HomeMy WebLinkAboutX2021-2737 - Soils (3) 475 Goddard, Suite 200 | Irvine, California 92618 | p. 949.753.7070 | www.ninyoandmoore.com July 19, 2022 Project No. 209537009 Mr. Roger Bernstein Vice President of Construction Oppidan 1100 Lincoln Avenue San Jose, California 95125 Subject: Geotechnical Observation and Testing Building Pad Preparation Clearwater at Newport Beach 101 Bayview Place Newport Beach, California 92660 References: Ninyo & Moore, 2021, Geotechnical Evaluation, Newport Beach Senior Living Facility, 101 Bayview Place, Newport Beach, California, Project 209537007, dated November 24. Douglas Pancake Architects, 2022, Foundation & Underground Utilities, Clearwater at Newport, Oppidan Investment Company, 101 Bayview Place, Newport Beach, California, 92660, California, dated July 8. Tait & Associates, Inc., 2022, Rough Grading and Temporary Shoring Plans, Clearwater at Newport, Oppidan Incorporated, 101 Bayview Place, Newport Beach, California, 92660, California, dated February 16. Dear Mr. Bernstein: In accordance with your request and authorization, we have provided geotechnical observation and field density testing services during construction of the basement-level building pad for the Clearwater at Newport Beach project. The geotechnical observation and field density testing services documented in this letter, were provided by Ninyo & Moore representatives during the overexcavation and re-compaction efforts performed between May 31, 2022 and June 22, 2022. Prior to the placement of fill, the exposed subgrade was scarified to a depth of approximately 6 inches or more, moisture-conditioned, and was re-compacted to be firm and competent. Subsequently, the engineered backfill was moisture conditioned to near optimum, placed in horizontal lifts, and was re-compacted to a relative compaction of 90 percent or more. Based on our observations and test results, it is our opinion that the proposed building pad was over excavated and re-compacted in general accordance with the reference project plans and soils report, and supplemental geotechnical recommendations provided by Ninyo & Moore. Our opinions are provided in accordance with the current practice and standard of care exercised by geotechnical consultants performing similar tasks in the project area. No warranty, expressed or Ninyo & Moore | Clearwater at Newport Beach , Newport Beach, California | 209537009 | July 19, 2022 implied, is made regarding our opinions and conclusions. We appreciate the opportunity to be of service on this project. Sincerely, NINYO & MOORE Emily Homan, PG Project Geologist Garreth Saiki, PE, GE Principal Engineer ECH/GMS/mlc 475 Goddard, Suite 200 | Irvine, California 92618 | p. 949.753.7070 | www.ninyoandmoore.com December 22, 2023 Project No. 209537009 Mr. Roger Bernstein Oppidan 1100 Lincoln Avenue San Jose, California 95125 Subject: Compaction Report – Clearwater at Newport Beach 101 Bayview Place Newport Beach, California References: Ninyo & Moore, 2023, Building Pad Compaction Report – Clearwater at Newport Beach, 101 Bayview Place, Newport Beach, California, dated October 3. Ninyo & Moore, 2021, Geotechnical Evaluation, Newport Beach Senior Living Facility, 101 Bayview Place, Newport Beach, California, dated November 24. Dear Mr. Bernstein: In accordance with your request and authorization, we have provided field observation and field density testing services during earthwork operations for the Clearwater at Newport Beach project located at 101 Bayview Place in Newport Beach, California (Figure 1). This report presents the results of our geotechnical observation and field density testing services. Our scope of services included project coordination, laboratory testing of selected soil samples, and field density testing during the grading operations that pertain to the new building area. We also provided field density testing during the various general site fill, trench, and structural excavation backfill, as well as for the placement and compaction of subgrade, aggregate base, and asphalt concrete. The earthwork operations observed and tested by Ninyo & Moore were performed between April 22, 2022, and November 2, 2023. The asphalt concrete placement and compaction operations observed and tested by Ninyo & Moore were performed between August 24, 2023 and August 28th, 2023. EARTHWORK The initial phase of grading for the project generally included stripping, clearing, and exporting the debris generated from the project demolition activities. Summaries of the earthwork operation for the new building and other improvements on site are as follows: • Building Pad Area – Ground preparation consisted primarily of overexcavation, scarification, moisture conditioning, and recompaction. The areas to receive fill were observed and approved by Ninyo & Moore prior to further construction. The subgrade soils were scarified to a depth of 6 inches or more, moisture conditioned, and recompacted to be firm and competent prior to placement of the new fill. The material utilized for fill was generated from excavated on-site soils Ninyo & Moore | 101 Bayview Place, Newport Beach, California | 209537009 | December 22, 2023 2 and import materials from an offsite location, which were brought to near optimum moisture and compacted in approximately 6 to 8-inch lifts to 90 percent or more relative compaction in accordance with project plans and geotechnical recommendations provided by Ninyo & Moore. During the earthwork operations, any oversized rocks (3-inches or greater) were removed by hand or equipment. The compacted fill soil placed within the building area is considered a primary structural fill. • Fire Lane – Ground preparation consisted primarily of overexcavation, scarification, moisture conditioning, and recompaction. After excavation, the subgrade was scarified, moisture conditioned, and compacted to 90 percent or more relative compaction in accordance with the geotechnical report. Upon satisfactory compaction of the subgrade, aggregate base was placed and compacted to 95 percent or more relative compaction to the specified thickness to receive the base of asphalt concrete. The subgrade soil and aggregate base in considered a secondary structural fill. • General Site Areas – Ground preparation included overexcavation, scarification, and recompaction below the proposed subgrades prior to further construction and/or fill. The fill, backfill, subgrade, soil placed and/or compacted is considered a secondary structural fill, and is intended to support new concrete, landscaped areas. • Utilities – Utility improvements include excavation and installation for storm drain, sanitary sewer, water service, and dry utilities. The soil placed and/or compacted is considered a secondary structural fill. Our services were provided as scheduled and coordinated by the construction manager, W. E. O’Neil. We were generally on site on a periodic basis during the earthwork operations. The earthwork was performed using heavy earthmoving equipment, including a Case loader, skip loader, and a Caterpillar D6 dozer, a medium-sized vibratory roller, rubber-wheel loader with full bucket and wacker Rammax compactors, and a water truck. ASPHALT CONCRETE PAVING Upon completion of the earthwork in the fire lane, asphalt concrete base course (Greenbook Type III B3 PG 64-10) was placed in 4-inch layers. The asphalt concrete was compacted to 95 percent or more relative compaction. Our services were provided as scheduled and coordinated by the construction manager, W. E. O’Neil. We were generally on site on a daily basis during the asphalt concrete paving operations. The asphalt concrete paving was performed using an asphalt concrete paving machine, material transfer vehicle, and breakdown and finish rollers. FIELD AND LABORATORY TESTING In-place moisture and density tests of the compacted materials were performed in general accordance with the ASTM International (ASTM) 6938 (Nuclear Gauge method). The laboratory maximum dry density test results were performed in general accordance with ASTM D 1557. In-place density tests of compacted asphalt concrete were performed in general accordance with ASTM D2950 (Nuclear Gauge Method). The laboratory maximum density / unit weight test results were Ninyo & Moore | 101 Bayview Place, Newport Beach, California | 209537009 | December 22, 2023 3 performed in general accordance with ASTM D1560. Maximum density test results are presented in Table 1. The field density test results for compacted fill, sewer main, storm drain, utility main, subgrade, and aggregate base are summarized in Table 2. The field density test results for asphalt concrete are summarized in Table 3. The approximate locations of the field density tests are shown on Figure 2. The field density test results were used to evaluate the relative compaction of the fill materials and asphalt concrete. CONCLUSIONS Based on our observation and testing, it is our opinion that the earthwork and asphalt concrete paving operations observed and tested by Ninyo & Moore were performed in general accordance with the referenced geotechnical engineering report, dated November 24, 2021 and supplemental geotechnical recommendations provided by Ninyo & Moore. Our observations and testing indicate that the fill soils placed between April 22, 2022, and November 2, 2023, were compacted 90 percent or more (subgrade) and 95 percent or more (aggregate base) relative compaction utilizing test methods ASTM D 6938 and D 1557. The asphalt concrete placed between August 24, 2023 and August 28, 2023 was compacted to 95 percent or more relative compaction utilizing ASTM D2950 and ASTM D1560. LIMITATIONS The field and laboratory testing presented in this report have been conducted in general accordance with current practice and the standard of care exercised by geotechnical consultants performing similar tasks in this area. No warranty, expressed or implied, is made regarding the opinions expressed in this report. It is important to note that the precision of field density tests and the maximum dry density tests is not exact and variations should be expected. We appreciate the opportunity to be of service on this project. Sincerely, NINYO & MOORE Emily Homan, PG Project Geologist Garreth M. Saiki, PE, GE Principal Engineer ECH/GMS/mlc Attachments: Table 1 – Maximum Density Test Results Table 2 – Summary of Field Density Tests Table 3 – Summary of Field Density Tests – Asphalt Concrete Figure 1 – Site Location Figure 2 – Field Density Test Locations Ninyo & Moore | 101 Bayview Place, Newport Beach, California | 209537009 | December 22, 2023 1 Table 1 – Maximum Density Test Results Soil Type No. Description U.S.C.S. Method of Soil Class. Maximum Density (pcf) Optimum Moisture (%) 1 Brown Clayey Sand SC 127 10.5 2 Pale Brown Sandy Silt ML 119.0 12.5 3 Yellowish Brown Silt with Sand ML 123.5 11.5 4 Brown Clayey Silt with Sand ML 125.5 10.5 5 Imported Crushed Miscellaneous Base CMB 125.5 10.5 6 Imported Crushed Miscellaneous Base CMB 127 9.5 1AC III B3 PB64-10 AC 152 - Notes: pcf – pounds per cubic foot SUMMARY OF FIELD DENSITY TESTS TABLE 2 PROJECT NO. Moisture Content (%) Dry Density (pcf) Proctor Density (pcf) Optimum Moisture Content (%) 1 # 4/22/22 CF North Side of Site; Fire Road; Bottom; Sta 0+50 55.0 1 12.0 114.1 127.0 10.5 90 2 # 4/22/22 CF North Side of Site; Fire Road; Bottom; Sta 1+50 55.5 1 11.6 114.2 127.0 10.5 90 3 # 4/22/22 CF North Side of Site; Fire Road; Bottom; Sta 2+50 55.5 1 15.3 110.3 127.0 10.5 90 Retest on 5 4 # 4/22/22 CF North Side of Site; Fire Road; Bottom; Sta 3+50 55.5 1 13.6 110.7 127.0 10.5 90 Retest on 6 5 # 4/25/22 CF North Side of Site; Fire Road; Bottom; Sta 2+50 55.5 1 10.3 116.4 127.0 10.5 90 Retest of 3 6 # 4/25/22 CF North Side of Site; Fire Road; Bottom; Sta 3+50 55.5 1 9.4 119.7 127.0 10.5 90 Retest of 4 7 # 4/25/22 CF North Side of Site; Fire Road; Bottom; Sta 4+50 55.5 1 9.2 119.0 127.0 10.5 90 8 # 4/26/22 CF South Side of Site; Fire Road; Bottom 55.0 1 8.6 115.8 127.0 10.5 90 9 # 4/26/22 CF South Side of Site; Fire Road; Bottom; Sta 4+80 57.5 1 7.4 114.6 127.0 10.5 90 10 # 4/26/22 CF West Side of Site; Sta 3+00 57.5 1 7.7 115.0 127.0 10.5 90 11 # 4/26/22 CF North Side of Site; Fire Road, Sta 2+00 57.5 1 7.6 117.0 127.0 10.5 90 12 # 4/26/22 CF North Side of Site; Fire Road; Sta 0+75 57.5 1 9.2 116.3 127.0 10.5 90 13 # 4/26/22 CF South Side of Site; Fire Road 57.5 1 9.0 114.8 127.0 10.5 90 14 # 5/31/22 CF South Site of Site; Driveway 55.5 2 14.7 108.4 119.0 12.5 90 15 # 5/31/22 CF South Side of Site; Driveway 56.5 2 9.1 107.3 119.0 12.5 90 16 # 6/14/22 CF Northwest Corner of Building Pit; Overexcavation Footing Bottom; 43.0 3 11.5 108.3 123.5 11.5 90 Retest on 17 17 # 6/15/22 CF Northeast Corner of Building Pit; Overexcavation; Footing Bottom 43.0 3 11.6 110.8 123.5 11.5 90 Retest of 16 18 # 6/15/22 CF West Center of Building Pit; Overexcavation; Footing Bottom 43.0 3 9.7 111.6 123.5 11.5 90 19 # 6/15/22 CF East Center of Building Pit; Overexcavation; Footing Bottom 43.0 3 9.4 112.7 123.5 11.5 90 20 # 6/15/22 CF Southwest Center of Building pit; Overexcavation; Footing Bottom 43.0 3 10.2 114.2 123.5 11.5 90 21 # 6/20/22 CF East Side of Building Pad; Overexcavation; Footing Bottom 43.0 3 14.0 114.9 123.5 11.5 90 22 # 6/20/22 CF Southeast Side of Building Pad; Overexcavation; Footing Bottom 43.0 3 11.9 115.3 123.5 11.5 90 23 # 6/20/22 CF Southwest Side of Building Pad; Overexcavation; Footing Bottom 43.0 2 13.2 110.7 119.0 12.5 90 24 # 6/20/22 CF West Side of Building Pad; Overexcavation; Footing Bottom 43.0 3 13.8 117.8 123.5 11.5 90 25 * 6/20/22 CF West Side of Building Pad; Overexcavation; Footing Bottom 43.0 2 14.0 115.2 119.0 12.5 90 26 # 6/20/22 CF East Side of Building Pad; Overexcavation; Footing Bottom 43.0 3 14.7 115.9 123.5 11.5 90 27 # 6/20/22 CF South Side of Building Pad; Backfill; Footing Bottom 44.0 3 13.5 113.7 123.5 11.5 90 28 # 6/20/22 CF South Side of Building Pad; Backfill; Footing Bottom 44.0 3 13.7 117.7 123.5 11.5 90 29 # 6/20/22 CF West Side of Building Pad; Backfill; Footing Bottom 45.0 3 14.3 118.4 123.5 11.5 90 30 # 6/20/22 CF West Side of Building Pad; Backfill; Footing Bottom 45.0 3 13.1 114.9 123.5 11.5 90 TEST OF: Date Test Location Soil Type No. Elevation (ft) Test of Test No. Field Laboratory 93 90 90 91 92 95 97 93 93 93 90 90 87 87 Remarks 209537009 Compacted Fill, Sewer Main, Storm Drain, Utility Main, Subgrade, Aggregate Base Specified Relative Compaction (%) Relative Compaction (%) 94 92 95 96 92 94 94 91 90 91 92 92 90 91 90 88 209537009 FD - Final 1 of 7 SUMMARY OF FIELD DENSITY TESTS TABLE 2 PROJECT NO. Moisture Content (%) Dry Density (pcf) Proctor Density (pcf) Optimum Moisture Content (%) TEST OF: Date Test Location Soil Type No. Elevation (ft) Test of Test No. Field Laboratory Remarks 209537009 Compacted Fill, Sewer Main, Storm Drain, Utility Main, Subgrade, Aggregate Base Specified Relative Compaction (%) Relative Compaction (%) 31 # 6/21/22 CF North Side of Building Pad; Backfill; Overexcavation; Footing Bottom 43.0 2 12.7 114.5 119.0 12.5 90 32 # 6/21/22 CF Northeast Side of Building Pad; Overexcavation; Footing Bottom 43.0 2 13.5 113.1 119.0 12.5 90 33 # 6/21/22 CF East Side of Building Pad; Overexcavation; Footing Bottom 43.0 3 11.8 116.5 123.5 11.5 90 34 # 6/21/22 CF East Side of Building Pad; Overexcavation; Footing Bottom 43.0 3 13.9 115.7 123.5 11.5 90 35 * 6/21/22 CF Northwest Side of Building Pad; Backfill; Footing Bottom 44.0 3 13.1 113.2 123.5 11.5 90 36 # 6/21/22 CF North Side of Building Pad; Backfill; Footing Bottom 45.0 3 12.0 116.0 123.5 11.5 90 37 # 6/21/22 CF Northeast Side of Building Pad; Backfill; Footing Bottom 45.0 3 12.4 115.7 123.5 11.5 90 38 # 6/22/22 CF East Side of Building Pad; Backfill; Footing Bottom 45.0 3 13.4 114.8 123.5 11.5 90 39 # 6/22/22 CF Northeast Side of Building Pad; Backfill; Footing Bottom 45.0 3 11.6 114.2 123.5 11.5 90 40 # 6/22/22 SG Center of Building Pad; Backfill; Footing Bottom 45.0 3 11.0 117.1 123.5 11.5 90 41 # 6/22/22 SG Center of Building Pad; Backfill; Footing Bottom 45.0 3 11.7 115.5 123.5 11.5 90 42 # 6/22/22 SG Center of Building Pad; Backfill; Footing Bottom 45.0 3 11.0 118.8 123.5 11.5 90 43 # 6/22/22 SG Center of Building Pad; Backfill; Footing Bottom 45.0 3 12.0 119.6 123.5 11.5 90 44 # 6/30/22 WM Water Lines inside building footing, North West Corner 43.0 2 9.5 108.0 119.0 12.5 90 45 # 6/30/22 WM Water Lines inside building footing, North West Corner 43.0 2 11.5 117.4 119.0 12.5 90 46 # 6/30/22 WM Water Lines inside building footing, North West Corner 43.0 2 10.1 110.9 119.0 12.5 90 47 # 6/30/22 WM Water Lines inside building footing, North West Corner 43.0 2 13.7 109.9 119.0 12.5 90 48 # 7/1/22 WM Water Lines inside building footing 44.0 2 14.5 113.6 119.0 12.5 90 49 # 7/1/22 WM Water Lines inside building footing 44.0 2 15.5 113.6 119.0 12.5 90 50 # 7/1/22 UM Electric Conduit lines, North End of Building Footing 43.0 2 15.8 103.0 119.0 12.5 90 Retest on 51 51 # 7/1/22 UM Electric Conduit lines, North End of Building Footing 44.0 2 18.1 107.5 119.0 12.5 90 Retest of 50 52 # 7/1/22 SM Sewer Line at Entrance by Manhole; Southeast Portion of the site 44.0 2 14.4 110.0 119.0 12.5 90 53 # 7/1/22 SM Sewer Line at Entrance by Manhole 44.0 2 10.7 109.6 199.0 23.5 90 54 # 7/5/22 SM Sewer Line at Entrance by Clean out 43.0 1 15.9 104.3 127.0 10.5 90 Retest on 55 55 # 7/5/22 SM Sewer Line at Entrance by Clean out 45.0 1 13.6 116.7 127.0 10.5 90 Retest of 54 56 # 7/5/22 SM Sewer Line at Entrance, 10' past clean out. 44.0 1 11.1 117.6 127.0 10.5 90 57 # 7/5/22 CF Center of building pad 43.0 3 11.0 103.7 123.5 11.5 90 Retest of 58 58 # 7/5/22 CF Center of building pad 44.0 3 10.3 114.4 123.5 11.5 90 Retest of 57 59 # 7/6/22 UM Electric Conduit lines, Center of building Pad 47.0 2 13.8 114.9 119.0 12.5 90 60 # 7/6/22 UM Electric Conduit lines, Center of building Pad 46.0 2 10.9 116.4 119.0 12.5 90 93 92 95 95 93 84 93 97 98 96 82 92 95 94 96 97 93 92 95 94 94 94 87 90 92 92 94 92 91 99 209537009 FD - Final 2 of 7 SUMMARY OF FIELD DENSITY TESTS TABLE 2 PROJECT NO. Moisture Content (%) Dry Density (pcf) Proctor Density (pcf) Optimum Moisture Content (%) TEST OF: Date Test Location Soil Type No. Elevation (ft) Test of Test No. Field Laboratory Remarks 209537009 Compacted Fill, Sewer Main, Storm Drain, Utility Main, Subgrade, Aggregate Base Specified Relative Compaction (%) Relative Compaction (%) 61 # 7/6/22 UM Electric Conduit lines, Center of building Pad 44.0 2 14.0 113.9 119.0 12.5 90 62 # 7/6/22 UM Electric Conduit lines, Center of building Pad 45.0 2 12.5 113.3 119.0 12.5 90 63 # 7/6/22 UM Electric Conduit lines, Center of building Pad 50.0 2 14.0 116.2 119.0 12.5 90 64 # 7/6/22 UM Electric Conduit lines, Center of building Pad 49.0 1 9.7 118.5 127.0 10.5 90 65 # 7/7/22 WM Water lines at south end of building pad 48.0 2 15.1 101.8 119.0 12.5 90 Retest on 66 66 # 7/7/22 WM Water lines at south end of building pad 49.0 2 14.4 108.3 119.0 12.5 90 Retest of 65 67 # 7/7/22 WM Water lines at south end of building pad 50.0 2 12.9 11.3 119.0 12.5 90 68 # 7/7/22 SM Sewer line at South end 51.0 1 13.0 113.7 127.0 12.5 90 69 # 7/7/22 SM Sewer Line at South end 43.0 2 13.6 106.3 119.0 12.5 90 Restest on 73 70 # 7/7/22 UM Electric Conduit lines, North east of building pad 44.0 2 11.4 111.4 119.0 12.5 90 71 # 7/7/22 UM Electric Conduit lines, North East of building Pad 44.0 2 18.2 112.0 119.0 12.5 90 72 # 7/7/22 UM Electric Conduit lines, North East of building Pad 45.0 2 14.7 109.8 119.0 12.5 90 73 # 7/8/22 SM Sewer line at Sorth end of building 50.0 3 10.7 122.0 123.5 11.5 90 74 # 7/8/22 SM Sewer line at Sorth end of building 49.0 3 11.8 120.4 123.5 11.5 90 75 # 7/8/22 SM Sewer line at Sorth end of building 48.0 3 13.9 114.0 123.5 11.5 90 76 # 7/8/22 SM Sewer line at Sorth end of building 49.0 3 14.3 110.6 123.5 11.5 90 77 # 7/8/22 SM Sewer line at Sorth end of building 50.0 3 12.8 119.1 123.5 11.5 90 78 # 7/8/22 SM Sewer line at Sorth end of building 51.0 3 11.5 113.1 123.5 11.5 90 79 # 7/11/22 UM Electrical Line, Riser; Eastern corner of the building 43.0 3 13.7 115.9 123.5 11.5 90 80 # 7/11/22 UM Electrical Line, Riser: Southern corner of the building 44.0 3 10.0 116.2 123.5 11.5 90 81 # 7/11/22 UM Electrical Line, Riser: Southern corner of the building 44.0 3 9.3 122.6 123.5 11.5 90 82 # 7/14/22 WM Water Lines, at the North Center of the Pad. 44.0 3 16.0 99.5 123.5 11.5 90 Retest on 83 83 # 7/14/22 WM Water Lines, at the North Center of the Pad. 44.0 3 14.6 114.0 123.5 11.5 90 Retest of 83 84 # 7/14/22 WM Water Lines, at the North Center of the Pad. 43.0 3 9.8 108.2 123.5 11.5 90 Retest on 85 85 # 7/14/22 WM Water Lines, at the North Center of the Pad. 44.0 3 10.6 118.4 123.5 11.5 90 Retest on 84 86 # 7/14/22 WM Water Lines, at the North Center of the Pad. 43.0 3 10.2 115.0 123.5 11.5 90 87 # 7/14/22 WM Water Lines, at the North Center of the Pad. 45.0 3 11.1 118.7 123.5 11.5 90 88 # 7/15/22 SD Backfill around Storm Drain Capture System 56.0 3 11.8 119.3 123.5 11.5 90 89 # 7/15/22 SD Backfill around Storm Drain Capture System 56.0 3 12.8 115.0 123.5 11.5 90 90 # 7/16/22 SD Backfill around Storm Drain Capture System 56.0 3 9.4 112.2 123.5 11.5 90 94 90 89 94 94 92 99 93 96 96 93 91 94 99 81 92 88 96 91 94 96 97 92 90 96 92 86 93 98 95 209537009 FD - Final 3 of 7 SUMMARY OF FIELD DENSITY TESTS TABLE 2 PROJECT NO. Moisture Content (%) Dry Density (pcf) Proctor Density (pcf) Optimum Moisture Content (%) TEST OF: Date Test Location Soil Type No. Elevation (ft) Test of Test No. Field Laboratory Remarks 209537009 Compacted Fill, Sewer Main, Storm Drain, Utility Main, Subgrade, Aggregate Base Specified Relative Compaction (%) Relative Compaction (%) 91 # 7/17/22 SD Backfill around Storm Drain Capture System 56.0 3 9.3 114.6 123.5 11.5 90 92 # 7/15/22 SD Backfill around Storm Drain Capture System 56.0 3 16.0 117.4 123.5 11.5 90 93 # 7/18/22 UM Electrical Room at South of building 45.0 3 14.6 121.3 123.5 11.5 90 94 # 7/18/22 UM Electrical Room at South 0f building 45.0 3 9.8 117.0 123.5 11.5 90 95 # 7/18/22 WL Water Lines at South East of building pad. 44.0 3 10.6 118.4 123.5 11.5 90 96 # 9/30/22 CF Backfill; Southeast side of Building 56.0 3 10.2 114.9 123.5 11.5 90 97 # 9/30/22 CF Backfill; Southeast side of Building 56.0 3 11.1 117.7 123.5 11.5 90 98 # 9/30/22 CF Backfill; Southeast side of Building 58.0 3 11.8 116.0 123.5 11.5 90 99 # 10/3/22 CF Backfill; Southeast side of Building 55.0 3 12.8 113.4 123.5 11.5 90 100 # 10/3/22 CF Backfill; Southwest side of Building 56.0 3 9.4 115.2 123.5 11.5 90 101 # 10/6/22 CF Backfill; CMB; Northwest side of Building 56.0 5 11.6 112.9 125.5 10.5 90 102 # 10/6/22 CF Backfill; CMB; Northwest side of Building 56.0 5 12.4 113.4 125.5 10.5 90 103 # 10/6/22 CF Backfill; CMB; Northwest side of Building 56.0 5 12.5 115.7 125.5 10.5 90 104 # 10/7/22 CF Backfill; CMB; Sidewalk Southeast of Building 56.0 5 12.5 113.3 125.5 10.5 90 105 # 10/7/22 CF Backfill; CMB; Sidewalk Southeast of Building 56.0 5 11.6 113.3 125.5 10.5 90 106 # 10/7/22 CF Backfill; South side of Building 58.0 4 9.6 120.4 125.5 10.5 90 107 # 10/10/22 CF Backfill; East side of Building 55.0 4 10.0 121.9 125.5 10.5 90 108 # 10/10/22 CF Backfill; East side of Building 56.0 4 10.9 116.3 125.5 10.5 90 109 # 10/11/22 SG Fire exit; Northwest of Building 58.0 5 9.2 113.3 125.5 10.5 90 110 # 10/11/22 SG Fire exit; West of Building 58.0 5 10.4 113.1 125.5 10.5 90 111 # 10/11/22 SG Fire exit; Southwest of Building 58.0 5 8.9 113.5 125.5 10.5 90 112 # 10/11/22 SG Fire exit; Southwest of Building 58.0 5 8.7 113.3 125.5 10.5 90 113 # 10/11/22 SG Fire exit; Southof Building 58.0 5 9.5 117.9 125.5 10.5 90 114 # 10/13/22 SG Soils placement; East side building 58.0 4 9.8 120.9 125.5 10.5 90 115 # 10/13/22 SG Soils placement; East side building 58.0 4 10.4 113.7 125.5 10.5 90 116 # 10/13/22 SG Soils placement; East side building 58.0 4 12.0 113.3 125.5 10.5 90 117 # 10/14/22 SF Garage ramp; East of building 50.0 4 8.7 116.9 125.5 10.5 90 118 # 10/14/22 SF Garage ramp; East of building 53.5 4 9.2 112.3 125.5 10.5 90 119 # 10/14/22 SG Soils; East side of Building 58.0 4 10.2 113.2 125.5 10.5 90 120 # 10/14/22 SG Soils; East side of Building 58.0 4 10.3 113.8 125.5 10.5 90 90 91 96 94 90 90 93 90 91 92 90 92 90 90 92 95 98 95 96 92 93 90 90 96 97 93 93 97 90 90 209537009 FD - Final 4 of 7 SUMMARY OF FIELD DENSITY TESTS TABLE 2 PROJECT NO. Moisture Content (%) Dry Density (pcf) Proctor Density (pcf) Optimum Moisture Content (%) TEST OF: Date Test Location Soil Type No. Elevation (ft) Test of Test No. Field Laboratory Remarks 209537009 Compacted Fill, Sewer Main, Storm Drain, Utility Main, Subgrade, Aggregate Base Specified Relative Compaction (%) Relative Compaction (%) 121 # 10/26/22 UM Bottomo of Power Trench, Southeast Corner of the Building 52.0 4 8.9 113.4 125.5 10.5 90 122 # 10/27/22 UM Bottomo of Power Trench, Southeast Corner of the Building 51.0 4 11.9 112.7 125.5 10.5 90 123 # 10/28/22 UM Generator/Edison Trench, Southwest of the building 55.0 4 12.4 1117.3 125.5 10.5 90 124 # 10/28/22 UM Generator/Edison Trench, Southwest of the building 56.5 4 11.9 115.3 125.5 10.5 90 125 # 10/31/22 UM Generator/Edison Trench, Southwest of the building 57.0 3 12.0 113.7 125.5 10.5 90 126 # 10/31/22 UM Power Vault at South of the Project 53.0 4 10.7 118.3 125.5 10.5 90 127 # 10/31/22 UM Power Vault at South of the Project 54.5 4 11.9 115.9 125.5 10.5 90 128 # 10/31/22 UM Power Vault at South of the Project 55.5 4 12.1 114.2 125.5 10.5 90 129 # 11/18/22 UM Bottom of Electric Power trench-Bldg. to Southeast corner of site 50.0 2 13.7 107.3 119.0 12.5 90 130 # 11/22/22 UM Bottom of Electric Power trench-Bldg. to Southeast corner of site 52.5 3 12.5 114.6 123.5 11.5 90 131 # 11/22/22 UM Bottom of Electric Power trench-Bldg. to Southeast corner of site 51.0 3 11.9 115.4 123.5 11.5 90 132 # 11/22/22 UM Bottom of Electric Power trench-Bldg. to Southeast corner of site 53.0 4 11.6 119.8 125.5 10.5 90 133 # 11/22/22 UM Bottom of Electric Power trench-Bldg. to Southeast corner of site 50.5 4 11.5 114.6 125.5 10.5 90 134 # 11/22/22 UM Bottom of Electric Power trench-Bldg. to Southeast corner of site 53.5 3 12.7 118.2 123.5 11.5 90 135 # 11/22/22 UM Bottom of Electric Power trench-Bldg. to Southeast corner of site 50.5 3 13.2 117.6 123.5 11.5 90 136 # 11/22/22 UM Bottom of Electric Power trench-Bldg. to Southeast corner of site 52.0 3 12.9 114.9 123.5 11.5 90 137 # 11/22/22 UM Bottom of Electric Power trench-Bldg. to Southeast corner of site 50.5 3 12.6 113.7 123.5 11.5 90 138 # 11/22/22 UM Bottom of Electric Power trench-Bldg. to Southeast corner of site 52.0 2 13.9 109.6 119.0 12.5 90 139 # 11/22/22 UM Bottom of Electric Power trench-Bldg. to Southeast corner of site 53.5 2 13.6 113.8 119.0 12.5 90 140 # 11/22/22 UM Bottom of Electric Power trench-Bldg. to Southeast corner of site 55.0 3 12.3 118.6 123.5 11.5 90 141 # 11/22/22 UM Bottom of Primary Electric trench; south section of site 52.0 4 11.9 115.7 125.5 10.5 90 142 # 11/22/22 UM Power Line trench; Southeast corner of site 50.0 2 14.2 109.8 119.0 12.5 90 143 # 11/23/22 UM Power Line trench; Southeast corner of site 52.0 2 14.2 108.4 119.0 12.5 90 144 # 11/23/22 UM Power Line trench; Southeast corner of site 52.0 3 12.7 114.7 123.5 11.5 90 145 # 11/23/22 UM Power Line trench; Southeast corner of site 53.0 3 13.3 118.2 123.5 11.5 90 146 # 11/23/22 UM Power Line trench; Southeast corner of site 53.0 4 12.4 120.4 125.5 10.5 90 147 # 11/23/22 UM Power Line trench; Southeast corner of site 53.0 4 12.2 120.0 125.5 10.5 90 148 # 11/23/22 UM Power Line trench; Southeast corner of site 51.5 3 13.4 116.7 123.5 11.5 90 149 # 11/23/22 UM Power Line trench; Southeast corner of site 52.5 3 12.6 116.9 123.5 11.5 90 150 # 11/23/22 UM Power Line trench; Southeast corner of site 54.0 3 12.9 118.2 123.5 11.5 90 94 93 96 96 96 96 92 92 91 92 93 90 92 96 93 93 95 91 96 95 92 94 92 91 92 90 90 93 95 96 209537009 FD - Final 5 of 7 SUMMARY OF FIELD DENSITY TESTS TABLE 2 PROJECT NO. Moisture Content (%) Dry Density (pcf) Proctor Density (pcf) Optimum Moisture Content (%) TEST OF: Date Test Location Soil Type No. Elevation (ft) Test of Test No. Field Laboratory Remarks 209537009 Compacted Fill, Sewer Main, Storm Drain, Utility Main, Subgrade, Aggregate Base Specified Relative Compaction (%) Relative Compaction (%) 151 # 11/23/22 UM Power Line trench; Southeast corner of site 54.0 3 13.3 117.6 123.5 11.5 90 152 # 11/23/22 UM Power Line trench; Southeast corner of site 50.5 3 11.9 112.7 123.5 11.5 90 153 # 11/23/22 UM Power Line trench; Southeast corner of site 52.0 4 10.8 116.2 125.5 10.5 90 154 # 11/23/22 UM Power Line trench; Southeast corner of site 53.5 4 11.9 119.8 125.5 10.5 90 155 # 11/23/22 UM Power Line trench; Southeast corner of site 55.0 3 12.7 118.4 123.5 11.5 90 156 # 11/29/22 CF Ramp-Wall; East Side of site 54.0 4 11.8 114.4 125.5 10.5 90 157 # 11/29/22 CF Ramp-Wall; East Side of site 58.0 4 12.1 116.0 125.5 10.5 90 158 # 4/10/23 WM Fire Lane Main Line; east and south of Building 57.5 1 10.9 121.7 127.0 10.5 90 159 # 4/10/23 WM Fire Lane Main Line; east and south of Building 56.5 1 12.4 122.9 127.0 10.5 90 160 # 4/10/23 WM Fire Lane Main Line; east and south of Building 56.5 1 11.9 121.9 127.0 10.5 90 161 # 4/10/23 WM Fire Line Main trench south and east of existing Building 57.0 1 12.2 122.1 127.0 10.5 90 162 # 4/10/23 WM Fire Line Main trench south and east of existing Building 57.0 4 11.4 120.7 125.5 10.5 90 163 # 4/10/23 WM Fire Line Main trench south and east of existing Building 57.5 4 10.8 121.6 125.5 10.5 90 164 # 4/10/23 WM Fire Line Main trench south and east of existing Building 58.0 4 11.6 120.8 125.5 10.5 90 516658 # 8/16/23 SM Sewer Riser at West Side of Building 58.0 1 11.5 119.3 127.0 10.5 90 167 # 8/16/23 SM Sewer Riser at West Side of Building 58.0 1 12.3 119.6 127.0 10.5 90 168 # 8/16/23 SM Sewer Riser at West Side of Building 58.0 1 10.6 118.8 127.0 10.5 90 169 # 8/16/23 SM Sewer Riser at South Side of Building 58.0 1 12.1 114.8 127.0 10.5 90 170 # 8/16/23 SM Sewer Riser at Southeast Corner of Site. 58.0 1 10.3 118.0 127.0 10.5 90 171 # 8/16/23 SM Riser at Souteast Corner of Site 58.0 1 13.6 114.2 127.0 10.5 90 172 # 8/16/23 SM Riser at Bayview Entrance 58.0 1 7.3 122.1 127.0 10.5 90 173 # 8/23/23 FL Fire Lane; Southwest 58.0 6 9.8 123.8 127.0 9.5 95 174 # 8/23/23 FL Fire Lane; Southwest 58.0 6 9.3 126.8 127.0 9.5 95 175 # 8/23/23 FL Fire Lane; West of building 58.0 6 9.5 124.3 127.0 9.5 95 176 # 8/23/23 FL Fire Lane; Northwest of building 58.0 6 9.2 124.5 127.0 9.5 95 177 # 8/23/23 FL Fire Lane Northwest of building 58.0 6 9.9 123.6 127.0 9.5 95 178 # 8/23/23 FL Fire Lane; West of building 58.0 6 10.4 124.4 127.0 9.5 95 184 # 11/2/23 CF Southeast of building 58.0 5 9.7 120.2 125.0 10.0 95 185 # 11/2/23 CF Southeast of building 58.0 5 9.2 122.8 125.0 10.0 95 186 # 11/2/23 CF Southeast of building 58.0 5 9.6 121.7 125.0 10.0 95 96 96 96 96 97 96 94 97 97 97 100 98 98 91 98 93 90 94 95 94 98 90 97 96 95 96 92 91 96 93 209537009 FD - Final 6 of 7 SUMMARY OF FIELD DENSITY TESTS TABLE 2 PROJECT NO. Moisture Content (%) Dry Density (pcf) Proctor Density (pcf) Optimum Moisture Content (%) TEST OF: Date Test Location Soil Type No. Elevation (ft) Test of Test No. Field Laboratory Remarks 209537009 Compacted Fill, Sewer Main, Storm Drain, Utility Main, Subgrade, Aggregate Base Specified Relative Compaction (%) Relative Compaction (%) 187 # 11/2/23 CF Southeast of building 58.0 5 8.9 121.8 125.0 10.0 95 188 # 11/2/23 CF Southeast of building; Approach off Bayview Place 58.0 5 8.7 123.1 125.0 10.0 95 189 # 11/2/23 CF Southeast of building; Approach off Bayview Plave 58.0 5 9.1 122.8 125.0 10.0 95 190 # 11/2/23 CF Southeast of building 58.0 5 9.4 120.4 125.0 10.0 95 191 # 11/2/23 CF Southeast of building 58.0 5 8.9 121.7 125.0 10.0 95 98 98 96 97 97 209537009 FD - Final 7 of 7 SUMMARY OF FIELD DENSITY TESTS TABLE 3 Field Laboratory Wet Density (pcf) Marshall Density (pcf) 179 # 8/24/23 AC Fire Lane, Northwest FG 1AC 149.4 152.0 95 180 # 8/28/23 AC Fire Lane, Northwest FG 1AC 148.8 152.0 95 181 # 8/28/23 AC Fire Lane, Northwest FG 1AC 150.1 152.0 95 182 # 8/28/23 AC Fire Lane, Northwest FG 1AC 150.5 152.0 95 183 # 8/28/23 AC Fire Lane, Southwest FG 1AC 151.6 152.0 95 Test No.: (#) - Nuclear Gauge Test Method; (*) - Sand Cone Test Method; (+) - 12-inch Sand Cone Method; (^) - Drive-Cylinder Method Test of: AC - Asphalt Concrete 209537009 Specified Relative Compaction (%) PROJECT NO. Remarks TEST OF: Test of Relative Compaction (%) Date Test Location 98 Notes: Elevation (ft) Material Type No. Test No. Asphalt Concrete 98 99 99 100 1 of 1 Ninyo & Moore | 101 Bayview Place, Newport Beach, California | 209537009 | December 22, 2023 1 FIGURES SITE Geotechnical & Environmental Sciences Consultants 1_ 2 0 9 5 3 7 0 0 9 _ S L . d w g 1 2 / 1 8 / 2 0 2 3 G K SITE LOCATION FIGURE 1 NOTE: DIMENSIONS, DIRECTIONS AND LOCATIONS ARE APPROXIMATE. I REFERENCE: USGS, 2018.0 FEET 2,000 4,000 CLEARWATER AT NEWPORT BEACH 101 BAYVIEW PLACE NEWPORT BEACH, CALIFORNIA 209537009 I 12/23 N 35 31 71 70 37 39 79 106 47 50 87 16, 17 51 40 57 86 59 44, 45 41 30 101 1091 102 25 29 24 111 11 66 67 65 49 64 95 43 80 82, 83 1863 62 84, 85 48 60 6146 42 81 9394 27 23105 28 106 9978 3 5 100 77 76 124 4 6 11375 74 69 125 68 132139 130 134 7 141 58 99137 127 88 22 9089 55 98 105 117 156 38 21 8 53 14 54 13 17215 116 43 3272 36 33 19 103 12 110 2 123 112 10 96 73 97 98 140 131 9 151 145 170 129 143 136 171 144 142 133 138 146 152 153 155128 148 126 149 56 92 91 52 26 115 108 34 119 118 157 104 20 120 188 179180 176 187 166 167 168 173 121,122 169 114 183 182 175 181 178177 114 136 107 163 158 164 189 154 135 147 150 161 160 159 129 162 185 187191 184 FIELD DENSITY TEST LOCATIONS 0 FEET 30 600 Geotechnical & Environmental Sciences Consultants LEGEND CLEARWATER AT NEWPORT BEACH 101 BAYVIEW PLACE NEWPORT BEACH, CALIFORNIA 209537009 I 12/23 FIGURE 2 20 9 5 3 7 0 0 9 . d w g _ F D T L 1 2 / 2 2 / 2 0 2 3 G K N NOTE: DIMENSIONS, DIRECTIONS AND LOCATIONS ARE APPROXIMATE. I REFERENCE: DPI, 2023. LEGEND 191 43 FIELD DENSITY TEST BOTTOM ELEVATION BUILDING OVEREXCAVATION LIMITS GRADING LIMITS 475 Goddard, Suite 200 | Irvine, California 92618 | p. 949.753.7070 | www.ninyoandmoore.com October 3, 2022 Project No. 209537009 Mr. Roger Bernstein Oppidan 1100 Lincoln Avenue San Jose, California 95125 Subject: Building Pad Compaction Report – Clearwater at Newport Beach 101 Bayview Place Newport Beach, California Reference: Ninyo & Moore, 2021, Geotechnical Evaluation, Newport Beach Senior Living Facility, 101 Bayview Place, Newport Beach, California, dated November 24. Dear Mr. Bernstein: In accordance with your request and authorization, we have provided field observation and field density testing services during construction of the basement-level building pad for the Clearwater at Newport Beach project located at 101 Bayview Place in Newport Beach, California (Figure 1). This report presents the results of our geotechnical observation and field density testing services that pertain to the structural fills placed during the earthwork operations for the building. Our scope of services included project coordination, laboratory testing of selected soil samples, and field density testing during the building overexcavation and recompaction operations. The earthwork operations for the building pad observed and tested by Ninyo & Moore were performed between June 14, 2022, and June 22, 2022. EARTHWORK The initial phase of earthwork included stripping, clearing, and exporting the debris generated from the project demolition activities. In general, ground preparation within the building pad area consisted primarily of overexcavation, scarification, moisture conditioning, and recompaction. The areas to receive fill were observed and approved by Ninyo & Moore prior to further construction. The subgrade soils were scarified to a depth of 6 inches or more, moisture conditioned, and recompacted to be firm and competent prior to placement of the new fill. The material utilized for fill was generated from excavated on-site soils and import materials from an offsite location, which were brought to near optimum moisture and compacted in approximately 6 to 8-inch lifts to 90 percent or more relative compaction in accordance with the referenced project plans and geotechnical recommendations Ninyo & Moore | 101 Bayview Place, Newport Beach, California | 209537009 | October 3, 2022 2 provided by Ninyo & Moore. During the earthwork operations, any oversized rocks (3-inches or greater) were removed by hand or equipment. Our services were provided as scheduled and coordinated by the construction manager, W. E. O’Neil. We were generally on site on a periodic basis during the earthwork operations. The earthwork was performed using heavy earthmoving equipment, including a Case loader, skip loader, and a Caterpillar D6 dozer, a medium-sized vibratory roller, rubber-wheel loader with full bucket and wacker Rammax compactors, and a water truck. FIELD AND LABORATORY TESTING In-place moisture and density tests of the compacted materials were performed in general accordance with the ASTM International (ASTM) D 6938 (Nuclear Gauge method) and D 1556 (Sand Cone method). The laboratory maximum dry density test result was performed in general accordance with ASTM D 1557 and is presented in Table 1. The field density test results are summarized in Table 2. The approximate locations of the field density tests are shown on Figure 2. The field density test results were used to evaluate the relative compaction of the fill materials. We should note that field density tests for minor fills outside of the building pad are not shown. CONCLUSIONS Based on our observation and testing, it is our opinion that the earthwork operations observed and tested by Ninyo & Moore were performed in general accordance with the referenced geotechnical engineering report, dated November 24, 2021 and supplemental geotechnical recommendations provided by Ninyo & Moore. Our observations and testing indicate that the fill soils placed between June 14, 2022, and June 22, 2022, were compacted to 90 percent or more relative compaction utilizing test methods ASTM D 6938, D 1556, and D 1557. Nuclear gauge density testing was performed in conformance with P/BC 2017-28. The compacted fill soil placed within the building pad areas is considered a structural fill, and is intended to support foundations and interior slabs-on- grade. LIMITATIONS The field and laboratory testing presented in this report have been conducted in general accordance with current practice and the standard of care exercised by geotechnical consultants performing similar tasks in this area. No warranty, expressed or implied, is mad e regarding the opinions expressed in this report. It is important to note that the precision of field density tests and the maximum dry density tests is not exact and variations should be expected. Ninyo & Moore | 101 Bayview Place, Newport Beach, California | 209537009 | October 3, 2022 3 We appreciate the opportunity to be of service on this project. Sincerely, NINYO & MOORE Emily Homan, PG Project Geologist Garreth M. Saiki, PE, GE Principal Engineer ECH/GMS/shs Attachments: Table 1 – Maximum Density Test Results Table 2 – Summary of Field Density Tests Figure 1 – Site Location Figure 2 – Field Density Test Locations Ninyo & Moore | 101 Bayview Place, Newport Beach, California | 209537009 | October 3, 2022 1 Table 1 – Maximum Density Test Results Soil Type No. Description U.S.C.S. Method of Soil Class. Maximum Density (pcf) Optimum Moisture (%) 2 Pale Brown Sandy Silt ML 119.0 12.5 3 Yellowish-Brown Clayey Sand SC 123.5 11.5 Notes: pcf – pounds per cubic foot SUMMARY OF FIELD DENSITY TESTS TABLE 2 PROJECT NO. Moisture Content (%) Dry Density (pcf) Proctor Density (pcf) Optimum Moisture Content (%) 17 # 6/15/22 CF Northeast Corner of Building Pit; Overexcavation; Footing Bottom 43.0 3 11.6 110.8 123.5 11.5 90 18 # 6/15/22 CF West Center of Building Pit; Overexcavation; Footing Bottom 43.0 3 9.7 111.6 123.5 11.5 90 19 # 6/15/22 CF East Center of Building Pit; Overexcavation; Footing Bottom 43.0 3 9.4 112.7 123.5 11.5 90 20 # 6/15/22 CF Southwest Center of Building pit; Overexcavation; Footing Bottom 43.0 3 10.2 114.2 123.5 11.5 90 21 # 6/20/22 CF East Side of Building Pad; Overexcavation; Footing Bottom 43.0 3 14.0 114.9 123.5 11.5 90 22 # 6/20/22 CF Southeast Side of Building Pad; Overexcavation; Footing Bottom 43.0 3 11.9 115.3 123.5 11.5 90 23 # 6/20/22 CF Southwest Side of Building Pad; Overexcavation; Footing Bottom 43.0 2 13.2 110.7 119.0 12.5 90 24 # 6/20/22 CF West Side of Building Pad; Overexcavation; Footing Bottom 43.0 3 13.8 117.8 123.5 11.5 90 25 * 6/20/22 CF West Side of Building Pad; Overexcavation; Footing Bottom 43.0 2 14.0 115.2 119.0 12.5 90 26 # 6/20/22 CF East Side of Building Pad; Overexcavation; Footing Bottom 43.0 3 14.7 115.9 123.5 11.5 90 27 # 6/20/22 CF South Side of Building Pad; Backfill; Footing Bottom 44.0 3 13.5 113.7 123.5 11.5 90 28 # 6/20/22 CF South Side of Building Pad; Backfill; Footing Bottom 44.0 3 13.7 117.7 123.5 11.5 90 29 # 6/20/22 CF West Side of Building Pad; Backfill; Footing Bottom 45.0 3 14.3 118.4 123.5 11.5 90 30 # 6/20/22 CF West Side of Building Pad; Backfill; Footing Bottom 45.0 3 13.1 114.9 123.5 11.5 90 31 # 6/21/22 CF North Side of Building Pad; Backfill; Overexcavation; Footing Bottom 43.0 2 12.7 114.5 119.0 12.5 90 32 # 6/21/22 CF Northeast Side of Building Pad; Overexcavation; Footing Bottom 43.0 2 13.5 113.1 119.0 12.5 90 33 # 6/21/22 CF East Side of Building Pad; Overexcavation; Footing Bottom 43.0 3 11.8 116.5 123.5 11.5 90 34 # 6/21/22 CF East Side of Building Pad; Overexcavation; Footing Bottom 43.0 3 13.9 115.7 123.5 11.5 90 35 * 6/21/22 CF Northwest Side of Building Pad; Backfill; Footing Bottom 44.0 3 13.1 113.2 123.5 11.5 90 36 # 6/21/22 CF North Side of Building Pad; Backfill; Footing Bottom 45.0 3 12.0 116.0 123.5 11.5 90 37 # 6/21/22 CF Northeast Side of Building Pad; Backfill; Footing Bottom 45.0 3 12.4 115.7 123.5 11.5 90 38 # 6/22/22 CF East Side of Building Pad; Backfill; Footing Bottom 45.0 3 13.4 114.8 123.5 11.5 90 39 # 6/22/22 CF Northeast Side of Building Pad; Backfill; Footing Bottom 45.0 3 11.6 114.2 123.5 11.5 90 40 # 6/22/22 SG Center of Building Pad; Backfill; Footing Bottom 45.0 3 11.0 117.1 123.5 11.5 90 41 # 6/22/22 SG Center of Building Pad; Backfill; Footing Bottom 45.0 3 11.7 115.5 123.5 11.5 90 94 94 TEST OF: Date Test Location Soil Type No. Elevation (ft) Test of Test No. Field Laboratory 93 96 90 90 91 92 95 97 93 93 93 93 92 95 94 Remarks 209537009 BUILDING PAD FOOTING Specified Relative Compaction (%) Relative Compaction (%) 94 92 95 96 95 94 94 92 209537009 FD 1 of 2 SUMMARY OF FIELD DENSITY TESTS TABLE 2 PROJECT NO. Moisture Content (%) Dry Density (pcf) Proctor Density (pcf) Optimum Moisture Content (%) TEST OF: Date Test Location Soil Type No. Elevation (ft) Test of Test No. Field Laboratory Remarks 209537009 BUILDING PAD FOOTING Specified Relative Compaction (%) Relative Compaction (%) 42 # 6/22/22 SG Center of Building Pad; Backfill; Footing Bottom 45.0 3 11.0 118.8 123.5 11.5 90 43 # 6/22/22 SG Center of Building Pad; Backfill; Footing Bottom 45.0 3 12.0 119.6 123.5 11.5 90 96 97 209537009 FD 2 of 2 Ninyo & Moore | 101 Bayview Place, Newport Beach, California | 209537009 | October 3, 2022 FIGURES SITE Geotechnical & Environmental Sciences Consultants 1_ 2 0 9 5 3 7 0 0 9 _ S L . d w g 0 9 / 3 0 / 2 0 2 2 G K SITE LOCATION FIGURE 1 NOTE: DIMENSIONS, DIRECTIONS AND LOCATIONS ARE APPROXIMATE. I REFERENCE: USGS, 2018.0 FEET 2,000 4,000 CLEARWATER AT NEWPORT BEACH 101 BAYVIEW PLACE NEWPORT BEACH, CALIFORNIA 209537009 I 10/22 N 30 25 29 24 37 3317 40 41 42 19 18 43 20 28 38 35 31 36 32 39 21 34 27 23 22 26 43 Geotechnical & Environmental Sciences Consultants 2_ 2 0 9 5 3 7 0 0 9 _ F D T L . d w g 9 / 3 0 / 2 0 2 2 G K FIELD DENSITY TEST LOCATIONS NOTE: DIMENSIONS, DIRECTIONS AND LOCATIONS ARE APPROXIMATE. I REFERENCE: DCI, UNDATED.0 FEET 40 80 LEGEND CLEARWATER AT NEWPORT BEACH 101 BAYVIEW PLACE NEWPORT BEACH, CALIFORNIA 209537009 I 10/22 N FIGURE 2 43 43 FIELD DENSITY TEST BOTTOM ELEVATION