Loading...
HomeMy WebLinkAboutX2021-2737 - Misc (2) 465 Borrego Court, Suite C San Dimas, CA 91773 Phone: (909) 305-4881 Lic # 837772 www.Inlandairbalance.com Test & Balance Report Project Name: Clearwater at Newport Beach Oppidan Investments Company Address: 101 Bayview Place, Newport Beach, CA 92660 Job Number: 2312-39 Technician: R. Watson, D. Ramirez Contractor: Christian Bros Date: 01/29/2024 WARRANTY INFORMATION: THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, AND BALANCING OF ENVIROMENTAL SYSTEMS. THE MEASURMENTS SHOWN, AND THE INFORMATION GIVEN, IN THIS REPORT ARE CERTIFIED TO BE ACCURATE AND COMPETE, AT THE TIME AND DATE INFORMATION WAS GATHERED. ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE TEST - ADJUST - BALANCE REPORT PROJECT SUMMARY. Model No.Serial No. CH-15D 2300106 PR-TH-1 2300126 PR-T-4-6 2300123 335 88303077 S-DP-250 2200158 S-DP-250 2200158 PR-TH-1 2300126 S-PVF-1 2200540C MT-200 B22933010P AK Free Area Factor HZ Hertz BHP Brake Horse Power LAT Leaving Air Temperature CD Ceiling Diffuser LSD Linear Slot Diffuser CFM Cubic Feet per Minute LWT Leaving Water Temperature CHWR Chilled Water Return MAT Mixed Air Temperature CHWS Chilled Water Supply N/A Not Accessible CSD Ceiling Supply Diffuser N/I Not Installed CSG Ceiling Supply Grille N/L Not Listed CWR Condensor Water Return N/S Not Shown CWS Condensor Water Supply NVL No Valid Location DA Direct Acting OSA Outside Air DNA Data Not Available R.A Reverse Acting DT Duct Traverse RA Return Air EA Exhaust Air RG Return Grill EAT Entering Air Temperature RPM Revolutions per Minute EG Exhaust Grill SA Supply Air ESP External Static Pressure SP Static Pressure EWT Entering Water Temperature SWG Sidewall Diffuser FFU Fan Filter Unit TBD To Be Determined FLA Full Load Amps TSP Total Static Pressure FPM Feet per Minute T-STAT Thermostat GF Grease Filter UTR Unable to Read HEPA High Efficiency Particulate Air V Volts HP Horse Power VAV Variable Air Volume HWR Hot Water Return VP Velocity Pressure HWS Hot Water Supply Abbreviation Index Instrumentation: 11/30/2024Air Temperature/Pressure/Velocity Evergreen Telem. Non-Contact Tachometer Tach Cal 3/6/2024 3/31/2024 4/4/2024 3/6/2024 9/7/2024 9/7/2024 3/31/2024 Evergreen Telem. Evergreen Telem. Fluke Evergreen Telem. Evergreen Telem. Evergreen Telem. Air Temperature W/ Probe Immersion Temperature W/ Probe Voltage-Amperage Meter Hydronic Pressure Hydronic Differential Pressure Humidity Instrument Manufacturer Calibration Due Balancing Hood Evergreen Telem.N/A Table Of ContentsPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Table Of Contents 1 Field Note Report Summary.....................................................................................................................................1 2 Fan Unit....................................................................................................................................................................2 2.1 EF-01..................................................................................................................................................................2 2.2 EF-02..................................................................................................................................................................3 2.3 EF-03..................................................................................................................................................................4 2.4 EF-04..................................................................................................................................................................5 2.5 EF-05..................................................................................................................................................................6 2.6 EF-06..................................................................................................................................................................7 2.7 EF-07..................................................................................................................................................................8 2.8 EF-08..................................................................................................................................................................10 2.9 EF-09..................................................................................................................................................................11 2.10 EF-10................................................................................................................................................................12 2.11 EF-11................................................................................................................................................................13 2.12 EF-12................................................................................................................................................................14 2.13 EF-13................................................................................................................................................................15 2.14 GEF-01.............................................................................................................................................................16 2.15 MAU-01(kitchen hoods)....................................................................................................................................18 2.16 MAU-01(kitchen hoods)/Kitchen Hood-01........................................................................................................19 2.17 MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-01..........................................................................................20 2.18 MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-02..........................................................................................22 2.19 RF-1-01............................................................................................................................................................24 2.20 RF-1-02............................................................................................................................................................25 2.21 RF-2-01............................................................................................................................................................25 2.22 RF-2-02............................................................................................................................................................26 2.23 RF-3-01............................................................................................................................................................27 2.24 RF-3-02............................................................................................................................................................29 3 Fan Coil....................................................................................................................................................................31 3.1 AC-1-01..............................................................................................................................................................31 3.2 AC-1-02..............................................................................................................................................................31 3.3 AC-2-01..............................................................................................................................................................32 3.4 AC-2-02..............................................................................................................................................................32 3.5 AC-2-03..............................................................................................................................................................33 3.6 AC-3-01..............................................................................................................................................................33 3.7 AC-3-02..............................................................................................................................................................34 3.8 AC-3-03..............................................................................................................................................................34 3.9 AC-B-01..............................................................................................................................................................35 3.10 AC-B-02............................................................................................................................................................35 3.11 AC-B-03............................................................................................................................................................36 3.12 AC-B-04............................................................................................................................................................36 3.13 AC-B-06............................................................................................................................................................37 3.14 AC-B-07............................................................................................................................................................38 Inland Air Balance, Inc. Table Of ContentsPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones 3.15 FCU-1-01..........................................................................................................................................................39 3.16 FCU-1-02..........................................................................................................................................................41 3.17 FCU-1-03..........................................................................................................................................................43 3.18 FCU-1-04..........................................................................................................................................................45 3.19 FCU-1-05..........................................................................................................................................................47 3.20 FCU-1-06..........................................................................................................................................................49 3.21 FCU-1-07..........................................................................................................................................................51 3.22 FCU-1-08..........................................................................................................................................................53 3.23 FCU-1-09A.......................................................................................................................................................55 3.24 FCU-1-09B.......................................................................................................................................................57 3.25 FCU-1-10..........................................................................................................................................................59 3.26 FCU-1-11..........................................................................................................................................................61 3.27 FCU-1-12..........................................................................................................................................................63 3.28 FCU-1-13..........................................................................................................................................................65 3.29 FCU-1-14..........................................................................................................................................................67 3.30 FCU-2-01..........................................................................................................................................................69 3.31 FCU-2-02..........................................................................................................................................................71 3.32 FCU-2-03..........................................................................................................................................................73 3.33 FCU-2-04..........................................................................................................................................................75 3.34 FCU-2-05..........................................................................................................................................................77 3.35 FCU-2-6............................................................................................................................................................79 3.36 FCU-2-7............................................................................................................................................................81 3.37 FCU-3-1............................................................................................................................................................83 3.38 FCU-3-2............................................................................................................................................................85 3.39 FCU-3-3............................................................................................................................................................88 3.40 FCU-3-4............................................................................................................................................................90 3.41 FCU-B-01.........................................................................................................................................................92 3.42 FCU-B-02A.......................................................................................................................................................94 3.43 FCU-B-02B.......................................................................................................................................................96 3.44 FCU-B-03.........................................................................................................................................................98 3.45 FCU-B-04.........................................................................................................................................................100 3.46 FCU-B-05.........................................................................................................................................................102 3.47 FCU-B-08.........................................................................................................................................................104 3.48 FCU-B-09.........................................................................................................................................................106 4 Clearwater Coded Drawing 1st Flr Area A.pdf.........................................................................................................108 5 Clearwater Coded Drawing 1st Flr Area B.pdf.........................................................................................................109 6 Clearwater Coded Drawing 1st Flr Area C.pdf.........................................................................................................110 7 Clearwater Coded Drawing 1st Flr Area D.pdf.........................................................................................................111 8 Clearwater Coded Drawing 2nd Flr Area A.pdf........................................................................................................112 9 Clearwater Coded Drawing 2nd Flr Area B.pdf........................................................................................................113 10 Clearwater Coded Drawing 2nd Flr Area C.pdf......................................................................................................114 11 Clearwater Coded Drawing 2nd Flr Area D.pdf......................................................................................................115 Inland Air Balance, Inc. Table Of ContentsPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones 12 Clearwater Coded Drawing 3rd Flr Area A.pdf.......................................................................................................116 13 Clearwater Coded Drawing 3rd Flr Area B.pdf.......................................................................................................117 14 Clearwater Coded Drawing 3rd Flr Area C.pdf.......................................................................................................118 15 Clearwater Coded Drawing 3rd Flr Area D.pdf.......................................................................................................119 16 Clearwater Coded Drawing Basement Area B.pdf.................................................................................................120 17 Clearwater Coded Drawing Basement Area C.pdf.................................................................................................121 18 Clearwater Coded Drawing Basement Area D.pdf.................................................................................................122 19 Instrument Certifications.pdf..................................................................................................................................123 Inland Air Balance, Inc. Page 1 of 129 Field Note Report SummaryPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Test System / Unit Name Date Contact Notes / Logs Fan Unit EF-01 29-Dec-23 David Ramirez Self contained fan. Fan Unit EF-06 29-Jan-24 Robert Watson Self contained fan Fan Unit EF-09 3-Jan-24 Robert Watson Self contained fan Fan Unit EF-12 28-Dec-23 David Ramirez Self-contained fan. Fan Unit RF-1-02 4-Jan-24 Robert Watson Self-contained fan Fan Unit RF-2-01 29-Jan-24 Robert Watson Self contained fan Fan Unit RF-2-02 21-Dec-23 David Ramirez Self-contained Relief Fan Unit. Fan Coil AC-B-06 29-Dec-23 David Ramirez Schedule change. FCU is now a 2 ton wall-split Fan Coil AC-B-07 29-Dec-23 David Ramirez Schedule change. FCU is now a wall-split. Fan Coil FCU-1-01 21-Dec-23 David Ramirez RA+OSA does not equate to SA volume. Return Inlet 01, in corridor 104, was set to make up the difference in air volume. Fan Coil FCU-1-09A 27-Dec-23 David Ramirez Right RA volume damper shaft is disconnected from handle. Fan Coil FCU-3-2 29-Jan-24 Robert Watson OSA Increased to make up for OSA not being installed on FC 3–3. All fan coils on third-floor serve common Corredor. Fan Coil FCU-3-3 19-Jan-24 Robert Watson No OSA run to unit. OSA increased on 3 other fan coil serving common Corridor as FC 3–3. Fan Coil FCU-3-4 29-Jan-24 Robert Watson OSA increased to make up for OSA not being installed on FC 3–3. All fan coils on third-floor serve common Corredor. Fan Coil FCU-B-05 28-Dec-23 David Ramirez CFM value was not specified for Office B07. Supply Air was set to an approximation determined by room square footage. Fan Coil FCU-B-09 28-Dec-23 David Ramirez FCU installed is a ducted fancoil unit. Air values are not specified for three diffusers. Unit was set for total. Supply Outlet FCU-2-03/Outlet-02 21-Dec-23 David Ramirez Fire/Smoke Damper does not have power landed. Mechanical and Electrical contractors have been made aware. FSD was manually opened, FCU was balanced. Outside Air Intake FCU-3-1/OS-01 29-Jan-24 Robert Watson OSA increased to make up for OSA not being installed on FC 3–3. All fan coils on third floor Serve common corridor. Outside Air Intake FCU-3-3/OS-01 19-Jan-24 Robert Watson No outside air duct run to unit K-EF MAU-01(kitchen hoods)/Kitchen Hood-01/K- EF-02 3-Jan-24 Robert Watson Dishwasher fan does not run through ACCRUEX panel. Tested Fan with Vfd in hand Inland Air Balance, Inc. Page 2 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/29/2023 SYSTEM/UNIT: EF-01 AREA: Staff Break Log:EF-01 12/29/2023 David Ramirez Self contained fan. Unit Data Unit Manufacturer Pennbarry Unit Model Number Z12GP Unit Serial Number E23IZ89062 Test Data Motor Operating HZ/Speed 60 HZ/Speed 33 Motor Volts T1-T2 204 Volts Motor Amps T1 1.00 Amps Motor Data Thermally Protected?Yes Nameplate Motor Manufacturer Genteq Nameplate Motor Frame Direct Drive Nameplate Motor HP 1/2 HP Nameplate Motor Rated Volts 208 Volts Nameplate Motor RPM 1355 RPM Nameplate Motor FL Amps 8.10 Amps Nameplate Motor Phase 1 Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Sheave Data Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP 1.00 in. wc Actual Total SP NA in. wc Design External SP NS in. wc Actual External SP NA in. wc Actual Suction SP NVL in. wc Actual Discharge SP NVL in. wc Test Results Design Airflow 85 CFM Actual Airflow 90 CFM Design Fan RPM 1355 RPM Actual Fan RPM NVL RPM Actual Motor RPM NVL Inland Air Balance, Inc. Page 3 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/29/2024 SYSTEM/UNIT: EF-02 AREA: Women Unit Data Unit Manufacturer Pennbarry Unit Model Number Z12GP Unit Serial Number D23EZ30794 Test Data Motor Operating HZ/Speed 60 HZ/Speed 44 Motor Volts T1-T2 204 Volts Motor Amps T1 1.00 Amps Motor Data Thermally Protected?Yes Nameplate Motor Manufacturer Genteq Nameplate Motor Frame Direct Drive Nameplate Motor HP 1/2 HP Nameplate Motor Rated Volts 208 Volts Nameplate Motor RPM 1355 RPM Nameplate Motor FL Amps 8.10 Amps Nameplate Motor Phase 1 Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Sheave Data Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP 1.00 in. wc Actual Total SP NA in. wc Design External SP NS in. wc Actual External SP NA in. wc Actual Suction SP NVL in. wc Actual Discharge SP NVL in. wc Test Results Design Airflow 210 CFM Actual Airflow 237 CFM Design Fan RPM 1355 RPM Actual Fan RPM NVL RPM Actual Motor RPM NVL System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Men’s EG 22x12 1.00 *215 237 110 Totals:----215 0 237 110 - EF-02 Exhaust Inlet Summary Inland Air Balance, Inc. Page 4 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/10/2024 SYSTEM/UNIT: EF-03 AREA: Men Unit Data Unit Manufacturer Pennbarry Unit Model Number Z12GP Unit Serial Number D23EZ03799 Test Data Motor Operating HZ/Speed 60 HZ/Speed 24 Motor Volts T1-T2 204 Volts Motor Amps T1 3.00 Amps Motor Data Thermally Protected?Yes Nameplate Motor Manufacturer Genteq Nameplate Motor Frame Direct Drive Nameplate Motor HP 1/2 HP Nameplate Motor Rated Volts 208 Volts Nameplate Motor RPM 1355 RPM Nameplate Motor FL Amps 8.10 Amps Nameplate Motor Phase 1 Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Sheave Data Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP 0.50 in. wc Actual Total SP NA in. wc Design External SP NS in. wc Actual External SP NA in. wc Actual Suction SP NVL in. wc Actual Discharge SP NVL in. wc Test Results Design Airflow 210 CFM Actual Airflow 213 CFM Design Fan RPM 1355 RPM Actual Fan RPM NVL RPM Actual Motor RPM NVL System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Mens EG 22x12 1.00 *210 213 101 Totals:----210 0 213 101 - EF-03 Exhaust Inlet Summary Inland Air Balance, Inc. Page 5 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/29/2024 SYSTEM/UNIT: EF-04 AREA: Salon/Spa B04 Unit Data Unit Manufacturer Pennbarry Unit Model Number Z12GP Unit Serial Number D23EZ037 Test Data Motor Operating HZ/Speed 33HZ/Speed Motor Volts T1-T2 204 Volts Motor Amps T1 4.00 Amps Motor Data Thermally Protected?Yes Nameplate Motor Manufacturer Genteq Nameplate Motor Frame Direct Drive Nameplate Motor HP 1/2 HP Nameplate Motor Rated Volts 208 Volts Nameplate Motor RPM 1355 RPM Nameplate Motor FL Amps 8.10 Amps Nameplate Motor Phase 1 Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Sheave Data Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP 0.50 in. wc Actual Total SP NA in. wc Design External SP NS in. wc Actual External SP NA in. wc Actual Suction SP NVL in. wc Actual Discharge SP NVL in. wc Test Results Design Airflow 400 CFM Actual Airflow 403 CFM Design Fan RPM NS RPM Actual Fan RPM NVL RPM Actual Motor RPM NVL System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Manicure EG 22x12 1.00 *400 403 101 Totals:----400 0 403 101 - EF-04 Exhaust Inlet Summary Inland Air Balance, Inc. Page 6 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/29/2023 SYSTEM/UNIT: EF-05 AREA: Laundry 147 Unit Data Unit Manufacturer Pennbarry Unit Model Number SX115VCGP Unit Serial Number D23EZ59636 Test Data Motor Operating HZ/Speed 60 Motor Volts T1-T2 205 Volts Motor Amps T1 1.30 Amps Motor Data Nameplate Motor Manufacturer No Access Nameplate Motor Frame Direct Drive Nameplate Motor HP 1/6 HP Nameplate Motor Rated Volts 208 Volts Nameplate Motor RPM 1050 RPM Nameplate Motor FL Amps Not Listed Amps Nameplate Motor Phase 1 Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Sheave Data Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP 1.00 in. wc Actual Total SP 0.60 in. wc Design External SP NS in. wc Actual External SP NA in. wc Actual Suction SP -0.56 in. wc Actual Discharge SP 0.04 in. wc Test Results Design Airflow 450 CFM Actual Airflow 475 CFM Design Fan RPM 1042 RPM Actual Fan RPM NVL RPM Actual Motor RPM NVL System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Laundry B20 EG 2412 1.00 450 475 106 Totals:----450 0 475 106 - EF-05 Exhaust Inlet Summary Inland Air Balance, Inc. Page 7 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/29/2024 SYSTEM/UNIT: EF-06 AREA: Corridor Log:EF-06 1/29/2024 Robert Watson Self contained fan Motor Data Nameplate Motor Hertz 60 Hz Nominal Efficiency (0.00)0.90 % Motor Power Factor (0.00)0.80 Test Results Design Airflow 470 CFM Actual Airflow 513 CFM System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Men 112 EG 2410 1.00 *230 252 110 Inlet-02 Women 113 EG 2410 1.00 *240 261 109 Totals:----470 0 513 109 - EF-06 Exhaust Inlet Summary Inland Air Balance, Inc. Page 8 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/4/2024 SYSTEM/UNIT: EF-07 AREA: Roof Unit Data Unit Manufacturer Penn Ventilator Unit Model Number FX 16 Unit Serial Number E23HZ02926 Test Data Motor Operating HZ/Speed 6 Motor Volts T1-T2 119 Volts Motor Amps T1 2.00 Amps Motor Data Nameplate Motor Manufacturer McMillan Nameplate Motor Frame Not Listed Nameplate Motor HP 243 watt Nameplate Motor Rated Volts 120 Volts Nameplate Motor RPM Ns RPM Nameplate Motor FL Amps 5.20 Amps Nameplate Motor Phase 1 Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Brake Horsepower 0.23 BHP Nominal Efficiency (0.00)0.90 % Motor Power Factor (0.00)0.80 Sheave Data Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP NVL in. wc Actual Suction SP NVL in. wc Actual Discharge SP NVL in. wc Test Results Design Airflow 360 CFM Actual Airflow 394 CFM Design Fan RPM NS RPM Actual Fan RPM NVL RPM Actual Motor RPM NVL Inland Air Balance, Inc. Page 9 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/4/2024 SYSTEM/UNIT: EF-07 AREA: Roof Unit Manufacturer Photo: Name:Unit Manufacturer.jpg Captured:1/2/2024 10:34 AM Caption: System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Laundry 250 EG 2408 1.00 *125 136 109 Inlet-02 Laundry 244 EG 2408 1.00 *110 121 110 Inlet-03 Laundry 147 EG 2408 1.00 *125 137 110 Totals:----360 0 394 109 - EF-07 Exhaust Inlet Summary Inland Air Balance, Inc. Page 10 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/4/2024 SYSTEM/UNIT: EF-08 AREA: Roof Unit Data Unit Manufacturer Penn Ventilator Unit Model Number FX 16 Unit Serial Number E23HZ02926 Test Data Motor Operating HZ/Speed 6 Motor Volts T1-T2 209 Volts Motor Amps T1 1.00 Amps Motor Data Nameplate Motor Manufacturer Mc millan Nameplate Motor Frame Not Listed Nameplate Motor HP 243 watt Nameplate Motor Rated Volts 208 Volts Nameplate Motor RPM Ns RPM Nameplate Motor FL Amps 3.20 Amps Nameplate Motor Phase 1 Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Brake Horsepower 0.20 BHP Nominal Efficiency (0.00)0.90 % Motor Power Factor (0.00)0.80 Sheave Data Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP NVL in. wc Actual Suction SP NVL in. wc Actual Discharge SP NVL in. wc Test Results Design Airflow 250 CFM Actual Airflow 271 CFM Design Fan RPM NS RPM Actual Fan RPM NVL RPM Actual Motor RPM NVL Inland Air Balance, Inc. Page 11 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/4/2024 SYSTEM/UNIT: EF-08 AREA: Roof Unit Manufacturer Photo: Name:Unit Manufacturer.jpg Captured:1/2/2024 10:42 AM Caption: System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Laundry 312 EG 2408 1.00 *125 136 109 Inlet-02 Beauty Salon 218 EG 48x3 1.00 *125 135 108 Totals:----250 0 271 108 - EF-08 Exhaust Inlet Summary Tested By:Robert Watson Date:1/3/2024 SYSTEM/UNIT: EF-09 AREA: Kitchen Log:EF-09 1/3/2024 Robert Watson Self contained fan System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Kitchen/Servery 239 EG 2408 1.00 195 208 107 Totals:----195 0 208 107 - EF-09 Exhaust Inlet Summary Inland Air Balance, Inc. Page 12 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/21/2023 SYSTEM/UNIT: EF-10 AREA: HSKP Unit Data Unit Manufacturer Pennbarry Unit Model Number Z12GP Unit Serial Number D23EZ3084 Test Data Motor Operating HZ/Speed Speed 60 Motor Volts T1-T2 213 Volts Motor Amps T1 2.30 Amps Motor Data Thermally Protected?Yes Nameplate Motor Manufacturer Genteq Nameplate Motor Frame Direct Drive Nameplate Motor HP 1/2 HP Nameplate Motor Rated Volts 208 Volts Nameplate Motor RPM 1355 RPM Nameplate Motor FL Amps 8.10 Amps Nameplate Motor Phase 1 Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Sheave Data Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP 0.50 in. wc Actual Total SP 0.08 in. wc Design External SP NS in. wc Actual External SP NA in. wc Actual Suction SP NVL in. wc Actual Discharge SP 0.08 in. wc Test Results Design Airflow 75 CFM Actual Airflow 80 CFM Design Fan RPM 1355 RPM Actual Fan RPM NVL RPM Actual Motor RPM NVL System/Unit Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 EG 22x12 1.00 *75 80 107 Totals:----75 0 80 107 - EF-10 Exhaust Inlet Summary Inland Air Balance, Inc. Page 13 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/28/2023 SYSTEM/UNIT: EF-11 AREA: RR Unit Data Unit Manufacturer Pennbarry Unit Model Number Z10GP Unit Serial Number D23EZ30808 Test Data Motor Operating HZ/Speed Speed 35 Motor Volts T1-T2 118 Volts Motor Amps T1 1.50 Amps Motor Data Thermally Protected?Yes Nameplate Motor Manufacturer Genteq Nameplate Motor Frame Direct Drive Nameplate Motor HP 1/4 HP Nameplate Motor Rated Volts 115 Volts Nameplate Motor RPM 400-1800 RPM Nameplate Motor FL Amps 3.50 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Sheave Data Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP 0.75 in. wc Actual Total SP NA in. wc Design External SP NS in. wc Actual External SP NA in. wc Actual Suction SP NVL in. wc Actual Discharge SP NVL in. wc Test Results Design Airflow 115 CFM Actual Airflow 120 CFM Design Fan RPM 400-1800 RPM Actual Fan RPM NVL RPM System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 RR 152 EG 15 1/2x11 1/2 1.00 *115 120 104 Totals:----115 0 120 104 - EF-11 Exhaust Inlet Summary Inland Air Balance, Inc. Page 14 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/28/2023 SYSTEM/UNIT: EF-12 AREA: HSKP Log:EF-12 12/28/2023 David Ramirez Self-contained fan. Unit Data Unit Manufacturer Pennbarry Unit Model Number Z12GP Unit Serial Number Not Listed Test Data Motor Operating HZ/Speed Speed 44 Motor Volts T1-T2 NVL Volts Motor Amps T1 NVL Amps Motor Data Thermally Protected?Yes Nameplate Motor Manufacturer Genteq Nameplate Motor Frame Direct Drive Nameplate Motor HP 1/2 HP Nameplate Motor Rated Volts 115 Volts Nameplate Motor RPM 1355 RPM Nameplate Motor FL Amps 8.10 Amps Nameplate Motor Phase 1 Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Sheave Data Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP 0.50 in. wc Actual Total SP NA in. wc Design External SP NS in. wc Actual External SP NA in. wc Actual Suction SP NVL in. wc Actual Discharge SP NVL in. wc Test Results Design Airflow 70 CFM Actual Airflow 73 CFM Design Fan RPM 1355 RPM Actual Fan RPM NVL RPM Actual Motor RPM NVL System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 HSKP 107 EG 24x12 1.00 70 73 104 Totals:----70 0 73 104 - EF-12 Exhaust Inlet Summary Inland Air Balance, Inc. Page 15 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/21/2023 SYSTEM/UNIT: EF-13 AREA: Unisex Unit Data Unit Manufacturer Pennbarry Unit Model Number Z10GP Unit Serial Number D23EZ30810 Test Data Motor Operating HZ/Speed Speed 34 Motor Volts T1-T2 NVL Volts Motor Amps T1 NVL Amps Motor Data Thermally Protected?Yes Nameplate Motor Manufacturer Genteq Nameplate Motor Frame Direct Drive Nameplate Motor HP 1/4 HP Nameplate Motor Rated Volts 115/230 Volts Nameplate Motor RPM 1500 RPM Nameplate Motor FL Amps 2.30 Amps Nameplate Motor Phase 1 Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Sheave Data Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP 0.75 in. wc Actual Total SP NA in. wc Design External SP NS in. wc Actual External SP NA in. wc Actual Suction SP NVL in. wc Actual Discharge SP NVL in. wc Test Results Design Airflow 90 CFM Actual Airflow 91 CFM Design Fan RPM 1580 RPM Actual Fan RPM NVL RPM Actual Motor RPM NVL System/Unit Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 EG 22x12 1.00 *90 91 101 Totals:----90 0 91 101 - EF-13 Exhaust Inlet Summary Inland Air Balance, Inc. Page 16 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/29/2023 SYSTEM/UNIT: GEF-01 AREA: Garage Unit Data Unit Manufacturer Pennbarry Unit Model Number MXI-201A9 Unit Serial Number Not Listed Test Data Motor Operating HZ/Speed 58 Motor Volts T1-T2 273 Volts Motor Volts T2-T3 274 Volts Motor Volts T1-T3 272 Volts Motor Amps T1 25.00 Amps Motor Amps T2 26.00 Amps Motor Amps T3 24.00 Amps Motor Data Nameplate Motor Manufacturer Weg Nameplate Motor Frame 254/6T Nameplate Motor HP 15 HP Nameplate Motor Rated Volts 230/460 Volts Nameplate Motor RPM 1770 RPM Nameplate Motor FL Amps 36.40 Amps Nameplate Motor Phase 3 Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.15 Brake Horsepower 11.95 BHP Nominal Efficiency (0.00)0.92 % Motor Power Factor (0.00)0.82 Sheave Data Sheave Position Fixed Number of Belts 3 Belt Size 5VX750 Sheave Center Line Distance No Access in. Sheave Data Motor Fan Sheave Diameter 3B5V42 in.No Access in. Sheave Bore 1 5/8 in.No Access in. Test Pressures Design Total SP 2.00 in. wc Actual Total SP 1.42 in. wc Design External SP NS in. wc Actual External SP NA in. wc Actual Suction SP -0.70 in. wc Actual Discharge SP -0.72 in. wc Test Results Design Airflow 17000 CFM Actual Airflow 17003 CFM Design Fan RPM 2077 RPM Actual Fan RPM NVL RPM Actual Motor RPM 1711 Inland Air Balance, Inc. Page 17 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Garage B30 EG 46x20 6.39 1077 3400 3677 108 Inlet-02 Garage B30 EG 46x20 6.39 624 3400 3546 104 Inlet-03 Garage B30 EG 46x20 6.39 408 3400 3479 102 Inlet-04 Garage B30 EG 46x20 6.39 293 3400 3176 93 Inlet-05 Garage B30 EG 46x20 6.39 232 3400 3125 92 Totals:----17000 0 17003 100 - GEF-01 Exhaust Inlet Summary Inland Air Balance, Inc. Page 18 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/2/2024 SYSTEM/UNIT: MAU-01(kitchen hoods) AREA: Kitchen Unit Data Unit Manufacturer Captiveaire Unit Model Number A2-20D Unit Serial Number Not Listed Test Data Motor Operating HZ/Speed 60 Motor Volts T1-T2 233 Volts Motor Volts T2-T3 230 Volts Motor Volts T1-T3 233 Volts Motor Amps T1 11.00 Amps Motor Amps T2 11.00 Amps Motor Amps T3 11.00 Amps Motor Data Nameplate Motor Manufacturer NA Nameplate Motor Frame NA Nameplate Motor HP 5 HP Nameplate Motor Rated Volts 230 Volts Nameplate Motor RPM Not Listed RPM Nameplate Motor FL Amps 14.50 Amps Nameplate Motor Phase 3 Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Brake Horsepower 4.27 BHP Nominal Efficiency (0.00)0.90 % Motor Power Factor (0.00)0.80 Sheave Data Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP 1.00 in. wc Actual Total SP 0.91 in. wc Actual Suction SP -0.40 in. wc Actual Discharge SP 0.51 in. wc Test Results Design Airflow 4600 CFM Actual Airflow 4596 CFM Design Fan RPM NS RPM Actual Fan RPM NVL RPM Actual Motor RPM NVL System/Unit Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 D.O.120x18 12.75 159 2049 2027 99 Outlet-02 D.O.126x18 13.39 138 1950 1848 95 Outlet-03 CD 2414 1.00 *800 721 90 Totals:----4799 0 4596 96 MAU-01(kitchen hoods) Supply Outlet Summary Inland Air Balance, Inc. Page 19 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/2/2024 SYSTEM/UNIT: MAU-01(kitchen hoods)/Kitchen Hood-01 Unit Data Hood Manufacturer ACCUREX Hood Model Number XXEW Exhaust Section AVG Velocity - Filter 1 140.0 FPM AVG Velocity - Filter 2 156.0 FPM AVG Velocity - Filter 3 165.0 FPM AVG Velocity - Filter 4 144.0 FPM AVG Velocity - Filter 5 141.0 FPM AVG Velocity - Filter 6 155.0 FPM AVG Velocity - Filter 7 128.0 FPM AVG Velocity - Filter 8 131.0 FPM AVG Velocity - Filter 9 166.0 FPM AVG Velocity - Filter 10 122.0 FPM AVG Velocity - Filter 11 128.0 FPM AVG Velocity - Filter 12 117.0 FPM Exhaust Readings Filter 1 - Airflow 420 CFM Filter 2 - Airflow 468 CFM Filter 3 - Airflow 495 CFM Filter 4 - Airflow 432 CFM Filter 5 - Airflow 423 CFM Filter 6 - Airflow 465 CFM Filter 7 - Airflow 384 CFM Filter 8 - Airflow 393 CFM Filter 9 - Airflow 374 CFM Filter 10 - Airflow 366 CFM Filter 11 - Airflow 288 CFM Filter 12 - Airflow 351 CFM Final Data Design Exhaust Airflow 4750 CFM Duct Size 36x10 in Hood Duct Connection Area 2.5 Riser Velocity 1944 FPM Actual Exhaust Airflow 4859 CFM Design Airflow vs. Actual Airflow 102.3 % HZ Setting @ Actual Airflow 60.00 Hz Filter Data Filter Manufacturer Greenheck Filter Type Grease Size - Filter 1 20x20 Size - Filter 2 20x20 Size - Filter 3 20x20 Size - Filter 4 20x20 Size - Filter 5 20x20 Size - Filter 6 20x20 Size - Filter 7 20x20 Size - Filter 8 20x20 Size - Filter 9 16x20 Size - Filter 10 20x20 Size - Filter 11 16x20 Size - Filter 12 20x20 Filter Area - Filter 1 3.00 Filter Area - Filter 2 3.00 Filter Area - Filter 3 3.00 Filter Area - Filter 4 3.00 Filter Area - Filter 5 3.00 Filter Area - Filter 6 3.00 Filter Area - Filter 7 3.00 Filter Area - Filter 8 3.00 Filter Area - Filter 9 2.25 Filter Area - Filter 10 3.00 Filter Area - Filter 11 2.25 Filter Area - Filter 12 3.00 Inland Air Balance, Inc. Page 20 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/2/2024 SYSTEM/UNIT: MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-01 AREA: Kitchen Unit Data Fan Manufacturer Captive Aire Fan Model Number USB124DD Fan Serial Number Not listed Linear Feet of Hood 20 ft Test Data Actual AirFlow 4859 CFM Design AirFlow 4750 CFM MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-01/EF Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60 Hz Motor Volts T1-T2 210 Volts Motor Volts T2-T3 210 Volts Motor Volts T1-T3 209 Volts Motor Amps T1 11.00 Amps Motor Amps T2 11.00 Amps Motor Amps T3 11.00 Amps Motor Data MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-01/EF Fan Nameplate Motor Manufacturer Teco Nameplate Motor Frame 143T Nameplate Motor FL Amps 15.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.15 Brake Horsepower 3.86 BHP Nominal Efficiency (0.00)0.90 % Motor Power Factor (0.00)0.80 Motor Data MAU-01(kitchen hoods)/Kitchen Hood-01/K- EF-01/EF Fan Design Nameplate Motor HP 5 HP Motor Voltage 208-230/460 Volts Motor RPM Not Legible RPM Motor Phase 3 Sheave Data MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-01/EF Fan Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Na in. Sheave Data MAU-01(kitchen hoods)/Kitchen Hood-01/K- EF-01/EF Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Inland Air Balance, Inc. Page 21 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/2/2024 SYSTEM/UNIT: MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-01 AREA: Kitchen Fan Manufacturer Photo: Name:Fan Manufacturer.jpg Captured:1/2/2024 11:20 AM Caption: Inland Air Balance, Inc. Page 22 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/2/2024 SYSTEM/UNIT: MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-02 AREA: Kitchen Unit Data Fan Manufacturer Captive Aire Fan Model Number USBI15DD Fan Serial Number Not listed Linear Feet of Hood 7 ft Test Data Actual AirFlow 1419 CFM Design AirFlow 1400 CFM MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-02/EF Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60 Hz Motor Volts T1-T2 209 Volts Motor Volts T2-T3 209 Volts Motor Volts T1-T3 210 Volts Motor Amps T1 3.20 Amps Motor Amps T2 3.20 Amps Motor Amps T3 3.20 Amps Motor Data MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-02/EF Fan Nameplate Motor Manufacturer Teco Nameplate Motor Frame 143T Nameplate Motor FL Amps 3.20 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.15 Brake Horsepower 1.12 BHP Nominal Efficiency (0.00)0.90 % Motor Power Factor (0.00)0.80 Motor Data MAU-01(kitchen hoods)/Kitchen Hood-01/K- EF-02/EF Fan Design Nameplate Motor HP 5 HP Motor Voltage 208-230/460 Volts Motor RPM Not Legible RPM Motor Phase 3 Sheave Data MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-02/EF Fan Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Na in. Sheave Data MAU-01(kitchen hoods)/Kitchen Hood-01/K- EF-02/EF Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Inland Air Balance, Inc. Page 23 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/2/2024 SYSTEM/UNIT: MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-02 AREA: Kitchen Log:MAU-01(kitchen hoods)/Kitchen Hood- 01/K-EF-02 1/3/2024 Robert Watson Dishwasher fan does not run through ACCRUEX panel. Tested Fan with Vfd in hand Fan Manufacturer Photo: Name:Fan Manufacturer.jpg Captured:1/2/2024 11:21 AM Caption: System/Unit Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 D.O.14x12 1.17 1213 1400 1419 101 Totals:----1400 0 1419 101 - MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-02 Exhaust Inlet Summary Inland Air Balance, Inc. Page 24 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/29/2024 SYSTEM/UNIT: RF-1-01 AREA: Corridor Unit Data Unit Manufacturer Pennbarry Unit Model Number Z12GP Unit Serial Number D23EZ30791 Test Data Motor Operating HZ/Speed 42 Motor Volts T1-T2 116 Volts Motor Amps T1 4.00 Amps Motor Data Thermally Protected?Yes Nameplate Motor Manufacturer Genteq Nameplate Motor Frame Direct Drive Nameplate Motor HP 1/2 HP Nameplate Motor Rated Volts 115 Volts Nameplate Motor RPM 1355 RPM Nameplate Motor FL Amps 8.10 Amps Nameplate Motor Phase 1 Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Sheave Data Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP 0.50 in. wc Actual Total SP 0.23 in. wc Actual Suction SP 0.13 in. wc Actual Discharge SP 0.10 in. wc Test Results Design Airflow 595 CFM Actual Airflow 540 CFM Design Fan RPM 1355 RPM Actual Fan RPM NVL RPM System/Unit Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 RG 22x12 1.00 *595 540 91 Totals:----595 0 540 91 - RF-1-01 Return Inlet Summary Inland Air Balance, Inc. Page 25 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/4/2024 SYSTEM/UNIT: RF-1-02 AREA: Patio Log:RF-1-02 1/4/2024 Robert Watson Self-contained fan System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Fire Side Patio 108 EG 10x10 1.00 *200 220 110 Inlet-02 Fire Side Patio 108 EG 10x10 1.00 *200 219 110 Totals:----400 0 439 110 - RF-1-02 Exhaust Inlet Summary Tested By:Robert Watson Date:1/29/2024 SYSTEM/UNIT: RF-2-01 AREA: Corridor Log:RF-2-01 1/29/2024 Robert Watson Self contained fan Motor Data Nameplate Motor Hertz 60 Hz Nominal Efficiency (0.00)0.90 % Motor Power Factor (0.00)0.80 Test Results Design Airflow 100 CFM Actual Airflow 110 CFM System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Living 238 EG 12x10 1.00 *100 110 110 Totals:----100 0 110 110 - RF-2-01 Exhaust Inlet Summary Inland Air Balance, Inc. Page 26 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/21/2023 SYSTEM/UNIT: RF-2-02 AREA: Corridor Log:RF-2-02 12/21/2023 David Ramirez Self-contained Relief Fan Unit. Unit Data Unit Manufacturer Pennbarry Unit Model Number Z12GP Unit Serial Number D23EZ30793 Test Data Motor Operating HZ/Speed Speed 60 Motor Volts T1-T2 122 Volts Motor Amps T1 6.30 Amps Motor Data Thermally Protected?Yes Nameplate Motor Manufacturer Genteq Nameplate Motor Frame Direct Drive Nameplate Motor HP 1/2 HP Nameplate Motor Rated Volts 115 Volts Nameplate Motor RPM 1355 RPM Nameplate Motor FL Amps 8.10 Amps Nameplate Motor Phase 1 Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Sheave Data Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP 0.50 in. wc Actual Total SP 0.08 in. wc Design External SP NS in. wc Actual External SP NA in. wc Actual Suction SP NVL in. wc Actual Discharge SP 0.08 in. wc Test Results Design Airflow 780 CFM Actual Airflow 710 CFM Design Fan RPM 1355 RPM Actual Fan RPM NVL RPM Actual Motor RPM NVL System/Unit Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 RG 22x12 1.00 *780 710 91 Totals:----780 0 710 91 - RF-2-02 Return Inlet Summary Inland Air Balance, Inc. Page 27 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/4/2024 SYSTEM/UNIT: RF-3-01 AREA: Corridor Unit Data Unit Manufacturer Penn Ventilator Unit Model Number FX11 Unit Serial Number E23HZ02926 Test Data Motor Operating HZ/Speed 60 Motor Volts T1-T2 207 Volts Motor Amps T1 1.50 Amps Motor Data Nameplate Motor Manufacturer Mc millan Nameplate Motor Frame Not Listed Nameplate Motor HP 1/6 HP Nameplate Motor Rated Volts 208 Volts Nameplate Motor RPM Not Listed RPM Nameplate Motor FL Amps 3.20 Amps Nameplate Motor Phase 1 Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Brake Horsepower 0.30 BHP Nominal Efficiency (0.00)0.90 % Motor Power Factor (0.00)0.80 Sheave Data Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP NVL in. wc Actual Suction SP NVL in. wc Actual Discharge SP NVL in. wc Test Results Design Airflow 125 CFM Actual Airflow 137 CFM Design Fan RPM Ns RPM Actual Fan RPM NVL RPM Actual Motor RPM NVL Inland Air Balance, Inc. Page 28 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/4/2024 SYSTEM/UNIT: RF-3-01 AREA: Corridor Unit Manufacturer Photo: Name:Unit Manufacturer.jpg Captured:1/2/2024 11:05 AM Caption: System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Corridor 3rd Flr RG 2408 1.00 *125 137 110 Totals:----125 0 137 110 - RF-3-01 Exhaust Inlet Summary Inland Air Balance, Inc. Page 29 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/4/2024 SYSTEM/UNIT: RF-3-02 AREA: Corridor Unit Data Unit Manufacturer Penn Ventilator Unit Model Number FX 11 Unit Serial Number E23HZ02926 Test Data Motor Operating HZ/Speed 6 Motor Volts T1-T2 209 Volts Motor Amps T1 1.30 Amps Motor Data Nameplate Motor Manufacturer Mc millan Nameplate Motor Frame Not Listed Nameplate Motor HP 1/4 watt Nameplate Motor Rated Volts 120 Volts Nameplate Motor RPM Ns RPM Nameplate Motor FL Amps 3.20 Amps Nameplate Motor Phase 1 Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Brake Horsepower 0.26 BHP Nominal Efficiency (0.00)0.90 % Motor Power Factor (0.00)0.80 Sheave Data Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP NVL in. wc Actual Suction SP NVL in. wc Actual Discharge SP NVL in. wc Test Results Design Airflow 170 CFM Actual Airflow 183 CFM Design Fan RPM NS RPM Actual Fan RPM NVL RPM Actual Motor RPM NVL Inland Air Balance, Inc. Page 30 of 129 Fan UnitPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/4/2024 SYSTEM/UNIT: RF-3-02 AREA: Corridor Unit Manufacturer Photo: Name:Unit Manufacturer.jpg Captured:1/2/2024 11:01 AM Caption: System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Corridor 3rd Flr EG 2408 1.00 *170 183 108 Totals:----170 0 183 108 - RF-3-02 Exhaust Inlet Summary Inland Air Balance, Inc. Page 31 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/4/2024 SYSTEM/UNIT: AC-1-01 AREA: Elec Unit Data Unit Manufacturer LG Unit Model Number LSN240HEV2 Unit Serial Number 210HAGF7U533 Test Data Design Airflow 689 CFM Actual Airflow 699 CFM Design OSA 0 CFM Actual OSA 0 CFM Motor Data AC-1-01/Supply Fan Nameplate Motor Hertz 60 Hz Nominal Efficiency (0.00)0.90 % Motor Power Factor (0.00)0.80 Test Pressures Design Total SP NS in. wc Actual Total SP NA in. wc Suction SP NVL in. wc Discharge SP NVL in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Elec 144 Swing Blade 34x4 0.94 744 689 699 101 Totals:----689 0 699 101 AC-1-01 Supply Outlet Summary Tested By:Robert Watson Date:1/4/2024 SYSTEM/UNIT: AC-1-02 AREA: IDF Unit Data Unit Manufacturer LG Unit Model Number LSN240HEV2 Unit Serial Number 210HAGF7U531 Test Data Design Airflow 689 CFM Actual Airflow 704 CFM Design OSA 0 CFM Actual OSA 0 CFM Motor Data AC-1-02/Supply Fan Nameplate Motor Hertz 60 Hz Nominal Efficiency (0.00)0.90 % Motor Power Factor (0.00)0.80 Test Pressures Design Total SP NS in. wc Actual Total SP NA in. wc Suction SP NVL in. wc Discharge SP NVL in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 IDF 145 Swing Blade 34x4 0.94 749 689 704 102 Totals:----689 0 704 102 AC-1-02 Supply Outlet Summary Inland Air Balance, Inc. Page 32 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/3/2024 SYSTEM/UNIT: AC-2-01 AREA: Elec Unit Data Unit Manufacturer LG Unit Model Number LSN240HEV2 Unit Serial Number 210HAGF7U520 Test Data Design Airflow 689 CFM Actual Airflow 713 CFM Design OSA 0 CFM Actual OSA 0 CFM Motor Data AC-2-01/Supply Fan Nameplate Motor Hertz 60 Hz Nominal Efficiency (0.00)0.90 % Motor Power Factor (0.00)0.80 Test Pressures Design Total SP NS in. wc Actual Total SP NA in. wc Suction SP NVL in. wc Discharge SP NVL in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Elect 214 Swing Blade 34x4 0.94 759 689 713 103 Totals:----689 0 713 103 AC-2-01 Supply Outlet Summary Tested By:David Ramirez Date:12/28/2023 SYSTEM/UNIT: AC-2-02 AREA: IDF Unit Data Unit Manufacturer LG Unit Model Number LSN240HEV2 Unit Serial Number 210HAGF7U519 Test Data Design Airflow 689 CFM Actual Airflow 696 CFM Design OSA 0 CFM Actual OSA 0 CFM Test Pressures Design Total SP NS in. wc Actual Total SP NA in. wc Suction SP NVL in. wc Discharge SP NVL in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 IDF 249 Swing Blade 34x4 0.94 740 689 696 101 Totals:----689 0 696 101 AC-2-02 Supply Outlet Summary Inland Air Balance, Inc. Page 33 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/3/2024 SYSTEM/UNIT: AC-2-03 AREA: Elec Unit Data Unit Manufacturer LG Unit Model Number LSN24 Unit Serial Number 210hagf7u519 Test Data Design Airflow 689 CFM Actual Airflow 690 CFM Design OSA 0 CFM Actual OSA 0 CFM Motor Data AC-2-03/Supply Fan Nameplate Motor Hertz 60 Hz Nominal Efficiency (0.00)0.90 % Motor Power Factor (0.00)0.80 Test Pressures Design Total SP NS in. wc Actual Total SP NA in. wc Suction SP NVL in. wc Discharge SP NVL in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Elec 260 Swing Blade 34x4 0.94 734 689 690 100 Totals:----689 0 690 100 AC-2-03 Supply Outlet Summary Tested By:Robert Watson Date:1/4/2024 SYSTEM/UNIT: AC-3-01 AREA: Elec Unit Data Unit Manufacturer LG Unit Model Number LSN240HEV2 Unit Serial Number 210HAGF7U524 Test Data Design Airflow 689 CFM Actual Airflow 695 CFM Design OSA 0 CFM Actual OSA 0 CFM Motor Data AC-3-01/Supply Fan Nameplate Motor Hertz 60 Hz Nominal Efficiency (0.00)0.90 % Motor Power Factor (0.00)0.80 Test Pressures Design Total SP NS in. wc Actual Total SP NA in. wc Suction SP NVL in. wc Discharge SP NVL in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Elec 309 Swing Blade 34x4 0.94 739 689 695 101 Totals:----689 0 695 101 AC-3-01 Supply Outlet Summary Inland Air Balance, Inc. Page 34 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/4/2024 SYSTEM/UNIT: AC-3-02 AREA: Elec Unit Data Unit Manufacturer LG Unit Model Number LSN240HEV2 Unit Serial Number 210HAGF7U521 Test Data Design Airflow 689 CFM Actual Airflow 709 CFM Design OSA 0 CFM Actual OSA 0 CFM Motor Data AC-3-02/Supply Fan Nameplate Motor Hertz 60 Hz Nominal Efficiency (0.00)0.90 % Motor Power Factor (0.00)0.80 Test Pressures Design Total SP NS in. wc Actual Total SP NA in. wc Suction SP NVL in. wc Discharge SP NVL in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Elect 348 Swing Blade 34x4 0.94 754 689 709 103 Totals:----689 0 709 103 AC-3-02 Supply Outlet Summary Tested By:Robert Watson Date:1/4/2024 SYSTEM/UNIT: AC-3-03 AREA: IDF Unit Data Unit Manufacturer LG Unit Model Number LSN240HEV2 Unit Serial Number 210HAGF7U523 Test Data Design Airflow 689 CFM Actual Airflow 710 CFM Design OSA 0 CFM Actual OSA 0 CFM Motor Data AC-3-03/Supply Fan Nameplate Motor Hertz 60 Hz Nominal Efficiency (0.00)0.90 % Motor Power Factor (0.00)0.80 Test Pressures Design Total SP NS in. wc Actual Total SP NA in. wc Suction SP NVL in. wc Discharge SP NVL in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 IDF 346 Swing Blade 34x4 0.94 755 689 710 103 Totals:----689 0 710 103 AC-3-03 Supply Outlet Summary Inland Air Balance, Inc. Page 35 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/29/2023 SYSTEM/UNIT: AC-B-01 AREA: Elev Unit Data Unit Manufacturer LG Unit Model Number LSN240HEV2 Unit Serial Number 210HAYE7U538 Test Data Design Airflow 813 CFM Actual Airflow 825 CFM Design OSA 0 CFM Actual OSA 0 CFM Test Pressures Design Total SP NS in. wc Actual Total SP NA in. wc Suction SP NVL in. wc Discharge SP NVL in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Elevator Equipment B21 Swing Blade 34x4 0.94 878 813 825 101 Totals:----813 0 825 101 AC-B-01 Supply Outlet Summary Tested By:David Ramirez Date:12/29/2023 SYSTEM/UNIT: AC-B-02 AREA: Electrical B16 Unit Data Unit Manufacturer LG Unit Model Number LSN240HEV2 Unit Serial Number 210HACQ7U515 Test Data Design Airflow 813 CFM Actual Airflow 821 CFM Design OSA 0 CFM Actual OSA 0 CFM Test Pressures Design Total SP NS in. wc Actual Total SP NA in. wc Suction SP NVL in. wc Discharge SP NVL in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Electrical B16 Swing Blade 34x4 0.94 873 813 821 101 Totals:----813 0 821 101 AC-B-02 Supply Outlet Summary Inland Air Balance, Inc. Page 36 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/4/2024 SYSTEM/UNIT: AC-B-03 AREA: Elev Unit Data Unit Manufacturer LG Unit Model Number LSN240HEV2 Unit Serial Number 210HACQ7U538 Test Data Design Airflow 813 CFM Actual Airflow 804 CFM Design OSA 0 CFM Actual OSA 0 CFM Motor Data AC-B-03/Supply Fan Nameplate Motor Hertz 60 Hz Nominal Efficiency (0.00)0.90 % Motor Power Factor (0.00)0.80 Test Pressures Design Total SP NS in. wc Actual Total SP NA in. wc Suction SP NVL in. wc Discharge SP NVL in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Elevator Equipment B16 Swing Blade 34x4 0.94 855 813 804 99 Totals:----813 0 804 99 AC-B-03 Supply Outlet Summary Tested By:David Ramirez Date:12/29/2023 SYSTEM/UNIT: AC-B-04 AREA: Elevator Equipment B21 Unit Data Unit Manufacturer LG Unit Model Number LSN240HEV2 Unit Serial Number 210HALW7U520 Test Data Design Airflow 813 CFM Actual Airflow 821 CFM Design OSA 0 CFM Actual OSA 0 CFM Test Pressures Design Total SP NS in. wc Actual Total SP NA in. wc Suction SP NVL in. wc Discharge SP NVL in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Elevator Equipment B21 Swing Blade 34x4 0.94 870 813 821 101 Totals:----813 0 821 101 AC-B-04 Supply Outlet Summary Inland Air Balance, Inc. Page 37 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/29/2023 SYSTEM/UNIT: AC-B-06 AREA: MPOE Log:AC-B-06 12/29/2023 David Ramirez Schedule change. FCU is now a 2 ton wall-split Unit Data Unit Manufacturer LG Unit Model Number LSN243HLV3 Unit Serial Number 305KARW0E878 Test Data Design Airflow Ns CFM Actual Airflow 840 CFM Design OSA 0 CFM Actual OSA 0 CFM Test Pressures Design Total SP NS in. wc Actual Total SP NA in. wc Suction SP NVL in. wc Discharge SP NVL in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 MPOE B24 Swing Blade 35x4 0.97 867 Ns 840 Totals:----0 0 840 0 AC-B-06 Supply Outlet Summary Inland Air Balance, Inc. Page 38 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/29/2023 SYSTEM/UNIT: AC-B-07 AREA: Emergency Log:AC-B-07 12/29/2023 David Ramirez Schedule change. FCU is now a wall-split. Unit Data Unit Manufacturer LG Unit Model Number LSN368HLV3 Unit Serial Number 303KAVH03Y75 Test Data Design Airflow Ns CFM Actual Airflow 1267 CFM Design OSA 0 CFM Actual OSA 0 CFM Test Pressures Design Total SP NS in. wc Actual Total SP NA in. wc Suction SP NVL in. wc Discharge SP NVL in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Emergency Elec Room B25 Swing Blade 41x4 1.14 1111 Ns 1267 Totals:----0 0 1267 0 AC-B-07 Supply Outlet Summary Inland Air Balance, Inc. Page 39 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/21/2023 SYSTEM/UNIT: FCU-1-01 AREA: Laundry Log:FCU-1-01 12/21/2023 David Ramirez RA+OSA does not equate to SA volume. Return Inlet 01, in corridor 104, was set to make up the difference in air volume. Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not Listed FCU-1-01/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 640 CFM Actual Airflow 640 CFM Design OSA 235 CFM Actual OSA 258 CFM FCU-1-01/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 0.91 Amps Motor Data FCU-1-01/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-1-01/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-1-01/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-1-01/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.33 in. wc Suction SP -0.12 in. wc Discharge SP 0.21 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Corridor 104 CD 2408 1.00 *150 155 103 Outlet-02 Seating 146 CD 2408 1.00 *155 160 103 Outlet-03 Laundry 147 CD 2408 1.00 *185 175 95 Outlet-04 Corridor 104 CD 2408 1.00 *NS 150 Totals:----490 0 640 131 FCU-1-01 Supply Outlet Summary Inland Air Balance, Inc. Page 40 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Corridor 104 RG 2408 1.00 *NS 322 Inlet-02 Laundry 147 RG 2406 1.00 *NS 60 Totals:----0 0 382 0 - FCU-1-01 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 10” Ø Velgrid 0.55 469 235 258 110 Totals:-----235 0 258 110 FCU-1-01 Outside Air Intake Summary Inland Air Balance, Inc. Page 41 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/3/2024 SYSTEM/UNIT: FCU-1-02 AREA: Office Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not listed FCU-1-02/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 640 CFM Actual Airflow 643 CFM Design OSA 15 CFM Actual OSA 16 CFM FCU-1-02/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 0.99 Amps Motor Data FCU-1-02/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-1-02/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-1-02/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-1-02/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP Ns in. wc Actual Total SP 0.39 in. wc Suction SP -0.16 in. wc Discharge SP 0.23 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 ED Office 102 CD 2410 1.00 *270 277 103 Outlet-02 ED Office 102 LD 48x2 1.00 *370 366 99 Totals:----640 0 643 100 FCU-1-02 Supply Outlet Summary Inland Air Balance, Inc. Page 42 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 ED Office 102 RG 2410 1.00 *205 222 108 Inlet-02 ED Office 102 RG 48x2 1.00 *280 301 108 Totals:----485 0 523 108 - FCU-1-02 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 8 Airfoil 0.35 46 15 16 107 Totals:-----15 0 16 107 FCU-1-02 Outside Air Intake Summary Inland Air Balance, Inc. Page 43 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/10/2024 SYSTEM/UNIT: FCU-1-03 AREA: Office Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not Listed FCU-1-03/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 660 CFM Actual Airflow 691 CFM Design OSA 75 CFM Actual OSA 75 CFM FCU-1-03/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 0.90 Amps Motor Data FCU-1-03/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-1-03/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-1-03/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-1-03/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.40 in. wc Suction SP 0.13 in. wc Discharge SP 0.27 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 BOM Office 151 CD 2408 1.00 *110 103 94 Outlet-02 S&M Office 153 CD 2408 1.00 *175 159 91 Outlet-03 W.R. 150 CD 2408 1.00 *NS 90 Outlet-04 S&M Office 154 CD 2408 1.00 *175 158 90 Outlet-05 Parcel Room 155 CD 2408 1.00 *100 91 91 Outlet-06 Reception 101 CD 2408 1.00 *100 90 90 Totals:----660 0 691 105 FCU-1-03 Supply Outlet Summary Inland Air Balance, Inc. Page 44 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 BOM Office 151 RG 2414 1.00 *565 372 66 Inlet-02 S&M Office 153 RG 2408 1.00 *175 109 62 Inlet-03 S&M Office 154 RG 2408 1.00 *175 108 62 Totals:----915 0 589 64 - FCU-1-03 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 6 Air-foil 0.20 376 75 75 100 Totals:-----75 0 75 100 FCU-1-03 Outside Air Intake Summary Inland Air Balance, Inc. Page 45 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/27/2023 SYSTEM/UNIT: FCU-1-04 AREA: Kitchen Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not Listed FCU-1-04/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 640 CFM Actual Airflow 645 CFM Design OSA 90 CFM Actual OSA 92 CFM FCU-1-04/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 0.90 Amps Motor Data FCU-1-04/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-1-04/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-1-04/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-1-04/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.51 in. wc Suction SP -0.31 in. wc Discharge SP 0.20 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Servery 119 CD 2410 1.00 *280 285 102 Outlet-02 Servery 119 LD 48x3 1.00 *360 360 100 Totals:----640 0 645 101 FCU-1-04 Supply Outlet Summary Inland Air Balance, Inc. Page 46 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 RG 2412 1.00 525 553 105 Totals:----525 0 553 105 - FCU-1-04 Return Inlet Summary System/Unit Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity OS-01 DUCT 6” Ø Air-foil 0.20 460 90 92 102 102 Totals:-----90 0 92 102 - FCU-1-04 Outside Air Intake Summary Inland Air Balance, Inc. Page 47 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/27/2023 SYSTEM/UNIT: FCU-1-05 AREA: Corridor Unit Data Unit Manufacturer LG Unit Model Number LHN368HV Unit Serial Number Not Listed FCU-1-05/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x25x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 880 CFM Actual Airflow 845 CFM Design OSA 480 CFM Actual OSA 491 CFM FCU-1-05/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 1.34 Amps Motor Data FCU-1-05/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 2.30 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-1-05/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-1-05/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-1-05/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.29 in. wc Suction SP -0.18 in. wc Discharge SP 0.11 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Women 113 CD 2408 1.00 *205 205 100 Outlet-02 Men 112 CD 2408 1.00 *205 205 100 Outlet-03 Corridor 1st Floor CD 2408 1.00 *230 220 96 Outlet-04 Corridor 1st Floor CD 2408 1.00 *230 215 93 Totals:----870 0 845 97 FCU-1-05 Supply Outlet Summary Inland Air Balance, Inc. Page 48 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Corridor 1st Floor RG 2414 1.00 *400 365 91 Totals:----400 0 365 91 - FCU-1-05 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 12” Ø Velgrid 0.78 630 480 491 102 Totals:-----480 0 491 102 FCU-1-05 Outside Air Intake Summary Inland Air Balance, Inc. Page 49 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:12/28/2023 SYSTEM/UNIT: FCU-1-06 AREA: Restaurant Unit Data Unit Manufacturer LG Unit Model Number lvhn428 Unit Serial Number Not Listed FCU-1-06/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 2 Filter Size - S1 16x25x2 Test Data Design Airflow 1080 CFM Actual Airflow 1070 CFM Design OSA 370 CFM Actual OSA 380 CFM FCU-1-06/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 1.10 Amps Motor Data FCU-1-06/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.30 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-1-06/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-1-06/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-1-06/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.51 in. wc Suction SP -0.22 in. wc Discharge SP 0.29 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Savor Restaurant 124 LD 48x3 1.00 358 360 358 99 Outlet-02 Savor Restaurant 124 LD 48x3 1.00 363 360 363 101 Outlet-03 Savor Restaurant 124 LD 48x3 1.00 349 360 349 97 Totals:----1080 0 1070 99 FCU-1-06 Supply Outlet Summary Inland Air Balance, Inc. Page 50 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Savor Restaurant 124 RG 48x3 1.00 *235 218 93 Inlet-02 Savor Restaurant 124 RG 48x3 1.00 *235 220 94 Inlet-03 Savor Restaurant 124 RG 48x3 1.00 *235 219 93 Totals:----705 0 657 93 - FCU-1-06 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit LOUVER 18x18 Velgrid 2.25 169 370 380 103 Totals:-----370 0 380 103 FCU-1-06 Outside Air Intake Summary Inland Air Balance, Inc. Page 51 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/3/2024 SYSTEM/UNIT: FCU-1-07 AREA: Dr's Pub Unit Data Unit Manufacturer LG Unit Model Number LHN428 Unit Serial Number Not Listed FCU-1-07/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 2 Filter Size - S1 16x25x2 Test Data Design Airflow 1040 CFM Actual Airflow 1042 CFM Design OSA 435 CFM Actual OSA 442 CFM FCU-1-07/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 1.00 Amps Motor Data FCU-1-07/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.30 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-1-07/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-1-07/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-1-07/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.54 in. wc Suction SP -0.23 in. wc Discharge SP 0.31 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 D's Pub 122 LD 48x2 1.00 *260 264 102 Outlet-02 D's Pub 122 LD 48x2 1.00 *260 271 104 Outlet-03 D's Pub 122 LD 48x2 1.00 *260 246 95 Outlet-04 D's Pub 122 LD 48x2 1.00 *260 261 100 Totals:----1040 0 1042 100 FCU-1-07 Supply Outlet Summary Inland Air Balance, Inc. Page 52 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 D's Pub 122 RG 48x3 1.00 *305 288 94 Inlet-02 D's Pub 122 RG 48x3 1.00 *305 289 95 Totals:----610 0 577 95 - FCU-1-07 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 12 Velgrid 0.78 567 435 442 102 Totals:-----435 0 442 102 FCU-1-07 Outside Air Intake Summary Inland Air Balance, Inc. Page 53 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:12/27/2023 SYSTEM/UNIT: FCU-1-08 AREA: Kitchen Unit Data Unit Manufacturer LG Unit Model Number LHN428hv Unit Serial Number Not Listed FCU-1-08/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 2 Filter Size - S1 16x25x2 Test Data Design Airflow 1210 CFM Actual Airflow 1100 CFM Design OSA 160 CFM Actual OSA 161 CFM FCU-1-08/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 1.23 Amps Motor Data FCU-1-08/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.30 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-1-08/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-1-08/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-1-08/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.66 in. wc Suction SP -0.17 in. wc Discharge SP 0.49 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Hostess 123 LD 48x2 1.00 *300 278 93 Outlet-02 Hostess 123 LD 48x2 1.00 *300 270 90 Outlet-03 Hostess 123 LD 48x2 1.00 *300 272 91 Outlet-04 Hostess 123 LD 48x2 1.00 *300 280 93 Totals:----1200 0 1100 92 FCU-1-08 Supply Outlet Summary Inland Air Balance, Inc. Page 54 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Hostess 123 RG 2412 1.00 *525 501 95 Inlet-02 Hostess 123 RG 2412 1.00 *525 477 91 Totals:----1050 0 978 93 - FCU-1-08 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 8 airfoil 0.35 459 160 161 101 Totals:-----160 0 161 101 FCU-1-08 Outside Air Intake Summary Inland Air Balance, Inc. Page 55 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/29/2023 SYSTEM/UNIT: FCU-1-09A AREA: Kitchen Log:FCU-1-09A 12/27/2023 David Ramirez Right RA volume damper shaft is disconnected from handle. Unit Data Unit Manufacturer LG Unit Model Number LHN488HV Unit Serial Number Not Listed FCU-1-09A/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 2 Filter Size - S1 16x25x2 Test Data Design Airflow 1450 CFM Actual Airflow 1335 CFM Design OSA 180 CFM Actual OSA 183 CFM FCU-1-09A/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 1.10 Amps Motor Data FCU-1-09A/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.30 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-1-09A/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-1-09A/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-1-09A/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.31 in. wc Suction SP -0.21 in. wc Discharge SP 0.10 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Kitchen 118 CD 2410 1.00 *345 345 100 Outlet-02 Kitchen 118 CD 2410 1.00 *345 345 100 Outlet-03 Kitchen 118 CD 2410 1.00 *345 335 97 Outlet-04 Kitchen 118 CD 2410 1.00 *345 310 90 Totals:----1380 0 1335 97 FCU-1-09A Supply Outlet Summary Inland Air Balance, Inc. Page 56 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Kitchen 118 RG 2412 1.00 *635 572 90 Inlet-02 Kitchen 118 RG 2412 1.00 *635 571 90 Totals:----1270 0 1143 90 - FCU-1-09A Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 8 Air-foil 0.35 523 180 183 102 Totals:-----180 0 183 102 FCU-1-09A Outside Air Intake Summary Inland Air Balance, Inc. Page 57 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/29/2023 SYSTEM/UNIT: FCU-1-09B AREA: Kitchen Unit Data Unit Manufacturer LG Unit Model Number LHN488HV Unit Serial Number Not Listed FCU-1-09B/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 2 Filter Size - S1 16x25x2 Test Data Design Airflow 1450 CFM Actual Airflow 1480 CFM Design OSA 175 CFM Actual OSA 186 CFM FCU-1-09B/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 1.08 Amps Motor Data FCU-1-09B/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.30 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-1-09B/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-1-09B/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-1-09B/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.33 in. wc Suction SP -0.20 in. wc Discharge SP 0.13 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Kitchen 118 CD 2410 1.00 *340 340 100 Outlet-02 Kitchen 118 CD 2406 1.00 *110 115 105 Outlet-03 Kitchen 118 CD 2410 1.00 *340 345 101 Outlet-04 Kitchen 118 CD 2410 1.00 *340 335 99 Outlet-05 Kitchen 118 CD 2410 1.00 *340 345 101 Totals:----1470 0 1480 101 FCU-1-09B Supply Outlet Summary Inland Air Balance, Inc. Page 58 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Kitchen 118 RG 2412 1.00 *648 650 100 Inlet-02 Kitchen 118 RG 2412 1.00 *647 640 99 Totals:----1295 0 1290 100 - FCU-1-09B Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 8 Air-foil 0.35 530 175 186 106 Totals:-----175 0 186 106 FCU-1-09B Outside Air Intake Summary Inland Air Balance, Inc. Page 59 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:12/27/2023 SYSTEM/UNIT: FCU-1-10 AREA: Dining Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not Listed FCU-1-10/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 640 CFM Actual Airflow 648 CFM Design OSA 190 CFM Actual OSA 190 CFM FCU-1-10/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 0.95 Amps Motor Data FCU-1-10/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-1-10/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-1-10/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-1-10/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.29 in. wc Suction SP -0.07 in. wc Discharge SP 0.22 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Kitchen Office 118A CD 2406 1.00 *100 104 104 Outlet-02 Serve St. 117 CD 2406 1.00 *100 110 110 Outlet-03 Cellar PVT Dining 115 LD 48x2 1.00 *220 211 96 Outlet-04 Cellar PVT Dining 115 LD 48x2 1.00 *220 223 101 Totals:----640 0 648 101 FCU-1-10 Supply Outlet Summary Inland Air Balance, Inc. Page 60 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Cellar PVT Dining 115 RG 48x3 1.00 *N/S 212 Inlet-02 RG 48x3 1.00 *N/S 186 Totals:----0 0 398 0 - FCU-1-10 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 10 Velgrid 0.35 544 190 190 100 Totals:-----190 0 190 100 FCU-1-10 Outside Air Intake Summary Inland Air Balance, Inc. Page 61 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:12/27/2023 SYSTEM/UNIT: FCU-1-11 AREA: Living Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not Listed FCU-1-11/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 725 CFM Actual Airflow 724 CFM Design OSA 80 CFM Actual OSA 88 CFM FCU-1-11/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 1.00 Amps Motor Data FCU-1-11/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-1-11/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-1-11/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-1-11/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.35 in. wc Suction SP -0.13 in. wc Discharge SP 0.22 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Living Room 105 CD 48x2 1.00 *245 231 94 Outlet-02 Living Room 105 CD 48x2 1.00 *245 247 101 Outlet-03 Living Room 105 CD 48x2 1.00 *245 246 100 Totals:----735 0 724 99 FCU-1-11 Supply Outlet Summary Inland Air Balance, Inc. Page 62 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Living Room 105 RG 48x2 1.00 *215 205 95 Inlet-02 Living Room 105 RG 48x2 1.00 *215 209 97 Inlet-03 Living Room 105 RG 48x2 1.00 *215 208 97 Totals:----645 0 622 96 - FCU-1-11 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 6 Airfoil 0.20 440 80 88 110 Totals:-----80 0 88 110 FCU-1-11 Outside Air Intake Summary Inland Air Balance, Inc. Page 63 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:12/27/2023 SYSTEM/UNIT: FCU-1-12 AREA: Gameroom Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not Listed FCU-1-12/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 755 CFM Actual Airflow 746 CFM Design OSA 105 CFM Actual OSA 110 CFM FCU-1-12/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 0.96 Amps Motor Data FCU-1-12/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-1-12/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-1-12/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-1-12/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.31 in. wc Suction SP -0.10 in. wc Discharge SP 0.21 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Game Room 106 LD 48x2 1.00 *375 369 98 Outlet-02 Game Room 106 LD 48x2 1.00 *380 377 99 Totals:----755 0 746 99 FCU-1-12 Supply Outlet Summary Inland Air Balance, Inc. Page 64 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Game Room 106 RG 48x2 1.00 *325 297 91 Inlet-02 Game Room 106 RG 48x2 1.00 *325 292 90 Totals:----650 0 589 91 - FCU-1-12 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit LOUVER 48x22 Velgrid 7.33 15 105 110 105 Totals:-----105 0 110 105 FCU-1-12 Outside Air Intake Summary Inland Air Balance, Inc. Page 65 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:12/27/2023 SYSTEM/UNIT: FCU-1-13 AREA: Discovery Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not Listed FCU-1-13/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 640 CFM Actual Airflow 604 CFM Design OSA 55 CFM Actual OSA 60 CFM FCU-1-13/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 0.97 Amps Motor Data FCU-1-13/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-1-13/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-1-13/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-1-13/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.33 in. wc Suction SP -0.11 in. wc Discharge SP 0.22 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Discovery 103 LD 60x3 1.00 *640 604 94 Totals:----640 0 604 94 FCU-1-13 Supply Outlet Summary System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Discovery 103 RG 60x3 1.00 *585 539 92 Totals:----585 0 539 92 - FCU-1-13 Return Inlet Summary Inland Air Balance, Inc. Page 66 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit LOUVER 6 velgrid 0.20 300 55 60 109 Totals:-----55 0 60 109 FCU-1-13 Outside Air Intake Summary Inland Air Balance, Inc. Page 67 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/27/2023 SYSTEM/UNIT: FCU-1-14 AREA: Corridor Unit Data Unit Manufacturer LG Unit Model Number LH368HV Unit Serial Number Not Listed FCU-1-14/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x25x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 920 CFM Actual Airflow 882 CFM Design OSA 80 CFM Actual OSA 81 CFM FCU-1-14/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 1.20 Amps Motor Data FCU-1-14/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 2.30 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-1-14/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-1-14/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-1-14/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.32 in. wc Suction SP -0.10 in. wc Discharge SP 0.22 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Corridor 127 CD 2408 1.00 *115 112 97 Outlet-02 Corridor 127 CD 2408 1.00 *110 110 100 Outlet-03 Hall 5/A11.17 CD 2410 1.00 *350 315 90 Outlet-04 Hall 5/A11.17 CD 2410 1.00 *345 345 100 Totals:----920 0 882 96 FCU-1-14 Supply Outlet Summary Inland Air Balance, Inc. Page 68 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Corridor 127 RG 2414 1.00 *840 801 95 Totals:----840 0 801 95 - FCU-1-14 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 6” Ø Air-foil 0.20 404 80 81 101 Totals:-----80 0 81 101 FCU-1-14 Outside Air Intake Summary Inland Air Balance, Inc. Page 69 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/21/2023 SYSTEM/UNIT: FCU-2-01 AREA: Dining Unit Data Unit Manufacturer LG Unit Model Number LHN488HV Unit Serial Number Not Listed FCU-2-01/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 2 Filter Size - S1 16x25x2 Test Data Design Airflow 1590 CFM Actual Airflow 1465 CFM Design OSA 500 CFM Actual OSA 527 CFM FCU-2-01/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 1.00 Amps Motor Data FCU-2-01/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.30 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-2-01/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-2-01/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-2-01/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.54 in. wc Suction SP -0.33 in. wc Discharge SP 0.21 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 MC Dining 240 LD 48x2 1.00 *205 200 98 Outlet-02 MC Dining 240 LD 48x3 1.00 *300 285 95 Outlet-03 MC Dining 240 LD 48x2 1.00 *205 190 93 Outlet-04 MC Dining 240 LD 48x3 1.00 *300 290 97 Outlet-05 MC Dining 240 LD 48x2 1.00 *205 205 100 Outlet-06 MC Dining 240 LD 48x3 1.00 *300 295 98 Totals:----1515 0 1465 97 FCU-2-01 Supply Outlet Summary Inland Air Balance, Inc. Page 70 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 MC Dining 240 LRG 58x3 1.00 *545 490 90 Inlet-02 MC Dining 240 LRG 58x3 1.00 *545 495 91 Totals:----1090 0 985 90 - FCU-2-01 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 10” Ø Air-Foil 0.55 958 500 527 105 Totals:-----500 0 527 105 FCU-2-01 Outside Air Intake Summary Inland Air Balance, Inc. Page 71 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:12/21/2023 SYSTEM/UNIT: FCU-2-02 AREA: Living Unit Data Unit Manufacturer LG Unit Model Number LHN428HV Unit Serial Number Not Listed FCU-2-02/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 2 Filter Size - S1 16x25x2 Test Data Design Airflow 1290 CFM Actual Airflow 1360 CFM Design OSA 250 CFM Actual OSA 260 CFM FCU-2-02/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 1.30 Amps Motor Data FCU-2-02/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.30 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-2-02/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-2-02/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-2-02/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.48 in. wc Suction SP -0.18 in. wc Discharge SP 0.30 in. wc Inland Air Balance, Inc. Page 72 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:12/21/2023 SYSTEM/UNIT: FCU-2-02 AREA: Living Unit Manufacturer Photo: Name:Unit Manufacturer.jpg Captured:12/21/2023 8:37 AM Caption: System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Living 238 LD 48x3 1.00 273 260 273 105 Outlet-02 Living 238 LD 48x3 1.00 274 260 274 105 Outlet-03 Living 238 LD 48x3 1.00 269 260 269 103 Outlet-04 Living 238 LD 48x3 1.00 270 255 270 106 Outlet-05 Living 238 LD 48x3 1.00 274 255 274 107 Totals:----1290 0 1360 105 FCU-2-02 Supply Outlet Summary System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Living 238 RG 58x3 1.21 417 500 504 101 Inlet-02 Living 238 RG 58x3 1.21 404 500 489 98 Totals:----1000 0 993 99 - FCU-2-02 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit LOUVER 33x8 Velgrid 1.83 142 250 260 104 Totals:-----250 0 260 104 FCU-2-02 Outside Air Intake Summary Inland Air Balance, Inc. Page 73 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/21/2023 SYSTEM/UNIT: FCU-2-03 AREA: Office Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not Listed FCU-2-03/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 640 CFM Actual Airflow 648 CFM Design OSA 160 CFM Actual OSA 161 CFM FCU-2-03/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 0.83 Amps Motor Data FCU-2-03/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-2-03/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-2-03/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-2-03/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.23 in. wc Suction SP -0.08 in. wc Discharge SP 0.15 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Med 246 CD 2408 1.00 *240 241 100 Outlet-02*Laundry 244 CD 2408 1.00 *160 172 108 Outlet-03 Care Giver 245 CD 2408 1.00 *240 235 98 Totals:----640 0 648 101 FCU-2-03 Supply Outlet Summary Log:FCU-2-03/Outlet-02 12/21/2023 David Ramirez Fire/Smoke Damper does not have power landed. Mechanical and Electrical contractors have been made aware. FSD was manually opened, FCU was balanced. Inland Air Balance, Inc. Page 74 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Care Office 245 RG 2412 1.00 480 481 100 Totals:----480 0 481 100 - FCU-2-03 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 10” Ø Air-Foil 0.55 292 160 161 101 Totals:-----160 0 161 101 FCU-2-03 Outside Air Intake Summary Inland Air Balance, Inc. Page 75 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/4/2024 SYSTEM/UNIT: FCU-2-04 AREA: Office Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not Listed FCU-2-04/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 640 CFM Actual Airflow 655 CFM Design OSA 170 CFM Actual OSA 178 CFM FCU-2-04/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 0.70 Amps Motor Data FCU-2-04/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-2-04/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-2-04/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-2-04/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.14 in. wc Suction SP -0.01 in. wc Discharge SP 0.13 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Laundry 250 CD 2408 1.00 *190 195 103 Outlet-02 MC Dir. Office 248 CD 2408 1.00 *150 155 103 Outlet-03 Corridor 104 CD 2408 1.00 *150 155 103 Outlet-04 Corridor 104 CD 2408 1.00 *150 150 100 Totals:----640 0 655 102 FCU-2-04 Supply Outlet Summary Inland Air Balance, Inc. Page 76 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Corridor 261 RG 2410 1.00 *295 280 95 Inlet-02 MC Dir. Office 248 RG 2408 1.00 *150 144 96 Totals:----445 0 424 95 - FCU-2-04 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 10” Ø Air-foil 0.55 323 175 178 102 Totals:-----175 0 178 102 FCU-2-04 Outside Air Intake Summary Inland Air Balance, Inc. Page 77 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/21/2023 SYSTEM/UNIT: FCU-2-05 AREA: Kitchen Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not Listed FCU-2-05/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 640 CFM Actual Airflow 635 CFM Design OSA 235 CFM Actual OSA 235 CFM FCU-2-05/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 0.80 Amps Motor Data FCU-2-05/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-2-05/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-2-05/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-2-05/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.19 in. wc Suction SP -0.05 in. wc Discharge SP 0.14 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Kitchen/Servery 239 CD 2408 1.00 *320 320 100 Outlet-02 Kitchen/Servery 239 CD 2408 1.00 *320 315 98 Totals:----640 0 635 99 FCU-2-05 Supply Outlet Summary Inland Air Balance, Inc. Page 78 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Kitchen/Servery 239 RG 2412 1.00 *405 400 99 Totals:----405 0 400 99 - FCU-2-05 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 10” Ø Air-Foil 0.55 427 235 235 100 Totals:-----235 0 235 100 FCU-2-05 Outside Air Intake Summary Inland Air Balance, Inc. Page 79 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/20/2023 SYSTEM/UNIT: FCU-2-6 AREA: Corridor Unit Data Unit Manufacturer LG Unit Model Number LHN368HV Unit Serial Number Not Listed FCU-2-6/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x25x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 915 CFM Actual Airflow 920 CFM Design OSA 85 CFM Actual OSA 88 CFM FCU-2-6/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 1.40 Amps Motor Data FCU-2-6/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 2.30 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-2-6/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-2-6/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-2-6/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.45 in. wc Suction SP -0.18 in. wc Discharge SP 0.27 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Corridor 237 CD 2412 1.00 *305 310 102 Outlet-02 Corridor 237 CD 2412 1.00 *305 305 100 Outlet-03 Corridor 237 CD 2412 1.00 *305 305 100 Totals:----915 0 920 101 FCU-2-6 Supply Outlet Summary Inland Air Balance, Inc. Page 80 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Corridor 237 RG 2414 1.00 *830 832 100 Totals:----830 0 832 100 - FCU-2-6 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 10” Ø Velgrid 0.55 160 85 88 104 Totals:-----85 0 88 104 FCU-2-6 Outside Air Intake Summary Inland Air Balance, Inc. Page 81 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/4/2024 SYSTEM/UNIT: FCU-2-7 AREA: Corridor Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not Listed FCU-2-7/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 655 CFM Actual Airflow 660 CFM Design OSA 230 CFM Actual OSA 239 CFM FCU-2-7/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 0.87 Amps Motor Data FCU-2-7/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-2-7/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-2-7/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-2-7/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.33 in. wc Suction SP -0.11 in. wc Discharge SP 0.22 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Corridor 237 CD 2408 1.00 *150 145 97 Outlet-02 Corridor 237 CD 2408 1.00 *150 145 97 Outlet-03 Beauty Salon 218 LD 48x3 1.00 *140 145 104 Outlet-04 STO 216 CD 2408 1.00 *75 75 100 Outlet-05 Corridor 237 CD 2408 1.00 *140 150 107 Totals:----655 0 660 101 FCU-2-7 Supply Outlet Summary Inland Air Balance, Inc. Page 82 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Corridor 237 RG 2412 1.00 425 408 96 Totals:----425 0 408 96 - FCU-2-7 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 12” Ø Velgrid 0.78 307 230 239 104 Totals:-----230 0 239 104 FCU-2-7 Outside Air Intake Summary Inland Air Balance, Inc. Page 83 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/20/2023 SYSTEM/UNIT: FCU-3-1 AREA: Corridor Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not Listed FCU-3-1/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 640 CFM Actual Airflow 653 CFM Design OSA 100 CFM Actual OSA 162 CFM FCU-3-1/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 0.90 Amps Motor Data FCU-3-1/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-3-1/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-3-1/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-3-1/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.23 in. wc Suction SP -0.10 in. wc Discharge SP 0.13 in. wc Inland Air Balance, Inc. Page 84 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/20/2023 SYSTEM/UNIT: FCU-3-1 AREA: Corridor Unit Manufacturer Photo: Name:Unit Manufacturer.jpg Captured:12/20/2023 7:48 AM Caption: System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Corridor 300 CD 2408 1.00 *200 205 103 Outlet-02 Care Giver ST. 344 CD 2408 1.00 *70 70 100 Outlet-03 Med 345 CD 2406 1.00 *70 72 103 Outlet-04 AL Dir. Office 347 CD 2406 1.00 *100 102 102 Outlet-05 Corridor 300 CD 2408 1.00 *200 204 102 Totals:----640 0 653 102 FCU-3-1 Supply Outlet Summary System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Corridor 300 RG 2412 1.00 *440 443 101 Inlet-02 AL Dir. Office 347 RG 2406 1.00 *100 101 101 Totals:----540 0 544 101 - FCU-3-1 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01*Unit DUCT 6” Ø Pitot Tube 0.20 810 100 162 162 Totals:-----100 0 162 162 FCU-3-1 Outside Air Intake Summary Log:FCU-3-1/OS-01 1/29/2024 Robert Watson OSA increased to make up for OSA not being installed on FC 3–3. All fan coils on third floor Serve common corridor. Inland Air Balance, Inc. Page 85 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/20/2023 SYSTEM/UNIT: FCU-3-2 AREA: Corridor Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not Listed FCU-3-2/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 640 CFM Actual Airflow 630 CFM Design OSA 65 CFM Actual OSA 127 CFM FCU-3-2/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 0.87 Amps Motor Data FCU-3-2/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-3-2/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-3-2/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-3-2/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.40 in. wc Suction SP -0.18 in. wc Discharge SP 0.22 in. wc Inland Air Balance, Inc. Page 86 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/20/2023 SYSTEM/UNIT: FCU-3-2 AREA: Corridor Log:FCU-3-2 1/29/2024 Robert Watson OSA Increased to make up for OSA not being installed on FC 3–3. All fan coils on third-floor serve common Corredor. Unit Manufacturer Photo: Name:Unit Manufacturer.jpg Captured:12/20/2023 9:52 AM Caption: Unit Model Number Photo: Name:Unit Manufacturer.jpg Captured:12/20/2023 9:52 AM Caption: System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Corridor 320 CD 2408 1.00 *135 130 96 Outlet-02 Corridor 320 CD 2408 1.00 *135 135 100 Outlet-03 Corridor 320 CD 2410 1.00 *370 365 99 Totals:----640 0 630 98 FCU-3-2 Supply Outlet Summary Inland Air Balance, Inc. Page 87 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Corridor 320 RG 2412 1.00 *575 562 98 Totals:----575 0 562 98 - FCU-3-2 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 6” Ø Velgrid 0.20 635 65 127 195 Totals:-----65 0 127 195 FCU-3-2 Outside Air Intake Summary Inland Air Balance, Inc. Page 88 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/19/2024 SYSTEM/UNIT: FCU-3-3 AREA: Corridor Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not Listed FCU-3-3/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 640 CFM Actual Airflow 672 CFM Design OSA 185 CFM Actual OSA 0 CFM FCU-3-3/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 1.00 Amps Motor Data FCU-3-3/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-3-3/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-3-3/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-3-3/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP Ns in. wc Actual Total SP 0.44 in. wc Suction SP -0.20 in. wc Discharge SP 0.24 in. wc Inland Air Balance, Inc. Page 89 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/19/2024 SYSTEM/UNIT: FCU-3-3 AREA: Corridor Log:FCU-3-3 1/19/2024 Robert Watson No OSA run to unit. OSA increased on 3 other fan coil serving common Corridor as FC 3–3. Unit Manufacturer Photo: Name:Unit Manufacturer.jpg Captured:12/20/2023 10:56 AM Caption: System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Corridor 3rd Flr CD 2408 1.00 *220 235 107 Outlet-02 Laundry 312 CD 2408 1.00 *200 195 98 Outlet-03 Corridor 3rd Flr CD 2408 1.00 *220 242 110 Totals:----640 0 672 105 FCU-3-3 Supply Outlet Summary System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Corridor 3rd Flr RG 2412 1.00 *455 644 142 Totals:----455 0 644 142 - FCU-3-3 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01*Unit DUCT Air Foil 185 0 0 Totals:-----185 0 0 0 FCU-3-3 Outside Air Intake Summary Log:FCU-3-3/OS-01 1/19/2024 Robert Watson No outside air duct run to unit Inland Air Balance, Inc. Page 90 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/20/2023 SYSTEM/UNIT: FCU-3-4 AREA: Corridor Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not Listed FCU-3-4/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 640 CFM Actual Airflow 687 CFM Design OSA 70 CFM Actual OSA 132 CFM FCU-3-4/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 1.00 Amps Motor Data FCU-3-4/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-3-4/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-3-4/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-3-4/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.38 in. wc Suction SP -0.17 in. wc Discharge SP 0.21 in. wc Inland Air Balance, Inc. Page 91 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/20/2023 SYSTEM/UNIT: FCU-3-4 AREA: Corridor Log:FCU-3-4 1/29/2024 Robert Watson OSA increased to make up for OSA not being installed on FC 3–3. All fan coils on third-floor serve common Corredor. Unit Manufacturer Photo: Name:Unit Manufacturer.jpg Captured:12/20/2023 9:05 AM Caption: System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Corridor 3rd Flr CD 2408 1.00 *135 146 108 Outlet-02 Corridor 3rd Flr CD 2408 1.00 *135 149 110 Outlet-03 Corridor 3rd Flr CD 2412 1.00 *370 392 106 Totals:----640 0 687 107 FCU-3-4 Supply Outlet Summary System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Corridor 3rd Flr RG 2414 1.00 570 614 108 Totals:----570 0 614 108 - FCU-3-4 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 6” Ø Air Foil 0.20 660 70 132 189 Totals:-----70 0 132 189 FCU-3-4 Outside Air Intake Summary Inland Air Balance, Inc. Page 92 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/28/2023 SYSTEM/UNIT: FCU-B-01 AREA: Staff Break Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not Listed FCU-B-01/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 640 CFM Actual Airflow 640 CFM Design OSA 90 CFM Actual OSA 92 CFM FCU-B-01/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 0.80 Amps Motor Data FCU-B-01/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-B-01/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-B-01/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-B-01/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.25 in. wc Suction SP -0.15 in. wc Discharge SP 0.10 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Staff Break B23 CD 2410 1.00 *320 325 102 Outlet-02 Staff Break B23 CD 2410 1.00 *320 315 98 Totals:----640 0 640 100 FCU-B-01 Supply Outlet Summary Inland Air Balance, Inc. Page 93 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Staff Break B23 RG 2412 1.00 550 548 100 Totals:----550 0 548 100 - FCU-B-01 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 8” Ø Air-foil 0.35 263 90 92 102 Totals:-----90 0 92 102 FCU-B-01 Outside Air Intake Summary Inland Air Balance, Inc. Page 94 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/10/2024 SYSTEM/UNIT: FCU-B-02A AREA: Corridor Unit Data Unit Manufacturer LG Unit Model Number LHN368HV Unit Serial Number Not Listed FCU-B-02A/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x25x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 935 CFM Actual Airflow 978 CFM Design OSA 260 CFM Actual OSA 264 CFM FCU-B-02A/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 1.20 Amps Motor Data FCU-B-02A/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 2.30 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-B-02A/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-B-02A/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-B-02A/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.48 in. wc Suction SP 0.19 in. wc Discharge SP 0.29 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Wellness B09 SWS 12x10 0.63 413 250 260 104 Outlet-02 Wellness B09 SWS 12x10 0.63 411 250 258 103 Outlet-03 Corridor B13 CD 2408 1.00 *215 223 104 Outlet-04 Corridor B13 CD 2408 1.00 *220 237 108 Totals:----935 0 978 105 FCU-B-02A Supply Outlet Summary Inland Air Balance, Inc. Page 95 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Corridor B13 RG 2412 1.00 *435 421 97 Inlet-02 Wellness B09 SWR 12x10 0.83 333 265 276 104 Totals:----700 0 697 100 - FCU-B-02A Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 8” Ø Air-foil 0.35 754 260 264 102 Totals:-----260 0 264 102 FCU-B-02A Outside Air Intake Summary Inland Air Balance, Inc. Page 96 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:12/29/2023 SYSTEM/UNIT: FCU-B-02B AREA: Wellness Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not listed FCU-B-02B/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 650 CFM Actual Airflow 681 CFM Design OSA 225 CFM Actual OSA 226 CFM FCU-B-02B/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 1.01 Amps Motor Data FCU-B-02B/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-B-02B/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-B-02B/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-B-02B/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.40 in. wc Suction SP -0.20 in. wc Discharge SP 0.20 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Wellness B09 CD 2406 1.00 *55 59 107 Outlet-02 Wellness B09 SWS 20x10 1.00 *595 622 105 Totals:----650 0 681 105 FCU-B-02B Supply Outlet Summary Inland Air Balance, Inc. Page 97 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Wellness B09 SWR 14x10 1.00 *425 433 102 Totals:----425 0 433 102 - FCU-B-02B Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 10 airfoil 0.55 411 225 226 100 Totals:-----225 0 226 100 FCU-B-02B Outside Air Intake Summary Inland Air Balance, Inc. Page 98 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:12/29/2023 SYSTEM/UNIT: FCU-B-03 AREA: Corridor Unit Data Unit Manufacturer LG Unit Model Number LHN248HV Unit Serial Number Not listed FCU-B-03/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 620 CFM Actual Airflow 672 CFM Design OSA 235 CFM Actual OSA 245 CFM FCU-B-03/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 0.98 Amps Motor Data FCU-B-03/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 1.60 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-B-03/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-B-03/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-B-03/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.40 in. wc Suction SP -0.18 in. wc Discharge SP 0.22 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Corridor B02 CD 2410 1.00 *215 223 104 Outlet-02 Theater B03 SWG 18x4 0.40 563 205 225 110 Outlet-03 Theater B03 SWG 18x4 0.40 560 205 224 109 Totals:----625 0 672 108 FCU-B-03 Supply Outlet Summary Inland Air Balance, Inc. Page 99 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Theater B03 SWR 18x4 0.50 371 190 186 98 Inlet-02 Theater B03 SWR 18x4 0.50 368 195 184 94 Totals:----385 0 370 96 - FCU-B-03 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 10 Airfoil 0.55 445 235 245 104 Totals:-----235 0 245 104 FCU-B-03 Outside Air Intake Summary Inland Air Balance, Inc. Page 100 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:Robert Watson Date:1/10/2024 SYSTEM/UNIT: FCU-B-04 AREA: Salon Unit Data Unit Manufacturer LG Unit Model Number LHN368HV Unit Serial Number Not listed FCU-B-04/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 1 Filter Size - S1 14x16x2 Filter Qty - S2 1 Filer Size - S2 14x25x2 Test Data Design Airflow 670 CFM Actual Airflow 677 CFM Design OSA 360 CFM Actual OSA 377 CFM FCU-B-04/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 233 Volts Motor Amps T1 1.50 Amps Motor Data FCU-B-04/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 2.30 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-B-04/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-B-04/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-B-04/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP Ns in. wc Actual Total SP 0.41 in. wc Suction SP 0.11 in. wc Discharge SP 0.30 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Salon/Spa B04 SWG 12x8 0.57 560 310 319 103 Outlet-02 Salon/Spa B04 SWG 12x8 0.57 532 310 303 98 Outlet-03 Massage SWG 8x8 0.38 145 50 55 110 Totals:----670 0 677 101 FCU-B-04 Supply Outlet Summary Inland Air Balance, Inc. Page 101 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Salon/Spa B04 SWR 10x10 0.69 371 280 256 91 Inlet-02 Massage SWR 8x8 0.44 115 50 51 102 Totals:----330 0 307 93 - FCU-B-04 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 16x10 Velgrid 1.11 340 360 377 105 Totals:-----360 0 377 105 FCU-B-04 Outside Air Intake Summary Inland Air Balance, Inc. Page 102 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/28/2023 SYSTEM/UNIT: FCU-B-05 AREA: Activity Log:FCU-B-05 12/28/2023 David Ramirez CFM value was not specified for Office B07. Supply Air was set to an approximation determined by room square footage. Unit Data Unit Manufacturer LG Unit Model Number LHN368HV Unit Serial Number Not Listed FCU-B-05/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 2 Filter Size - S1 14x25x2 Test Data Design Airflow 730 CFM Actual Airflow 810 CFM Design OSA 150 CFM Actual OSA 160 CFM FCU-B-05/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 205 Volts Motor Amps T1 1.50 Amps Motor Data FCU-B-05/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 2.30 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-B-05/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-B-05/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-B-05/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.31 in. wc Suction SP -0.20 in. wc Discharge SP 0.11 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Activity B06 CD 2410 1.00 *365 355 97 Outlet-02 Activity B06 CD 2410 1.00 *365 350 96 Outlet-03 Office B07 CD 2406 1.00 *NS 105 Totals:----730 0 810 111 FCU-B-05 Supply Outlet Summary Inland Air Balance, Inc. Page 103 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Activity B06 RG 2414 1.00 *635 580 91 Totals:----635 0 580 91 - FCU-B-05 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 8” Ø Air-foil 0.35 457 150 160 107 Totals:-----150 0 160 107 FCU-B-05 Outside Air Intake Summary Inland Air Balance, Inc. Page 104 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/28/2023 SYSTEM/UNIT: FCU-B-08 AREA: Laundry Unit Data Unit Manufacturer LG Unit Model Number LHN368HV Unit Serial Number Not Listed FCU-B-08/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 2 Filter Size - S1 14x25x2 Test Data Design Airflow 595 CFM Actual Airflow 595 CFM Design OSA 450 CFM Actual OSA 455 CFM FCU-B-08/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 205 Volts Motor Amps T1 1.30 Amps Motor Data FCU-B-08/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 2.30 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-B-08/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-B-08/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-B-08/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.39 in. wc Suction SP -0.10 in. wc Discharge SP 0.29 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Laundry B20 CD 2410 1.00 *300 305 102 Outlet-02 Laundry B20 CD 2410 1.00 *295 290 98 Totals:----595 0 595 100 FCU-B-08 Supply Outlet Summary Inland Air Balance, Inc. Page 105 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Area Served Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 Laundry B20 RG 2410 1.00 *145 140 97 Totals:----145 0 140 97 - FCU-B-08 Return Inlet Summary System/Unit Area Served Outlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final OS-01 Unit DUCT 12” Ø Velgrid 0.78 583 450 455 101 Totals:-----450 0 455 101 FCU-B-08 Outside Air Intake Summary Inland Air Balance, Inc. Page 106 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones Tested By:David Ramirez Date:12/28/2023 SYSTEM/UNIT: FCU-B-09 AREA: Main Elec. Log:FCU-B-09 12/28/2023 David Ramirez FCU installed is a ducted fancoil unit. Air values are not specified for three diffusers. Unit was set for total. Unit Data Unit Manufacturer LG Unit Model Number LHN368HV Unit Serial Number Not Listed FCU-B-09/SF Filter Filter Manufacturer Endurex Filter Type Pleated Design MERV Rating 13 Actual MERV Rating 13 Filter Qty - S1 2 Filter Size - S1 14x25x2 Test Data Design Airflow 1412 CFM Actual Airflow 1493 CFM Design OSA 0 CFM Actual OSA 0 CFM FCU-B-09/Supply Fan Design Fan RPM NS RPM Actual Fan RPM NVL RPM Motor Operating HZ/Speed 60/High-Speed Hz Motor Volts T1-T2 205 Volts Motor Amps T1 3.20 Amps Motor Data FCU-B-09/Supply Fan Nameplate Motor Manufacturer LG Nameplate Motor Frame Direct Drive Nameplate Motor FL Amps 2.30 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.00 Motor Data FCU-B-09/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 208-230 Volts Motor RPM Not Listed RPM Motor Phase 1 Sheave Data FCU-B-09/Supply Fan Sheave Position Direct Drive Number of Belts 0 Belt Size Direct Drive Sheave Center Line Distance Direct Drive in. Sheave Data FCU-B-09/Supply Fan Motor Fan Sheave Diameter Direct Drive in. Direct Drive in. Sheave Bore Direct Drive in. Direct Drive in. Test Pressures Design Total SP NS in. wc Actual Total SP 0.08 in. wc Suction SP -0.02 in. wc Discharge SP 0.06 in. wc System/Unit Area Served Outlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Outlet-01 Electrical Room B26 SWS 18x10 1.00 *1412 498 35 Outlet-02 Electrical Room B26 SWS 18x10 1.00 *NS 498 Outlet-03 Electrical Room B26 SWS 18x10 1.00 *NS 497 Totals:----1412 0 1493 106 FCU-B-09 Supply Outlet Summary Inland Air Balance, Inc. Page 107 of 129 Fan CoilPROJECT: LOCATION: Clearwater at Newport Beach Oppidan Investments Company Newport Beach, CA 2312-39PROJECT #: DATE: CONTACT: 1/29/2024 David Jones System/Unit Inlet Type Size LxW / D AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final % Final Velocity Inlet-01 S.O.47 1/2x12 3.96 377 1412 1493 106 Totals:----1412 0 1493 106 - FCU-B-09 Return Inlet Summary Inland Air Balance, Inc. Page 108 of 129 14 1 14 2 14 1 Page 109 of 129 1 1 1 1 1 2 1 3 1 4 1 2 1 1 2 1 11 01 3 1 3 2 3 3 3 1 3 2 3 3 3 4 3 5 3 6 2 1 2 2 2 1 2 2 7 3 Page 110 of 129 14 3 14 4 6 1 6 2 6 3 6 1 6 2 6 3 7 1 7 2 7 1 7 2 7 3 7 4 8 1 8 2 8 1 8 2 8 3 8 4 9A 1 9A 2 9A 1 9A 2 9A 3 9A 4 9B 1 9B 2 9B 1 9B 2 9B 3 9B 4 9B 5 10 1 10 1 10 2 10 3 10 4 1 1 1 2 1 3 1 4 1 5 1 6 1 1 Page 111 of 129 5 1 5 1 5 2 5 3 5 4 6 1 6 2 12 01 13 1 13 1 12 112 2 12 1 12 2 1 1 2 1 2 2 11 1 11 2 11 3 11 1 11 2 11 3 Page 112 of 129 6 1 6 1 13 01 9 1 5 1 5 1 5 2 1 1 1 2 1 1 1 2 1 3 1 4 1 5 1 6 2 1 2 2 2 1 2 2 2 3 2 4 2 5 3 1 3 1 3 2 1 1 7 2 Page 113 of 129 EF-7 7 1 4 1 4 2 4 1 4 2 4 3 4 4 2 1 3 1 Page 114 of 129 6 2 6 3 7 1 7 1 7 2 2 2 1 Page 115 of 129 7 3 7 4 7 5 EF-8 8 2 10 01 1 1 Page 116 of 129 4 1 4 1 4 2 4 3 RF-3-1 1 1 Page 117 of 129 1 1 1 1 1 2 1 3 1 4 1 5 1 2 2 1 3 1 Page 118 of 129 2 1 2 1 2 2 2 3 Page 119 of 129 3 1 3 1 3 2 8 1 EF-3-2 2 1 3 3 1 1 Page 120 of 129 1 1 1 2 1 1 1 1 3 12 1 2A 1 2A 2 2A 1 2A 2 2A 3 2A 4 1 1 2 1 Page 121 of 129 8 1 8 1 8 2 5 1 1 1 1 2 1 3 1 4 1 5 6 1 4 1 Page 122 of 129 4 1 2B 1 2B 1 2B 2 3 1 3 2 3 1 3 2 3 3 4 1 4 1 4 2 5 1 5 2 5 1 5 3 3 1 7 1 9 1 Page 123 of 129 Page 124 of 129 Page 125 of 129 Page 126 of 129 Page 127 of 129 Manufacturer Evergreen Telemetry Calibration Environment Product Pressure / Velocitv Module Temperature 74 oF Model S-PVF-1 Rel. Humiditv 26 % SN 2200540C Bar. Pressure 28.6 in Hq EVEBONEEil Certificate of Cal i bration lnland Air BalancefELEMEINY [[ ns rouno p as lett F 'n Tolerance E out of rolerance Calibration Data N|ST-Traceable Lab Calibration Standards This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be within the specified tolerance unless otherwise stated. lt has been calibrated using measurement standards traceable to the National lnstitue of Standards and Technology, or accepted intrinsic standards of measurement, or derived by the ratio type of self calibrated techniques. 30-Nov-2023 30-Nov-2025 Calibration Date Date Due , Mesa, AZ85202 Measurement Variable Test Point Cal Standard Allowable Range Test lnstrumentMinMax Barometric Pressure (in Hg) Spec -2Yo - 0.1 + 2o/o + 0.1 1 20.0 20.1 2 28.6 28.7 3 33.0 33.1 Differental Pressure (in wc) Via Pitot Velocity Pressure (inW.C. / FPM) -3Yo -7 Spec -2Yo-.001 +2o/o+.001 1 10.00 9.976 2 2.000 1.994 3 0.5000 0.4966 4 0.0500 0.0498 5 -10.00 -10.009 6 -0.0s00 -0.0497 -3% -7 +3o/o + 7 7 0,00064 / 101 101 B 0.0160 i 507 506 lndicates out of tolerance condition --------t Variable Svstem lD Calibration Last Calibration Due Pressure 7481227 8-Mar-23 B-Mar-25 Pressure 7568470 8-Mar-23 8-Mar-25 Pressure 787 1917 12-Seo-23 12-Sep-25 Pressure 7870754 1 2-Sep-23 12-Sep-25 Pressure 2205000006 1 3-Sep-23 1 3-Sep-25 Pressure 1 208000080 1 3-Feb-23 '13-Feb-25 Pressure 41 001 F6C 27-Apr-23 27-Aor-25 Velocity 21 001 91A 24-Feb-23 24-Feb-25 Velocity 21 001 90A 1-May-23 1-May-25 Calibrated By 602.574.6192 t i r33S Page 128 of 129 Manufacturer Evergreen Telemetry Calibration Environment Product Water Pressure Sensing Module Temperature 77 oF Model s-DP-250 Rel. Humidity 32 o/o SN 22001588 Bar. Pressure 28.6 in Hq EYENfrNEEN Certificate of Cal ibration lnland Air BalanceTELEMEIfrY E Rs rouno E eslen E tn Toterance E out of rolerance Calibration Data NIST-Traceable Calibration Lab Standards This instrument has been checked foraccuracy, calibrated lo manufactureds specifications, and found to be within the specilied lolerance unless otherwise stated. lt has been calibrated using measurement standards traceable to the National lnstitue of Standards and Technology, or accepted intrinsic standards of measuremenl, 7-Sep-2023 7-Sep-2024 Calibration Date Date Due Mesa,M85202 Specification +l- 2o/" +l- last dioit Cal srd Sensor 1 Diff Pres Difference Cal std Sensor 2 Gaqe Lo Ditr Approx Set Point (Yo)ofto PSI (ffwc)(flwc)(ftwc)(ftwc) 0.13 0.3 0.3 0 0.3 0.3 0 o.434 1.0 1.0 0 1.0 1.0 0 0.867 2.0 2.0 0 2.0 2.0 0 2.168 5.0 5.0 0 5.0 5.0 0 PSI PSI PSI PSI 10 10.0 10.0 0.0 10.0 10.1 1.0 40 40.0 40.0 0.0 40.0 40.1 0.3 80 80.0 80.4 0.5 80.0 80.5 0.6 120 120.0 120.1 0.1 120.0 120.1 0.1 240 240.0 240.3 0.1 240.0 240.3 0.1 Gonversion PSI ftwc inwc 1.00 2.307 27.68 0.434 1.00 12.00 lndicat€s out of tolerance condition -,1 Variable System lD Calibration Last Calibration Due Pressure 5564304 20-Sep-21 20-Sep-23 Temoerature 21396189 5-Oct-21 SOct-23 or derived.by the ratio type qf s9(calibrated techniques. r33S602.574.6192t Page 129 of 129