HomeMy WebLinkAboutX2021-2737 - Misc (2)
465 Borrego Court, Suite C
San Dimas, CA 91773
Phone: (909) 305-4881
Lic # 837772
www.Inlandairbalance.com
Test & Balance Report
Project Name: Clearwater at Newport Beach Oppidan Investments Company
Address: 101 Bayview Place, Newport Beach, CA 92660
Job Number: 2312-39
Technician: R. Watson, D. Ramirez
Contractor: Christian Bros
Date: 01/29/2024
WARRANTY INFORMATION:
THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL
ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB
PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, AND BALANCING OF ENVIROMENTAL SYSTEMS. THE
MEASURMENTS SHOWN, AND THE INFORMATION GIVEN, IN THIS REPORT ARE CERTIFIED TO BE ACCURATE
AND COMPETE, AT THE TIME AND DATE INFORMATION WAS GATHERED. ANY VARIANCES FROM DESIGN
QUANTITIES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE TEST - ADJUST - BALANCE REPORT
PROJECT SUMMARY.
Model No.Serial No.
CH-15D 2300106
PR-TH-1 2300126
PR-T-4-6 2300123
335 88303077
S-DP-250 2200158
S-DP-250 2200158
PR-TH-1 2300126
S-PVF-1 2200540C
MT-200 B22933010P
AK Free Area Factor HZ Hertz
BHP Brake Horse Power LAT Leaving Air Temperature
CD Ceiling Diffuser LSD Linear Slot Diffuser
CFM Cubic Feet per Minute LWT Leaving Water Temperature
CHWR Chilled Water Return MAT Mixed Air Temperature
CHWS Chilled Water Supply N/A Not Accessible
CSD Ceiling Supply Diffuser N/I Not Installed
CSG Ceiling Supply Grille N/L Not Listed
CWR Condensor Water Return N/S Not Shown
CWS Condensor Water Supply NVL No Valid Location
DA Direct Acting OSA Outside Air
DNA Data Not Available R.A Reverse Acting
DT Duct Traverse RA Return Air
EA Exhaust Air RG Return Grill
EAT Entering Air Temperature RPM Revolutions per Minute
EG Exhaust Grill SA Supply Air
ESP External Static Pressure SP Static Pressure
EWT Entering Water Temperature SWG Sidewall Diffuser
FFU Fan Filter Unit TBD To Be Determined
FLA Full Load Amps TSP Total Static Pressure
FPM Feet per Minute T-STAT Thermostat
GF Grease Filter UTR Unable to Read
HEPA High Efficiency Particulate Air V Volts
HP Horse Power VAV Variable Air Volume
HWR Hot Water Return VP Velocity Pressure
HWS Hot Water Supply
Abbreviation Index
Instrumentation:
11/30/2024Air Temperature/Pressure/Velocity Evergreen Telem.
Non-Contact Tachometer Tach Cal 3/6/2024
3/31/2024
4/4/2024
3/6/2024
9/7/2024
9/7/2024
3/31/2024
Evergreen Telem.
Evergreen Telem.
Fluke
Evergreen Telem.
Evergreen Telem.
Evergreen Telem.
Air Temperature W/ Probe
Immersion Temperature W/ Probe
Voltage-Amperage Meter
Hydronic Pressure
Hydronic Differential Pressure
Humidity
Instrument Manufacturer Calibration Due
Balancing Hood Evergreen Telem.N/A
Table Of ContentsPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Table Of Contents
1 Field Note Report Summary.....................................................................................................................................1
2 Fan Unit....................................................................................................................................................................2
2.1 EF-01..................................................................................................................................................................2
2.2 EF-02..................................................................................................................................................................3
2.3 EF-03..................................................................................................................................................................4
2.4 EF-04..................................................................................................................................................................5
2.5 EF-05..................................................................................................................................................................6
2.6 EF-06..................................................................................................................................................................7
2.7 EF-07..................................................................................................................................................................8
2.8 EF-08..................................................................................................................................................................10
2.9 EF-09..................................................................................................................................................................11
2.10 EF-10................................................................................................................................................................12
2.11 EF-11................................................................................................................................................................13
2.12 EF-12................................................................................................................................................................14
2.13 EF-13................................................................................................................................................................15
2.14 GEF-01.............................................................................................................................................................16
2.15 MAU-01(kitchen hoods)....................................................................................................................................18
2.16 MAU-01(kitchen hoods)/Kitchen Hood-01........................................................................................................19
2.17 MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-01..........................................................................................20
2.18 MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-02..........................................................................................22
2.19 RF-1-01............................................................................................................................................................24
2.20 RF-1-02............................................................................................................................................................25
2.21 RF-2-01............................................................................................................................................................25
2.22 RF-2-02............................................................................................................................................................26
2.23 RF-3-01............................................................................................................................................................27
2.24 RF-3-02............................................................................................................................................................29
3 Fan Coil....................................................................................................................................................................31
3.1 AC-1-01..............................................................................................................................................................31
3.2 AC-1-02..............................................................................................................................................................31
3.3 AC-2-01..............................................................................................................................................................32
3.4 AC-2-02..............................................................................................................................................................32
3.5 AC-2-03..............................................................................................................................................................33
3.6 AC-3-01..............................................................................................................................................................33
3.7 AC-3-02..............................................................................................................................................................34
3.8 AC-3-03..............................................................................................................................................................34
3.9 AC-B-01..............................................................................................................................................................35
3.10 AC-B-02............................................................................................................................................................35
3.11 AC-B-03............................................................................................................................................................36
3.12 AC-B-04............................................................................................................................................................36
3.13 AC-B-06............................................................................................................................................................37
3.14 AC-B-07............................................................................................................................................................38
Inland Air Balance, Inc.
Table Of ContentsPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
3.15 FCU-1-01..........................................................................................................................................................39
3.16 FCU-1-02..........................................................................................................................................................41
3.17 FCU-1-03..........................................................................................................................................................43
3.18 FCU-1-04..........................................................................................................................................................45
3.19 FCU-1-05..........................................................................................................................................................47
3.20 FCU-1-06..........................................................................................................................................................49
3.21 FCU-1-07..........................................................................................................................................................51
3.22 FCU-1-08..........................................................................................................................................................53
3.23 FCU-1-09A.......................................................................................................................................................55
3.24 FCU-1-09B.......................................................................................................................................................57
3.25 FCU-1-10..........................................................................................................................................................59
3.26 FCU-1-11..........................................................................................................................................................61
3.27 FCU-1-12..........................................................................................................................................................63
3.28 FCU-1-13..........................................................................................................................................................65
3.29 FCU-1-14..........................................................................................................................................................67
3.30 FCU-2-01..........................................................................................................................................................69
3.31 FCU-2-02..........................................................................................................................................................71
3.32 FCU-2-03..........................................................................................................................................................73
3.33 FCU-2-04..........................................................................................................................................................75
3.34 FCU-2-05..........................................................................................................................................................77
3.35 FCU-2-6............................................................................................................................................................79
3.36 FCU-2-7............................................................................................................................................................81
3.37 FCU-3-1............................................................................................................................................................83
3.38 FCU-3-2............................................................................................................................................................85
3.39 FCU-3-3............................................................................................................................................................88
3.40 FCU-3-4............................................................................................................................................................90
3.41 FCU-B-01.........................................................................................................................................................92
3.42 FCU-B-02A.......................................................................................................................................................94
3.43 FCU-B-02B.......................................................................................................................................................96
3.44 FCU-B-03.........................................................................................................................................................98
3.45 FCU-B-04.........................................................................................................................................................100
3.46 FCU-B-05.........................................................................................................................................................102
3.47 FCU-B-08.........................................................................................................................................................104
3.48 FCU-B-09.........................................................................................................................................................106
4 Clearwater Coded Drawing 1st Flr Area A.pdf.........................................................................................................108
5 Clearwater Coded Drawing 1st Flr Area B.pdf.........................................................................................................109
6 Clearwater Coded Drawing 1st Flr Area C.pdf.........................................................................................................110
7 Clearwater Coded Drawing 1st Flr Area D.pdf.........................................................................................................111
8 Clearwater Coded Drawing 2nd Flr Area A.pdf........................................................................................................112
9 Clearwater Coded Drawing 2nd Flr Area B.pdf........................................................................................................113
10 Clearwater Coded Drawing 2nd Flr Area C.pdf......................................................................................................114
11 Clearwater Coded Drawing 2nd Flr Area D.pdf......................................................................................................115
Inland Air Balance, Inc.
Table Of ContentsPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
12 Clearwater Coded Drawing 3rd Flr Area A.pdf.......................................................................................................116
13 Clearwater Coded Drawing 3rd Flr Area B.pdf.......................................................................................................117
14 Clearwater Coded Drawing 3rd Flr Area C.pdf.......................................................................................................118
15 Clearwater Coded Drawing 3rd Flr Area D.pdf.......................................................................................................119
16 Clearwater Coded Drawing Basement Area B.pdf.................................................................................................120
17 Clearwater Coded Drawing Basement Area C.pdf.................................................................................................121
18 Clearwater Coded Drawing Basement Area D.pdf.................................................................................................122
19 Instrument Certifications.pdf..................................................................................................................................123
Inland Air Balance, Inc.
Page 1 of 129
Field Note Report SummaryPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Test System / Unit Name Date Contact Notes / Logs
Fan Unit EF-01 29-Dec-23 David Ramirez Self contained fan.
Fan Unit EF-06 29-Jan-24 Robert Watson Self contained fan
Fan Unit EF-09 3-Jan-24 Robert Watson Self contained fan
Fan Unit EF-12 28-Dec-23 David Ramirez Self-contained fan.
Fan Unit RF-1-02 4-Jan-24 Robert Watson Self-contained fan
Fan Unit RF-2-01 29-Jan-24 Robert Watson Self contained fan
Fan Unit RF-2-02 21-Dec-23 David Ramirez Self-contained Relief Fan Unit.
Fan Coil AC-B-06 29-Dec-23 David Ramirez Schedule change. FCU is now a 2 ton wall-split
Fan Coil AC-B-07 29-Dec-23 David Ramirez Schedule change. FCU is now a wall-split.
Fan Coil FCU-1-01 21-Dec-23 David Ramirez RA+OSA does not equate to SA volume. Return
Inlet 01, in corridor 104, was set to make up
the difference in air volume.
Fan Coil FCU-1-09A 27-Dec-23 David Ramirez Right RA volume damper shaft is disconnected
from handle.
Fan Coil FCU-3-2 29-Jan-24 Robert Watson OSA Increased to make up for OSA not being
installed on FC 3–3. All fan coils on third-floor
serve common Corredor.
Fan Coil FCU-3-3 19-Jan-24 Robert Watson No OSA run to unit. OSA increased on 3 other
fan coil serving common Corridor as FC 3–3.
Fan Coil FCU-3-4 29-Jan-24 Robert Watson OSA increased to make up for OSA not being
installed on FC 3–3. All fan coils on third-floor
serve common Corredor.
Fan Coil FCU-B-05 28-Dec-23 David Ramirez CFM value was not specified for Office B07.
Supply Air was set to an approximation
determined by room square footage.
Fan Coil FCU-B-09 28-Dec-23 David Ramirez FCU installed is a ducted fancoil unit. Air values
are not specified for three diffusers. Unit was
set for total.
Supply Outlet FCU-2-03/Outlet-02 21-Dec-23 David Ramirez Fire/Smoke Damper does not have power
landed. Mechanical and Electrical contractors
have been made aware. FSD was manually
opened, FCU was balanced.
Outside Air Intake FCU-3-1/OS-01 29-Jan-24 Robert Watson OSA increased to make up for OSA not being
installed on FC 3–3. All fan coils on third floor
Serve common corridor.
Outside Air Intake FCU-3-3/OS-01 19-Jan-24 Robert Watson No outside air duct run to unit
K-EF MAU-01(kitchen
hoods)/Kitchen Hood-01/K-
EF-02
3-Jan-24 Robert Watson Dishwasher fan does not run through ACCRUEX
panel. Tested Fan with Vfd in hand
Inland Air Balance, Inc.
Page 2 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/29/2023
SYSTEM/UNIT: EF-01
AREA: Staff Break
Log:EF-01 12/29/2023 David Ramirez Self contained fan.
Unit Data
Unit Manufacturer Pennbarry
Unit Model Number Z12GP
Unit Serial Number E23IZ89062
Test Data
Motor Operating HZ/Speed 60 HZ/Speed 33
Motor Volts T1-T2 204 Volts
Motor Amps T1 1.00 Amps
Motor Data
Thermally Protected?Yes
Nameplate Motor Manufacturer Genteq
Nameplate Motor Frame Direct Drive
Nameplate Motor HP 1/2 HP
Nameplate Motor Rated Volts 208 Volts
Nameplate Motor RPM 1355 RPM
Nameplate Motor FL Amps 8.10 Amps
Nameplate Motor Phase 1
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Sheave Data
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP 1.00 in. wc
Actual Total SP NA in. wc
Design External SP NS in. wc
Actual External SP NA in. wc
Actual Suction SP NVL in. wc
Actual Discharge SP NVL in. wc
Test Results
Design Airflow 85 CFM
Actual Airflow 90 CFM
Design Fan RPM 1355 RPM
Actual Fan RPM NVL RPM
Actual Motor RPM NVL
Inland Air Balance, Inc.
Page 3 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/29/2024
SYSTEM/UNIT: EF-02
AREA: Women
Unit Data
Unit Manufacturer Pennbarry
Unit Model Number Z12GP
Unit Serial Number D23EZ30794
Test Data
Motor Operating HZ/Speed 60 HZ/Speed 44
Motor Volts T1-T2 204 Volts
Motor Amps T1 1.00 Amps
Motor Data
Thermally Protected?Yes
Nameplate Motor Manufacturer Genteq
Nameplate Motor Frame Direct Drive
Nameplate Motor HP 1/2 HP
Nameplate Motor Rated Volts 208 Volts
Nameplate Motor RPM 1355 RPM
Nameplate Motor FL Amps 8.10 Amps
Nameplate Motor Phase 1
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Sheave Data
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP 1.00 in. wc
Actual Total SP NA in. wc
Design External SP NS in. wc
Actual External SP NA in. wc
Actual Suction SP NVL in. wc
Actual Discharge SP NVL in. wc
Test Results
Design Airflow 210 CFM
Actual Airflow 237 CFM
Design Fan RPM 1355 RPM
Actual Fan RPM NVL RPM
Actual Motor RPM NVL
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Men’s EG 22x12 1.00 *215 237 110
Totals:----215 0 237 110 -
EF-02 Exhaust Inlet Summary
Inland Air Balance, Inc.
Page 4 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/10/2024
SYSTEM/UNIT: EF-03
AREA: Men
Unit Data
Unit Manufacturer Pennbarry
Unit Model Number Z12GP
Unit Serial Number D23EZ03799
Test Data
Motor Operating HZ/Speed 60 HZ/Speed 24
Motor Volts T1-T2 204 Volts
Motor Amps T1 3.00 Amps
Motor Data
Thermally Protected?Yes
Nameplate Motor Manufacturer Genteq
Nameplate Motor Frame Direct Drive
Nameplate Motor HP 1/2 HP
Nameplate Motor Rated Volts 208 Volts
Nameplate Motor RPM 1355 RPM
Nameplate Motor FL Amps 8.10 Amps
Nameplate Motor Phase 1
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Sheave Data
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP 0.50 in. wc
Actual Total SP NA in. wc
Design External SP NS in. wc
Actual External SP NA in. wc
Actual Suction SP NVL in. wc
Actual Discharge SP NVL in. wc
Test Results
Design Airflow 210 CFM
Actual Airflow 213 CFM
Design Fan RPM 1355 RPM
Actual Fan RPM NVL RPM
Actual Motor RPM NVL
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Mens EG 22x12 1.00 *210 213 101
Totals:----210 0 213 101 -
EF-03 Exhaust Inlet Summary
Inland Air Balance, Inc.
Page 5 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/29/2024
SYSTEM/UNIT: EF-04
AREA: Salon/Spa B04
Unit Data
Unit Manufacturer Pennbarry
Unit Model Number Z12GP
Unit Serial Number D23EZ037
Test Data
Motor Operating HZ/Speed 33HZ/Speed
Motor Volts T1-T2 204 Volts
Motor Amps T1 4.00 Amps
Motor Data
Thermally Protected?Yes
Nameplate Motor Manufacturer Genteq
Nameplate Motor Frame Direct Drive
Nameplate Motor HP 1/2 HP
Nameplate Motor Rated Volts 208 Volts
Nameplate Motor RPM 1355 RPM
Nameplate Motor FL Amps 8.10 Amps
Nameplate Motor Phase 1
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Sheave Data
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP 0.50 in. wc
Actual Total SP NA in. wc
Design External SP NS in. wc
Actual External SP NA in. wc
Actual Suction SP NVL in. wc
Actual Discharge SP NVL in. wc
Test Results
Design Airflow 400 CFM
Actual Airflow 403 CFM
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Actual Motor RPM NVL
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Manicure EG 22x12 1.00 *400 403 101
Totals:----400 0 403 101 -
EF-04 Exhaust Inlet Summary
Inland Air Balance, Inc.
Page 6 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/29/2023
SYSTEM/UNIT: EF-05
AREA: Laundry 147
Unit Data
Unit Manufacturer Pennbarry
Unit Model Number SX115VCGP
Unit Serial Number D23EZ59636
Test Data
Motor Operating HZ/Speed 60
Motor Volts T1-T2 205 Volts
Motor Amps T1 1.30 Amps
Motor Data
Nameplate Motor Manufacturer No Access
Nameplate Motor Frame Direct Drive
Nameplate Motor HP 1/6 HP
Nameplate Motor Rated Volts 208 Volts
Nameplate Motor RPM 1050 RPM
Nameplate Motor FL Amps Not Listed Amps
Nameplate Motor Phase 1
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Sheave Data
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP 1.00 in. wc
Actual Total SP 0.60 in. wc
Design External SP NS in. wc
Actual External SP NA in. wc
Actual Suction SP -0.56 in. wc
Actual Discharge SP 0.04 in. wc
Test Results
Design Airflow 450 CFM
Actual Airflow 475 CFM
Design Fan RPM 1042 RPM
Actual Fan RPM NVL RPM
Actual Motor RPM NVL
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Laundry B20 EG 2412 1.00 450 475 106
Totals:----450 0 475 106 -
EF-05 Exhaust Inlet Summary
Inland Air Balance, Inc.
Page 7 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/29/2024
SYSTEM/UNIT: EF-06
AREA: Corridor
Log:EF-06 1/29/2024 Robert Watson Self contained fan
Motor Data
Nameplate Motor Hertz 60 Hz
Nominal Efficiency (0.00)0.90 %
Motor Power Factor (0.00)0.80
Test Results
Design Airflow 470 CFM
Actual Airflow 513 CFM
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Men 112 EG 2410 1.00 *230 252 110
Inlet-02 Women 113 EG 2410 1.00 *240 261 109
Totals:----470 0 513 109 -
EF-06 Exhaust Inlet Summary
Inland Air Balance, Inc.
Page 8 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/4/2024
SYSTEM/UNIT: EF-07
AREA: Roof
Unit Data
Unit Manufacturer Penn Ventilator
Unit Model Number FX 16
Unit Serial Number E23HZ02926
Test Data
Motor Operating HZ/Speed 6
Motor Volts T1-T2 119 Volts
Motor Amps T1 2.00 Amps
Motor Data
Nameplate Motor Manufacturer McMillan
Nameplate Motor Frame Not Listed
Nameplate Motor HP 243 watt
Nameplate Motor Rated Volts 120 Volts
Nameplate Motor RPM Ns RPM
Nameplate Motor FL Amps 5.20 Amps
Nameplate Motor Phase 1
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Brake Horsepower 0.23 BHP
Nominal Efficiency (0.00)0.90 %
Motor Power Factor (0.00)0.80
Sheave Data
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP NVL in. wc
Actual Suction SP NVL in. wc
Actual Discharge SP NVL in. wc
Test Results
Design Airflow 360 CFM
Actual Airflow 394 CFM
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Actual Motor RPM NVL
Inland Air Balance, Inc.
Page 9 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/4/2024
SYSTEM/UNIT: EF-07
AREA: Roof
Unit Manufacturer Photo:
Name:Unit Manufacturer.jpg
Captured:1/2/2024 10:34 AM
Caption:
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Laundry 250 EG 2408 1.00 *125 136 109
Inlet-02 Laundry 244 EG 2408 1.00 *110 121 110
Inlet-03 Laundry 147 EG 2408 1.00 *125 137 110
Totals:----360 0 394 109 -
EF-07 Exhaust Inlet Summary
Inland Air Balance, Inc.
Page 10 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/4/2024
SYSTEM/UNIT: EF-08
AREA: Roof
Unit Data
Unit Manufacturer Penn Ventilator
Unit Model Number FX 16
Unit Serial Number E23HZ02926
Test Data
Motor Operating HZ/Speed 6
Motor Volts T1-T2 209 Volts
Motor Amps T1 1.00 Amps
Motor Data
Nameplate Motor Manufacturer Mc millan
Nameplate Motor Frame Not Listed
Nameplate Motor HP 243 watt
Nameplate Motor Rated Volts 208 Volts
Nameplate Motor RPM Ns RPM
Nameplate Motor FL Amps 3.20 Amps
Nameplate Motor Phase 1
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Brake Horsepower 0.20 BHP
Nominal Efficiency (0.00)0.90 %
Motor Power Factor (0.00)0.80
Sheave Data
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP NVL in. wc
Actual Suction SP NVL in. wc
Actual Discharge SP NVL in. wc
Test Results
Design Airflow 250 CFM
Actual Airflow 271 CFM
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Actual Motor RPM NVL
Inland Air Balance, Inc.
Page 11 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/4/2024
SYSTEM/UNIT: EF-08
AREA: Roof
Unit Manufacturer Photo:
Name:Unit Manufacturer.jpg
Captured:1/2/2024 10:42 AM
Caption:
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Laundry 312 EG 2408 1.00 *125 136 109
Inlet-02 Beauty Salon
218
EG 48x3 1.00 *125 135 108
Totals:----250 0 271 108 -
EF-08 Exhaust Inlet Summary
Tested By:Robert Watson
Date:1/3/2024
SYSTEM/UNIT: EF-09
AREA: Kitchen
Log:EF-09 1/3/2024 Robert Watson Self contained fan
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Kitchen/Servery
239
EG 2408 1.00 195 208 107
Totals:----195 0 208 107 -
EF-09 Exhaust Inlet Summary
Inland Air Balance, Inc.
Page 12 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/21/2023
SYSTEM/UNIT: EF-10
AREA: HSKP
Unit Data
Unit Manufacturer Pennbarry
Unit Model Number Z12GP
Unit Serial Number D23EZ3084
Test Data
Motor Operating HZ/Speed Speed 60
Motor Volts T1-T2 213 Volts
Motor Amps T1 2.30 Amps
Motor Data
Thermally Protected?Yes
Nameplate Motor Manufacturer Genteq
Nameplate Motor Frame Direct Drive
Nameplate Motor HP 1/2 HP
Nameplate Motor Rated Volts 208 Volts
Nameplate Motor RPM 1355 RPM
Nameplate Motor FL Amps 8.10 Amps
Nameplate Motor Phase 1
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Sheave Data
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP 0.50 in. wc
Actual Total SP 0.08 in. wc
Design External SP NS in. wc
Actual External SP NA in. wc
Actual Suction SP NVL in. wc
Actual Discharge SP 0.08 in. wc
Test Results
Design Airflow 75 CFM
Actual Airflow 80 CFM
Design Fan RPM 1355 RPM
Actual Fan RPM NVL RPM
Actual Motor RPM NVL
System/Unit Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 EG 22x12 1.00 *75 80 107
Totals:----75 0 80 107 -
EF-10 Exhaust Inlet Summary
Inland Air Balance, Inc.
Page 13 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/28/2023
SYSTEM/UNIT: EF-11
AREA: RR
Unit Data
Unit Manufacturer Pennbarry
Unit Model Number Z10GP
Unit Serial Number D23EZ30808
Test Data
Motor Operating HZ/Speed Speed 35
Motor Volts T1-T2 118 Volts
Motor Amps T1 1.50 Amps
Motor Data
Thermally Protected?Yes
Nameplate Motor Manufacturer Genteq
Nameplate Motor Frame Direct Drive
Nameplate Motor HP 1/4 HP
Nameplate Motor Rated Volts 115 Volts
Nameplate Motor RPM 400-1800 RPM
Nameplate Motor FL Amps 3.50 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Sheave Data
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP 0.75 in. wc
Actual Total SP NA in. wc
Design External SP NS in. wc
Actual External SP NA in. wc
Actual Suction SP NVL in. wc
Actual Discharge SP NVL in. wc
Test Results
Design Airflow 115 CFM
Actual Airflow 120 CFM
Design Fan RPM 400-1800 RPM
Actual Fan RPM NVL RPM
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 RR 152 EG 15 1/2x11
1/2
1.00 *115 120 104
Totals:----115 0 120 104 -
EF-11 Exhaust Inlet Summary
Inland Air Balance, Inc.
Page 14 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/28/2023
SYSTEM/UNIT: EF-12
AREA: HSKP
Log:EF-12 12/28/2023 David Ramirez Self-contained fan.
Unit Data
Unit Manufacturer Pennbarry
Unit Model Number Z12GP
Unit Serial Number Not Listed
Test Data
Motor Operating HZ/Speed Speed 44
Motor Volts T1-T2 NVL Volts
Motor Amps T1 NVL Amps
Motor Data
Thermally Protected?Yes
Nameplate Motor Manufacturer Genteq
Nameplate Motor Frame Direct Drive
Nameplate Motor HP 1/2 HP
Nameplate Motor Rated Volts 115 Volts
Nameplate Motor RPM 1355 RPM
Nameplate Motor FL Amps 8.10 Amps
Nameplate Motor Phase 1
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Sheave Data
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP 0.50 in. wc
Actual Total SP NA in. wc
Design External SP NS in. wc
Actual External SP NA in. wc
Actual Suction SP NVL in. wc
Actual Discharge SP NVL in. wc
Test Results
Design Airflow 70 CFM
Actual Airflow 73 CFM
Design Fan RPM 1355 RPM
Actual Fan RPM NVL RPM
Actual Motor RPM NVL
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 HSKP 107 EG 24x12 1.00 70 73 104
Totals:----70 0 73 104 -
EF-12 Exhaust Inlet Summary
Inland Air Balance, Inc.
Page 15 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/21/2023
SYSTEM/UNIT: EF-13
AREA: Unisex
Unit Data
Unit Manufacturer Pennbarry
Unit Model Number Z10GP
Unit Serial Number D23EZ30810
Test Data
Motor Operating HZ/Speed Speed 34
Motor Volts T1-T2 NVL Volts
Motor Amps T1 NVL Amps
Motor Data
Thermally Protected?Yes
Nameplate Motor Manufacturer Genteq
Nameplate Motor Frame Direct Drive
Nameplate Motor HP 1/4 HP
Nameplate Motor Rated Volts 115/230 Volts
Nameplate Motor RPM 1500 RPM
Nameplate Motor FL Amps 2.30 Amps
Nameplate Motor Phase 1
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Sheave Data
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP 0.75 in. wc
Actual Total SP NA in. wc
Design External SP NS in. wc
Actual External SP NA in. wc
Actual Suction SP NVL in. wc
Actual Discharge SP NVL in. wc
Test Results
Design Airflow 90 CFM
Actual Airflow 91 CFM
Design Fan RPM 1580 RPM
Actual Fan RPM NVL RPM
Actual Motor RPM NVL
System/Unit Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 EG 22x12 1.00 *90 91 101
Totals:----90 0 91 101 -
EF-13 Exhaust Inlet Summary
Inland Air Balance, Inc.
Page 16 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/29/2023
SYSTEM/UNIT: GEF-01
AREA: Garage
Unit Data
Unit Manufacturer Pennbarry
Unit Model Number MXI-201A9
Unit Serial Number Not Listed
Test Data
Motor Operating HZ/Speed 58
Motor Volts T1-T2 273 Volts
Motor Volts T2-T3 274 Volts
Motor Volts T1-T3 272 Volts
Motor Amps T1 25.00 Amps
Motor Amps T2 26.00 Amps
Motor Amps T3 24.00 Amps
Motor Data
Nameplate Motor Manufacturer Weg
Nameplate Motor Frame 254/6T
Nameplate Motor HP 15 HP
Nameplate Motor Rated Volts 230/460 Volts
Nameplate Motor RPM 1770 RPM
Nameplate Motor FL Amps 36.40 Amps
Nameplate Motor Phase 3
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.15
Brake Horsepower 11.95 BHP
Nominal Efficiency (0.00)0.92 %
Motor Power Factor (0.00)0.82
Sheave Data
Sheave Position Fixed
Number of Belts 3
Belt Size 5VX750
Sheave Center Line Distance No Access in.
Sheave Data
Motor Fan
Sheave Diameter 3B5V42 in.No Access in.
Sheave Bore 1 5/8 in.No Access in.
Test Pressures
Design Total SP 2.00 in. wc
Actual Total SP 1.42 in. wc
Design External SP NS in. wc
Actual External SP NA in. wc
Actual Suction SP -0.70 in. wc
Actual Discharge SP -0.72 in. wc
Test Results
Design Airflow 17000 CFM
Actual Airflow 17003 CFM
Design Fan RPM 2077 RPM
Actual Fan RPM NVL RPM
Actual Motor RPM 1711
Inland Air Balance, Inc.
Page 17 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Garage B30 EG 46x20 6.39 1077 3400 3677 108
Inlet-02 Garage B30 EG 46x20 6.39 624 3400 3546 104
Inlet-03 Garage B30 EG 46x20 6.39 408 3400 3479 102
Inlet-04 Garage B30 EG 46x20 6.39 293 3400 3176 93
Inlet-05 Garage B30 EG 46x20 6.39 232 3400 3125 92
Totals:----17000 0 17003 100 -
GEF-01 Exhaust Inlet Summary
Inland Air Balance, Inc.
Page 18 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/2/2024
SYSTEM/UNIT: MAU-01(kitchen hoods)
AREA: Kitchen
Unit Data
Unit Manufacturer Captiveaire
Unit Model Number A2-20D
Unit Serial Number Not Listed
Test Data
Motor Operating HZ/Speed 60
Motor Volts T1-T2 233 Volts
Motor Volts T2-T3 230 Volts
Motor Volts T1-T3 233 Volts
Motor Amps T1 11.00 Amps
Motor Amps T2 11.00 Amps
Motor Amps T3 11.00 Amps
Motor Data
Nameplate Motor Manufacturer NA
Nameplate Motor Frame NA
Nameplate Motor HP 5 HP
Nameplate Motor Rated Volts 230 Volts
Nameplate Motor RPM Not Listed RPM
Nameplate Motor FL Amps 14.50 Amps
Nameplate Motor Phase 3
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Brake Horsepower 4.27 BHP
Nominal Efficiency (0.00)0.90 %
Motor Power Factor (0.00)0.80
Sheave Data
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP 1.00 in. wc
Actual Total SP 0.91 in. wc
Actual Suction SP -0.40 in. wc
Actual Discharge SP 0.51 in. wc
Test Results
Design Airflow 4600 CFM
Actual Airflow 4596 CFM
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Actual Motor RPM NVL
System/Unit Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 D.O.120x18 12.75 159 2049 2027 99
Outlet-02 D.O.126x18 13.39 138 1950 1848 95
Outlet-03 CD 2414 1.00 *800 721 90
Totals:----4799 0 4596 96
MAU-01(kitchen hoods) Supply Outlet Summary
Inland Air Balance, Inc.
Page 19 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/2/2024
SYSTEM/UNIT: MAU-01(kitchen hoods)/Kitchen
Hood-01
Unit Data
Hood Manufacturer ACCUREX
Hood Model Number XXEW
Exhaust Section
AVG Velocity - Filter 1 140.0 FPM
AVG Velocity - Filter 2 156.0 FPM
AVG Velocity - Filter 3 165.0 FPM
AVG Velocity - Filter 4 144.0 FPM
AVG Velocity - Filter 5 141.0 FPM
AVG Velocity - Filter 6 155.0 FPM
AVG Velocity - Filter 7 128.0 FPM
AVG Velocity - Filter 8 131.0 FPM
AVG Velocity - Filter 9 166.0 FPM
AVG Velocity - Filter 10 122.0 FPM
AVG Velocity - Filter 11 128.0 FPM
AVG Velocity - Filter 12 117.0 FPM
Exhaust Readings
Filter 1 - Airflow 420 CFM
Filter 2 - Airflow 468 CFM
Filter 3 - Airflow 495 CFM
Filter 4 - Airflow 432 CFM
Filter 5 - Airflow 423 CFM
Filter 6 - Airflow 465 CFM
Filter 7 - Airflow 384 CFM
Filter 8 - Airflow 393 CFM
Filter 9 - Airflow 374 CFM
Filter 10 - Airflow 366 CFM
Filter 11 - Airflow 288 CFM
Filter 12 - Airflow 351 CFM
Final Data
Design Exhaust Airflow 4750 CFM
Duct Size 36x10 in
Hood Duct Connection Area 2.5
Riser Velocity 1944 FPM
Actual Exhaust Airflow 4859 CFM
Design Airflow vs. Actual Airflow 102.3 %
HZ Setting @ Actual Airflow 60.00 Hz
Filter Data
Filter Manufacturer Greenheck
Filter Type Grease
Size - Filter 1 20x20
Size - Filter 2 20x20
Size - Filter 3 20x20
Size - Filter 4 20x20
Size - Filter 5 20x20
Size - Filter 6 20x20
Size - Filter 7 20x20
Size - Filter 8 20x20
Size - Filter 9 16x20
Size - Filter 10 20x20
Size - Filter 11 16x20
Size - Filter 12 20x20
Filter Area - Filter 1 3.00
Filter Area - Filter 2 3.00
Filter Area - Filter 3 3.00
Filter Area - Filter 4 3.00
Filter Area - Filter 5 3.00
Filter Area - Filter 6 3.00
Filter Area - Filter 7 3.00
Filter Area - Filter 8 3.00
Filter Area - Filter 9 2.25
Filter Area - Filter 10 3.00
Filter Area - Filter 11 2.25
Filter Area - Filter 12 3.00
Inland Air Balance, Inc.
Page 20 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/2/2024
SYSTEM/UNIT: MAU-01(kitchen hoods)/Kitchen
Hood-01/K-EF-01
AREA: Kitchen
Unit Data
Fan Manufacturer Captive Aire
Fan Model Number USB124DD
Fan Serial Number Not listed
Linear Feet of Hood 20 ft
Test Data
Actual AirFlow 4859 CFM
Design AirFlow 4750 CFM
MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-01/EF Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60 Hz
Motor Volts T1-T2 210 Volts
Motor Volts T2-T3 210 Volts
Motor Volts T1-T3 209 Volts
Motor Amps T1 11.00 Amps
Motor Amps T2 11.00 Amps
Motor Amps T3 11.00 Amps
Motor Data
MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-01/EF Fan
Nameplate Motor Manufacturer Teco
Nameplate Motor Frame 143T
Nameplate Motor FL Amps 15.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.15
Brake Horsepower 3.86 BHP
Nominal Efficiency (0.00)0.90 %
Motor Power Factor (0.00)0.80
Motor Data
MAU-01(kitchen
hoods)/Kitchen Hood-01/K-
EF-01/EF Fan
Design Nameplate
Motor HP 5 HP
Motor Voltage 208-230/460
Volts
Motor RPM Not Legible
RPM
Motor Phase 3
Sheave Data
MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-01/EF Fan
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Na in.
Sheave Data
MAU-01(kitchen
hoods)/Kitchen Hood-01/K-
EF-01/EF Fan
Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Inland Air Balance, Inc.
Page 21 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/2/2024
SYSTEM/UNIT: MAU-01(kitchen hoods)/Kitchen
Hood-01/K-EF-01
AREA: Kitchen
Fan Manufacturer Photo:
Name:Fan Manufacturer.jpg
Captured:1/2/2024 11:20 AM
Caption:
Inland Air Balance, Inc.
Page 22 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/2/2024
SYSTEM/UNIT: MAU-01(kitchen hoods)/Kitchen
Hood-01/K-EF-02
AREA: Kitchen
Unit Data
Fan Manufacturer Captive Aire
Fan Model Number USBI15DD
Fan Serial Number Not listed
Linear Feet of Hood 7 ft
Test Data
Actual AirFlow 1419 CFM
Design AirFlow 1400 CFM
MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-02/EF Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60 Hz
Motor Volts T1-T2 209 Volts
Motor Volts T2-T3 209 Volts
Motor Volts T1-T3 210 Volts
Motor Amps T1 3.20 Amps
Motor Amps T2 3.20 Amps
Motor Amps T3 3.20 Amps
Motor Data
MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-02/EF Fan
Nameplate Motor Manufacturer Teco
Nameplate Motor Frame 143T
Nameplate Motor FL Amps 3.20 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.15
Brake Horsepower 1.12 BHP
Nominal Efficiency (0.00)0.90 %
Motor Power Factor (0.00)0.80
Motor Data
MAU-01(kitchen
hoods)/Kitchen Hood-01/K-
EF-02/EF Fan
Design Nameplate
Motor HP 5 HP
Motor Voltage 208-230/460
Volts
Motor RPM Not Legible
RPM
Motor Phase 3
Sheave Data
MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-02/EF Fan
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Na in.
Sheave Data
MAU-01(kitchen
hoods)/Kitchen Hood-01/K-
EF-02/EF Fan
Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Inland Air Balance, Inc.
Page 23 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/2/2024
SYSTEM/UNIT: MAU-01(kitchen hoods)/Kitchen
Hood-01/K-EF-02
AREA: Kitchen
Log:MAU-01(kitchen hoods)/Kitchen Hood-
01/K-EF-02
1/3/2024 Robert Watson Dishwasher fan does not run through ACCRUEX
panel. Tested Fan with Vfd in hand
Fan Manufacturer Photo:
Name:Fan Manufacturer.jpg
Captured:1/2/2024 11:21 AM
Caption:
System/Unit Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 D.O.14x12 1.17 1213 1400 1419 101
Totals:----1400 0 1419 101 -
MAU-01(kitchen hoods)/Kitchen Hood-01/K-EF-02 Exhaust Inlet Summary
Inland Air Balance, Inc.
Page 24 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/29/2024
SYSTEM/UNIT: RF-1-01
AREA: Corridor
Unit Data
Unit Manufacturer Pennbarry
Unit Model Number Z12GP
Unit Serial Number D23EZ30791
Test Data
Motor Operating HZ/Speed 42
Motor Volts T1-T2 116 Volts
Motor Amps T1 4.00 Amps
Motor Data
Thermally Protected?Yes
Nameplate Motor Manufacturer Genteq
Nameplate Motor Frame Direct Drive
Nameplate Motor HP 1/2 HP
Nameplate Motor Rated Volts 115 Volts
Nameplate Motor RPM 1355 RPM
Nameplate Motor FL Amps 8.10 Amps
Nameplate Motor Phase 1
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Sheave Data
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP 0.50 in. wc
Actual Total SP 0.23 in. wc
Actual Suction SP 0.13 in. wc
Actual Discharge SP 0.10 in. wc
Test Results
Design Airflow 595 CFM
Actual Airflow 540 CFM
Design Fan RPM 1355 RPM
Actual Fan RPM NVL RPM
System/Unit Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 RG 22x12 1.00 *595 540 91
Totals:----595 0 540 91 -
RF-1-01 Return Inlet Summary
Inland Air Balance, Inc.
Page 25 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/4/2024
SYSTEM/UNIT: RF-1-02
AREA: Patio
Log:RF-1-02 1/4/2024 Robert Watson Self-contained fan
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Fire Side Patio
108
EG 10x10 1.00 *200 220 110
Inlet-02 Fire Side Patio
108
EG 10x10 1.00 *200 219 110
Totals:----400 0 439 110 -
RF-1-02 Exhaust Inlet Summary
Tested By:Robert Watson
Date:1/29/2024
SYSTEM/UNIT: RF-2-01
AREA: Corridor
Log:RF-2-01 1/29/2024 Robert Watson Self contained fan
Motor Data
Nameplate Motor Hertz 60 Hz
Nominal Efficiency (0.00)0.90 %
Motor Power Factor (0.00)0.80
Test Results
Design Airflow 100 CFM
Actual Airflow 110 CFM
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Living 238 EG 12x10 1.00 *100 110 110
Totals:----100 0 110 110 -
RF-2-01 Exhaust Inlet Summary
Inland Air Balance, Inc.
Page 26 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/21/2023
SYSTEM/UNIT: RF-2-02
AREA: Corridor
Log:RF-2-02 12/21/2023 David Ramirez Self-contained Relief Fan Unit.
Unit Data
Unit Manufacturer Pennbarry
Unit Model Number Z12GP
Unit Serial Number D23EZ30793
Test Data
Motor Operating HZ/Speed Speed 60
Motor Volts T1-T2 122 Volts
Motor Amps T1 6.30 Amps
Motor Data
Thermally Protected?Yes
Nameplate Motor Manufacturer Genteq
Nameplate Motor Frame Direct Drive
Nameplate Motor HP 1/2 HP
Nameplate Motor Rated Volts 115 Volts
Nameplate Motor RPM 1355 RPM
Nameplate Motor FL Amps 8.10 Amps
Nameplate Motor Phase 1
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Sheave Data
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP 0.50 in. wc
Actual Total SP 0.08 in. wc
Design External SP NS in. wc
Actual External SP NA in. wc
Actual Suction SP NVL in. wc
Actual Discharge SP 0.08 in. wc
Test Results
Design Airflow 780 CFM
Actual Airflow 710 CFM
Design Fan RPM 1355 RPM
Actual Fan RPM NVL RPM
Actual Motor RPM NVL
System/Unit Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 RG 22x12 1.00 *780 710 91
Totals:----780 0 710 91 -
RF-2-02 Return Inlet Summary
Inland Air Balance, Inc.
Page 27 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/4/2024
SYSTEM/UNIT: RF-3-01
AREA: Corridor
Unit Data
Unit Manufacturer Penn Ventilator
Unit Model Number FX11
Unit Serial Number E23HZ02926
Test Data
Motor Operating HZ/Speed 60
Motor Volts T1-T2 207 Volts
Motor Amps T1 1.50 Amps
Motor Data
Nameplate Motor Manufacturer Mc millan
Nameplate Motor Frame Not Listed
Nameplate Motor HP 1/6 HP
Nameplate Motor Rated Volts 208 Volts
Nameplate Motor RPM Not Listed RPM
Nameplate Motor FL Amps 3.20 Amps
Nameplate Motor Phase 1
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Brake Horsepower 0.30 BHP
Nominal Efficiency (0.00)0.90 %
Motor Power Factor (0.00)0.80
Sheave Data
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP NVL in. wc
Actual Suction SP NVL in. wc
Actual Discharge SP NVL in. wc
Test Results
Design Airflow 125 CFM
Actual Airflow 137 CFM
Design Fan RPM Ns RPM
Actual Fan RPM NVL RPM
Actual Motor RPM NVL
Inland Air Balance, Inc.
Page 28 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/4/2024
SYSTEM/UNIT: RF-3-01
AREA: Corridor
Unit Manufacturer Photo:
Name:Unit Manufacturer.jpg
Captured:1/2/2024 11:05 AM
Caption:
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Corridor 3rd Flr RG 2408 1.00 *125 137 110
Totals:----125 0 137 110 -
RF-3-01 Exhaust Inlet Summary
Inland Air Balance, Inc.
Page 29 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/4/2024
SYSTEM/UNIT: RF-3-02
AREA: Corridor
Unit Data
Unit Manufacturer Penn Ventilator
Unit Model Number FX 11
Unit Serial Number E23HZ02926
Test Data
Motor Operating HZ/Speed 6
Motor Volts T1-T2 209 Volts
Motor Amps T1 1.30 Amps
Motor Data
Nameplate Motor Manufacturer Mc millan
Nameplate Motor Frame Not Listed
Nameplate Motor HP 1/4 watt
Nameplate Motor Rated Volts 120 Volts
Nameplate Motor RPM Ns RPM
Nameplate Motor FL Amps 3.20 Amps
Nameplate Motor Phase 1
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Brake Horsepower 0.26 BHP
Nominal Efficiency (0.00)0.90 %
Motor Power Factor (0.00)0.80
Sheave Data
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP NVL in. wc
Actual Suction SP NVL in. wc
Actual Discharge SP NVL in. wc
Test Results
Design Airflow 170 CFM
Actual Airflow 183 CFM
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Actual Motor RPM NVL
Inland Air Balance, Inc.
Page 30 of 129
Fan UnitPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/4/2024
SYSTEM/UNIT: RF-3-02
AREA: Corridor
Unit Manufacturer Photo:
Name:Unit Manufacturer.jpg
Captured:1/2/2024 11:01 AM
Caption:
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Corridor 3rd Flr EG 2408 1.00 *170 183 108
Totals:----170 0 183 108 -
RF-3-02 Exhaust Inlet Summary
Inland Air Balance, Inc.
Page 31 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/4/2024
SYSTEM/UNIT: AC-1-01
AREA: Elec
Unit Data
Unit Manufacturer LG
Unit Model Number LSN240HEV2
Unit Serial Number 210HAGF7U533
Test Data
Design Airflow 689 CFM
Actual Airflow 699 CFM
Design OSA 0 CFM
Actual OSA 0 CFM
Motor Data
AC-1-01/Supply Fan
Nameplate Motor Hertz 60 Hz
Nominal Efficiency (0.00)0.90 %
Motor Power Factor (0.00)0.80
Test Pressures
Design Total SP NS in. wc
Actual Total SP NA in. wc
Suction SP NVL in. wc
Discharge SP NVL in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Elec 144 Swing
Blade
34x4 0.94 744 689 699 101
Totals:----689 0 699 101
AC-1-01 Supply Outlet Summary
Tested By:Robert Watson
Date:1/4/2024
SYSTEM/UNIT: AC-1-02
AREA: IDF
Unit Data
Unit Manufacturer LG
Unit Model Number LSN240HEV2
Unit Serial Number 210HAGF7U531
Test Data
Design Airflow 689 CFM
Actual Airflow 704 CFM
Design OSA 0 CFM
Actual OSA 0 CFM
Motor Data
AC-1-02/Supply Fan
Nameplate Motor Hertz 60 Hz
Nominal Efficiency (0.00)0.90 %
Motor Power Factor (0.00)0.80
Test Pressures
Design Total SP NS in. wc
Actual Total SP NA in. wc
Suction SP NVL in. wc
Discharge SP NVL in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 IDF 145 Swing
Blade
34x4 0.94 749 689 704 102
Totals:----689 0 704 102
AC-1-02 Supply Outlet Summary
Inland Air Balance, Inc.
Page 32 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/3/2024
SYSTEM/UNIT: AC-2-01
AREA: Elec
Unit Data
Unit Manufacturer LG
Unit Model Number LSN240HEV2
Unit Serial Number 210HAGF7U520
Test Data
Design Airflow 689 CFM
Actual Airflow 713 CFM
Design OSA 0 CFM
Actual OSA 0 CFM
Motor Data
AC-2-01/Supply Fan
Nameplate Motor Hertz 60 Hz
Nominal Efficiency (0.00)0.90 %
Motor Power Factor (0.00)0.80
Test Pressures
Design Total SP NS in. wc
Actual Total SP NA in. wc
Suction SP NVL in. wc
Discharge SP NVL in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Elect 214 Swing
Blade
34x4 0.94 759 689 713 103
Totals:----689 0 713 103
AC-2-01 Supply Outlet Summary
Tested By:David Ramirez
Date:12/28/2023
SYSTEM/UNIT: AC-2-02
AREA: IDF
Unit Data
Unit Manufacturer LG
Unit Model Number LSN240HEV2
Unit Serial Number 210HAGF7U519
Test Data
Design Airflow 689 CFM
Actual Airflow 696 CFM
Design OSA 0 CFM
Actual OSA 0 CFM
Test Pressures
Design Total SP NS in. wc
Actual Total SP NA in. wc
Suction SP NVL in. wc
Discharge SP NVL in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 IDF 249 Swing
Blade
34x4 0.94 740 689 696 101
Totals:----689 0 696 101
AC-2-02 Supply Outlet Summary
Inland Air Balance, Inc.
Page 33 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/3/2024
SYSTEM/UNIT: AC-2-03
AREA: Elec
Unit Data
Unit Manufacturer LG
Unit Model Number LSN24
Unit Serial Number 210hagf7u519
Test Data
Design Airflow 689 CFM
Actual Airflow 690 CFM
Design OSA 0 CFM
Actual OSA 0 CFM
Motor Data
AC-2-03/Supply Fan
Nameplate Motor Hertz 60 Hz
Nominal Efficiency (0.00)0.90 %
Motor Power Factor (0.00)0.80
Test Pressures
Design Total SP NS in. wc
Actual Total SP NA in. wc
Suction SP NVL in. wc
Discharge SP NVL in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Elec 260 Swing
Blade
34x4 0.94 734 689 690 100
Totals:----689 0 690 100
AC-2-03 Supply Outlet Summary
Tested By:Robert Watson
Date:1/4/2024
SYSTEM/UNIT: AC-3-01
AREA: Elec
Unit Data
Unit Manufacturer LG
Unit Model Number LSN240HEV2
Unit Serial Number 210HAGF7U524
Test Data
Design Airflow 689 CFM
Actual Airflow 695 CFM
Design OSA 0 CFM
Actual OSA 0 CFM
Motor Data
AC-3-01/Supply Fan
Nameplate Motor Hertz 60 Hz
Nominal Efficiency (0.00)0.90 %
Motor Power Factor (0.00)0.80
Test Pressures
Design Total SP NS in. wc
Actual Total SP NA in. wc
Suction SP NVL in. wc
Discharge SP NVL in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Elec 309 Swing
Blade
34x4 0.94 739 689 695 101
Totals:----689 0 695 101
AC-3-01 Supply Outlet Summary
Inland Air Balance, Inc.
Page 34 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/4/2024
SYSTEM/UNIT: AC-3-02
AREA: Elec
Unit Data
Unit Manufacturer LG
Unit Model Number LSN240HEV2
Unit Serial Number 210HAGF7U521
Test Data
Design Airflow 689 CFM
Actual Airflow 709 CFM
Design OSA 0 CFM
Actual OSA 0 CFM
Motor Data
AC-3-02/Supply Fan
Nameplate Motor Hertz 60 Hz
Nominal Efficiency (0.00)0.90 %
Motor Power Factor (0.00)0.80
Test Pressures
Design Total SP NS in. wc
Actual Total SP NA in. wc
Suction SP NVL in. wc
Discharge SP NVL in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Elect 348 Swing
Blade
34x4 0.94 754 689 709 103
Totals:----689 0 709 103
AC-3-02 Supply Outlet Summary
Tested By:Robert Watson
Date:1/4/2024
SYSTEM/UNIT: AC-3-03
AREA: IDF
Unit Data
Unit Manufacturer LG
Unit Model Number LSN240HEV2
Unit Serial Number 210HAGF7U523
Test Data
Design Airflow 689 CFM
Actual Airflow 710 CFM
Design OSA 0 CFM
Actual OSA 0 CFM
Motor Data
AC-3-03/Supply Fan
Nameplate Motor Hertz 60 Hz
Nominal Efficiency (0.00)0.90 %
Motor Power Factor (0.00)0.80
Test Pressures
Design Total SP NS in. wc
Actual Total SP NA in. wc
Suction SP NVL in. wc
Discharge SP NVL in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 IDF 346 Swing
Blade
34x4 0.94 755 689 710 103
Totals:----689 0 710 103
AC-3-03 Supply Outlet Summary
Inland Air Balance, Inc.
Page 35 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/29/2023
SYSTEM/UNIT: AC-B-01
AREA: Elev
Unit Data
Unit Manufacturer LG
Unit Model Number LSN240HEV2
Unit Serial Number 210HAYE7U538
Test Data
Design Airflow 813 CFM
Actual Airflow 825 CFM
Design OSA 0 CFM
Actual OSA 0 CFM
Test Pressures
Design Total SP NS in. wc
Actual Total SP NA in. wc
Suction SP NVL in. wc
Discharge SP NVL in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Elevator
Equipment B21
Swing
Blade
34x4 0.94 878 813 825 101
Totals:----813 0 825 101
AC-B-01 Supply Outlet Summary
Tested By:David Ramirez
Date:12/29/2023
SYSTEM/UNIT: AC-B-02
AREA: Electrical B16
Unit Data
Unit Manufacturer LG
Unit Model Number LSN240HEV2
Unit Serial Number 210HACQ7U515
Test Data
Design Airflow 813 CFM
Actual Airflow 821 CFM
Design OSA 0 CFM
Actual OSA 0 CFM
Test Pressures
Design Total SP NS in. wc
Actual Total SP NA in. wc
Suction SP NVL in. wc
Discharge SP NVL in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Electrical B16 Swing
Blade
34x4 0.94 873 813 821 101
Totals:----813 0 821 101
AC-B-02 Supply Outlet Summary
Inland Air Balance, Inc.
Page 36 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/4/2024
SYSTEM/UNIT: AC-B-03
AREA: Elev
Unit Data
Unit Manufacturer LG
Unit Model Number LSN240HEV2
Unit Serial Number 210HACQ7U538
Test Data
Design Airflow 813 CFM
Actual Airflow 804 CFM
Design OSA 0 CFM
Actual OSA 0 CFM
Motor Data
AC-B-03/Supply Fan
Nameplate Motor Hertz 60 Hz
Nominal Efficiency (0.00)0.90 %
Motor Power Factor (0.00)0.80
Test Pressures
Design Total SP NS in. wc
Actual Total SP NA in. wc
Suction SP NVL in. wc
Discharge SP NVL in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Elevator
Equipment B16
Swing
Blade
34x4 0.94 855 813 804 99
Totals:----813 0 804 99
AC-B-03 Supply Outlet Summary
Tested By:David Ramirez
Date:12/29/2023
SYSTEM/UNIT: AC-B-04
AREA: Elevator Equipment B21
Unit Data
Unit Manufacturer LG
Unit Model Number LSN240HEV2
Unit Serial Number 210HALW7U520
Test Data
Design Airflow 813 CFM
Actual Airflow 821 CFM
Design OSA 0 CFM
Actual OSA 0 CFM
Test Pressures
Design Total SP NS in. wc
Actual Total SP NA in. wc
Suction SP NVL in. wc
Discharge SP NVL in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Elevator
Equipment B21
Swing
Blade
34x4 0.94 870 813 821 101
Totals:----813 0 821 101
AC-B-04 Supply Outlet Summary
Inland Air Balance, Inc.
Page 37 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/29/2023
SYSTEM/UNIT: AC-B-06
AREA: MPOE
Log:AC-B-06 12/29/2023 David Ramirez Schedule change. FCU is now a 2 ton wall-split
Unit Data
Unit Manufacturer LG
Unit Model Number LSN243HLV3
Unit Serial Number 305KARW0E878
Test Data
Design Airflow Ns CFM
Actual Airflow 840 CFM
Design OSA 0 CFM
Actual OSA 0 CFM
Test Pressures
Design Total SP NS in. wc
Actual Total SP NA in. wc
Suction SP NVL in. wc
Discharge SP NVL in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 MPOE B24 Swing
Blade
35x4 0.97 867 Ns 840
Totals:----0 0 840 0
AC-B-06 Supply Outlet Summary
Inland Air Balance, Inc.
Page 38 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/29/2023
SYSTEM/UNIT: AC-B-07
AREA: Emergency
Log:AC-B-07 12/29/2023 David Ramirez Schedule change. FCU is now a wall-split.
Unit Data
Unit Manufacturer LG
Unit Model Number LSN368HLV3
Unit Serial Number 303KAVH03Y75
Test Data
Design Airflow Ns CFM
Actual Airflow 1267 CFM
Design OSA 0 CFM
Actual OSA 0 CFM
Test Pressures
Design Total SP NS in. wc
Actual Total SP NA in. wc
Suction SP NVL in. wc
Discharge SP NVL in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Emergency
Elec Room B25
Swing
Blade
41x4 1.14 1111 Ns 1267
Totals:----0 0 1267 0
AC-B-07 Supply Outlet Summary
Inland Air Balance, Inc.
Page 39 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/21/2023
SYSTEM/UNIT: FCU-1-01
AREA: Laundry
Log:FCU-1-01 12/21/2023 David Ramirez RA+OSA does not equate to SA volume. Return Inlet
01, in corridor 104, was set to make up the difference
in air volume.
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not Listed
FCU-1-01/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 640 CFM
Actual Airflow 640 CFM
Design OSA 235 CFM
Actual OSA 258 CFM
FCU-1-01/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 0.91 Amps
Motor Data
FCU-1-01/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-1-01/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-1-01/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-1-01/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.33 in. wc
Suction SP -0.12 in. wc
Discharge SP 0.21 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Corridor 104 CD 2408 1.00 *150 155 103
Outlet-02 Seating 146 CD 2408 1.00 *155 160 103
Outlet-03 Laundry 147 CD 2408 1.00 *185 175 95
Outlet-04 Corridor 104 CD 2408 1.00 *NS 150
Totals:----490 0 640 131
FCU-1-01 Supply Outlet Summary
Inland Air Balance, Inc.
Page 40 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Corridor 104 RG 2408 1.00 *NS 322
Inlet-02 Laundry 147 RG 2406 1.00 *NS 60
Totals:----0 0 382 0 -
FCU-1-01 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 10” Ø Velgrid 0.55 469 235 258 110
Totals:-----235 0 258 110
FCU-1-01 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 41 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/3/2024
SYSTEM/UNIT: FCU-1-02
AREA: Office
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not listed
FCU-1-02/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 640 CFM
Actual Airflow 643 CFM
Design OSA 15 CFM
Actual OSA 16 CFM
FCU-1-02/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 0.99 Amps
Motor Data
FCU-1-02/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-1-02/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-1-02/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-1-02/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP Ns in. wc
Actual Total SP 0.39 in. wc
Suction SP -0.16 in. wc
Discharge SP 0.23 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 ED Office 102 CD 2410 1.00 *270 277 103
Outlet-02 ED Office 102 LD 48x2 1.00 *370 366 99
Totals:----640 0 643 100
FCU-1-02 Supply Outlet Summary
Inland Air Balance, Inc.
Page 42 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 ED Office 102 RG 2410 1.00 *205 222 108
Inlet-02 ED Office 102 RG 48x2 1.00 *280 301 108
Totals:----485 0 523 108 -
FCU-1-02 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 8 Airfoil 0.35 46 15 16 107
Totals:-----15 0 16 107
FCU-1-02 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 43 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/10/2024
SYSTEM/UNIT: FCU-1-03
AREA: Office
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not Listed
FCU-1-03/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 660 CFM
Actual Airflow 691 CFM
Design OSA 75 CFM
Actual OSA 75 CFM
FCU-1-03/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 0.90 Amps
Motor Data
FCU-1-03/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-1-03/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-1-03/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-1-03/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.40 in. wc
Suction SP 0.13 in. wc
Discharge SP 0.27 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 BOM Office 151 CD 2408 1.00 *110 103 94
Outlet-02 S&M Office 153 CD 2408 1.00 *175 159 91
Outlet-03 W.R. 150 CD 2408 1.00 *NS 90
Outlet-04 S&M Office 154 CD 2408 1.00 *175 158 90
Outlet-05 Parcel Room
155
CD 2408 1.00 *100 91 91
Outlet-06 Reception 101 CD 2408 1.00 *100 90 90
Totals:----660 0 691 105
FCU-1-03 Supply Outlet Summary
Inland Air Balance, Inc.
Page 44 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 BOM Office 151 RG 2414 1.00 *565 372 66
Inlet-02 S&M Office 153 RG 2408 1.00 *175 109 62
Inlet-03 S&M Office 154 RG 2408 1.00 *175 108 62
Totals:----915 0 589 64 -
FCU-1-03 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 6 Air-foil 0.20 376 75 75 100
Totals:-----75 0 75 100
FCU-1-03 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 45 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/27/2023
SYSTEM/UNIT: FCU-1-04
AREA: Kitchen
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not Listed
FCU-1-04/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 640 CFM
Actual Airflow 645 CFM
Design OSA 90 CFM
Actual OSA 92 CFM
FCU-1-04/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 0.90 Amps
Motor Data
FCU-1-04/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-1-04/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-1-04/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-1-04/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.51 in. wc
Suction SP -0.31 in. wc
Discharge SP 0.20 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Servery 119 CD 2410 1.00 *280 285 102
Outlet-02 Servery 119 LD 48x3 1.00 *360 360 100
Totals:----640 0 645 101
FCU-1-04 Supply Outlet Summary
Inland Air Balance, Inc.
Page 46 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 RG 2412 1.00 525 553 105
Totals:----525 0 553 105 -
FCU-1-04 Return Inlet Summary
System/Unit Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
OS-01 DUCT 6” Ø Air-foil 0.20 460 90 92 102 102
Totals:-----90 0 92 102 -
FCU-1-04 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 47 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/27/2023
SYSTEM/UNIT: FCU-1-05
AREA: Corridor
Unit Data
Unit Manufacturer LG
Unit Model Number LHN368HV
Unit Serial Number Not Listed
FCU-1-05/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x25x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 880 CFM
Actual Airflow 845 CFM
Design OSA 480 CFM
Actual OSA 491 CFM
FCU-1-05/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 1.34 Amps
Motor Data
FCU-1-05/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 2.30 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-1-05/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-1-05/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-1-05/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.29 in. wc
Suction SP -0.18 in. wc
Discharge SP 0.11 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Women 113 CD 2408 1.00 *205 205 100
Outlet-02 Men 112 CD 2408 1.00 *205 205 100
Outlet-03 Corridor 1st
Floor
CD 2408 1.00 *230 220 96
Outlet-04 Corridor 1st
Floor
CD 2408 1.00 *230 215 93
Totals:----870 0 845 97
FCU-1-05 Supply Outlet Summary
Inland Air Balance, Inc.
Page 48 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Corridor 1st
Floor
RG 2414 1.00 *400 365 91
Totals:----400 0 365 91 -
FCU-1-05 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 12” Ø Velgrid 0.78 630 480 491 102
Totals:-----480 0 491 102
FCU-1-05 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 49 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:12/28/2023
SYSTEM/UNIT: FCU-1-06
AREA: Restaurant
Unit Data
Unit Manufacturer LG
Unit Model Number lvhn428
Unit Serial Number Not Listed
FCU-1-06/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 2
Filter Size - S1 16x25x2
Test Data
Design Airflow 1080 CFM
Actual Airflow 1070 CFM
Design OSA 370 CFM
Actual OSA 380 CFM
FCU-1-06/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 1.10 Amps
Motor Data
FCU-1-06/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.30 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-1-06/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-1-06/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-1-06/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.51 in. wc
Suction SP -0.22 in. wc
Discharge SP 0.29 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Savor
Restaurant 124
LD 48x3 1.00 358 360 358 99
Outlet-02 Savor
Restaurant 124
LD 48x3 1.00 363 360 363 101
Outlet-03 Savor
Restaurant 124
LD 48x3 1.00 349 360 349 97
Totals:----1080 0 1070 99
FCU-1-06 Supply Outlet Summary
Inland Air Balance, Inc.
Page 50 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Savor
Restaurant 124
RG 48x3 1.00 *235 218 93
Inlet-02 Savor
Restaurant 124
RG 48x3 1.00 *235 220 94
Inlet-03 Savor
Restaurant 124
RG 48x3 1.00 *235 219 93
Totals:----705 0 657 93 -
FCU-1-06 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit LOUVER 18x18 Velgrid 2.25 169 370 380 103
Totals:-----370 0 380 103
FCU-1-06 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 51 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/3/2024
SYSTEM/UNIT: FCU-1-07
AREA: Dr's Pub
Unit Data
Unit Manufacturer LG
Unit Model Number LHN428
Unit Serial Number Not Listed
FCU-1-07/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 2
Filter Size - S1 16x25x2
Test Data
Design Airflow 1040 CFM
Actual Airflow 1042 CFM
Design OSA 435 CFM
Actual OSA 442 CFM
FCU-1-07/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 1.00 Amps
Motor Data
FCU-1-07/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.30 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-1-07/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-1-07/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-1-07/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.54 in. wc
Suction SP -0.23 in. wc
Discharge SP 0.31 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 D's Pub 122 LD 48x2 1.00 *260 264 102
Outlet-02 D's Pub 122 LD 48x2 1.00 *260 271 104
Outlet-03 D's Pub 122 LD 48x2 1.00 *260 246 95
Outlet-04 D's Pub 122 LD 48x2 1.00 *260 261 100
Totals:----1040 0 1042 100
FCU-1-07 Supply Outlet Summary
Inland Air Balance, Inc.
Page 52 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 D's Pub 122 RG 48x3 1.00 *305 288 94
Inlet-02 D's Pub 122 RG 48x3 1.00 *305 289 95
Totals:----610 0 577 95 -
FCU-1-07 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 12 Velgrid 0.78 567 435 442 102
Totals:-----435 0 442 102
FCU-1-07 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 53 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:12/27/2023
SYSTEM/UNIT: FCU-1-08
AREA: Kitchen
Unit Data
Unit Manufacturer LG
Unit Model Number LHN428hv
Unit Serial Number Not Listed
FCU-1-08/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 2
Filter Size - S1 16x25x2
Test Data
Design Airflow 1210 CFM
Actual Airflow 1100 CFM
Design OSA 160 CFM
Actual OSA 161 CFM
FCU-1-08/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 1.23 Amps
Motor Data
FCU-1-08/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.30 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-1-08/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-1-08/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-1-08/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.66 in. wc
Suction SP -0.17 in. wc
Discharge SP 0.49 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Hostess 123 LD 48x2 1.00 *300 278 93
Outlet-02 Hostess 123 LD 48x2 1.00 *300 270 90
Outlet-03 Hostess 123 LD 48x2 1.00 *300 272 91
Outlet-04 Hostess 123 LD 48x2 1.00 *300 280 93
Totals:----1200 0 1100 92
FCU-1-08 Supply Outlet Summary
Inland Air Balance, Inc.
Page 54 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Hostess 123 RG 2412 1.00 *525 501 95
Inlet-02 Hostess 123 RG 2412 1.00 *525 477 91
Totals:----1050 0 978 93 -
FCU-1-08 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 8 airfoil 0.35 459 160 161 101
Totals:-----160 0 161 101
FCU-1-08 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 55 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/29/2023
SYSTEM/UNIT: FCU-1-09A
AREA: Kitchen
Log:FCU-1-09A 12/27/2023 David Ramirez Right RA volume damper shaft is disconnected from
handle.
Unit Data
Unit Manufacturer LG
Unit Model Number LHN488HV
Unit Serial Number Not Listed
FCU-1-09A/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 2
Filter Size - S1 16x25x2
Test Data
Design Airflow 1450 CFM
Actual Airflow 1335 CFM
Design OSA 180 CFM
Actual OSA 183 CFM
FCU-1-09A/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 1.10 Amps
Motor Data
FCU-1-09A/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.30 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-1-09A/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-1-09A/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-1-09A/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.31 in. wc
Suction SP -0.21 in. wc
Discharge SP 0.10 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Kitchen 118 CD 2410 1.00 *345 345 100
Outlet-02 Kitchen 118 CD 2410 1.00 *345 345 100
Outlet-03 Kitchen 118 CD 2410 1.00 *345 335 97
Outlet-04 Kitchen 118 CD 2410 1.00 *345 310 90
Totals:----1380 0 1335 97
FCU-1-09A Supply Outlet Summary
Inland Air Balance, Inc.
Page 56 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Kitchen 118 RG 2412 1.00 *635 572 90
Inlet-02 Kitchen 118 RG 2412 1.00 *635 571 90
Totals:----1270 0 1143 90 -
FCU-1-09A Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 8 Air-foil 0.35 523 180 183 102
Totals:-----180 0 183 102
FCU-1-09A Outside Air Intake Summary
Inland Air Balance, Inc.
Page 57 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/29/2023
SYSTEM/UNIT: FCU-1-09B
AREA: Kitchen
Unit Data
Unit Manufacturer LG
Unit Model Number LHN488HV
Unit Serial Number Not Listed
FCU-1-09B/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 2
Filter Size - S1 16x25x2
Test Data
Design Airflow 1450 CFM
Actual Airflow 1480 CFM
Design OSA 175 CFM
Actual OSA 186 CFM
FCU-1-09B/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 1.08 Amps
Motor Data
FCU-1-09B/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.30 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-1-09B/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-1-09B/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-1-09B/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.33 in. wc
Suction SP -0.20 in. wc
Discharge SP 0.13 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Kitchen 118 CD 2410 1.00 *340 340 100
Outlet-02 Kitchen 118 CD 2406 1.00 *110 115 105
Outlet-03 Kitchen 118 CD 2410 1.00 *340 345 101
Outlet-04 Kitchen 118 CD 2410 1.00 *340 335 99
Outlet-05 Kitchen 118 CD 2410 1.00 *340 345 101
Totals:----1470 0 1480 101
FCU-1-09B Supply Outlet Summary
Inland Air Balance, Inc.
Page 58 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Kitchen 118 RG 2412 1.00 *648 650 100
Inlet-02 Kitchen 118 RG 2412 1.00 *647 640 99
Totals:----1295 0 1290 100 -
FCU-1-09B Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 8 Air-foil 0.35 530 175 186 106
Totals:-----175 0 186 106
FCU-1-09B Outside Air Intake Summary
Inland Air Balance, Inc.
Page 59 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:12/27/2023
SYSTEM/UNIT: FCU-1-10
AREA: Dining
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not Listed
FCU-1-10/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 640 CFM
Actual Airflow 648 CFM
Design OSA 190 CFM
Actual OSA 190 CFM
FCU-1-10/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 0.95 Amps
Motor Data
FCU-1-10/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-1-10/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-1-10/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-1-10/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.29 in. wc
Suction SP -0.07 in. wc
Discharge SP 0.22 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Kitchen Office
118A
CD 2406 1.00 *100 104 104
Outlet-02 Serve St. 117 CD 2406 1.00 *100 110 110
Outlet-03 Cellar PVT
Dining 115
LD 48x2 1.00 *220 211 96
Outlet-04 Cellar PVT
Dining 115
LD 48x2 1.00 *220 223 101
Totals:----640 0 648 101
FCU-1-10 Supply Outlet Summary
Inland Air Balance, Inc.
Page 60 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Cellar PVT
Dining 115
RG 48x3 1.00 *N/S 212
Inlet-02 RG 48x3 1.00 *N/S 186
Totals:----0 0 398 0 -
FCU-1-10 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 10 Velgrid 0.35 544 190 190 100
Totals:-----190 0 190 100
FCU-1-10 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 61 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:12/27/2023
SYSTEM/UNIT: FCU-1-11
AREA: Living
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not Listed
FCU-1-11/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 725 CFM
Actual Airflow 724 CFM
Design OSA 80 CFM
Actual OSA 88 CFM
FCU-1-11/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 1.00 Amps
Motor Data
FCU-1-11/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-1-11/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-1-11/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-1-11/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.35 in. wc
Suction SP -0.13 in. wc
Discharge SP 0.22 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Living Room
105
CD 48x2 1.00 *245 231 94
Outlet-02 Living Room
105
CD 48x2 1.00 *245 247 101
Outlet-03 Living Room
105
CD 48x2 1.00 *245 246 100
Totals:----735 0 724 99
FCU-1-11 Supply Outlet Summary
Inland Air Balance, Inc.
Page 62 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Living Room
105
RG 48x2 1.00 *215 205 95
Inlet-02 Living Room
105
RG 48x2 1.00 *215 209 97
Inlet-03 Living Room
105
RG 48x2 1.00 *215 208 97
Totals:----645 0 622 96 -
FCU-1-11 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 6 Airfoil 0.20 440 80 88 110
Totals:-----80 0 88 110
FCU-1-11 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 63 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:12/27/2023
SYSTEM/UNIT: FCU-1-12
AREA: Gameroom
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not Listed
FCU-1-12/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 755 CFM
Actual Airflow 746 CFM
Design OSA 105 CFM
Actual OSA 110 CFM
FCU-1-12/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 0.96 Amps
Motor Data
FCU-1-12/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-1-12/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-1-12/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-1-12/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.31 in. wc
Suction SP -0.10 in. wc
Discharge SP 0.21 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Game Room
106
LD 48x2 1.00 *375 369 98
Outlet-02 Game Room
106
LD 48x2 1.00 *380 377 99
Totals:----755 0 746 99
FCU-1-12 Supply Outlet Summary
Inland Air Balance, Inc.
Page 64 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Game Room
106
RG 48x2 1.00 *325 297 91
Inlet-02 Game Room
106
RG 48x2 1.00 *325 292 90
Totals:----650 0 589 91 -
FCU-1-12 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit LOUVER 48x22 Velgrid 7.33 15 105 110 105
Totals:-----105 0 110 105
FCU-1-12 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 65 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:12/27/2023
SYSTEM/UNIT: FCU-1-13
AREA: Discovery
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not Listed
FCU-1-13/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 640 CFM
Actual Airflow 604 CFM
Design OSA 55 CFM
Actual OSA 60 CFM
FCU-1-13/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 0.97 Amps
Motor Data
FCU-1-13/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-1-13/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-1-13/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-1-13/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.33 in. wc
Suction SP -0.11 in. wc
Discharge SP 0.22 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Discovery 103 LD 60x3 1.00 *640 604 94
Totals:----640 0 604 94
FCU-1-13 Supply Outlet Summary
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Discovery 103 RG 60x3 1.00 *585 539 92
Totals:----585 0 539 92 -
FCU-1-13 Return Inlet Summary
Inland Air Balance, Inc.
Page 66 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit LOUVER 6 velgrid 0.20 300 55 60 109
Totals:-----55 0 60 109
FCU-1-13 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 67 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/27/2023
SYSTEM/UNIT: FCU-1-14
AREA: Corridor
Unit Data
Unit Manufacturer LG
Unit Model Number LH368HV
Unit Serial Number Not Listed
FCU-1-14/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x25x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 920 CFM
Actual Airflow 882 CFM
Design OSA 80 CFM
Actual OSA 81 CFM
FCU-1-14/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 1.20 Amps
Motor Data
FCU-1-14/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 2.30 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-1-14/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-1-14/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-1-14/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.32 in. wc
Suction SP -0.10 in. wc
Discharge SP 0.22 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Corridor 127 CD 2408 1.00 *115 112 97
Outlet-02 Corridor 127 CD 2408 1.00 *110 110 100
Outlet-03 Hall 5/A11.17 CD 2410 1.00 *350 315 90
Outlet-04 Hall 5/A11.17 CD 2410 1.00 *345 345 100
Totals:----920 0 882 96
FCU-1-14 Supply Outlet Summary
Inland Air Balance, Inc.
Page 68 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Corridor 127 RG 2414 1.00 *840 801 95
Totals:----840 0 801 95 -
FCU-1-14 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 6” Ø Air-foil 0.20 404 80 81 101
Totals:-----80 0 81 101
FCU-1-14 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 69 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/21/2023
SYSTEM/UNIT: FCU-2-01
AREA: Dining
Unit Data
Unit Manufacturer LG
Unit Model Number LHN488HV
Unit Serial Number Not Listed
FCU-2-01/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 2
Filter Size - S1 16x25x2
Test Data
Design Airflow 1590 CFM
Actual Airflow 1465 CFM
Design OSA 500 CFM
Actual OSA 527 CFM
FCU-2-01/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 1.00 Amps
Motor Data
FCU-2-01/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.30 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-2-01/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-2-01/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-2-01/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.54 in. wc
Suction SP -0.33 in. wc
Discharge SP 0.21 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 MC Dining 240 LD 48x2 1.00 *205 200 98
Outlet-02 MC Dining 240 LD 48x3 1.00 *300 285 95
Outlet-03 MC Dining 240 LD 48x2 1.00 *205 190 93
Outlet-04 MC Dining 240 LD 48x3 1.00 *300 290 97
Outlet-05 MC Dining 240 LD 48x2 1.00 *205 205 100
Outlet-06 MC Dining 240 LD 48x3 1.00 *300 295 98
Totals:----1515 0 1465 97
FCU-2-01 Supply Outlet Summary
Inland Air Balance, Inc.
Page 70 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 MC Dining 240 LRG 58x3 1.00 *545 490 90
Inlet-02 MC Dining 240 LRG 58x3 1.00 *545 495 91
Totals:----1090 0 985 90 -
FCU-2-01 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 10” Ø Air-Foil 0.55 958 500 527 105
Totals:-----500 0 527 105
FCU-2-01 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 71 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:12/21/2023
SYSTEM/UNIT: FCU-2-02
AREA: Living
Unit Data
Unit Manufacturer LG
Unit Model Number LHN428HV
Unit Serial Number Not Listed
FCU-2-02/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 2
Filter Size - S1 16x25x2
Test Data
Design Airflow 1290 CFM
Actual Airflow 1360 CFM
Design OSA 250 CFM
Actual OSA 260 CFM
FCU-2-02/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 1.30 Amps
Motor Data
FCU-2-02/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.30 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-2-02/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-2-02/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-2-02/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.48 in. wc
Suction SP -0.18 in. wc
Discharge SP 0.30 in. wc
Inland Air Balance, Inc.
Page 72 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:12/21/2023
SYSTEM/UNIT: FCU-2-02
AREA: Living
Unit Manufacturer Photo:
Name:Unit Manufacturer.jpg
Captured:12/21/2023 8:37 AM
Caption:
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Living 238 LD 48x3 1.00 273 260 273 105
Outlet-02 Living 238 LD 48x3 1.00 274 260 274 105
Outlet-03 Living 238 LD 48x3 1.00 269 260 269 103
Outlet-04 Living 238 LD 48x3 1.00 270 255 270 106
Outlet-05 Living 238 LD 48x3 1.00 274 255 274 107
Totals:----1290 0 1360 105
FCU-2-02 Supply Outlet Summary
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Living 238 RG 58x3 1.21 417 500 504 101
Inlet-02 Living 238 RG 58x3 1.21 404 500 489 98
Totals:----1000 0 993 99 -
FCU-2-02 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit LOUVER 33x8 Velgrid 1.83 142 250 260 104
Totals:-----250 0 260 104
FCU-2-02 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 73 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/21/2023
SYSTEM/UNIT: FCU-2-03
AREA: Office
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not Listed
FCU-2-03/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 640 CFM
Actual Airflow 648 CFM
Design OSA 160 CFM
Actual OSA 161 CFM
FCU-2-03/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 0.83 Amps
Motor Data
FCU-2-03/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-2-03/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-2-03/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-2-03/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.23 in. wc
Suction SP -0.08 in. wc
Discharge SP 0.15 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Med 246 CD 2408 1.00 *240 241 100
Outlet-02*Laundry 244 CD 2408 1.00 *160 172 108
Outlet-03 Care Giver 245 CD 2408 1.00 *240 235 98
Totals:----640 0 648 101
FCU-2-03 Supply Outlet Summary
Log:FCU-2-03/Outlet-02 12/21/2023 David Ramirez Fire/Smoke Damper does not have power landed.
Mechanical and Electrical contractors have been
made aware. FSD was manually opened, FCU was
balanced.
Inland Air Balance, Inc.
Page 74 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Care Office 245 RG 2412 1.00 480 481 100
Totals:----480 0 481 100 -
FCU-2-03 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 10” Ø Air-Foil 0.55 292 160 161 101
Totals:-----160 0 161 101
FCU-2-03 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 75 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/4/2024
SYSTEM/UNIT: FCU-2-04
AREA: Office
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not Listed
FCU-2-04/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 640 CFM
Actual Airflow 655 CFM
Design OSA 170 CFM
Actual OSA 178 CFM
FCU-2-04/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 0.70 Amps
Motor Data
FCU-2-04/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-2-04/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-2-04/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-2-04/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.14 in. wc
Suction SP -0.01 in. wc
Discharge SP 0.13 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Laundry 250 CD 2408 1.00 *190 195 103
Outlet-02 MC Dir. Office
248
CD 2408 1.00 *150 155 103
Outlet-03 Corridor 104 CD 2408 1.00 *150 155 103
Outlet-04 Corridor 104 CD 2408 1.00 *150 150 100
Totals:----640 0 655 102
FCU-2-04 Supply Outlet Summary
Inland Air Balance, Inc.
Page 76 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Corridor 261 RG 2410 1.00 *295 280 95
Inlet-02 MC Dir. Office
248
RG 2408 1.00 *150 144 96
Totals:----445 0 424 95 -
FCU-2-04 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 10” Ø Air-foil 0.55 323 175 178 102
Totals:-----175 0 178 102
FCU-2-04 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 77 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/21/2023
SYSTEM/UNIT: FCU-2-05
AREA: Kitchen
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not Listed
FCU-2-05/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 640 CFM
Actual Airflow 635 CFM
Design OSA 235 CFM
Actual OSA 235 CFM
FCU-2-05/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 0.80 Amps
Motor Data
FCU-2-05/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-2-05/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-2-05/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-2-05/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.19 in. wc
Suction SP -0.05 in. wc
Discharge SP 0.14 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Kitchen/Servery
239
CD 2408 1.00 *320 320 100
Outlet-02 Kitchen/Servery
239
CD 2408 1.00 *320 315 98
Totals:----640 0 635 99
FCU-2-05 Supply Outlet Summary
Inland Air Balance, Inc.
Page 78 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Kitchen/Servery
239
RG 2412 1.00 *405 400 99
Totals:----405 0 400 99 -
FCU-2-05 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 10” Ø Air-Foil 0.55 427 235 235 100
Totals:-----235 0 235 100
FCU-2-05 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 79 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/20/2023
SYSTEM/UNIT: FCU-2-6
AREA: Corridor
Unit Data
Unit Manufacturer LG
Unit Model Number LHN368HV
Unit Serial Number Not Listed
FCU-2-6/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x25x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 915 CFM
Actual Airflow 920 CFM
Design OSA 85 CFM
Actual OSA 88 CFM
FCU-2-6/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 1.40 Amps
Motor Data
FCU-2-6/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 2.30 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-2-6/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-2-6/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-2-6/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.45 in. wc
Suction SP -0.18 in. wc
Discharge SP 0.27 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Corridor 237 CD 2412 1.00 *305 310 102
Outlet-02 Corridor 237 CD 2412 1.00 *305 305 100
Outlet-03 Corridor 237 CD 2412 1.00 *305 305 100
Totals:----915 0 920 101
FCU-2-6 Supply Outlet Summary
Inland Air Balance, Inc.
Page 80 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Corridor 237 RG 2414 1.00 *830 832 100
Totals:----830 0 832 100 -
FCU-2-6 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 10” Ø Velgrid 0.55 160 85 88 104
Totals:-----85 0 88 104
FCU-2-6 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 81 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/4/2024
SYSTEM/UNIT: FCU-2-7
AREA: Corridor
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not Listed
FCU-2-7/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 655 CFM
Actual Airflow 660 CFM
Design OSA 230 CFM
Actual OSA 239 CFM
FCU-2-7/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 0.87 Amps
Motor Data
FCU-2-7/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-2-7/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-2-7/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-2-7/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.33 in. wc
Suction SP -0.11 in. wc
Discharge SP 0.22 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Corridor 237 CD 2408 1.00 *150 145 97
Outlet-02 Corridor 237 CD 2408 1.00 *150 145 97
Outlet-03 Beauty Salon
218
LD 48x3 1.00 *140 145 104
Outlet-04 STO 216 CD 2408 1.00 *75 75 100
Outlet-05 Corridor 237 CD 2408 1.00 *140 150 107
Totals:----655 0 660 101
FCU-2-7 Supply Outlet Summary
Inland Air Balance, Inc.
Page 82 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Corridor 237 RG 2412 1.00 425 408 96
Totals:----425 0 408 96 -
FCU-2-7 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 12” Ø Velgrid 0.78 307 230 239 104
Totals:-----230 0 239 104
FCU-2-7 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 83 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/20/2023
SYSTEM/UNIT: FCU-3-1
AREA: Corridor
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not Listed
FCU-3-1/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 640 CFM
Actual Airflow 653 CFM
Design OSA 100 CFM
Actual OSA 162 CFM
FCU-3-1/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 0.90 Amps
Motor Data
FCU-3-1/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-3-1/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-3-1/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-3-1/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.23 in. wc
Suction SP -0.10 in. wc
Discharge SP 0.13 in. wc
Inland Air Balance, Inc.
Page 84 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/20/2023
SYSTEM/UNIT: FCU-3-1
AREA: Corridor
Unit Manufacturer Photo:
Name:Unit Manufacturer.jpg
Captured:12/20/2023 7:48 AM
Caption:
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Corridor 300 CD 2408 1.00 *200 205 103
Outlet-02 Care Giver ST.
344
CD 2408 1.00 *70 70 100
Outlet-03 Med 345 CD 2406 1.00 *70 72 103
Outlet-04 AL Dir. Office
347
CD 2406 1.00 *100 102 102
Outlet-05 Corridor 300 CD 2408 1.00 *200 204 102
Totals:----640 0 653 102
FCU-3-1 Supply Outlet Summary
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Corridor 300 RG 2412 1.00 *440 443 101
Inlet-02 AL Dir. Office
347
RG 2406 1.00 *100 101 101
Totals:----540 0 544 101 -
FCU-3-1 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01*Unit DUCT 6” Ø Pitot Tube 0.20 810 100 162 162
Totals:-----100 0 162 162
FCU-3-1 Outside Air Intake Summary
Log:FCU-3-1/OS-01 1/29/2024 Robert Watson OSA increased to make up for OSA not being
installed on FC 3–3. All fan coils on third floor Serve
common corridor.
Inland Air Balance, Inc.
Page 85 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/20/2023
SYSTEM/UNIT: FCU-3-2
AREA: Corridor
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not Listed
FCU-3-2/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 640 CFM
Actual Airflow 630 CFM
Design OSA 65 CFM
Actual OSA 127 CFM
FCU-3-2/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 0.87 Amps
Motor Data
FCU-3-2/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-3-2/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-3-2/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-3-2/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.40 in. wc
Suction SP -0.18 in. wc
Discharge SP 0.22 in. wc
Inland Air Balance, Inc.
Page 86 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/20/2023
SYSTEM/UNIT: FCU-3-2
AREA: Corridor
Log:FCU-3-2 1/29/2024 Robert Watson OSA Increased to make up for OSA not being
installed on FC 3–3. All fan coils on third-floor serve
common Corredor.
Unit Manufacturer Photo:
Name:Unit Manufacturer.jpg
Captured:12/20/2023 9:52 AM
Caption:
Unit Model Number Photo:
Name:Unit Manufacturer.jpg
Captured:12/20/2023 9:52 AM
Caption:
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Corridor 320 CD 2408 1.00 *135 130 96
Outlet-02 Corridor 320 CD 2408 1.00 *135 135 100
Outlet-03 Corridor 320 CD 2410 1.00 *370 365 99
Totals:----640 0 630 98
FCU-3-2 Supply Outlet Summary
Inland Air Balance, Inc.
Page 87 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Corridor 320 RG 2412 1.00 *575 562 98
Totals:----575 0 562 98 -
FCU-3-2 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 6” Ø Velgrid 0.20 635 65 127 195
Totals:-----65 0 127 195
FCU-3-2 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 88 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/19/2024
SYSTEM/UNIT: FCU-3-3
AREA: Corridor
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not Listed
FCU-3-3/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 640 CFM
Actual Airflow 672 CFM
Design OSA 185 CFM
Actual OSA 0 CFM
FCU-3-3/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 1.00 Amps
Motor Data
FCU-3-3/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-3-3/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-3-3/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-3-3/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP Ns in. wc
Actual Total SP 0.44 in. wc
Suction SP -0.20 in. wc
Discharge SP 0.24 in. wc
Inland Air Balance, Inc.
Page 89 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/19/2024
SYSTEM/UNIT: FCU-3-3
AREA: Corridor
Log:FCU-3-3 1/19/2024 Robert Watson No OSA run to unit. OSA increased on 3 other fan
coil serving common Corridor as FC 3–3.
Unit Manufacturer Photo:
Name:Unit Manufacturer.jpg
Captured:12/20/2023 10:56 AM
Caption:
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Corridor 3rd Flr CD 2408 1.00 *220 235 107
Outlet-02 Laundry 312 CD 2408 1.00 *200 195 98
Outlet-03 Corridor 3rd Flr CD 2408 1.00 *220 242 110
Totals:----640 0 672 105
FCU-3-3 Supply Outlet Summary
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Corridor 3rd Flr RG 2412 1.00 *455 644 142
Totals:----455 0 644 142 -
FCU-3-3 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01*Unit DUCT Air Foil 185 0 0
Totals:-----185 0 0 0
FCU-3-3 Outside Air Intake Summary
Log:FCU-3-3/OS-01 1/19/2024 Robert Watson No outside air duct run to unit
Inland Air Balance, Inc.
Page 90 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/20/2023
SYSTEM/UNIT: FCU-3-4
AREA: Corridor
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not Listed
FCU-3-4/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 640 CFM
Actual Airflow 687 CFM
Design OSA 70 CFM
Actual OSA 132 CFM
FCU-3-4/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 1.00 Amps
Motor Data
FCU-3-4/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-3-4/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-3-4/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-3-4/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.38 in. wc
Suction SP -0.17 in. wc
Discharge SP 0.21 in. wc
Inland Air Balance, Inc.
Page 91 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/20/2023
SYSTEM/UNIT: FCU-3-4
AREA: Corridor
Log:FCU-3-4 1/29/2024 Robert Watson OSA increased to make up for OSA not being
installed on FC 3–3. All fan coils on third-floor serve
common Corredor.
Unit Manufacturer Photo:
Name:Unit Manufacturer.jpg
Captured:12/20/2023 9:05 AM
Caption:
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Corridor 3rd Flr CD 2408 1.00 *135 146 108
Outlet-02 Corridor 3rd Flr CD 2408 1.00 *135 149 110
Outlet-03 Corridor 3rd Flr CD 2412 1.00 *370 392 106
Totals:----640 0 687 107
FCU-3-4 Supply Outlet Summary
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Corridor 3rd Flr RG 2414 1.00 570 614 108
Totals:----570 0 614 108 -
FCU-3-4 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 6” Ø Air Foil 0.20 660 70 132 189
Totals:-----70 0 132 189
FCU-3-4 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 92 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/28/2023
SYSTEM/UNIT: FCU-B-01
AREA: Staff Break
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not Listed
FCU-B-01/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 640 CFM
Actual Airflow 640 CFM
Design OSA 90 CFM
Actual OSA 92 CFM
FCU-B-01/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 0.80 Amps
Motor Data
FCU-B-01/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-B-01/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-B-01/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-B-01/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.25 in. wc
Suction SP -0.15 in. wc
Discharge SP 0.10 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Staff Break B23 CD 2410 1.00 *320 325 102
Outlet-02 Staff Break B23 CD 2410 1.00 *320 315 98
Totals:----640 0 640 100
FCU-B-01 Supply Outlet Summary
Inland Air Balance, Inc.
Page 93 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Staff Break B23 RG 2412 1.00 550 548 100
Totals:----550 0 548 100 -
FCU-B-01 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 8” Ø Air-foil 0.35 263 90 92 102
Totals:-----90 0 92 102
FCU-B-01 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 94 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/10/2024
SYSTEM/UNIT: FCU-B-02A
AREA: Corridor
Unit Data
Unit Manufacturer LG
Unit Model Number LHN368HV
Unit Serial Number Not Listed
FCU-B-02A/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x25x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 935 CFM
Actual Airflow 978 CFM
Design OSA 260 CFM
Actual OSA 264 CFM
FCU-B-02A/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 1.20 Amps
Motor Data
FCU-B-02A/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 2.30 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-B-02A/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-B-02A/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-B-02A/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.48 in. wc
Suction SP 0.19 in. wc
Discharge SP 0.29 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Wellness B09 SWS 12x10 0.63 413 250 260 104
Outlet-02 Wellness B09 SWS 12x10 0.63 411 250 258 103
Outlet-03 Corridor B13 CD 2408 1.00 *215 223 104
Outlet-04 Corridor B13 CD 2408 1.00 *220 237 108
Totals:----935 0 978 105
FCU-B-02A Supply Outlet Summary
Inland Air Balance, Inc.
Page 95 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Corridor B13 RG 2412 1.00 *435 421 97
Inlet-02 Wellness B09 SWR 12x10 0.83 333 265 276 104
Totals:----700 0 697 100 -
FCU-B-02A Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 8” Ø Air-foil 0.35 754 260 264 102
Totals:-----260 0 264 102
FCU-B-02A Outside Air Intake Summary
Inland Air Balance, Inc.
Page 96 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:12/29/2023
SYSTEM/UNIT: FCU-B-02B
AREA: Wellness
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not listed
FCU-B-02B/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 650 CFM
Actual Airflow 681 CFM
Design OSA 225 CFM
Actual OSA 226 CFM
FCU-B-02B/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 1.01 Amps
Motor Data
FCU-B-02B/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-B-02B/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-B-02B/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-B-02B/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.40 in. wc
Suction SP -0.20 in. wc
Discharge SP 0.20 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Wellness B09 CD 2406 1.00 *55 59 107
Outlet-02 Wellness B09 SWS 20x10 1.00 *595 622 105
Totals:----650 0 681 105
FCU-B-02B Supply Outlet Summary
Inland Air Balance, Inc.
Page 97 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Wellness B09 SWR 14x10 1.00 *425 433 102
Totals:----425 0 433 102 -
FCU-B-02B Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 10 airfoil 0.55 411 225 226 100
Totals:-----225 0 226 100
FCU-B-02B Outside Air Intake Summary
Inland Air Balance, Inc.
Page 98 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:12/29/2023
SYSTEM/UNIT: FCU-B-03
AREA: Corridor
Unit Data
Unit Manufacturer LG
Unit Model Number LHN248HV
Unit Serial Number Not listed
FCU-B-03/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 620 CFM
Actual Airflow 672 CFM
Design OSA 235 CFM
Actual OSA 245 CFM
FCU-B-03/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 0.98 Amps
Motor Data
FCU-B-03/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 1.60 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-B-03/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-B-03/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-B-03/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.40 in. wc
Suction SP -0.18 in. wc
Discharge SP 0.22 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Corridor B02 CD 2410 1.00 *215 223 104
Outlet-02 Theater B03 SWG 18x4 0.40 563 205 225 110
Outlet-03 Theater B03 SWG 18x4 0.40 560 205 224 109
Totals:----625 0 672 108
FCU-B-03 Supply Outlet Summary
Inland Air Balance, Inc.
Page 99 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Theater B03 SWR 18x4 0.50 371 190 186 98
Inlet-02 Theater B03 SWR 18x4 0.50 368 195 184 94
Totals:----385 0 370 96 -
FCU-B-03 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 10 Airfoil 0.55 445 235 245 104
Totals:-----235 0 245 104
FCU-B-03 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 100 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:Robert Watson
Date:1/10/2024
SYSTEM/UNIT: FCU-B-04
AREA: Salon
Unit Data
Unit Manufacturer LG
Unit Model Number LHN368HV
Unit Serial Number Not listed
FCU-B-04/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 1
Filter Size - S1 14x16x2
Filter Qty - S2 1
Filer Size - S2 14x25x2
Test Data
Design Airflow 670 CFM
Actual Airflow 677 CFM
Design OSA 360 CFM
Actual OSA 377 CFM
FCU-B-04/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 233 Volts
Motor Amps T1 1.50 Amps
Motor Data
FCU-B-04/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 2.30 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-B-04/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-B-04/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-B-04/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP Ns in. wc
Actual Total SP 0.41 in. wc
Suction SP 0.11 in. wc
Discharge SP 0.30 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Salon/Spa B04 SWG 12x8 0.57 560 310 319 103
Outlet-02 Salon/Spa B04 SWG 12x8 0.57 532 310 303 98
Outlet-03 Massage SWG 8x8 0.38 145 50 55 110
Totals:----670 0 677 101
FCU-B-04 Supply Outlet Summary
Inland Air Balance, Inc.
Page 101 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Salon/Spa B04 SWR 10x10 0.69 371 280 256 91
Inlet-02 Massage SWR 8x8 0.44 115 50 51 102
Totals:----330 0 307 93 -
FCU-B-04 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 16x10 Velgrid 1.11 340 360 377 105
Totals:-----360 0 377 105
FCU-B-04 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 102 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/28/2023
SYSTEM/UNIT: FCU-B-05
AREA: Activity
Log:FCU-B-05 12/28/2023 David Ramirez CFM value was not specified for Office B07. Supply
Air was set to an approximation determined by room
square footage.
Unit Data
Unit Manufacturer LG
Unit Model Number LHN368HV
Unit Serial Number Not Listed
FCU-B-05/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 2
Filter Size - S1 14x25x2
Test Data
Design Airflow 730 CFM
Actual Airflow 810 CFM
Design OSA 150 CFM
Actual OSA 160 CFM
FCU-B-05/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 205 Volts
Motor Amps T1 1.50 Amps
Motor Data
FCU-B-05/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 2.30 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-B-05/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-B-05/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-B-05/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.31 in. wc
Suction SP -0.20 in. wc
Discharge SP 0.11 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Activity B06 CD 2410 1.00 *365 355 97
Outlet-02 Activity B06 CD 2410 1.00 *365 350 96
Outlet-03 Office B07 CD 2406 1.00 *NS 105
Totals:----730 0 810 111
FCU-B-05 Supply Outlet Summary
Inland Air Balance, Inc.
Page 103 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Activity B06 RG 2414 1.00 *635 580 91
Totals:----635 0 580 91 -
FCU-B-05 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 8” Ø Air-foil 0.35 457 150 160 107
Totals:-----150 0 160 107
FCU-B-05 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 104 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/28/2023
SYSTEM/UNIT: FCU-B-08
AREA: Laundry
Unit Data
Unit Manufacturer LG
Unit Model Number LHN368HV
Unit Serial Number Not Listed
FCU-B-08/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 2
Filter Size - S1 14x25x2
Test Data
Design Airflow 595 CFM
Actual Airflow 595 CFM
Design OSA 450 CFM
Actual OSA 455 CFM
FCU-B-08/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 205 Volts
Motor Amps T1 1.30 Amps
Motor Data
FCU-B-08/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 2.30 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-B-08/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-B-08/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-B-08/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.39 in. wc
Suction SP -0.10 in. wc
Discharge SP 0.29 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Laundry B20 CD 2410 1.00 *300 305 102
Outlet-02 Laundry B20 CD 2410 1.00 *295 290 98
Totals:----595 0 595 100
FCU-B-08 Supply Outlet Summary
Inland Air Balance, Inc.
Page 105 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Area Served Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 Laundry B20 RG 2410 1.00 *145 140 97
Totals:----145 0 140 97 -
FCU-B-08 Return Inlet Summary
System/Unit Area Served Outlet
Type
Size LxW /
D
Instrument AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
OS-01 Unit DUCT 12” Ø Velgrid 0.78 583 450 455 101
Totals:-----450 0 455 101
FCU-B-08 Outside Air Intake Summary
Inland Air Balance, Inc.
Page 106 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
Tested By:David Ramirez
Date:12/28/2023
SYSTEM/UNIT: FCU-B-09
AREA: Main Elec.
Log:FCU-B-09 12/28/2023 David Ramirez FCU installed is a ducted fancoil unit. Air values are
not specified for three diffusers. Unit was set for total.
Unit Data
Unit Manufacturer LG
Unit Model Number LHN368HV
Unit Serial Number Not Listed
FCU-B-09/SF Filter
Filter Manufacturer Endurex
Filter Type Pleated
Design MERV Rating 13
Actual MERV Rating 13
Filter Qty - S1 2
Filter Size - S1 14x25x2
Test Data
Design Airflow 1412 CFM
Actual Airflow 1493 CFM
Design OSA 0 CFM
Actual OSA 0 CFM
FCU-B-09/Supply Fan
Design Fan RPM NS RPM
Actual Fan RPM NVL RPM
Motor Operating HZ/Speed 60/High-Speed Hz
Motor Volts T1-T2 205 Volts
Motor Amps T1 3.20 Amps
Motor Data
FCU-B-09/Supply Fan
Nameplate Motor Manufacturer LG
Nameplate Motor Frame Direct Drive
Nameplate Motor FL Amps 2.30 Amps
Nameplate Motor Hertz 60 Hz
Nameplate Motor Service Factor 1.00
Motor Data
FCU-B-09/Supply Fan Design Nameplate
Motor HP Not Listed HP
Motor Voltage 208-230 Volts
Motor RPM Not Listed
RPM
Motor Phase 1
Sheave Data
FCU-B-09/Supply Fan
Sheave Position Direct Drive
Number of Belts 0
Belt Size Direct Drive
Sheave Center Line Distance Direct Drive in.
Sheave Data
FCU-B-09/Supply Fan Motor Fan
Sheave Diameter Direct Drive
in.
Direct Drive
in.
Sheave Bore Direct Drive
in.
Direct Drive
in.
Test Pressures
Design Total SP NS in. wc
Actual Total SP 0.08 in. wc
Suction SP -0.02 in. wc
Discharge SP 0.06 in. wc
System/Unit Area Served Outlet
Type
Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final
Outlet-01 Electrical Room
B26
SWS 18x10 1.00 *1412 498 35
Outlet-02 Electrical Room
B26
SWS 18x10 1.00 *NS 498
Outlet-03 Electrical Room
B26
SWS 18x10 1.00 *NS 497
Totals:----1412 0 1493 106
FCU-B-09 Supply Outlet Summary
Inland Air Balance, Inc.
Page 107 of 129
Fan CoilPROJECT:
LOCATION:
Clearwater at Newport Beach Oppidan Investments Company
Newport Beach, CA
2312-39PROJECT #:
DATE:
CONTACT:
1/29/2024
David Jones
System/Unit Inlet Type Size LxW /
D
AK
Factor
Final
FPM
Design
CFM
Prelim
CFM
Final CFM % Final % Final
Velocity
Inlet-01 S.O.47 1/2x12 3.96 377 1412 1493 106
Totals:----1412 0 1493 106 -
FCU-B-09 Return Inlet Summary
Inland Air Balance, Inc.
Page 108 of 129
14
1
14
2
14
1
Page 109 of 129
1
1
1
1
1
2
1
3
1
4
1
2
1
1
2
1
11
01
3
1
3
2
3
3
3
1
3
2
3
3
3
4
3
5
3
6
2
1
2
2
2
1
2
2
7
3
Page 110 of 129
14
3
14
4
6
1
6
2
6
3
6
1
6
2
6
3
7
1
7
2
7
1
7
2
7
3
7
4
8
1
8
2
8
1
8
2
8
3
8
4
9A
1
9A
2
9A
1
9A
2
9A
3
9A
4
9B
1
9B
2
9B
1
9B
2
9B
3
9B
4
9B
5
10
1
10
1
10
2
10
3
10
4
1
1
1
2
1
3
1
4
1
5
1
6
1
1
Page 111 of 129
5
1
5
1 5
2
5
3
5
4
6
1
6
2
12
01
13
1
13
1
12
112
2
12
1
12
2
1
1
2
1
2
2
11
1
11
2
11
3
11
1
11
2
11
3
Page 112 of 129
6
1
6
1
13
01
9
1
5
1
5
1
5
2
1
1
1
2
1
1
1
2
1
3
1
4
1
5
1
6
2
1
2
2
2
1
2
2
2
3
2
4
2
5
3
1
3
1
3
2
1
1
7
2
Page 113 of 129
EF-7
7
1
4
1
4
2
4
1
4
2
4
3 4
4
2
1
3
1
Page 114 of 129
6
2
6
3
7
1
7
1 7
2
2
2
1
Page 115 of 129
7
3
7
4
7
5
EF-8
8
2
10
01
1
1
Page 116 of 129
4
1
4
1
4
2
4
3
RF-3-1
1
1
Page 117 of 129
1
1
1
1
1
2
1
3
1
4
1
5
1
2
2
1
3
1
Page 118 of 129
2
1
2
1
2
2
2
3
Page 119 of 129
3
1
3
1
3
2
8
1
EF-3-2
2
1
3
3
1
1
Page 120 of 129
1
1
1
2
1
1
1
1
3
12
1
2A
1
2A
2
2A
1 2A
2
2A
3
2A
4
1
1
2
1
Page 121 of 129
8
1
8
1
8
2
5
1
1
1
1
2
1
3
1
4
1
5
6
1
4
1
Page 122 of 129
4
1
2B
1
2B
1
2B
2
3
1
3
2
3
1
3
2
3
3
4
1
4
1
4
2
5
1
5
2
5
1
5
3
3
1
7
1
9
1
Page 123 of 129
Page 124 of 129
Page 125 of 129
Page 126 of 129
Page 127 of 129
Manufacturer Evergreen Telemetry Calibration Environment
Product Pressure / Velocitv Module Temperature 74 oF
Model S-PVF-1 Rel. Humiditv 26 %
SN 2200540C Bar. Pressure 28.6 in Hq
EVEBONEEil Certificate of Cal i bration
lnland Air BalancefELEMEINY
[[ ns rouno p as lett F 'n
Tolerance E out of rolerance
Calibration Data
N|ST-Traceable Lab Calibration Standards
This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be
within the specified tolerance unless otherwise stated. lt has been calibrated using measurement standards
traceable to the National lnstitue of Standards and Technology, or accepted intrinsic standards of measurement,
or derived by the ratio type of self calibrated techniques.
30-Nov-2023 30-Nov-2025
Calibration Date Date Due
, Mesa, AZ85202
Measurement
Variable
Test
Point
Cal
Standard
Allowable Range Test
lnstrumentMinMax
Barometric
Pressure (in Hg)
Spec -2Yo - 0.1 + 2o/o + 0.1
1 20.0 20.1
2 28.6 28.7
3 33.0 33.1
Differental
Pressure
(in wc)
Via Pitot
Velocity Pressure
(inW.C. / FPM)
-3Yo -7
Spec -2Yo-.001 +2o/o+.001
1 10.00 9.976
2 2.000 1.994
3 0.5000 0.4966
4 0.0500 0.0498
5 -10.00 -10.009
6 -0.0s00 -0.0497
-3% -7 +3o/o + 7
7 0,00064 / 101 101
B 0.0160 i 507 506
lndicates out of tolerance condition --------t
Variable Svstem lD Calibration Last Calibration Due
Pressure 7481227 8-Mar-23 B-Mar-25
Pressure 7568470 8-Mar-23 8-Mar-25
Pressure 787 1917 12-Seo-23 12-Sep-25
Pressure 7870754 1 2-Sep-23 12-Sep-25
Pressure 2205000006 1 3-Sep-23 1 3-Sep-25
Pressure 1 208000080 1 3-Feb-23 '13-Feb-25
Pressure 41 001 F6C 27-Apr-23 27-Aor-25
Velocity 21 001 91A 24-Feb-23 24-Feb-25
Velocity 21 001 90A 1-May-23 1-May-25
Calibrated By
602.574.6192 t i r33S
Page 128 of 129
Manufacturer Evergreen Telemetry Calibration Environment
Product Water Pressure Sensing Module Temperature 77 oF
Model s-DP-250 Rel. Humidity 32 o/o
SN 22001588 Bar. Pressure 28.6 in Hq
EYENfrNEEN Certificate of Cal ibration
lnland Air BalanceTELEMEIfrY
E Rs rouno E eslen E tn Toterance E out of rolerance
Calibration Data
NIST-Traceable Calibration Lab Standards
This instrument has been checked foraccuracy, calibrated lo manufactureds specifications, and found to be
within the specilied lolerance unless otherwise stated. lt has been calibrated using measurement standards
traceable to the National lnstitue of Standards and Technology, or accepted intrinsic standards of measuremenl,
7-Sep-2023 7-Sep-2024
Calibration Date Date Due
Mesa,M85202
Specification
+l- 2o/" +l- last dioit
Cal
srd
Sensor 1
Diff Pres Difference
Cal
std
Sensor 2
Gaqe Lo Ditr
Approx Set Point (Yo)ofto
PSI (ffwc)(flwc)(ftwc)(ftwc)
0.13 0.3 0.3 0 0.3 0.3 0
o.434 1.0 1.0 0 1.0 1.0 0
0.867 2.0 2.0 0 2.0 2.0 0
2.168 5.0 5.0 0 5.0 5.0 0
PSI PSI PSI PSI
10 10.0 10.0 0.0 10.0 10.1 1.0
40 40.0 40.0 0.0 40.0 40.1 0.3
80 80.0 80.4 0.5 80.0 80.5 0.6
120 120.0 120.1 0.1 120.0 120.1 0.1
240 240.0 240.3 0.1 240.0 240.3 0.1
Gonversion
PSI ftwc inwc
1.00 2.307 27.68
0.434 1.00 12.00
lndicat€s out of tolerance condition
-,1
Variable System lD Calibration Last Calibration Due
Pressure 5564304 20-Sep-21 20-Sep-23
Temoerature 21396189 5-Oct-21 SOct-23
or derived.by the ratio type qf s9(calibrated techniques.
r33S602.574.6192t
Page 129 of 129