIRING 18-2 SHIELDED & STRANDED LOW VOLTAGE WIRING CIRCUIT BREAKER OR FUSED DISCONNECT S REQUIRED TO ADDITIONAL MASTER UNIT OR CENTRAL CONTROLLER. CHAIN TERMINATES AT CENTRAL CONTROLLER (REQUIRES 24 VAC POWER, 40 VA) CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CURRENT SWITCH BY CONTROLS CONTRACTOR SPEED CONTROLLER (PROVIDED WITH FAN) MOUNTED AND WIRED BY ELECTRICAL CONTRACTOR 24V WIRING CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED CURRENT SWITCH BY CONTROLS CONTRACTOR SPEED CONTROLLER (PROVIDED WITH FAN) MOUNTED AND WIRED BY ELECTRICAL CONTRACTOR RELAY (IF NECESSARY) WITH 24V COIL AND 120V RATED CONTACT. CIRCUIT BREAKER OR FUSED DISCONNECT AS REQUIRED DUCT OR AREA SMOKE DETECTOR BY ELECTRICIAN. NORMALLY CLOSED CONTACT FROM LOCAL SMOKE DETECTOR. BREAK ON ALARM TO CLOSE DAMPER. DEVICE & CONTROL BY ELEC CONTRACTOR NORMALLY CLOSED CONTACT TO ASSOCIATED AC UNIT/FAN FOR AC UNIT/FAN SHUT DOWN. SEE NOTE 3. BY FLS CONTRACTOR. SIGNAL FROM AC UNIT/FAN. NORMALLY OPEN RELAY FOR FSD OPEN/CLOSE DURING NORMAL OPERATION. CLOSE WHEN SIGNAL IS RECEIVED FROM AC UNIT/FAN TO OPEN DAMPER. DEVICE & CONTROL BY FLS CONT'R. (NOT REQUIRED IF DUCT OR AREA SMOKE DETECTOR DOES NOT HAVE MINIMUM FLOW REQUIREMENT PER CODE 2016 CBC 717.3.3.2.1) LOCAL DISCONNECT SWITCH BY ELECTRICIAN 120VAC, SPRING RETURN DAMPER ACTUATOR (PROVIDED WITH DAMPER ASSEMBLY) 6789 2345 1 SPLIT SYSTEM POWER LOAD FIRE SMOKE DAMPER POWER LOAD ELECTRICAL SHEET NOTESEXHAUST FAN POWER LOAD VRF-D POWER LOAD DIAGRAM CENSODU IDU A B A B A B CENSODU IDU A B A B A B 4 3 HEAT RECOVERY UNIT TO NEXT FCU/HRU IN SERIES, SEE SCHEDULE & FLOOR PLAN FOR QUANTITIES INDOOR UNIT INDOOR UNIT GROUNDGROUND 208V-1Ø208V-1Ø TO FIRE ALARM PANEL BY ELECTRICIAN THERMOSTAT THERMOSTAT 4 3 R G Y43 R G Y 208V-1Ø460V-3Ø460V-3Ø NOTE: UNGROUNDED SHIELD MAY USE WIRE NUT AS INDICATED ABOVE. ALL OTHER LG VRF COMMUNICATION WIRES MAY NOT CONTAIN SPLICES OR WIRE NUTS. WIRED CONTROLLER (PROVIDED WITH UNIT) SET THERMOSTAT @ 75°F COOLING, 70°F HEATING WIRED CONTROLLER (PROVIDED WITH UNIT) SET THERMOSTAT @ 75°F COOLING, 70°F HEATING OUTDOOR UNIT MASTER (LARGEST TONNAGE) OUTDOOR UNIT SLAVE SHIELD GROUND CENSODU IDU A B A B A B 460V-3Ø OUTDOOR UNIT SLAVE SHIELD GROUND FCU - LG VRF FAN COIL SEE FLOOR PLAN FOR FAN COILS WHICH DO NOT NEED SMOKE DETECTORS FCU - LG VRF FAN COIL W/ DSD SEE FLOOR PLAN FOR FAN COILS WHICH NEED SMOKE DETECTORS HRU - LG VRF HEAT RECOVERY UNIT SEE FLOOR PLAN FOR LOCATION (QTY. 4) CU D LG VRF CONDENSING UNIT ROOF (QTY. 3 AS SHOWN) EF 2-2 EXHAUST FAN IN-LINE 115V-1Ø MOTOR STATUS START/STOP GROUND EF 2-3 EF 1-1 MOUNT ON WALL IN ZONE ROOM AT 48" A.F.F. THERMOSTAT R G W1 W2 Y Y2 C O INDOOR UNIT 208V-1Ø OUTDOOR UNIT 208V-1Ø GROUND BAS INTEGRATION THROUGH COMMUNICATION LINK COMMUNICATION INTEGRATION GROUND SUPPLY FAN POWER LOAD DUST COLTR POWER LOAD (NOT USED) 2-4 OSA SUPPLY FAN IN-LINE 115V-1Ø MOTOR STATUS START/STOP GROUND 2-32-2 1-31-2 SF 1-1 2-1 SF SF SFSFSFSF 120V-1Ø FSD OPEN/CLOSE NOTES: 1. ALL ASSOCIATED FIRE/SMOKE DAMPERS SHALL OPEN WHENEVER A SIGNAL IS RECEIVED FROM THE TIMECLOCK/FAN RUN SIGNAL. 2. ALL ASSOCIATED FIRE/SMOKE DAMPERS SHALL CLOSE WHENEVER A SIGNAL FROM THE TIMECLOCK/FAN PROOF RUN SIGNAL IS REMOVED. 3. THE AC UNIT/FAN AND ALL ASSOCIATED FIRE/SMOKE DAMPERS SHALL SHUT DOWN WHENEVER: ·AN ALARM IS RECEIVED FROM THE AC UNIT/FAN SUPPLY AIR SMOKE DETECTOR. ·AN ALARM IS RECEIVED FROM ANY OF THE LOCAL SMOKE DETECTORS AT ANY OF THE FIRE/SMOKE DAMPERS. FSD 1 FIRE SMOKE DAMPER SEE PLANS FOR LOCATION 2-4 EF 2-1 EF EF 1-6 EF 1-3 EF 1-2 EF 1-4 EF 1-5 EF 1-8 -- EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By 2/ 5 / 2 0 2 1 3 : 1 2 : 1 2 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC7.02 POWER LOAD DIAGRAMS (CONT.) 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t N/A B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 0 09/11/20 ISSUED FOR CONSTRUCTION CD 016 12/09/20 CCD-016 DN 1 01/22/21 CITY PERMIT AMENDMENT CD EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By 2/ 5 / 2 0 2 1 3 : 1 2 : 1 6 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC7.03 SEQUENCE OF OPERATIONS 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t N/A A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 0 09/11/20 ISSUED FOR CONSTRUCTION CD 1 01/22/21 CITY PERMIT AMENDMENT CD CC 1 3 10 10 16 16 20 20 22 25 25 Z Y V S N K H E B 27 27 2 4 5 18 D F G AA X DD U Q C 8 8 13 13 19 19 21 21 17 17 11 11 P M 12 6 L R T W 24 26 23 23 14 14 7 9 J 23.5 15 15 CCCC 1 1 3 3 10 10 16 16 20 20 22 22 25 25 ZZ YY V V SS NN KK HH EE BB 27 27 2 2 4 4 5 5 18 18 DD FF GG AAAA XX DDDD UU QQ C 8 8 13 13 19 19 21 21 17 17 11 11 OFFICE 124A 4TH GRADE CLASSROOM 120 3RD GRADE CLASSROOM 118 SMALL GROUP 119A 4TH GRADE CLASSROOM 119 LOWER SCHOOL SCIENCE CLASSROOM 122 WORLD LANGUAGE CLASSROOM 121 CERAMICS 125A KILN 125B UPPER SCHOOL ART LAB 125 1ST GRADE CLASSROOM 112 SMALL GROUP 113 2ND GRADE CLASSROOM 115 1ST GRADE CLASSROOM 114 SMALL GROUP 115A TEACHING AREA 131B WORKROOM 131A ELEV. E-1-1 ELECT. 110 DATA 109 CONFERENCE ROOM 107 ASSOCIATES 134 PSYCH. 137A SMALL GROUP AREA 137 2ND GRADE CLASSROOM 116 SMALL GROUP 117A 3RD GRADE CLASSROOM 117 LANGUAGE ARTS SPECIALIST 137B CUSTODIAL 136 STAIR 1 STR1-1 ELECTRICAL 163 STAFF TOILET 145 UNISEX TOILET 142 STAIR 2 STR2-1 LOBBY 100 GIRLS' RESTROOM 140 BOYS' RESTROOM 139 GIRLS' RESTROOM 143 BOYS' RESTROOM 144 WORKROOM 106 FACILITIES DIR. 105 LOWER DIR. 102 TECHNOLOGY DIRECTOR 103 HEAD OF SCHOOL 104 HALLWAY 161 LIBRARY 131 TINKER AREA 133 STORY TELLING 132 MATH SPECIALIST 137C MAKER SPACE 123 LOWER SCHOOL ART LAB 126 OPEN OFFICE 159 HALLWAY 160 HALLWAY 162 ? ? FC B1-5 FC B1-6 FC B1-7 FC B1-8 FC B1-9 FC B1-10 FC A1-19 FC A1-17 FC A1-16 FC A1-13 FC A1-14 FCA1-15 FC B1-2 FC A1-1 FC A1-2 FC A1-4 FC A1-5 FC A1-7 FC A1-6 FC A1-8 FC A1-9FC A1-10 FC A1-11FC A1-12 FC B1-11 FC B1-12 FC B1-13 FC B1-14 FC B1-15 FC B1-16 FC B1-17 FC B1-18 FC A1-20 FC A1-21 FC D1-1 FC D1-2 FC D1-3 FC D1-4 FC D1-6 FC D1-7 FC D1-8 FC A1-18A FC A1-18B NURSE 101 TOILET 111A TOILET 108A WORK ROOM 108C STOR. 111B KINDERGARTEN 108 KINDERGARTEN 111 STOR. 108B ADMISSIONS DIR. 100ATOILET 101A TECH LAB 123A DESIGN CENTER 124 FC A1-3FC B1-4 FC B1-1FC B1-3 FC B1-19 FC D1-5 CC 1 4 10 15 18 22 25 27 Z 20 AA 2 635 2321 11 24 26 12 179 D G B C F H K M L N S P R T Q U XY W V DD 19 14 167 E 138 J BB 23.5 TOILET 100B STAFF TOILET 153 ELECT. 146 CUSTODIAN 151 UNISEX TOILET 152 ELEV. E-2-1 CORRIDOR 154 FIRE RISER 112A FC B1-20 PP MM 12 126 6 LL RR TT W W 24 24 26 26 23 2315 15 14 14 7 7 9 9 BBBB AA JJ T T T T T T T T T T TT T T T T T T TT T T T T T T T T T $ T T T T T T T T TTT T T T T TT T T T CO2 CO2 CO2 CO2 CO2CO2CO2CO2 CO2 CO2 CO2 CO2 CO2CO2 CO2 CO2 CO2 CO2 CO2 T FC D1-9 EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 N Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By A B 2/ 5 / 2 0 2 1 3 : 1 2 : 3 1 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC9.01 MECHANICAL LEVEL 01 HVAC ZONE PLAN 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t 1/16" = 1'-0" A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 1 01/22/21 CITY PERMIT AMENDMENT CD CC 1 3 10 10 16 16 20 20 22 25 25 Z Y V S N K H E B 27 27 2 4 5 18 D F G AA X DD U Q C 8 8 13 13 19 19 21 21 17 17 11 11 P M 12 6 L R T W 24 26 23 23 14 14 7 9 J 23.5 15 15 CCCC 1 1 3 3 10 10 16 16 20 20 22 22 25 25 ZZ YY V V SS NN KK HH EE BB 27 27 2 2 4 4 5 5 18 18 DD FF GG AAAA XX DDDD UU QQ C 8 8 13 13 19 19 21 21 17 17 11 11 UPPER SCHOOL SCIENCE LAB 230 PREP ROOM 229A UPPER SCHOOL SCIENCE LAB 229 WORKROOM 228 6TH -8TH CLASSROOM 226 6TH -8TH CLASSROOM 224 READING ROOM 231 STAIR 2 STR-2-2 6TH -8TH CLASSROOM 220 6TH -8TH CLASSROOM 216 6TH -8TH CLASSROOM 214 STAFF WORKROOM 208 SYSTEMS ADMIN. 209 UNASSIGNED 210 6TH -8TH CLASSROOM 219 6TH -8TH CLASSROOM 217 COLAB 218 COLAB 249 STORAGE 248 ELEV. E-1-2 CUSTODIAL 242 STAFF TOILET 244 UNISEX TOILET 247 DATA 240ELECT 241 STAIR 1 STR-1-2 COLAB 211A 5TH GRADE CLASSROOM 211 STAFF LOUNGE 207 UNASSIGNED 204 UPPER DIRECTOR 203DEVELOPMENT DIRECTOR 202 COMMUNICATIONS DIR. 201 5TH GRADE CLASSROOM 212 BOYS' RESTROOM 245 GIRLS' RESTROOM 246 HALLWAY 250 ROOF DECK 253 GIRLS' RESTROOM 238 BOYS' RESTROOM 237 6TH -8TH CLASSROOM 221 6TH -8TH CLASSROOM 223 6TH -8TH CLASSROOM 222 6TH -8TH CLASSROOM 215 6TH -8TH CLASSROOM 225 6TH -8TH CLASSROOM 227 6TH -8TH CLASSROOM 213 COLAB 254 ROOF DECK 254 OPEN OFFICE 252 HALLWAY 251 HALLWAY 255 FC A2-1 FC A2-2 FC A2-3 FC A2-4 FC A2-6 FC A2-7FC A2-8 FC A2-9 FC A2-10 FC A2-11 FC A2-12 FC A2-13 FC A2-14 FC A2-15 FC C2-10 FC C2-9 FC C2-8 FC C2-6 FC C2-7 FC C2-5 FC C2-4 FC C2-3 FC C2-2 FC C2-11 FC C2-12 FC C2-13 FC C2-14 FC C2-15 FC C2-16 FC C2-17 FC C2-18 FC C2-19 FC D2-1 FC D2-2 FC D2-3 FC D2-4 FC D2-5 FC D2-6 BUSINESS OFFICE 205 HUMAN RESOURCES DIR. 206 MOTHER'S ROOM 207A FC A2-5 CC 1 4 10 15 18 22 25 27 Z 20 AA 2 635 2321 11 24 26 12 179 D G B C F H K M L N S P R T Q U XY W V DD 19 14 167 E 138 J BB 23.5 ELECT 233 DATA 233B CUSTODIAL 235 ELEV. E-2-2 UNISEX TOILET 239 STAFF TOILET 236 FC C2-21 SS 1-2 PP MM 12 126 6 LL RR TT W W 24 24 26 26 23 2315 15 14 14 7 7 9 9 BBBB AA JJ SS 1-1 T T TT T TTT T T T T TT T T T T T T T T T T CO2CO2 CO2 CO2 CO2 CO2 CO2 T T T T T T T T T T T T T T T T T CO2 CO2 CO2 CO2 CO2 CO2 CO2 CO2 CO2 CO2 CO2 T ELEV. MACH. ROOM 234 FC C2-20 T EXP. 06/30/21 No.M33701 R EGISTER E D P R O FESSIONA L E N G I N EER S TATEOFCA L I F O R NIAMECHANICAL AS H L E Y M.DAVIT T THE PLANS AND SPECIFICATIONS HEREIN ARE ACCO ENGINEERED SYSTEMS, INC. ("ACCO"), OWNED BY AND FOR THE SOLE USE OF AND MAY NOT BE REPRODUCED OR USED BY OTHERS FOR ANY PURPOSE UNLESS AUTHORIZED BY ACCO IN WRITING. ACCO CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. 265 McCORMICK AVENUE COSTA MESA, CALIFORNIA 92626 (714) 352-2226 N Title Project Revisions Scale Drawn By Job Number Designed By No.Date of Sheets Project Manager Checked By Description By A B 2/ 5 / 2 0 2 1 3 : 1 2 : 4 6 P M P. ABERCROMBIE A. DAVITT P. ABERCROMBIE AC9.02 MECHANICAL LEVEL 02 HVAC ZONE PLAN 3443 PACIFIC VIEW DR. CORONA DEL MAR, CA 92625 HARBOR DAY SCHOOL R. REPP 652051 X:\ 6 5 2 0 5 1 & 6 4 1 1 7 1 _ H A R B O R D A Y S C H O O L \ 0 0 3 - E - H V A C \ R e v it ( C e n t r a l M o d e l ) / H D _ P 1 _ M _ M D L _ A C C O . r v t 1/16" = 1'-0" A 08/16/19 100% DESIGN DEVELOPMENT PKA B 10/25/19 1ST CITY SUBMITTAL PKA C 02/14/20 2ND CITY SUBMITTAL HH D 05/01/20 3RD CITY SUBMITTAL CD 1 01/22/21 CITY PERMIT AMENDMENT CD